This document uses the following definitions throughout as a guide to the user in
determining the nature of information presented:
Note: Additional information which may be helpful
Tip: Suggestion to make installation, set-up, and troubleshooting easier.
Caution: Items which may cause the equipment not to function correctly, but will
not otherwise damage components.
Warning: Errors which can result in damage to equipment and void warranties.
Design Guide 1-1
Section 1
A
V
Auto-Zone Basic
To HVAC Unit
Control Panel
Supply
ir Temp
Sensor
Optional Remote Li nk II
Connects to CommLink IV
And Provides Alarm Call-Outs
A Second Remote Link Is Required
If Connection To Job Site
Is Desired From Remote Computer
Remote Link II
(Optional)
CommLink IV
The CommLink IV Is
Required For All Systems.
The IP Module, Remote
Link II, And Computer Are
Optional On All Systems.
All Computers Requ ire
Installation of Prism
Graphical User Interface
Software
USB Cable To Computer
Phone Cable To
Telephone
Wall Outlet Jack
CommLink IV
Single Loop
Economizer
(Actuator By Others)
Outside
Air Temp
Sensor
Computer
(Optional)
24VAC
Ethernet Cable To Router
Ethernet Router
(By Others)
When IP Module
Option Is Used
RS-485
9600 Baud
Optional IP Module
Installs Into CommLink IV
And Provides
LAN And Internet
Communications
With The Control System
Static
Pressure
Sensor
Zone Controller
elocity Sensor
(Optional)
Return
Air Temp
Sensor
Bypass Air
Damper
Typical Zone
Damper Actuator
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
#1
Room Sensor
with Optional
Override & Adj.
#16
RS-485
Comm Loop
24 VAC
Figure 1-1: Auto-Zone Basic Control System
1-2 Design Guide
Auto-Zone Basic
Section 1
General Information
The primary application of the Auto-Zone Basic Control System is to provide multiple
controlled comfort zones from a single zone, unitary heating and air-conditioning
package unit. It can also be applied to existing installations for improved comfort to
multiple zones currently controlled by a single thermostat.
Description of System Components
A typical Auto-Zone Basic Control System is comprised of the following four basic
components.
Zone Manager
The Zone Manager is a microprocessor-based controller which monitors up to 16 zones
in the system. The zone manager then controls the HVAC unit to satisfy the requirements
of each individual zone while maintaining efficient operation and comfort. The zone
manager is also responsible for controlling duct static pressure.
In the Auto-Zone Basic version, the Zone Manager has a display and a keypad. The 4line by 20-character display is backlighted, making it easier to read in low light
environments.
Bypass Damper
The bypass damper controls proper duct static pressure to insure proper airflow. The
damper is modulated by the Zone Manager based on a signal received from the static
pressure sensor connected to the main duct.
Zone Controller
The Zone Controller monitors space temperature and allocates proper airflow to the
assigned zone to achieve desired comfort and ventilation levels. If supply air temperature
will benefit the local zone temperature setpoint, the zone damper modulates to reduce or
increase airflow as needed. If supply air will not benefit the local zone, the controller will
direct the damper actuator to a minimum position and wait for a change in supply air
temperature.
Design Guide 1-3
Section 1
Auto-Zone Basic
Zone Sensor
The patented zone sensor is a flush, wall-mounted design. A special plate on the face of
the sensor accurately senses space conditions. As a result of its unique design, the zone
sensor rejects the influence of internal wall temperature effects. The sensor comes in four
different configurations:
• Sensor only
• Sensor w/push-button override (override is fixed at 2 hours)
• Sensor w/setpoint adjustment
• Sensor w/override & setpoint adjustment
Any combination of these sensor configurations can be used with the system.
1-4 Design Guide
Auto-Zone Basic
Section 1
Design Considerations
Consider the following items when designing a system using Auto-Zone.
Zone Diversity
The Auto-Zone Basic Control System is designed to improve tenant comfort by
dynamically re-balancing the air distribution when used with a typical constant volume
rooftop heating/cooling unit. If zones with extremely different load conditions are
serviced by a single rooftop unit, the result will be poor control and excessive wear due
to cycling of the equipment.
