Autonics
LCD Display Multi Panel Meter
MX4W SERIES
I N S T R U C T I O N M A N U A L
Please read the following safety considerations before use.
Safety Considerations
00
※
Please observe all safety considerations for safe and proper product operation to avoid hazards.
※
A
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or fire.
4. Check 'Connections' before wiring.
Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or fire.
1. When connecting the power/measurement input, use 24(0.20mm2) to AWG 15(1.65mm2) cable
and tighten the terminal screw with a tightening torque of 0.78 to 0.98N.m.
Failure to follow this instruction may result in re or malfunction due to contact failure.
2. Use the unit within the rated specications.
Failure to follow this instruction may result in re or product damage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or re.
4. Do not use the unit in the place where ammable/explosive/corrosive gas, humidity, direct
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in re or explosion.
5. Keep metal chip, dust, and wire residue from owing into the unit.
Failure to follow this instruction may result in re or product damage.
Model
Model Measurement input Power supply Output
MX4W-V-FN
MX4W-V-F1 NPN open collector output
MX4W-V-F2 PNP open collector output
MX4W-A-FN
MX4W-A-F1 NPN open collector output
MX4W-A-F2 PNP open collector output
Unit Description
1
5. Control output (OUT1/OUT2) indicator (red, indicator model white)
6. MAX/MIN indicator (green, indicator model white)
: When input is over/below the range,
7. AC/DC indicator (green, indicator model white)
8. Unit (V/mV/A/mA/Hz/%) indicator (yellow, indicator model white)
Dimensions
00
~
● Terminal cover
Connections and Insulated Block Diagram
00
※
Use terminals of size specied below.
l~I
MX4W-V-F
WC?J~
※
1: DC±500mV/±200mV/±50mV,
※
2: DC±20V/±5V/1-5V/±2V,
※
3: DC±500V/±200V/±50V,
※
4: For using DC power, connect wires regardless
NPN open collector output PNP open collector output
Specications
00
Model MX4W-V-F
Measurement input DC/AC voltage DC/AC current
Max. allowable input
Power supply 24-240VAC 50/60Hz, 24-240VDC
Allowable voltage range 90 to 110% of the rated voltage
Power supply Max. 5VA (24-240VAC
Display method
Display accuracy
Display cycle 0.2 to 5.0 sec (select per 0.1 sec)
A/D conversion method Sigma-Delta (
Sampling cycle DC input: 50ms (resolution 1/20,000), AC input: 16.6ms (resolution 1/20,000)
Max. display range -9999 to 9999 (4-digit)
Preset output
AC measurement
Frequency measurement
Insulation resistance Over 100MΩ (at 500VDC megger)
Dielectric strength 3,000VAC 50/60Hz for 1 min (between all terminals and case)
Noise immunity ±2kV the square wave noise (pulse width: 1㎲) by the noise simulator
Vibration
Shock
Environment
Insulation type
Approval
Weight
※
1: When using the unit at low temperature (below 0
※
2: Indicator model (MX4W-
※
3: AC, frequency measurement are available when input type is AC.
※
4: The weight includes packaging. The weight in parenthesis is for unit only.
※
Environment resistance is rated at no freezing or condensation.
※
The above specications are subject to change and some models may be discontinued without notice.
※
Be sure to follow cautions written in the instruction manual and the technical descriptions (catalog, homepage).
Thank you for choosing our Autonics product.
symbol represents caution due to special circumstances in which hazards may occur.
Failure to follow these instructions may result in serious injury or death.
Warning
Failure to follow these instructions may result in personal injury or product damage.
Caution
Warning
Caution
DC/AC voltage
DC/AC current
5 6 7 8
HHHH
91.5
4
96
93.7
a b
a
b
Min.
<Forked>
※
Hold/Zero
AC0-500mV/0-200mV/0-50mV
AC0-20V/0-5V/0-2V
AC0-500V/0-200V/0-110V/0-50V
of polarity.
OUT2OUT1 Hold/Zero
※
※
2
※
Mechanical
Malfunction
Mechanical 100m/s
Malfunction 300m/s
Ambient temp. -10 to 50
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
※
Control output operates normally.
