8-PIN PLUG TYPE COUNTER
FS SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
00
Please observe all safety considerations for safe and proper product operation to avoid
※
hazards.
symbol represents caution due to special circumstances in which hazards may occur.
※
Failure to follow these instructions may result in serious injury or death.
Warning
Caution
Warning
1. Fail-safe device must be installed when using the unit with machinery that may
cause serious injury or substantial economic loss. (e.g. nuclear power control,
medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety
equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in re, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or re.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or re.
4. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in re.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or re.
Caution
1. When connecting the power/sensor input and relay output, use AWG 20(0.50mm2)
cable or over, and tighten the terminal screw with a tightening torque of 0.74 to 0.90N.m
Failure to follow this instruction may result in re or malfunc ion due to contact failure.
2. Use the unit within the rated specications.
Failure to follow this instruction may result in re or product damage.
3. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or re.
4. Do not use the unit in the place where ammable/explosive/corrosive gas, humidity,
direct sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in re or explosion.
5. Keep metal chip, dust, and wire residue from owing into the unit.
Failure to follow his instruc ion may result in re or product damage.
Dimensions
00
Bracket
44.9
※
The above specications are subject to change and some models may be
discontinued without notice.
※
Be sure to follow cautions written in the instruction manual and the technical
descriptions (catalog, homepage).
Failure to follow these instructions may result in personal injury or product damage.
12.3
48
10.5
63.8 14
■
45
□
Panel cut-out
Min. 65
30.5
36
i
.
'
55
45
48.6
□
[l]LE
J
Min. 65
56
(unit: mm)
Model
00
Model Display digit Size Output Power supply
FS4-1P2
FS4-1P4 100-240VAC 50/60Hz
FS5-I4 99999 (5-digit) Indicator 100-240VAC 50/60Hz
※8-pin
00
'
Model
Display digit 4-digit 5-digit
Character size (W×H) 3 8×7.6mm 4×8mm
Power supply
Permissible voltage range 90 to 110% of rated voltage
Power consumption
'
Max. counting speed for
COUNT IN
'
Return time Max. 500ms
'
Min. signal width RESET: approx. 20ms
Input method
One-shot output time 0 05 to 5 sec
I
Control
output
J
Relay
life cycle
Insulation resistance Over 100MΩ (at 500VDC megger)
External power supply Max. 12VDC
Memory retention Approx. 10 years (non-volatile memory)
Dielectric strength 2,000VAC 50/60Hz for 1 min (between all terminals and case)
Noise
immunity
Vibration
'
Shock
'
Environment
J
Protection structure IP20 (front part, EC standard)
Approval
.
Weight
※
1: The weight includes packaging. The weight in parenthesis is for unit only.
※
Environment resistance is rated at no freezing or condensation.
00
9999 (4-digit)
socket (PG-08, PS-08(N)) is sold separately.
D N W48×H48mm
I I
1-stage setting
Specications
1-stage setting FS4-1P2 FS4-1P4
I
Indicator
I
Contact
I
Mechanical Min. 5,000,000 operations
I
Electrical Min. 100,000 operations (250VAC 3A resistive load)
J
AC voltage ±2kV the square wave noise (pulse width 1㎲) by noise simulator
'
AC/DC voltage ±500V the square wave noise (pulse width 1㎲) by noise simulator
Mechanical
Malfunction
Mechanical 300m/s
Malfunction 100m/s
Ambient temp. -10 to 55℃, storage: -25 to 65
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
J
※
1
- -
24VACᜠ 50/60Hz,
24-48VDC
ᜡ
Max. 3 5VA
(24VACᜠ 50/60Hz),
Max. 2 3W (24-48VDC
Selectable 1cps/30cps/2kcps/5kcps (DIP switch)
Selectable voltage input (PNP) method or no-voltage input (NPN) method
[Voltage input (PNP) method]-input impedance: max. 10 8kΩ,
[No-voltage input (NPN) method]-short-circuit impedance: max. 470Ω,
Type Instantaneous SPST (1a)
Capacity 250VACᜠ 3A, 30VDCᜡ 3A resistive load
I
0.75mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z
direction for 1 hour
0 5mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z
direction for 10 minutes
2
(approx. 30G) in each X, Y, Z direction for 3 times
2
(approx. 10G) in each X, Y, Z direction for 3 times
CE
,'N:.