It is especially important to avoid mixing interior zones (which require cooling all year)
with exterior zones (which may require constant heat during winter months). If you must
mix zones under these conditions, consider using either VAV boxes with heat or separate
baseboard heat on exterior zones. Auto-Zone Basic Control Systems offer a variety of
methods to control additional zone heat to help you avoid problems.
Cooling - Partial Load Conditions
The engineer must be aware of several potential problems when applying the Auto-Zone
Basic Control System during cold weather operation.
Low Ambient Temperature Lockout
During very cold weather it is common for mechanical systems to have “low temp
lockouts” which protect equipment from damage if operated under these conditions.
Auto-Zone also provides user programmed lockouts for protection purposes, although
mechanical safeties should always be used as the final stage of protection.
If the rooftop unit services interior zones with thermal loads which require cooling when
outside temperatures are below the safe operating limits for your equipment, you should
seriously consider installing an economizer on your rooftop unit. The Auto-Zone control
system is designed to take advantage of an economizer if it is installed. The use of an
economizer will save money on utilities and provide comfort under conditions when it is
not possible to operate the mechanical cooling system.
Low Supply Air Temperatures
Under lightly loaded conditions much of the supply air may be bypassed back into the
return airside of the system. This bypassing will result in the lowering of the supply air
Design Guide 1-5
Section 1
temperature, which may result in the supply air temperature reaching the low temp safety
limit. If the supply air low temp safety limit is exceeded, the control system will “cut-off”
the mechanical cooling to protect it from damage. Excessive cycling of the mechanical
system will result if this condition persists. Comfort may also suffer if the system cannot
run long enough to satisfy cooling demands.
A number of things can be done to reduce this problem. Some of these things depend
upon the type of installation.
• Avoid oversizing the unit. Do your load calculations carefully. Since Auto-Zone
directs the heating or cooling to the zones which require it, you may find that you can
use a smaller unit in many cases. Oversizing is the number one cause of excessive
low supply air temperature cycling.
• Increase your cooling minimum airflow or damper position settings to allow more air
during cooling operation. Be careful to avoid settings which are so high you cause
over cooling of the spaces. Find a compromise position.
• Bypass the air into the plenum instead of into the return air intake. Be careful if you
use this method since you may get “dumping” of cold air from your return air grilles.
This method works best with plenum returns. Do not use this method with ducted
returns unless you have carefully considered the consequences.
• Increase your static pressure setpoint to help reduce the amount of air being bypassed.
Be aware of increased noise levels and the cost of operation if you use excessive
static pressures.
Auto-Zone Basic
Warning: If the fan system has the capability of producing static pressures
which could damage ductwork, you must provide a manual reset high
pressure limit switch to cut-off the fan system in the event of high
duct static. Do not use your Auto-Zone Basic Control System as a
safety device!
• Use an Economizer. Although this is not a cure-all, it greatly improves operation
during cool weather when cooling loads are minimal. Using an Economizer also
improves ventilation and lowers operating costs, both of which are significant.
1-6 Design Guide
Auto-Zone Basic
Section 1
Heating - Partial Load Conditions
Heating difficulties are less common than cooling difficulties. They are similar in nature,
however, and the cures are generally the same.
• Increase the Heating minimum setpoints on as many zones as possible.
• Increase the static pressure setting as high as is practical. Increasing static pressure
does not help if you are using pressure independent operation.
• Bypass to plenum instead of the return air intake if acceptable.
• Do not oversize your equipment.
• Use auxiliary heat in either your VAV boxes or baseboard.
Auto-Zone has a number of auxiliary heat control options which provide solutions to
most problems. Refer to the Auxiliary Heat Control Options topic near the end of this
section.
Override Conditions
After-hours overrides can produce aggravated partial load conditions in both the heating
and cooling modes. The problem is most commonly caused by a single zone being
overridden for after-hours use. This causes the rooftop equipment to operate for only one
zone. The Auto-Zone Basic Control System offers an improved solution to this common
problem by allowing a single override to trigger a group of zones via a “global” override.
This allows the system to operate with sufficient load to reduce cycling caused by light
load conditions.
Building Pressurization
If you are using an economizer, building pressurization must be addressed. Failure to
properly handle building pressurization may result in doors remaining open when the
economizer is operating. Pressurization problems can render economizer operation
useless. The following suggestions will help to avoid potential problems.