3.0mm
※
1
8
l&
l
cey
※
2
※
3
DC input: approx. -110 to 110% of each measurement input range
AC input: approx. 110% of each measurement input range
12-segment (measurement value display part: white, character height: 19mm),
1
other display parts (red, green, yellow, indicator model: white) LCD method
23
℃±5℃
0℃ to 50℃ - DC/AC input: ±0.5% F.S. ±3-digit
NPN/PNP open collector output
Load voltage: max. 30VDC Load current: max. 100mA
Residual voltage: max. 1VDC
3
Select RMS value/AVG value measurement methods
※
3
Measurement range: 0.100 to 1200Hz (varies depending on the decimal point)
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Double insulation or reinforced insulation (mark:
measurement input part and the power part: 1kV)
Approx. 100g (approx. 77g)
-FN) does not have the function.
□
20
00
48
15.9
Max.
6.0mm
I
y
OUT1 OUT2
Hold/Zero
□ □
(when not using minus input: -10 to 110%)
- DC input: ±0.1% F.S. ±2-digit, AC input: ±0.3% F.S. ±3-digit
※
The terminal for 5A of current input, ±0.3% F.S. ±3-digit
※
The terminal for 5A of current input, ±1% F.S. ±3-digit
- ) analog-to-digital converter
2
(approx. 10G) in each X, Y, Z direction for 3 times
2
(approx. 30G) in each X, Y, Z direction for 3 times
, storage: -20 to 60
℃
24-240VAC 50/60Hz,
24-240VDC
1. Measurement value display part
MODE
2.
key
: Press the key to enter parameter groups, return RUN
mode, move parameters, or save the setting values.
2
3.
key
: Press the key to move digits, enter parameters, or
3
move parameter setting values.
4.
key
4
: Press the key to change digit value, enter or change
parameters, or chage the parameter setting value.
LLLL
or
appears.
●
Panel cut-out
52
Min.
I I I I I i I I
44.4
● Bracket
15 5
MX4W-A-F
※
4
SOURCE
24 240
VAC/VDC
※
5: DC±20mA/4-20mA/±5mA/±2mA,
AC0-20mA/0-5mA/0-2mA
※
6: DC±500mA/±200mA/±50mA,
AC0-500mA/0-200mA/0-50mA
※
7: DC±5A/±2A, AC0-5A/0-2A
※
8: Indicator model does not have the hold/zero
terminal.
Option output
and hold/zero
1 32 4 5 76 8 9
※
Input and output are insulated from the power.
50/60Hz), Max. 3W (24-240VDC )
(NPN), max. 2VDC (PNP)
℃
), display cycle is slow due to characteristics of LCD.
℃
Indicator
Indicator
Min.
36
※
8
Hold/Zero
ADC input circuit
and display part
MX4W-A-F
, dielectric strength between the
116
4.9
3
22
※
5
※
6
※
7
(unit: mm)
0.8
92
0
Power
※
4
SOURCE
24 240
VAC/VDC
10
Measurement Input
DC voltage DC current
Measurement
input range
0.0-500 0V
0-500V
0.0-200 0V
0-200V
0.00-50.00V
0.0-50 0V
0.00-20.00V
0.0-20 0V
0.000-5.000V
0.00-5 00V
1.000-5.000V
1.00-5 00V
0.000-2.000V
0.00-2 00V
0.0-500.0mV
0-500mV
0.0-200.0mV
0-200mV
0.00-50.00mV
0.0-50 0mV
-500.0-500 0V
-500-500V
-200.0-200 0V
-200-200V
-50.00-50 00V
-50.0-50 0V
-20.00-20 00V
-20.0-20 0V
-5.000-5 000V
-5.00-5 00V
-2.000-2 000V
-2.00-2 00V
-500.0-500 0mV
-500-500mV
-200.0-200 0mV
-200-200mV
-50.00-50 00mV
-50.0-50 0mV
AC voltage AC current
Measurement
input range
0.0-500 0V
0-500V
0.0-200 0V
0-200V
0.0-110 0V
0-110V
0.00-50.00V
0.0-50 0V
0.00-20.00V
0.0-20 0V
0.000-5.000V
0.00-5 00V
0.000-2.000V
0.00-2 00V
0.0-500 0mV
0-500mV
0.0-200 0mV
0-200mV
0.00-50 00mV
0.0-50 0mV
※
Display range of [
(-9999 to 9999, -999.9 to 999 9, -99.99 to 99 99, -9.999 to 9 999)
※
W
hen changing measurement input type,
SPAN/ERO/eSPN/H RG/L RG/D.UNT/OU
※
Frequency measurement range (AC voltage/current): 0.100 to 1200Hz
※
Check the unit indicator when selecting measurement input
※
Parameter setting order of input range [
E.g.) AC current:
※
When "
HHHH
then check the cables.
