Auto-Zone Control Systems Auto-Zone Basic Systems User Manual

Design, Installation
and Operations Manual
Revision 02C
Auto-Zone
Basic
Design, Installation & Operations Manual
Section 1..............................................................................System Overview
Section 2...................................................................Installation and Wiring
Section 3....................................................................................Programming
Section 4........................................................Start-Up and Troubleshooting
This document is subject to change without notice.
WattMaster Controls, Inc. assumes no responsibility
for errors, or omissions herein.
Auto-Zone Basic Installation & Operations Manual - Form WM-AZB-IO-02C
Auto-Zone is a registered trademark of WattMaster Controls, Inc.
Copyright 2009 WattMaster Controls, Inc.
All rights reserved.
Section 1
Table of Contents
Conventions .....................................................................1
General Information.........................................................3
Description of System Components.................................................................................3
Design Considerations.....................................................5
Zone Diversity .................................................................................................................5
Cooling - Partial Load Conditions ...................................................................................5
Heating - Partial Load Conditions ...................................................................................7
Override Conditions.........................................................................................................7
Building Pressurization....................................................................................................7
Design Guide....................................................................8
Step #1 - Zoning ..............................................................................................................8
Step #2 - Sizing the Central Unit ...................................................................................10
Step #3 - Duct Design Considerations...........................................................................10
Step #4 - Room Air Motion/Diffuser Selection.............................................................11
Step #5 - Bypass Damper Sizing ...................................................................................11
Step #6 - Sizing Zone Dampers .....................................................................................13
Round Dampers .............................................................................................................15
Rectangular Dampers.....................................................................................................15
Pressure Independent Zone Dampers ............................................................................16
Auxiliary Heat Control Options......................................17
Relay Expansion Board .................................................................................................18
Table of Figures & Tables
Figure 1-1: Auto-Zone Basic Control System...............................................................2
Figure 1-2: Control Zones Affected by the Outdoor Load ............................................9
Figure 1-3: Locating the Static Pressure Sensor for Bypass Damper Control ............12
Figure 1-4: Round Damper Dimensions......................................................................14
Figure 1-5: Rectangular Damper & Kit Dimensions...................................................14
Table 1-1: Round Air Damper Selection .....................................................................15
Table 1-2: Rectangular Damper Selection...................................................................15
Table 1-3: Pressure Independent Flow Factors............................................................16
Design Guide
Auto-Zone Basic
Section 1
Conventions
This document uses the following definitions throughout as a guide to the user in determining the nature of information presented:
Note: Additional information which may be helpful
Tip: Suggestion to make installation, set-up, and troubleshooting easier.
Caution: Items which may cause the equipment not to function correctly, but will
not otherwise damage components.
Warning: Errors which can result in damage to equipment and void warranties.
Design Guide 1-1
Section 1
A
V
Auto-Zone Basic
To HVAC Unit Control Panel
Supply
ir Temp
Sensor
Optional Remote Li nk II
Connects to CommLink IV
And Provides Alarm Call-Outs
A Second Remote Link Is Required
If Connection To Job Site
Is Desired From Remote Computer
Remote Link II
(Optional)
CommLink IV
The CommLink IV Is
Required For All Systems.
The IP Module, Remote
Link II, And Computer Are
Optional On All Systems.
All Computers Requ ire
Installation of Prism
Graphical User Interface
Software
USB Cable To Computer
Phone Cable To Telephone Wall Outlet Jack
CommLink IV
Single Loop
Economizer
(Actuator By Others)
Outside
Air Temp
Sensor
Computer
(Optional)
24VAC
Ethernet Cable To Router
Ethernet Router
(By Others)
When IP Module
Option Is Used
RS-485
9600 Baud
Optional IP Module
Installs Into CommLink IV
And Provides LAN And Internet Communications
With The Control System
Static
Pressure
Sensor
Zone Controller
elocity Sensor
(Optional)
Return
Air Temp
Sensor
Bypass Air
Damper
Typical Zone
Damper Actuator
Zone Air Dampers
Up to 16 Zone Air Dampers Allowed
#1
Room Sensor
with Optional
Override & Adj.
#16
RS-485
Comm Loop
24 VAC
Figure 1-1: Auto-Zone Basic Control System
1-2 Design Guide
Auto-Zone Basic
Section 1
General Information
The primary application of the Auto-Zone Basic Control System is to provide multiple controlled comfort zones from a single zone, unitary heating and air-conditioning package unit. It can also be applied to existing installations for improved comfort to multiple zones currently controlled by a single thermostat.
Description of System Components
A typical Auto-Zone Basic Control System is comprised of the following four basic components.
Zone Manager
The Zone Manager is a microprocessor-based controller which monitors up to 16 zones
in the system. The zone manager then controls the HVAC unit to satisfy the requirements of each individual zone while maintaining efficient operation and comfort. The zone manager is also responsible for controlling duct static pressure.