• Use powered exhaust when the system uses ducted returns. The return duct pressure
drop will cause most barometric relief dampers to function poorly or not at all. AutoZone has the ability to control a powered exhaust whenever the economizer is
operating.
• Use a separate building pressure control which operates a relief fan or dampers.
Design Guide 1-7
Section 1
Auto-Zone Basic
Design Guide
There are six basic steps to designing an Auto-Zone Basic Control System:
1. Zoning
2. Sizing the Central Unit
3. Duct Design Considerations
4. Room Air Motion / Diffuser Selection
5. Bypass Damper Sizing
6. Sizing Zone Dampers
Step #1 - Zoning
Determine the number of zones. A single air handler unit can have no more than 16
zones. If the number of zones exceeds 16, then more than one Zone Manager will be
required. Consider using the Auto-Zone Plus system if more than one Zone Manager is
required.
The primary precaution to be taken in applying the Auto-Zone Basic Control System is to
select the zoning so that no zone will be at maximum (design) heating (or cooling) load
when any other zone requires the opposite temperature air to satisfy its load. For
example, depending on the wall, ceiling, floor material, and location within the building
(e.g. top or middle floor), a typical floor of a building usually has a minimum of 9
distinct temperature or control zones that are affected uniquely by the outdoor load.
These zones are depicted in Figure 1-2.
Depending on the size of the building and partition layout, some of these zones may
overlap or be insignificant from a zoning standpoint. For example, Zone 10 could be
multiple conference or computer rooms where additional zoning would be required, or it
could be as small as a corridor where no zoning is required. Similarly, zones 4 and 5
could have no external windows and no partitions between them and could be considered
a single zone. Zone 3 could be divided into multiple offices with full partitions between
them, thus requiring separate Zone Controllers because of different internal loads, but the
same external load.
Generally, the greater the number of individual Zone Controllers there are, the greater the
comfort. The designer will have to look at the specific building, balancing the costs of
multiple zones with the added comfort possible with multiple zones, to match the owner's
requirements.
1-8 Design Guide
Auto-Zone Basic
Section 1
It is important to recognize that there are purely internal zones, such as Zone 10, which
may contain separate offices/conference/computer rooms. These internal zones could
easily have high cooling requirements while external zones (1, 2, 3, etc.) could be at or
near design heating load. This is a misapplication of the Auto-Zone Basic or Plus (or any
heating/cooling changeover) system. The interior zones with cooling-only loads should
be served with a separate air-conditioning unit (that could be zoned between multiple
rooms with a similar load profile). Supplemental heat could be added to the perimeter
zones and controlled with the auxiliary heat control board from the Zone Controller.
System performance will generally be compromised and frequent changeover from the
heating to the cooling mode will occur during the heating season if purely internal zones
are combined on the same air-conditioning unit serving perimeter zones.
Zoned HVAC Unit
Supply Air Duct
Supply Air Duct
9
Constant Volume HVAC Unit
Return Air Plenum
Bypass Damper
System Manager
Round Zone Damper
(Typical)
Room Sensor
(Typical)
W
S
Return Air Plenum
N
E
8
ER
G
ANA
M
rm
la
A
EM
n
tio
a
ic
n
s
mu
D
u
e
l
m
d
E
i
o
r
P
SYST
r
C
e
W
v
e
O
n
M
o
P
Z
8
-
D
3
o
:
t
E
3
I
u
S
0
P
A
M
7
U
9
R
C
/
A
1
C
L
0
/
O
A
1
0
.
O
C
N
I
N
c
S
s
L
E
O
R
T
N
O
u
C
n
R
e
E
T
M
S
A
M
T
T
A
W
3
2
6
1
r
e
t
n
E
5
r
9
a
e
l
4
C
s
8
u
n
i
M
7
0
.
c
e
D
*
1
7
6
W
A
R
W
A
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
10
W
A
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
2
3
5
W
A
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
4
W
A
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
W
A
R
M
N
O
E
R
M
R
A
L
C
O
V
O
R
O
L
E
R
Figure 1-2: Control Zones Affected by the Outdoor Load
Design Guide 1-9
Section 1
Auto-Zone Basic
Step #2 - Sizing the Central Unit
Because the zones are controlled with variable air volume, it is unlikely that all zones
will be at design load at the same time. The zoning allows for the diversity of loads to be
taken into account and will often provide better comfort with a smaller HVAC unit.