※
Connect to the input terminals whose 30% to 100% of the input range includs the max. value of the
input range to measure. When the max. input value is under the 30% of the input terminal range,
display accuracy is degraded. When the max. input value is over the 100%, it may result in input
terminal damage.
Preset Output Operation Mode
0
0.6
Operation
45
~001
Output operation Description
mode
OFF
~
OUT1 output
-
HIGH
OUT1 output
'
LOW
OUT1 output
-
HL
OUT1 output
-
HL G
OUT1 output
※
Set preset output mode separately for each
※
OUT1/OUT2 are operated individually depending on the set preset output operation mode.
※
High/low preset value parameters of the parameter 0 group appear by setting preset output
operation mode.
※
When changing preset output operation mode,
______
Input
Display range
impedance
[
STND
0.0 to 500 0 0.000-5 000A
0 to 500 0.00-5 00A
0.0 to 200 0 0.000-2 000A
4.062MΩ
0 to 200 0.00-2 00A
0.00 to 50 00 0.0-500 0mA
0.0 to 50 0 0-500mA
0.00 to 20 00 0.0-200 0mA
0.0 to 20 0 0-200mA
0.000 to 5 000 0.00-50 00mA
0.00 to 5 00 0.0-50 0mA
162kΩ
1.000 to 5 000 0.00-20 00mA
1.00 to 5 00 0.0-20 0mA
0.000 to 2 000 4.00-20 00mA
0.00 to 2 00 4.0-20 0mA
0.0 to 500 0 0.000-5 000mA
0 to 500 0.00-5 00mA
0.0 to 200 0 0.000-2 000mA
4kΩ
0 to 200 0.00-2 00mA
0.00 to 50 00 -5.000-5 000A
0.0 to 50 0 -5.00-5 00A
-500 0 to 500 0 -2.000-2 000A
-500 to 500 -2.00-2 00A
4.062MΩ
-200 0 to 200 0 -500.0-500 0mA
-200 to 200 -500-500mA
-50 00 to 50 00 -200.0-200 0mA
-50.0 to 50.0 -200-200mA
-20 00 to 20 00 -50.00-50 00mA
-20.0 to 20.0 -50.0-50 0mA
162kΩ
-5 000 to 5 000 -20.00-20 00mA
-5.00 to 5.00 -20.0-20 0mA
-2 000 to 2 000 -5.000-5 000mA
-2.00 to 2.00 -5.00-5 00mA
-500 0 to 500 0 -2.000-2 000mA
-500 to 500 -2.00-2
-200 0 to 200 0
4kΩ
-200 to 200
-50 00 to 50 00
-50.0 to 50.0
Input
Display range
impedance
[
STND
0 0 to 500.0 0.000-5 000A
0 to 500 0.00-5 00A
0 0 to 200.0 0.000-2 000A
4 062MΩ
0 to 200 0.00-2 00A
0 0 to 110 0 0.0-500 0mA
0 to 110 0-500mA
0 00 to 50.00 0.0-200 0mA
0 0 to 50.0 0-200mA
0 00 to 20.00 0.00-50 00mA
0 0 to 20.0 0.0-50 0mA
162kΩ
0 000 to 5.000 0.00-20 00mA
=====-+1==-===--==it====t-----t===
0 00 to 5.00 0.0-20 0mA
0 000 to 2.000 0.000-5 000mA
0 00 to 2.00 0.00-5
0 0 to 500.0 0.000-2 000mA
0 to 500 0.00-2 00mA
==_
0 0 to 200.0
4kΩ
0 to 200
0 00 to 50.00
0 0 to 50.0
] will vary depending on the decimal point.
%00
@000
→
→
" is flashes with a certain measurement input, disconnect power supply and
" or
Display
50)0
500
20)0
200
5)00
5)0
2)00
2)0
%000
%00
1 5A
1 5B
@000
@00
50)0
500
20)0
200
5)00
5)0
50)0
500
20)0
200
5)00
5)0
2)00
2)0
%000
%00
@000
@00
50)0
500
20)0
200
5)00
5)0
Display
50)0
500
20)0
200
11)0
110
5)00
5)0
2)00
2)0
%000
%00
@000
@00
50)0
500
20)0
200
5)00
5)0
SCAL
%000
"LLLL
Measurement
]
input range
Measurement
]
input range
-==t======~L____t=-----=______;
.H/OU .L/H.PEK/L.PEK/DISP/IN T/DOT/H SC/L SC
OU
□ □
.T/HYs
parameters are reset.