In the Auto-Zone Basic version, the Zone Manager has a display and a keypad. The 4­line by 20-character display is backlighted, making it easier to read in low light environments.
Bypass Damper
The bypass damper controls proper duct static pressure to insure proper airflow. The
damper is modulated by the Zone Manager based on a signal received from the static pressure sensor connected to the main duct.
Zone Controller
The Zone Controller monitors space temperature and allocates proper airflow to the
assigned zone to achieve desired comfort and ventilation levels. If supply air temperature will benefit the local zone temperature setpoint, the zone damper modulates to reduce or increase airflow as needed. If supply air will not benefit the local zone, the controller will direct the damper actuator to a minimum position and wait for a change in supply air temperature.
Design Guide 1-3
Section 1
Auto-Zone Basic
Zone Sensor
The patented zone sensor is a flush, wall-mounted design. A special plate on the face of
the sensor accurately senses space conditions. As a result of its unique design, the zone sensor rejects the influence of internal wall temperature effects. The sensor comes in four different configurations:
Sensor only
Sensor w/push-button override (override is fixed at 2 hours)
Sensor w/setpoint adjustment
Sensor w/override & setpoint adjustment
Any combination of these sensor configurations can be used with the system.
1-4 Design Guide
Auto-Zone Basic
Section 1
Design Considerations
Consider the following items when designing a system using Auto-Zone.
Zone Diversity
The Auto-Zone Basic Control System is designed to improve tenant comfort by dynamically re-balancing the air distribution when used with a typical constant volume rooftop heating/cooling unit. If zones with extremely different load conditions are serviced by a single rooftop unit, the result will be poor control and excessive wear due to cycling of the equipment.
It is especially important to avoid mixing interior zones (which require cooling all year) with exterior zones (which may require constant heat during winter months). If you must mix zones under these conditions, consider using either VAV boxes with heat or separate baseboard heat on exterior zones. Auto-Zone Basic Control Systems offer a variety of methods to control additional zone heat to help you avoid problems.
Cooling - Partial Load Conditions
The engineer must be aware of several potential problems when applying the Auto-Zone Basic Control System during cold weather operation.
Low Ambient Temperature Lockout
During very cold weather it is common for mechanical systems to have “low temp lockouts” which protect equipment from damage if operated under these conditions. Auto-Zone also provides user programmed lockouts for protection purposes, although
mechanical safeties should always be used as the final stage of protection.
If the rooftop unit services interior zones with thermal loads which require cooling when outside temperatures are below the safe operating limits for your equipment, you should seriously consider installing an economizer on your rooftop unit. The Auto-Zone control system is designed to take advantage of an economizer if it is installed. The use of an economizer will save money on utilities and provide comfort under conditions when it is not possible to operate the mechanical cooling system.
Low Supply Air Temperatures
Under lightly loaded conditions much of the supply air may be bypassed back into the return airside of the system. This bypassing will result in the lowering of the supply air
Design Guide 1-5
Section 1
temperature, which may result in the supply air temperature reaching the low temp safety limit. If the supply air low temp safety limit is exceeded, the control system will “cut-off” the mechanical cooling to protect it from damage. Excessive cycling of the mechanical system will result if this condition persists. Comfort may also suffer if the system cannot run long enough to satisfy cooling demands.
A number of things can be done to reduce this problem. Some of these things depend upon the type of installation.
Avoid oversizing the unit. Do your load calculations carefully. Since Auto-Zone
directs the heating or cooling to the zones which require it, you may find that you can use a smaller unit in many cases. Oversizing is the number one cause of excessive low supply air temperature cycling.
Increase your cooling minimum airflow or damper position settings to allow more air
during cooling operation. Be careful to avoid settings which are so high you cause over cooling of the spaces. Find a compromise position.
Bypass the air into the plenum instead of into the return air intake. Be careful if you
use this method since you may get “dumping” of cold air from your return air grilles. This method works best with plenum returns. Do not use this method with ducted returns unless you have carefully considered the consequences.
Increase your static pressure setpoint to help reduce the amount of air being bypassed.
Be aware of increased noise levels and the cost of operation if you use excessive static pressures.
Auto-Zone Basic
Warning: If the fan system has the capability of producing static pressures
which could damage ductwork, you must provide a manual reset high pressure limit switch to cut-off the fan system in the event of high duct static. Do not use your Auto-Zone Basic Control System as a safety device!
Use an Economizer. Although this is not a cure-all, it greatly improves operation
during cool weather when cooling loads are minimal. Using an Economizer also improves ventilation and lowers operating costs, both of which are significant.
1-6 Design Guide
Auto-Zone Basic
Section 1
Heating - Partial Load Conditions
Heating difficulties are less common than cooling difficulties. They are similar in nature, however, and the cures are generally the same.
Increase the Heating minimum setpoints on as many zones as possible.
Increase the static pressure setting as high as is practical. Increasing static pressure
does not help if you are using pressure independent operation.
Bypass to plenum instead of the return air intake if acceptable.
Do not oversize your equipment.