In sizing the system, the individual zone loads should be calculated using any dependable
load estimating program. Because of diversity, the central unit should be selected for the
instantaneous peak load, not the sum of the peak loads, as would be done with a constant
volume single zone system. Consider the following when sizing the central unit.
• Size the peak cooling load based on the month and hour of the greatest total
building/system load.
• Heating should be sized for the lowest design temperature with an additional margin
for morning "pickup." This margin is generally recommended to be 20 to 25 percent
of base design.
Step #3 - Duct Design Considerations
The Auto-Zone Basic Control System uses a typical low pressure duct design. To reduce
noise problems, duct pressures should not exceed 1 inch W.C.
Primary trunk ducts should not be "undersized." This is especially true for "pressure
dependent" systems. Pressure dependent refers to the typical Auto-Zone Zone Controller
without the airflow sensor. With larger trunk ducts, it is easier to assure relatively constant
pressure to each zone. Runs should be as short as possible and the trunk duct system kept
as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk
ducts above corridors and locate the zone dampers above corridors to reduce the noise in
the space and facilitate service of the units. Trunk ducts should be sized for no more than
0.1 inch W.C. drop per 100 feet and a maximum duct velocity of 2000 FPM.
Note: For pressure independent terminal units with velocity sensors and
conventional "VAV" boxes properly selected for "quiet" operation, this 2000
FPM rule can be exceeded by up to 50 percent. The designer, however, should
be very experienced in VAV system design before considering modification
of this general rule.
Typical VAV systems with pressure independent terminals use the static regain method
for sizing ducts. The typical Auto-Zone Basic Control System is a low-pressure, pressure
dependent system that utilizes conventional unitary air-conditioning units. These systems
should use the equal-friction method of sizing the ducts and use the maximum loss of 0.1
inch per 100 feet as described above.
1-10 Design Guide
Auto-Zone Basic
Section 1
Step #4 - Room Air Motion/Diffuser
Selection
Air motion is a consideration for occupant comfort. The selection of diffusers for an
Auto-Zone Basic Control System requires more care than a constant volume system due
to varying flow of air into the zones. Slot diffusers are recommended due to their superior
performance at low airflows. Because the zone airflow is variable volume, lower cost
round or rectangular diffusers that were satisfactory for constant volume may prove
unsatisfactory with an Auto-Zone Basic Control System. These diffusers may result in
"dumping" of the cold air at low flows in the cooling mode and insufficient room air
motion at low air flows in the heating mode. Although high air motion in the heating
mode can be undesirable, a slot diffuser with a high induction ratio generally helps to
reduce room air "stratification" when the heating comes from a ceiling diffuser. Linear
slot diffusers should be properly selected for the airflow and "throw" suited to the
specific installation or zone.
Additional factors to consider in diffuser selection are sound level and throw at design
flow. Generally, multiple diffusers will result in lower sound levels in the space, but this
must be balanced with the additional hardware and installation costs. It is commonly
recommended that slot diffusers be located near the perimeter or outside wall with the
airflow directed into the room. Consult your diffuser supplier or catalog for proper
diffuser sizing and location.
Series fan boxes may be used instead of zone dampers where higher induction rates are
desirable. If the heat loss on perimeter walls is high, such as large areas of glass, the use
of Series Fan Boxes may be indicated to maintain higher induction rates to offset
“downdrafts.” If the heat loss is greater than 275 BTUH/LINEAR FOOT, you should use
high quality slot diffusers next to the outer wall with the airflow directed inward to
counteract downdrafts during heating. Serious downdraft problems occur when heat
losses exceed 400 BTUH/LINEAR FOOT. In such case, both high induction diffusers
and series fan boxes are recommended.
Step #5 - Bypass Damper Sizing
Using a load calculation program, the bypass damper should be sized to give you the
maximum CFM of air to be bypassed, typically 60 to 70 percent of the HVAC units rated
capacity. Bypass Dampers can either be round or rectangular depending on building or
job requirements. Use the appropriate round or rectangular damper selection table to
determine the correct damper size for your application. To size the damper, select a
damper from the table based on calculated bypass CFM and a maximum velocity
between 1750-2250 FPM. When determining the bypass duct size, be sure to take into
account any transition fittings and associated pressure drops. (See Table 1-1: Round Damper Selection or Table 1-2: Rectangular Damper Selection.)