□
□
] is followed by the above table.
IN R
→
@000
→
→
00mA
00mA
@00
type.
Display
%000
%00
@000
@00
50)0
500
20)0
200
5)00
5)0
2)00
2)0
4A20
4B20
%000
%00
@000
@00
%000
%00
@000
@00
50)0
500
20)0
200
5)00
5)0
2)00
2)0
%000
%00
@000
@00
Display
%000
%00
@000
@00
50)0
500
20)0
200
5)00
5)0
2)00
2)0
%000
%00
@000
@00
[PA 2 group:
No output
~'
OUT1.H
~~
OUT1.L
~
OUT1.H
OUT1.L
~
OUT1.H
OUT1.L
~
'
-
'
Hysteresis
(
Hysteresis
(
Hysteresis
(
Hysteresis
(
No output
ON period: Display value ≥
)
HYS
OFF period: Display value ≤
ON period: Display value ≤
)
HYS
OFF period: Display value ≥
ON period: Display value ≤
)
HYS
OFF period: Display value ≥
ON period: Display value ≥
)
HYS
OFF period: Display value ≤
OUT1/OUT2.
/
H
OU L/HYs
OU
□□
Display value ≥
Display value ≤
Display value ≤
Display value ≥
are reset.
□ □
Input
impedance
0 02Ω
0 87Ω
21 87Ω
0 02Ω
0 87Ω
21 87Ω
Input
impedance
0 02Ω
0 87Ω
21 87Ω
OU!T/OU@T
OU!H
OU!H- HYs1
OU!L
OU!L+ HYs1
OU!L
OU!H
OU!L+ HYs1
OU!H- HYs1
OU!L
OU!H
OU!H- HYs1
OU!H+ HYs1
Factory Defaults
Group Parameter
i
~
I
PA0
(PA 0
group)
'
'
PA1
(PA 1
~
group)
~
-
~
~
'
~
~
PA2
- -
(PA 2
~
group)
~
I
※
1: Does not appear in indicator models.
※
2: t will vary depending on input range [
Cautions during Use
■
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting
the power.
3. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and
shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
Connection with the line lter Connection with the varistor
110/
220VAC
4. This unit may be used in the following environments.
Indoors (in the environment condition rated in 'Specifications')
①
Pollution degree 2
③
OU!H
OU!L
OU@H
OU@L
hPEK
lPEK
DCAC
IN R
DISP
IN T
DOT
H SC
L SC
S
PAN
ERO
eSPN
H RG
L RG
dUNT
OU!T
OU@T
HYs1
HYs2
STaT
PEaK
DIsT
DI T
LOC
MX4W-V
(DC)
※
1
※
1
※
1
※
1
※
1
※
1
※
1, ※2
※
1, ※2
Earth ground
MX4W-V
(±DC)
50)0 50)0 50)0 %000 %000 %000
00)0 50)0 00)0 )000 %000 )000
50)0 50)0 50)0 %000 %000 %000
00)0 50)0 00)0 )000 %000 )000
)0 )0 )0 )0 )0 )0
)0 )0 )0 )0 )0 )0
DC DC AC DC DC AC
50)0 50)0 50)0 %000 %000 %000
STND STND STND STND STND STND
- -
00)0 00)0 00)0 )000 )000 )000
50)0 50)0 50)0 %000 %000 %000
00)0 50)0 00)0 )000 %000 )000
!000 !000 !000 !000 !000 !000
00 00 00 00 00 00
- -
50)0 50)0
00)0 50)0
V V V A A A
OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF
0)1 0)1 0)1 )001 )001 )001
0)1 0)1 0)1 )001 )001 )001
0)0 0)0 0)0 0)0 0)0 0)0
00 S 00 S 00 S 00 S 00 S 00 S
)2 S )2 S )2 S )2 S )2 S )2 S
HOLD HOLD HOLD HOLD HOLD HOLD
OFF OFF OFF OFF OFF OFF
Install the ine fi ter close
to the panel meter
HI
Panel meter
LOW
IN R
110/
220VAC
MX4W-V
(AC)
] setting.