Use auxiliary heat in either your VAV boxes or baseboard.
Auto-Zone has a number of auxiliary heat control options which provide solutions to
most problems. Refer to the Auxiliary Heat Control Options topic near the end of this
section.
Override Conditions
After-hours overrides can produce aggravated partial load conditions in both the heating and cooling modes. The problem is most commonly caused by a single zone being overridden for after-hours use. This causes the rooftop equipment to operate for only one zone. The Auto-Zone Basic Control System offers an improved solution to this common problem by allowing a single override to trigger a group of zones via a “global” override. This allows the system to operate with sufficient load to reduce cycling caused by light load conditions.
Building Pressurization
If you are using an economizer, building pressurization must be addressed. Failure to properly handle building pressurization may result in doors remaining open when the economizer is operating. Pressurization problems can render economizer operation useless. The following suggestions will help to avoid potential problems.
Use powered exhaust when the system uses ducted returns. The return duct pressure
drop will cause most barometric relief dampers to function poorly or not at all. Auto­Zone has the ability to control a powered exhaust whenever the economizer is operating.
Use a separate building pressure control which operates a relief fan or dampers.
Design Guide 1-7
Section 1
Auto-Zone Basic
Design Guide
There are six basic steps to designing an Auto-Zone Basic Control System:
1. Zoning
2. Sizing the Central Unit
3. Duct Design Considerations
4. Room Air Motion / Diffuser Selection
5. Bypass Damper Sizing
6. Sizing Zone Dampers
Step #1 - Zoning
Determine the number of zones. A single air handler unit can have no more than 16 zones. If the number of zones exceeds 16, then more than one Zone Manager will be required. Consider using the Auto-Zone Plus system if more than one Zone Manager is required.
The primary precaution to be taken in applying the Auto-Zone Basic Control System is to select the zoning so that no zone will be at maximum (design) heating (or cooling) load when any other zone requires the opposite temperature air to satisfy its load. For example, depending on the wall, ceiling, floor material, and location within the building (e.g. top or middle floor), a typical floor of a building usually has a minimum of 9 distinct temperature or control zones that are affected uniquely by the outdoor load.
These zones are depicted in Figure 1-2.
Depending on the size of the building and partition layout, some of these zones may overlap or be insignificant from a zoning standpoint. For example, Zone 10 could be multiple conference or computer rooms where additional zoning would be required, or it could be as small as a corridor where no zoning is required. Similarly, zones 4 and 5 could have no external windows and no partitions between them and could be considered a single zone. Zone 3 could be divided into multiple offices with full partitions between them, thus requiring separate Zone Controllers because of different internal loads, but the same external load.
Generally, the greater the number of individual Zone Controllers there are, the greater the comfort. The designer will have to look at the specific building, balancing the costs of multiple zones with the added comfort possible with multiple zones, to match the owner's requirements.
1-8 Design Guide
Auto-Zone Basic
Section 1
It is important to recognize that there are purely internal zones, such as Zone 10, which may contain separate offices/conference/computer rooms. These internal zones could easily have high cooling requirements while external zones (1, 2, 3, etc.) could be at or near design heating load. This is a misapplication of the Auto-Zone Basic or Plus (or any heating/cooling changeover) system. The interior zones with cooling-only loads should be served with a separate air-conditioning unit (that could be zoned between multiple rooms with a similar load profile). Supplemental heat could be added to the perimeter zones and controlled with the auxiliary heat control board from the Zone Controller. System performance will generally be compromised and frequent changeover from the heating to the cooling mode will occur during the heating season if purely internal zones are combined on the same air-conditioning unit serving perimeter zones.
Zoned HVAC Unit
Supply Air Duct
Supply Air Duct
9
Constant Volume HVAC Unit
Return Air Plenum
Bypass Damper
System Manager
Round Zone Damper (Typical)
Room Sensor
(Typical)
W
S
Return Air Plenum
N
E
8
ER
G ANA M
rm
la
A
EM
n
tio
a
ic
n
s
mu
D
u
e
l
m
d
E
i o
r
P
SYST
r C
e
W
v
e
O
n
M
o
P
Z
8
-
D
3
o
:
t
E 3 I
u
S
0
P
A
M
7
U
9
R C /
A 1 C
L 0 / O A 1 0
.
O
C N I
N
c
S
s
L
E
O R T N O
u
C
n
R
e
E T
M
S A M T T A W
3 2
6 1
r e t n E
5
r
9
a
e
l
4
C
s
8
u
n
i
M
7 0
. c e D
*
1
7
6
W
A R
W
A R M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
10
W
A R M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
2
3
5
W
A R M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
4
W
A R M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
W
A R M
N O
E
R M
R
A L
C
O V
O
R
O L
E R
Figure 1-2: Control Zones Affected by the Outdoor Load
Design Guide 1-9
Section 1
Auto-Zone Basic
Step #2 - Sizing the Central Unit
Because the zones are controlled with variable air volume, it is unlikely that all zones will be at design load at the same time. The zoning allows for the diversity of loads to be taken into account and will often provide better comfort with a smaller HVAC unit.