Design Guide 1-11
Section 1
Auto-Zone Basic
If space limitations or total airflow requires it, multiple bypass dampers can be controlled
in parallel. For proper control of the Bypass Damper, the static pressure sensor location is
very important. Refer to Figure 1-3: Locating the Static Pressure Sensor for Bypass Damper Control below for proper mounting locations.
Preferred Location
If the trunk ducts are properly sized
for minimum pressure drop, the
Fan
location of the static pickup probe is
not particularly critical. It should
ideally be located at right angles to
the airflow in a straight section of the
supply duct approximately ⅔ the
distance of the total length of the
supply duct. Also, the probe should
SA Sensor
Bypass Damper
SPPickup
Supply Air Duct
RASensor
Return Air Duct
SP Sensor
be located not less than 3 duct
diameters downstream and 2 duct
diameters upstream of any elbow or
3D
Min.2DMin.
takeoff.
Less Than Ideal, But
Acceptable
Since the "ideal" location is often
Fan
difficult to find in an installation, a
location in the main trunk where
the tip is not in a "negative
pressure area" (e.g. just
downstream of the inside curve of
Supply Air Duct
SP Sensor
SA Sensor
SPPickup
Bypass Damper
RASensor
Return Air Duct
an elbow) or an area where the
tube opening is directly impacted
by the velocity of the supply air is
acceptable.
Least Desirable, But
Acceptable
If the supply duct comes directly
from the unit and immediately
splits in opposite directions, the
pressure pickup should be located
ahead of the split or as close to it
Supply Air Duct
TubingToBeEqual
LengthAnd Size
Fan
Bypass Damper
SA Sensor
RASensor
Return Air Duct
as possible, even if the bypass
damper(s) are located downstream
of the split.
SPPickups
SP Sensor
Figure 1-3: Locating the Static Pressure Sensor for Bypass Damper Control
1-12 Design Guide
Auto-Zone Basic
Section 1
Step #6 – Sizing Zone Dampers
Use a load program to determine the peak load for each zone. These calculations will be
used in selecting the appropriate zone damper sizes.
A round damper or rectangular damper can be selected depending on the building or job
requirements. If the job requires pressure independent damper control, the damper
selected must be a round damper. Rectangular dampers are not available for pressure
independent control. Please see Table: 1-1 for round damper selection. Please see Table: 1-2 for rectangular damper selection.
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for
minimal noise), find the smallest damper that will deliver the required CFM as
determined by the load program.
Go to either the Round Damper Selection table (Table: 1-1) or the Rectangular Damper
Selection table (Table: 1-2) depending on your requirements to select the dampers.
Locate the branch velocity used in the duct design program on the left hand column of
either damper sizing chart (Table: 1-1 or Table: 1-2). Move across the chart and find the
damper which will provide the acceptable CFM to meet each zone’s airflow
requirements.
Note: Compare the damper size selected against the duct size to determine if the
next size up or down will provide acceptable performance without requiring a
transition fitting.
Up to two additional dampers may be slaved together for larger zones. See zone wiring
diagram for details. This should be reserved for situations when it is not practical to use a
single large damper.
Design Guide 1-13
Section 1
Note: Dimensions Are
Identical For Round Zone,
Bypass & Slave Dampers
Auto-Zone Basic
Figure 1-4: Round Damper Dimensions
Note: See Table 1-2 for
Available “A” x “B”
Rectangular Damper Sizes
Note: Dimensions Are Identical
For Rectangular Zone, Bypass &
Slave Dampers
Figure 1-5: Rectangular Damper & Kit Dimensions
1-14 Design Guide
Auto-Zone Basic
Section 1
Round Dampers
Round Air Damper Selection
Air Damper Round Duct Size
( Area Ft2 )
Velocity Through Round Air
Damper
(FPM)
750 - Zone
1000 - Zone
1250 - Zone
1500 - Zone
1750 - Bypass Only
2000 - Bypass Only
2250 - Bypass Only
Calculated Based On 1000 FPM Velocity Through The Rectangular Damper. Zone Damper
Recommended Velocity Is 1000 – 1500 FPM. Select 1000 FPM or Less for Quiet Operation. For Other
Velocities, Use The Following Multipliers To Obtain The Correct CFM: 500 FPM = 0.5, 750 FPM =
2.) Bypass Dampers Should Be Selected for 60% to 70% of the HVAC Units Rated CFM Capacity.