AVG
10 0
-
-
HI
Panel meter
LOW
MX4W-A
(DC)
- -
- -
%000 %000
)000 %000
Altitude max. 2,000m
②
Installation category II
④
MX4W-A
(±DC)
Display range
[
]
STND
0 000 to 5.000
0 00 to 5.00
0 000 to 2.000
0 00 to 2.00
0 0 to 500.0
0 to 500
0 0 to 200.0
0 to 200
0 00 to 50.00
0 0 to 50.0
0 00 to 20.00
0 0 to 20.0
4 00 to 20.00
4 0 to 20.0
0 000 to 5.000
0 00 to 5.00
0 000 to 2.000
0 00 to 2.00
-5.000 to 5.000
-5.00 to 5 00
-2.000 to 2.000
-2 00 to 2 00
-500.0 to 500.0
-500 to 500
-200.0 to 200.0
-200 to 200
-50.00 to 50.00
-50 0 to 50 0
-20.00 to 20.00
-20 0 to 20 0
-5.000 to 5.000
-5.00 to 5 00
-2.000 to 2.000
-2 00 to 2 00
Display range
[
]
STND
0 000 to 5.000
0 00 to 5.00
0 000 to 2.000
0 00 to 2.00
0 0 to 500.0
0 to 500
0 0 to 200.0
0 to 200
0 00 to 50.00
0 0 to 50.0
0 00 to 20.00
0 0 to 20.0
0 000 to 5.000
0 00 to 5.00
0 000 to 2.000
0 00 to 2.00
]
-
-
-
,
,
,
,
MX4W-A
(AC)
-
-
AVG
10 0
-
-
-
-
-
-
-
-
-
Zero Adjustment Reset
00
Forces the display value of measured input to 0 (Zero).
Zero adjustment range: -99 to 99
●
Zero adjustment method:
●
Hold + keys for 3 sec at the same time.
①
Set display holding/zero adjustment [
②
parameter 2 group as zero adjustment [
Short 3, 4 terminals and zero adjustment is
available.
※
When zero adjustment is completed by
, the display part displays zero and the
method
adjusted value is saved at [
1 group automatically.
※
If zero adjustment range is exceeded, the error
[
] flashes twice and it returns to RUN
OVER
mode, by maintaining previous setting value.
+ 3 sec
)15 )00
] of parameter
ERO
DI T
] of
ERO
①or②
00
RUN mode
MODE
+ + 5 sec
INiT NO YES
].
___
※
Flashes twice sequentially and returns to
1:
RUN mode.
Parameter Group
Parameter (0 to 2 group) setting
1. Each parameter and corresponding setting value will ash alternately every 0 5 sec.
2. Press the
3. If there is no key input for 60 sec, the unit will return to RUN mode.
4. Hold the
5. Press the , keys to change the set value.
(
※
※
1. Refer to
Parameter 0 group
MODE
OUT1 high-limit
OUT1 low-limit
OUT2 high-limit
OUT2 low-limit
Max. monitoring
Min. monitoring
Parameter 1 group
~!J
--
MODE
3 sec
!
□~
/
AC measurement
Standard
[
STN
display
[
-
Parameter 2 group
!J
r-
□-------------
MODE
OUT2 preset
output operation
-
OUT1 preset
-
-
OUT2 preset
compensation
Display period
Display value
Zero adjustment
Major Products
00
Photoelectric Sensors Temperature Controllers
■ ■
Fiber Optic Sensors Temperature/Humidity Transducers
■ ■
Door Sensors SSRs/Power Controllers
■ ■
Door Side Sensors Counters
■ ■
Area Sensors Timers
■ ■
Proximity Sensors Panel Meters
■ ■
Pressure Sensors Tachometers/Pulse (Rate) Meters
■ ■
Rotary Encoders Display Units
■ ■
Connector/Sockets Sensor Controllers
■ ■
Switching Mode Power Supplies
■
Control Switches/Lamps/Buzzers
■
I/O Terminal Blocks & Cables
■
Stepper Motors/Drivers/Motion Controllers
■
Graphic/Logic Panels
■
Field Network Devices
■
Laser Marking System (Fiber, Co₂, Nd:YAG)
■
Laser Welding/Cutting System
■
key to save the setting value and move to the next parameter.
~
key for 3 sec to return to RUN mode.
: moves digits, : changes setting value)
Dotted parameters may not appear by model type or other parameter settings.
Measurement Input Type And Range'.
RUN mode
MODE
preset value
preset value
preset value
preset value
value
value
RUN mode
MODE
D
:
---~-------
OU!H
MODE
OU!L
MODE
OU@H
MODE
OU@L
MODE
hPEK
reset
MODE
lPEK
reset
MODE
1-
□
2 sec
Max. value of
input range
Min. value of
input range
Max. value of
input range
Min. value of
input range
+
+
:
--------.