In sizing the system, the individual zone loads should be calculated using any dependable load estimating program. Because of diversity, the central unit should be selected for the instantaneous peak load, not the sum of the peak loads, as would be done with a constant volume single zone system. Consider the following when sizing the central unit.
Size the peak cooling load based on the month and hour of the greatest total
building/system load.
Heating should be sized for the lowest design temperature with an additional margin
for morning "pickup." This margin is generally recommended to be 20 to 25 percent of base design.
Step #3 - Duct Design Considerations
The Auto-Zone Basic Control System uses a typical low pressure duct design. To reduce noise problems, duct pressures should not exceed 1 inch W.C.
Primary trunk ducts should not be "undersized." This is especially true for "pressure dependent" systems. Pressure dependent refers to the typical Auto-Zone Zone Controller without the airflow sensor. With larger trunk ducts, it is easier to assure relatively constant pressure to each zone. Runs should be as short as possible and the trunk duct system kept as symmetrical as possible to facilitate system balancing. Wherever possible, run the trunk ducts above corridors and locate the zone dampers above corridors to reduce the noise in the space and facilitate service of the units. Trunk ducts should be sized for no more than
0.1 inch W.C. drop per 100 feet and a maximum duct velocity of 2000 FPM.
Note: For pressure independent terminal units with velocity sensors and
conventional "VAV" boxes properly selected for "quiet" operation, this 2000 FPM rule can be exceeded by up to 50 percent. The designer, however, should be very experienced in VAV system design before considering modification of this general rule.
Typical VAV systems with pressure independent terminals use the static regain method for sizing ducts. The typical Auto-Zone Basic Control System is a low-pressure, pressure dependent system that utilizes conventional unitary air-conditioning units. These systems should use the equal-friction method of sizing the ducts and use the maximum loss of 0.1 inch per 100 feet as described above.
1-10 Design Guide
Auto-Zone Basic
Section 1
Step #4 - Room Air Motion/Diffuser Selection
Air motion is a consideration for occupant comfort. The selection of diffusers for an Auto-Zone Basic Control System requires more care than a constant volume system due to varying flow of air into the zones. Slot diffusers are recommended due to their superior performance at low airflows. Because the zone airflow is variable volume, lower cost round or rectangular diffusers that were satisfactory for constant volume may prove unsatisfactory with an Auto-Zone Basic Control System. These diffusers may result in "dumping" of the cold air at low flows in the cooling mode and insufficient room air motion at low air flows in the heating mode. Although high air motion in the heating mode can be undesirable, a slot diffuser with a high induction ratio generally helps to reduce room air "stratification" when the heating comes from a ceiling diffuser. Linear slot diffusers should be properly selected for the airflow and "throw" suited to the specific installation or zone.
Additional factors to consider in diffuser selection are sound level and throw at design flow. Generally, multiple diffusers will result in lower sound levels in the space, but this must be balanced with the additional hardware and installation costs. It is commonly recommended that slot diffusers be located near the perimeter or outside wall with the airflow directed into the room. Consult your diffuser supplier or catalog for proper diffuser sizing and location.
Series fan boxes may be used instead of zone dampers where higher induction rates are desirable. If the heat loss on perimeter walls is high, such as large areas of glass, the use of Series Fan Boxes may be indicated to maintain higher induction rates to offset “downdrafts.” If the heat loss is greater than 275 BTUH/LINEAR FOOT, you should use high quality slot diffusers next to the outer wall with the airflow directed inward to counteract downdrafts during heating. Serious downdraft problems occur when heat losses exceed 400 BTUH/LINEAR FOOT. In such case, both high induction diffusers and series fan boxes are recommended.
Step #5 - Bypass Damper Sizing
Using a load calculation program, the bypass damper should be sized to give you the maximum CFM of air to be bypassed, typically 60 to 70 percent of the HVAC units rated capacity. Bypass Dampers can either be round or rectangular depending on building or job requirements. Use the appropriate round or rectangular damper selection table to determine the correct damper size for your application. To size the damper, select a damper from the table based on calculated bypass CFM and a maximum velocity between 1750-2250 FPM. When determining the bypass duct size, be sure to take into
account any transition fittings and associated pressure drops. (See Table 1-1: Round Damper Selection or Table 1-2: Rectangular Damper Selection.)
Design Guide 1-11
Section 1
Auto-Zone Basic
If space limitations or total airflow requires it, multiple bypass dampers can be controlled in parallel. For proper control of the Bypass Damper, the static pressure sensor location is
very important. Refer to Figure 1-3: Locating the Static Pressure Sensor for Bypass Damper Control below for proper mounting locations.