Approx. 130g (approx. 90g)
J J
±10% 50mA
ᜡ
l
_J
100-240VACᜠ 50/60Hz
I
Max. 4.6VA
(100-240VACᜠ
50/60Hz)
)
ᜡ
l
[H]: 5-30VDCᜡ, [L]: 0-2VDC
℃
Input Connection
24VAC 50/60Hz, 24-48VDC
short-circuit residual voltage: max. 1VDC,
open-circuit impedance: min. 100kΩ
Voltage input (PNP)
Solid state input (standard sensor: PNP output type sensor) Contact input
•
Sensor
(PNP output)
※
COUNT IN, RESET input part
Brown
Black
※
Blue
Counter
10.8kΩ
+12V
Inner circuit
0V
Sensor
(PNP open collector output)
Brown
Black
※
Blue
Counter
10.8kΩ
+12V
Inner circuit
0V
No-voltage input (NPN)
Solid state input (standard sensor: NPN output type sensor) Contact input
•
Sensor
(NPN output)
※
COUNT N, RESET input part
Connections
00
FS4-1P4
0
+ 0.6
45
PNP
NPN
FS5-I4
PNP
NPN
COUNT IN
RESET
COUNT IN
RESET
Counter
Brown
Black
※
Blue
0VDC
SOURCE:
100-240VAC 50/60Hz 4.6VA
0VDC
SOURCE:
100-240VAC 50/60Hz 3.8VA
+12V
5.4kΩ
Inner circuit
0V
12VDC 50mA
12VDC 50mA
CONTACT:
250VAC 3A,
30VDC 3A
RESISTIVE
LOAD
Sensor
(NPN open collector output)
Counter
Brown
Black
※
Blue
FS4-1P2
PNP
NPN
SOURCE:
24VAC 50/60Hz 3.5VA
24-48VDC 2.3W
+12V
5.4kΩ
Inner circuit
0V
COUNT IN
RESET
0VDC
FS5-I4
Max. 3 8VA
(100-240VACᜠ
j
50/60Hz)
-
~
J
Approx. 120g (approx. 80g)
•
Counter
※
•
※
12VDC 50mA
+12V
Inner
circuit
10.8kΩ
0V
※
Counting speed
: Set as 1 or 30cps
Counter
+12V
5.4kΩ
Inner
circuit
0V
※
Counting speed
: Set as 1 or 30cps
CONTACT:
250VAC 3A,
30VDC 3A
RESISTIVE
LOAD
DIP Switch Setting
00
I
C
0
-
Input logic (COUNT IN, RESET input)
•
SW1 Function
ON
NPN (no-voltage input)
OFF
1
ON
PNP (voltage input)
OFF
~
Up/Down mode
•
SW1 Function
ON
Down mode
-
J
OFF
2
ON
Up mode
OFF
~
Memory backup
•
SW1 Function
ON
No memory backup
OFF
6
ON
Memory backup
OFF
※
00
I
Output mode
(SW2)
F
OFF
N
OFF
C
OFF
R
OFF
K
OFF
P
OFF
Q
OFF
S
OFF
※
~
How to change settings
Power OFF → change settings → power ON → press
Output Operation Mode
One-shot output (0.05 to 5 sec) Self-holding output
·--
3 2 1
ON
3 2 1
ON
3 2 1
ON
3 2 1
ON
3 2 1
ON
3 2 1
ON
3 2 1
ON
3 2 1
ON
1■1■1■1
Set one-shot output time by front TIME volume switch.
SW1
RESET
Setting
0
Output
RESET
Setting
0
Output
RESET
Setting
0
Output
RESET
Setting
0
Output
RESET
Setting
0
Output
RESET
Setting
--'ZJZ:y-
0
Output
RESET
Setting
0
Output
RESET
Setting
0
Output
ON
2 23 34 5 6
2
ON
Up mode
OFF
: I :
I • •
※
1
3 2 1 6 5 4 3 2 1
ON
OFF
SW2
※
1: Indicator model (FS5-I4) does not have
no. 1, 2, 3 DIP switch of SW2 for output
operation mode setting.