Does not appear when OUT1 preset output
-----~
operation mode [
※
1
as OFF/LOW.
Setting range: -9999 to 9999
Does not appear when OUT1 preset output
operation mode [
※
1
as OFF/HIGH.
Setting range: -9999 to 9999
Does not appear when OUT2 preset output
operation mode [
※
1
as OFF/LOW.
Setting range: -9999 to 9999
Does not appear when OUT2 preset output
※
1
operation mode [
as OFF/HIGH.
Setting range: -9999 to 9999
)0
Do not appear when monitoring delay time [
of parameter 2 group is set as 00 sec [
+ for over 1 sec, to reset the parameter.
the
)0
PA1
Input type
DCAC
MODE
Input range
IN-R
I
l°I
MODE
Display
DISP
MODE
IN-T
MODE
] at
]
ISP
Decimal point location
:··--·---
High-limit scale value
H-SC
Low-limit scale value
: f
L-SC
Span correction of
high limit value
SPAN
MODE
Deviation correction of
low limit value
ZERO
MODE
Unit
dUNT
MODE
3 sec
DC
Max. value of
input range
~
.:::::::::::::::::::
Standard
STND SCAL FREQ PF
AVG RMS
Scale [
] at
SCAL
display [
DOT
ISP
Setting range:
0, )0, )00, )000
MODE
MODE
~:
MODE
!000
00
Setting range:
RUN mode
MODE
4 sec
]
Max. value of
input range
Min. value of
input range
Setting range:
0.100 to 9.999
(times)
Setting range:
-99 to 99
-
DC AC
Input range varies depending on model, input type [
※
1
Scale Frequency Power factor
Frequency [
[
ISP
Decimal point location
Mantissa of gradient
※
1
correction for frequency
SPAN
: :::~ '
※
1
Index of gradient
correction for frequency
eSPN
,
,
,
,
H
A
MV
V
MA
※
Only appears in input type is set as [AC].
] (AC voltage/current)
Setting range:
DOT
0, )0, )00, )000
MODE
MODE
MODE
,
OFF
FREQ
Setting range:
0.100 to 9.999
(times)
Setting range:
-- @
] at display
!000
10-0
0 0,0
0 2,0
PA2
OUT1 preset
output operation
mode
mode
hysteresis
hysteresis
Startup
time
Monitoring
delay time
holding/
Lock
OU!T
MODE
OU@T OFF
MODE
HYs1 0)1
to , _________
'---r--~
MODE
HYs2 0)1
:::::_d
MODE
STaT 0)0
MODE
PEaK
MODE
DIsT
MODE
DI-T
MODE
LOC
MODE
OFF
__
~
____
:_::::::::
00 S
)2 5
HOLD
OFF
---•
Setting range:
,
Does not appear when preset output operation mode
,
[
OU!T, OU@T
Setting range: within 10% of max. display range of input
(if display range is over 10000, it is fixed as 999)
Setting range: 00 0 to 99.9 sec
Setting range: 00 to 30 sec
Setting range: 0 2 to 5.0 sec
Set display holding or zero adjustment by shorting 3, 4
terminals.
Setting range:
※
Does not appear at indicator models.
Setting range:
OFF
LOC1
※
Do not appear at indicator models.
OFF, HIGH, LOW, HL, HL G
] is set as
(display holding),
H L
Unlock
Lock parameter
1 group
MODE
L____J::::·:::i
] of parameter 2 group is set
OU!T
] of parameter 2 group is set
OU!T
] of parameter 2 group is set
OU@T
] of parameter 2 group is set
OU@T
,-------
@)
DC voltage/currentAC voltage/current
Power factor [PF] at display
[
] (DC voltage/current)
ISP
High-limit
input value
H-RG
:-r-••••1~---------------1
D
MODE
Low-limit
input value
:::::-d:wi---------------•
L-RG
MODE
,
.
OFF
ZER
Lock parameter
LOC2
1, 2 groups
Lock parameter
LOC3
0, 1, 2 groups
I I
MODE
INiT
;:::::::;
>>>>
50)0
PEaK
]. Hold
00 S
].
DCAC
_________
;
Max. value of
input range
'---------------'
Min. value of
input range
(zero adjustment)
※
1
]
※
1
※
1