Preferred Location
If the trunk ducts are properly sized for minimum pressure drop, the
Fan
location of the static pickup probe is not particularly critical. It should ideally be located at right angles to the airflow in a straight section of the supply duct approximately ⅔ the distance of the total length of the supply duct. Also, the probe should
SA Sensor
Bypass Damper
SPPickup
Supply Air Duct
RASensor
Return Air Duct
SP Sensor
be located not less than 3 duct diameters downstream and 2 duct diameters upstream of any elbow or
3D Min.2DMin.
takeoff.
Less Than Ideal, But Acceptable
Since the "ideal" location is often
Fan
difficult to find in an installation, a location in the main trunk where the tip is not in a "negative pressure area" (e.g. just downstream of the inside curve of
Supply Air Duct
SP Sensor
SA Sensor
SPPickup
Bypass Damper
RASensor
Return Air Duct
an elbow) or an area where the tube opening is directly impacted by the velocity of the supply air is acceptable.
Least Desirable, But Acceptable
If the supply duct comes directly from the unit and immediately splits in opposite directions, the pressure pickup should be located ahead of the split or as close to it
Supply Air Duct
TubingToBeEqual LengthAnd Size
Fan
Bypass Damper
SA Sensor
RASensor
Return Air Duct
as possible, even if the bypass damper(s) are located downstream of the split.
SPPickups
SP Sensor
Figure 1-3: Locating the Static Pressure Sensor for Bypass Damper Control
1-12 Design Guide
Auto-Zone Basic
Section 1
Step #6 – Sizing Zone Dampers
Use a load program to determine the peak load for each zone. These calculations will be used in selecting the appropriate zone damper sizes.
A round damper or rectangular damper can be selected depending on the building or job requirements. If the job requires pressure independent damper control, the damper selected must be a round damper. Rectangular dampers are not available for pressure
independent control. Please see Table: 1-1 for round damper selection. Please see Table: 1-2 for rectangular damper selection.
Using the maximum acceptable velocity for a branch duct (typically 1000-1500 FPM for minimal noise), find the smallest damper that will deliver the required CFM as determined by the load program.
Go to either the Round Damper Selection table (Table: 1-1) or the Rectangular Damper Selection table (Table: 1-2) depending on your requirements to select the dampers.
Locate the branch velocity used in the duct design program on the left hand column of
either damper sizing chart (Table: 1-1 or Table: 1-2). Move across the chart and find the
damper which will provide the acceptable CFM to meet each zone’s airflow requirements.
Note: Compare the damper size selected against the duct size to determine if the
next size up or down will provide acceptable performance without requiring a transition fitting.
Up to two additional dampers may be slaved together for larger zones. See zone wiring diagram for details. This should be reserved for situations when it is not practical to use a single large damper.
Design Guide 1-13
Section 1
Note: Dimensions Are
Identical For Round Zone, Bypass & Slave Dampers
Auto-Zone Basic
Figure 1-4: Round Damper Dimensions
Note: See Table 1-2 for
Available “A” x “B” Rectangular Damper Sizes
Note: Dimensions Are Identical
For Rectangular Zone, Bypass & Slave Dampers
Figure 1-5: Rectangular Damper & Kit Dimensions
1-14 Design Guide
Auto-Zone Basic
Section 1
Round Dampers
Round Air Damper Selection
Air Damper Round Duct Size
( Area Ft2 )
Velocity Through Round Air
Damper
(FPM)
750 - Zone 1000 - Zone 1250 - Zone 1500 - Zone
1750 - Bypass Only 2000 - Bypass Only 2250 - Bypass Only
Table 1-1: Round Air Damper Selection
6”
(0.188)
(0.338)
141 254 399 577 788 1031 188 338 532 769 1050 1375 235 423 665 961 1313 1718 282 507 798 1154 1575 2062 329 592 931 1346 1838 2405 376 676 1064 1538 2100 2749 423 761 1197 1730 2363 3094
8”
10”
(0.532)
12”
(0.769)
14”
(1.050)
Volume Through Round Air Damper
(CFM)
16”
(1.375)
Rectangular Dampers
Rectangular Damper Selection
Damper
Height
(B)
Damper
Width
(A)
8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36”
Table 1-2: Rectangular Damper Selection
Notes: 1.) Zone Dampers Should Be Sized Based On The Required Zone CFM. The Table Above Is
8” 10” 12” 14” 16” 18” 20” 22” 24” 26” 28” 30” 32” 34” 36”
Airflow Through Rectangular Damper
CFM @ 1000 FPM Velocity
410 530 640 740 850 970 1080 1190 1300 1410 1520 1630 1740 1850 1970 510 590 690 800 910 1030 1150 1260 1380 1500 1610 1730 1840 2000 2080 560 650 730 850 970 1090 1210 1330 1460 1580 1700 1820 1940 2060 2190 660 770 880 1030 1180 1330 1480 1630 1760 1910 2060 2210 2360 2510 2640 750 890 1030 1200 1370 1540 1710 1880 2060 2230 2400 2570 2740 2910 3090 770 980 1180 1380 1580 1780 1980 2180 2350 2550 2750 2950 3150 3350 3540 850 1090 1330 1550 1770 1990 2210 2430 2650 2870 3090 3310 3530 3750 3990 930 1210 1480 1730 1980 2230 2480 2730 2950 3200 3450 3700 3950 4200 4440 950 1290 1630 1900 2170 2440 2710 2980 3250 3520 3790 4060 4330 4600 4880
990 1390 1780 2080 2380 2680 2980 3280 3550 3850 4150 4450 4750 1070 1500 1930 2250 2570 2890 3210 3530 3850 4170 4500 4820 1020 1550 2080 2430 2780 3130 3480 3830 4150 4500 4850 1090 1660 2230 2600 2970 3340 3710 4080 4450 4820 1150 1770 2380 2780 3180 3580 3980 4370 4750 NA NA NA NA NA NA 1060 1790 2520 2670 3090 3510 3930 4350 5040
NA NA NA NA NA
NA NA NA NA NA NA
NA NA NA
NA NA NA NA
Calculated Based On 1000 FPM Velocity Through The Rectangular Damper. Zone Damper Recommended Velocity Is 1000 – 1500 FPM. Select 1000 FPM or Less for Quiet Operation. For Other
Velocities, Use The Following Multipliers To Obtain The Correct CFM: 500 FPM = 0.5, 750 FPM =
0.75, 1250 FPM = 1.25, 1500 FPM = 1.5, 2000 FPM = 2.0, 2250 FPM = 2.25.