Recommended Bypass Damper Velocity is 1750 – 2250 FPM.
NA NA
Design Guide 1-15
Section 1
Auto-Zone Basic
Pressure Independent Zone Dampers
Pressure Independent operation is only available for round zone dampers. Use the chart
below to set the calibration of the zone damper after installation.
Damper
Size
6” 474
8” 950
10” 1417
12” 2120
14” 2908
16” 3700
Flow Probe “K” Factor =
CFM @ 1” Velocity Pressure
Table 1-3: Pressure Independent Flow Factors
Flow Probe
“K” Factor
Note: K Factors are programmed for each zone so that the correct CFM will be
calculated for the different size air valves.
1-16 Design Guide
Auto-Zone Basic
Section 1
Auxiliary Heat Control
Options
The Auto-Zone Basic Control System offers you a variety of methods to deal with zone
heating requirements. When deciding how to handle zone heating requirements, you
should consider the following:
• Does the rooftop unit have heat?
• Are you using fan-powered boxes?
• Is auxiliary heat used such as baseboard or radiant ceiling panels?
If the zone has some type of heat, you must consider how the heat is to be used. Typical
questions that should be asked:
Q: Should the zone heat be used as a first stage where it will become active before a
heating demand is created at the rooftop unit?
A: This mode is useful if you expect to have both heating and cooling demands at the
same time. The zone will use its own heat and allow the rooftop unit to continue to
provide cooling for other zones. This mode is also useful if the rooftop unit does not
have any heating capabilities.
Q: Is the zone heat only to be used as a second stage where it will be activated only if
the rooftop unit cannot maintain the space temperature such as during very cold
weather?
A: In this mode of operation the rooftop will examine the heating and cooling demands
and try to satisfy all of the zones by switching between heating and cooling as
required. The zone heat will only be activated if the zone temperature falls below a
selected limit.
Q: Should the zone heat be locked out if the rooftop unit is supplying warm air?
A: In many instances, it is desirable to use the rooftop heating whenever possible and
only use zone heat when the rooftop unit is in cooling or vent mode. This often
provides the most cost-effective operation since zone heat is typically electric. This
mode of operation will lockout zone heat if the rooftop is delivering heated air.
Design Guide 1-17
Section 1
Auto-Zone Basic
Relay Expansion Board
The following describes the operation of each of the relays on the optional relay
expansion board. You can choose the appropriate relays for any given application.
Relay #1 - Parallel Fan
If the Zone is in cooling mode or vent mode, the parallel fan can activate any time the
zone temperature drops 0.5°F below the heating setpoint. It de-activates when the
temperature rises above the heating setpoint. The space temperature must be below the
AUX HEAT setpoint in the occupied mode before the Parallel Fan relay can be
energized.
Relay #2 - Box Heat
If the zone is in cooling mode or vent mode, the box heat can activate any time the zone
temperature drops 1.5°F below the heating setpoint. It de-activates when the temperature
rises to within 1.0°F of the heating setpoint. Box heat is not allowed to activate in the
heating mode when there is hot air being supplied by the air handling unit. This output
was intended to allow zone re-heat while the Zone Manager is satisfying cooling
demands in other zones. The space temperature must be below the AUX HEAT setpoint
in the occupied mode before the Box Heat relay can be energized.
Relay #3 - Aux Heat
In the occupied mode, the aux heat can activate any time the zone temperature is 0.5°F
below the aux heat setpoint. It de-activates when the temperature rises 0.5°F above the
aux heat setpoint. In the unoccupied mode, the aux heat uses the unoccupied heating
setpoint with the same deadband values mentioned above. This prevents the zone from
maintaining the same aux heat setpoint at night that it does during the daytime.
This output was intended to allow zone heating to augment the normal heating mode and
also to allow a zone an attempt to satisfy its own heating needs before creating a heating
demand at the Zone Manager.
Relay #4 - Series Fan
The series fan runs any time the main fan is running. This includes occupied and
unoccupied modes. The fan can only start running when the zone damper is closed, so it
determines that the damper is closed before starting the fan.
1-18 Design Guide
Auto-Zone Basic
Index
Section 1
1 inch W.C. ......................................... 10