Max. counting speed
•
SW1 Function
OFF
OFF
OFF
'
OFF
l
RESET
c:::::::::J
2
ON
SW1
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
RESET
Setting
Output
Down mode Operation
OFF
0
0
0
0
0
0
0
0
Output operation mode
Memory backup
Max. counting speed
N C (not used)
Up/Down mode
Input logic (NPN/PNP)
Factory default
SW1
5 4
ON
ON
ON
[l]
5 4
[;I;]
5 4
1cps
30cps
2kcps
~
5 4
ON
key or input signal (min. 20ms)
[!]
5kcps
J
After count-up, counting
display value increases
or decreases until reset
signal input is applied
and self-holding output
is maintained.
After count-up, counting
display value and selfholding output are
maintained until reset
signal input is applied.
When count-up,
counting display value
is reset and it counts
simultaneously.
After count-up, counting
display value is reset
after one-shot output
time and it counts
simultaneously.
After count-up, counting
display value increases
or decreases until reset
signal input is applied.
After count-up, counting
display value is
maintained while output
is ON. Counting value
is internally reset and it
counts simultaneously.
After count-up, counting
display value increases
or decreases during
one-shot output time.
Output maintains ON
when counting display
value is larger or equal
than setting value.
Dot for Decimal Point
RESET
value
RUN mode
RESET
c:::::::::J
DP
RESET
----
0
3 sec
Setting mode
Set decimal point
RESET
by front
Push the plug to
the front.
※
In run mode, hold the
3 sec, and it enters setting mode [DP].
※
In setting mode, hold the
over 3 sec, and it saves the setting and
returns to RUN mode.
※
If there is no
when entering setting mode, it returns to
RUN mode.
Down mode
•
RESET
+Max. display
value
-Max. display
0
value
RESET
key for over
c:=i
RESET
c:=i
RESET
key input for 60 sec
c:=i
n n
~
RESET
c:::::::::J
3 sec
Detaching Case
00
※
Turn OFF the power before detaching the case.
-
Push the grooves at both side of the unit with a at head driver to the outside and push the plug part
to the front. The plug is detached.
Be sure not to be wounded when using a tool.
Counting Operation for Indicator (FS5-I4)
00
J
Up mode
•
+Max. display
※
- display is only for F, K, Q, S output operation mode and it cannot be set.
Error Display and Output Operation
Error Display Error description Troubleshooting
ERR0
※
When error occurs, the output turns OFF.
※
Indicator model does not have error display function.
Setting value is 0. Change the setting value anything but 0.
Cautions during Use
1. Follow instructions in ‘Cautions during Use’. Otherwise, It may cause unexpected accidents.
2. 24-48VDC, 24VAC power supply should be insulated and limited voltage/current or Class 2,
SELV power supply device.
3. Use the product, 0.1 sec after supplying power.
4. When supplying or turning off the power, use a switch or etc. to avoid chattering.
5. Install a power switch or circuit breaker in the easily accessible place for supplying or
disconnecting the power.
6. In case of contact input, set count speed to low speed mode (1cps or 30 cps) to operate.
If set to high speed mode (2kcps or 5kcps), counting error occurs due to chattering.
7. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line lter or varistor at power
line and shielded wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency
noise.
8. This product may be used in the following environments.
Indoors (in the environment condition rated in ‘Specications’)
①
Altitude max. 2,000m
②
Pollution degree 2
③
Installation category II
④
Major Products
00
Photoelectric Sensors Temperature Controllers
■
Fiber Optic Sensors Temperature/Humidity Transducers
■
Door Sensors SSRs/Power Controllers
■
Door Side Sensors Counters
■
Area Sensors Timers
■
Proximity Sensors Panel Meters
■
Pressure Sensors Tachometers/Pulse (Rate) Meters
■
Rotary Encoders Display Units
■
Connector/Sockets Sensor Controllers
■
Switching Mode Power Supplies
■
Control Switches/Lamps/Buzzers
■
I/O Terminal Blocks & Cables
■
Stepper Motors/Drivers/Motion Controllers
■
Graphic/Logic Panels
■
Field Network Devices
■
Laser Marking System (Fiber, Co₂, Nd: YAG)
■
Laser Welding/Cutting System
■
■
■
■
■
■
■
■
■
■
DRW161277AC
key for