2.) Bypass Dampers Should Be Selected for 60% to 70% of the HVAC Units Rated CFM Capacity.
Recommended Bypass Damper Velocity is 1750 – 2250 FPM.
NA NA
Design Guide 1-15
Section 1
Auto-Zone Basic
Pressure Independent Zone Dampers
Pressure Independent operation is only available for round zone dampers. Use the chart below to set the calibration of the zone damper after installation.
Damper
Size
6” 474
8” 950 10” 1417 12” 2120 14” 2908 16” 3700
Flow Probe “K” Factor =
CFM @ 1” Velocity Pressure
Table 1-3: Pressure Independent Flow Factors
Flow Probe “K” Factor
Note: K Factors are programmed for each zone so that the correct CFM will be
calculated for the different size air valves.
1-16 Design Guide
Auto-Zone Basic
Section 1
Auxiliary Heat Control Options
The Auto-Zone Basic Control System offers you a variety of methods to deal with zone heating requirements. When deciding how to handle zone heating requirements, you should consider the following:
Does the rooftop unit have heat?
Are you using fan-powered boxes?
Is auxiliary heat used such as baseboard or radiant ceiling panels?
If the zone has some type of heat, you must consider how the heat is to be used. Typical questions that should be asked:
Q: Should the zone heat be used as a first stage where it will become active before a
heating demand is created at the rooftop unit?
A: This mode is useful if you expect to have both heating and cooling demands at the
same time. The zone will use its own heat and allow the rooftop unit to continue to provide cooling for other zones. This mode is also useful if the rooftop unit does not have any heating capabilities.
Q: Is the zone heat only to be used as a second stage where it will be activated only if
the rooftop unit cannot maintain the space temperature such as during very cold weather?
A: In this mode of operation the rooftop will examine the heating and cooling demands
and try to satisfy all of the zones by switching between heating and cooling as required. The zone heat will only be activated if the zone temperature falls below a selected limit.
Q: Should the zone heat be locked out if the rooftop unit is supplying warm air?
A: In many instances, it is desirable to use the rooftop heating whenever possible and
only use zone heat when the rooftop unit is in cooling or vent mode. This often provides the most cost-effective operation since zone heat is typically electric. This mode of operation will lockout zone heat if the rooftop is delivering heated air.
Design Guide 1-17
Section 1
Auto-Zone Basic
Relay Expansion Board
The following describes the operation of each of the relays on the optional relay expansion board. You can choose the appropriate relays for any given application.
Relay #1 - Parallel Fan
If the Zone is in cooling mode or vent mode, the parallel fan can activate any time the zone temperature drops 0.5°F below the heating setpoint. It de-activates when the temperature rises above the heating setpoint. The space temperature must be below the AUX HEAT setpoint in the occupied mode before the Parallel Fan relay can be energized.
Relay #2 - Box Heat
If the zone is in cooling mode or vent mode, the box heat can activate any time the zone temperature drops 1.5°F below the heating setpoint. It de-activates when the temperature rises to within 1.0°F of the heating setpoint. Box heat is not allowed to activate in the heating mode when there is hot air being supplied by the air handling unit. This output was intended to allow zone re-heat while the Zone Manager is satisfying cooling demands in other zones. The space temperature must be below the AUX HEAT setpoint in the occupied mode before the Box Heat relay can be energized.
Relay #3 - Aux Heat
In the occupied mode, the aux heat can activate any time the zone temperature is 0.5°F below the aux heat setpoint. It de-activates when the temperature rises 0.5°F above the aux heat setpoint. In the unoccupied mode, the aux heat uses the unoccupied heating setpoint with the same deadband values mentioned above. This prevents the zone from maintaining the same aux heat setpoint at night that it does during the daytime.
This output was intended to allow zone heating to augment the normal heating mode and also to allow a zone an attempt to satisfy its own heating needs before creating a heating demand at the Zone Manager.
Relay #4 - Series Fan
The series fan runs any time the main fan is running. This includes occupied and unoccupied modes. The fan can only start running when the zone damper is closed, so it determines that the damper is closed before starting the fan.
1-18 Design Guide
Auto-Zone Basic
Index
Section 1
1 inch W.C. ......................................... 10
After-Hours
Overrides........................................... 7
Air
Bypassing.......................................... 6
Air Motion .......................................... 11
Auto-Zone Plus System ........................ 8
AUX HEAT
Setpoint ........................................... 18
Auxiliary Heat
Control Board ................................... 9
Control Options............................... 17
Recommendation .............................. 7
Barometric
Relief Dampers ................................. 7
Baseboard
Heat................................................. 17
Basic System
Design Guide .................................... 8
Diagram............................................. 2
Boards
Relay Expansion ............................. 18
Box Heat ............................................. 18
Building Pressurization......................... 7
Building Zones
Diagram............................................. 9
Bypass
Air ..................................................... 6
Plenum .............................................. 7
Return Air Intake .............................. 7
Bypass Damper
Overview........................................... 3
Sizing .......................................... 8, 11
Bypass Duct Size ................................ 11
Ceiling Diffuser .................................. 11
Central Unit
Sizing .......................................... 8, 10
CFM
Correct ............................................ 16
Maximum........................................ 11
Comfort............................................... 11
Cooling
Partial Load Conditions .................... 5
Cooling Load
Maximum.......................................... 8
Dampers
Slaved.............................................. 13
Design
Duct............................................. 8, 10
Room Air Motion.............................. 8
Zoning............................................... 8
Design Guide ........................................ 8
Diagrams
Basic System..................................... 2
Diffusers
Ceiling............................................. 11
High Induction ............................ 11
Selection...................................... 8, 11
Slot .................................................. 11
Dimensions
Rectangular Damper ....................... 14
Round Damper ................................ 14
Duct Design ........................................ 10
Considerations .................................. 8
Duct Static
High................................................... 6
Duct Static Pressure .............................. 3
Ducted Returns ..................................... 6
Ducts
Undersizing..................................... 10
Ductwork
Damaging.......................................... 6
Economizer
Benefits Of........................................ 6
Recommendation .............................. 5
Equipment
Oversizing......................................... 7
Exhaust
Powered............................................. 7
Exterior Zones....................................... 5
Global Override .................................... 7
Design Guide 1-19
Section 1
Auto-Zone Basic
Heat
Auxiliary ........................................... 7
Baseboard........................................ 17
Supplemental..................................... 9
Heating
Auxiliary ......................................... 17
Difficulties ........................................ 7
Partial Load Conditions .................... 7
Radiant Ceiling Panels.................... 17
Heating Load
Maximum.......................................... 8
Heating Minimum Setpoints................. 7
High Induction Diffusers .................... 11
High Pressure Switch
Manual Reset .................................... 6
Induction Ratio
High................................................. 11
Interior Zones........................................ 5
K Factors............................................. 16
Linear Slot Diffusers........................... 11
Load .................................................... 10
Diversity.......................................... 10
Load Calculation
Program........................................... 11
Load Estimating
Program........................................... 10
Lockout
Low Temp......................................... 5
Low Ambient Termperature Lockout ... 5
Low Supply Air Temperatures.............. 5
Low Temp Lockout............................... 5
Manual Reset
High Pressure Switch........................ 6
Maximum
CFM ................................................ 11
Cooling Load .................................... 8
Duct Velocity.................................. 10
Heating Load..................................... 8
Mechanical Safeties .............................. 5
Mutliple Zones...................................... 8
Negative Pressure Area....................... 12
Noise Levels ......................................... 6
Noise Problems ................................... 10
Operation
Quiet................................................ 10
Override
After-Hours....................................... 7
Conditions......................................... 7
Global................................................ 7
Oversizing
Equipment......................................... 7
Unit ................................................... 6
Overview
Auto-Zone System ............................ 3
Bypass Damper ................................. 3
Zone Controller................................. 3
Zone Manager ................................... 3
Zone Sensor ...................................... 4
Parallel Fan ......................................... 18
Partial Load Conditions ........................ 5
Aggravated........................................ 7
Heating.............................................. 7
Plenum Returns..................................... 6
Powered Exhaust................................... 7
Pressure Dependent............................. 10
Pressure Independent
Flow Factors ................................... 16
Zone Dampers................................. 16
Pressurization
Building ............................................ 7
Problems
Noise ............................................... 10
Program
Load Calculation............................. 11
Load Estimating.............................. 10
Quiet Operation................................... 10
Radiant Ceiling Panels........................ 17
Rectangular Damper
Dimensions ..................................... 14
Selection.......................................... 15
Relay Expansion Board ...................... 18
Relief Dampers
Barometric......................................... 7
Returns
Ducted............................................... 6
Plenum .............................................. 6
Room Air Motion................................ 11
Design ............................................... 8
Round Air Damper
Dimensions ..................................... 14
1-20 Design Guide
Auto-Zone Basic
Section 1
Selection.......................................... 15
Safeties.................................................. 5
Selection
Diffuser ....................................... 8, 11
Rectangular Damper ....................... 15
Room Air Motion............................ 11
Round Air Damper.......................... 15
Series Fan............................................ 18
Boxes............................................... 11
Setpoints
AUX HEAT .................................... 18
Heating Minimum............................. 7
Static Pressure................................... 6
Sizing
Bypass Damper ........................... 8, 11
Central Unit................................. 8, 10
Zone Dampers............................. 8, 13
Slaved
Dampers .......................................... 13
Slot Diffusers ...................................... 11
Linear .............................................. 11
Static Pickup Probe............................. 12
Static Pressure
Setpoint ............................................. 6
Setting ............................................... 7
Static Pressure Sensor........................... 3
Location .......................................... 12
Stratification........................................ 11
Supplemental
Heat................................................... 9
System
Design Guide .................................... 8
Overview........................................... 3
Performance ...................................... 9
Temperatures
Low Supply Air................................. 5
Temperature Lockout
Low Ambient .................................... 5
Undersizing
Ducts ............................................... 10
Units
Oversizing......................................... 6
Velocity
Maximum Acceptable..................... 13
Zone
Comfort............................................. 8
Design ............................................... 5
Diversity............................................ 5
Zone Controller
Overview........................................... 3
Zone Dampers
Pressure Independent ...................... 16
Sizing .......................................... 8, 13
Zone Heating
Auxiliary ......................................... 17
Zone Manager
Overview........................................... 3
Units Per ........................................... 8
Zone Sensor
Overview........................................... 4
Zones
Divided.............................................. 8
Exterior ............................................. 5
External............................................. 9
Interior .............................................. 5
Internal .............................................. 9
Multiple............................................. 8
Number Of ........................................ 8
Overlapping ...................................... 8
Perimeter........................................... 9
Zoning
Design ............................................... 8
Design Guide 1-21
Section 1
Auto-Zone Basic
1-22 Design Guide
Section 2
Table of Contents
Tips Before Beginning Installation..................................1
Zone Manager ..................................................................3
Communications Loop .....................................................8
Communications Loop Wiring Overview........................................................................9
Bypass Dampers ............................................................10
Zone Dampers................................................................13
Zone Controllers ............................................................14
Room Sensors ................................................................................................................21
Supply Air Temperature Sensor ....................................................................................23
Return Air Temperature Sensor.....................................................................................24
Outside Air Temperature Sensor ...................................................................................25
Duct Static Pressure Sensor ...........................................................................................26
Auxiliary Relay Board for Zone Controllers...................28
Zone Controller Auxiliary Relay Board Operation .......................................................29
CommLink IV Interface..................................................30
Basic System Worksheet................................................................................................33
Installation and Wiring
Section 2
Table of Figures
Figure 2-1: System Overview........................................................................................2
Figure 2-2: Typical System Component Locations.......................................................2
Figure 2-3: Zone Manager Dimensions ........................................................................3
Figure 2-4: Zone Manager Component Locations.........................................................4
Figure 2-5: Zone Manager Wiring.................................................................................5
Figure 2-6: Zone Manager Address Switch Setting ......................................................7
Figure 2-7: Communication Loop Wiring, Daisy-Chain Configuration .......................9
Figure 2-8: Round and Rectangular Bypass Dampers.................................................10
Figure 2-9: Bypass Damper Wiring.............................................................................12
Figure 2-10: Round and Rectangular Zone Dampers .................................................13
Figure 2-11: Zone Controller Components.................................................................15
Figure 2-12: Zone Controller Wiring..........................................................................17
Figure 2-13: Zone Controller Address Switch Settings..............................................19
Figure 2-14: Slaved Zone Controller Wiring..............................................................20
Figure 2-15: Room Sensor Installation .......................................................................21
Figure 2-16: Room Sensor Wiring..............................................................................22
Figure 2-17: Supply or Return Air Sensor Dimensions and Installation ....................23
Figure 2-18: Outside Air Temperature Sensor Dimensions and Installation..............25
Figure 2-19: Duct Static Pressure Sensor Dimensions and Installation .....................26
Figure 2-20: Static Pressure Sensor Wiring................................................................27
Figure 2-21: Auxiliary Relay Board Layout...............................................................28
Figure 2-22: CommLink IV Interface Communication Wiring..................................30
Figure 2-23: CommLink IV Interface Connections....................................................31
Figure 2-24: CommLink IVJumper Switch Settings ..................................................32
Installation and Wiring
Loading...
+ 120 hidden pages