SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Table of contents ACExC 01.2 Intrusive HART
Read operation instructions first.
●
Observe safety instructions.
●
These operation instructions are part of the product.
●
Retain operation instructions during product life.
●
Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff . It is intended
to support device installation and commissioning.
Reference documents:
●
Manual (Operation and setting) AUMATIC AC 01.2 HART
●
Manual (Device integration) AUMATIC AC 01.2 HART
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contentsPage
112.2.Short description
123.Transport, storage and packaging........................................................................................
1.1.Basic information on safety
Standards/directives
Safety instructions/warn-
ings
Qualification of staff
AUMA products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others standards and directives such as IEC/EN 60079 “Electrical
apparatus for explosive atmospheres" –
●
Part 14: Electrical installations in hazardous areas (other than mines).
●
Part 17: Inspection and maintenance of electrical installations in hazardous
areas (other than mines).
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to av oid personal injury or property
damage.
Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitab ly qualified personnel ha ving been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosiv e atmospheres is subject to special regulations
which have to be observed.The end user or contractor of the plant are responsible
for respect and control of these regulations, standards, and laws.
Commissioning
Operation
Protective measures
Maintenance
Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Prerequisites for safe and smooth operation:
●
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●
Only operate the device if it is in perf ect condition while observing these instructions.
●
Immediately report any faults and damage and allow for corrective measures.
●
Observe recognised rules for occupational health and safety.
●
Observe the national regulations.
●
During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prevent possible burns, we recommend checking the surf ace temperature using an appropriate thermometer and wearing protective gloves, if required, prior to working on the device.
The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
T o ensure saf e device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2.Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
5
Page 6
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Safety instructions ACExC 01.2 Intrusive HART
The devices described below are approved for use in the potentially explosive
atmospheres of zones 1, 2, 21, and 22.
If temperatures >40 °C are to be expected at the valve mounting flange or the valve
stem (e.g. due to hot media), please consult AUMA.Temperatures > 40 °C are not
considered with regards to the non-electrical explosion protection.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information
These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3.Warnings and notes
The following warnings draw special attention to saf ety-rele v ant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. F ailure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury . Ma y also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4.References and symbols
The following references and symbols are used in these instructions:
InformationThe term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
< >Reference to other sections
T erms in brack ets shown abov e refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may quickly be found.
7
Page 8
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Identification ACExC 01.2 Intrusive HART
2.Identification
2.1.Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
[1]Actuator name plate
[2]Actuator controls name plate
[3]Motor name plate
[4]Additional plate, e.g. KKS plate (Power Plant Classification System)
[5]Explosion protection approval plate
8
Page 9
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Identification
Actuator name plate
Figure 2: Actuator name plate (example)
[1]Name of manufacturer
[2]Address of manufacturer
[3]Type designation
[4]Order number
[5]Actuator serial number
[6]Speed
[7]Torque range in direction CLOSE
[8]Torque range in direction OPEN
[9]Type of lubricant
[10]Enclosure protection
[11]Permissible ambient temperature
[12]Can be assigned as an option upon customer request
[13]Can be assigned as an option upon customer request
[14]Data Matrix code
Actuator controls name plate
[1]Type designation
[2]Order number
[3]Serial number
[4]Actuator terminal plan
[5]Actuator controls terminal plan
[6]Mains voltage
[7]AUMA power class for switchgear
[8]Permissible ambient temperature
[9]Enclosure protection
[10]Control
[11]Data Matrix code
9
Page 10
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Identification ACExC 01.2 Intrusive HART
Descriptions
Type designationFigure 3:Type designation (example)
1.Type and size of actuator
2.Flange size
3.Ex marking
Type and size
These instructions apply to the following devices types and sizes:
SAEx 07.2, 07.6, 10.2, 14.2, 14.6, 16.2 = multi-turn actuators for open-close duty
SAREx 07.2, 07.6, 10.2, 14.2, 14.6, 16.2 = multi-turn actuators for modulating duty
ACExC 01.2 = AUMATIC actuator controls
Ex marking
Table 1: Marking for explosion protection (with example)
1b3a-/
1st position: Not used
–
2nd position: motor type
ADX or VDX: 3-phase AC motor
a
AEX, ACX, VEX and VCX: 1-phase AC motor
b
3rd position: protection type of electrical connection
Terminal compartment Ex e increased safety:
3
Types: KP, KPH or KES
Terminal compartment Ex d flameproof enclosure:
4
Type: KES-Exd
4th position: protection type of position transmitter
Without intrinsically safe electric circuita
Electric circuit Ex i Intrinsic safety:
b
Type: RWG 5020.2Ex
5th position: protection type of position transmitter
Standard fieldbus connection1
Ex nL non incendive fieldbus connection2
Ex ic intrinsically safe fieldbus connection3
Order number
The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be compiled.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com, we offer a service allowing authorised
users to download order-related documents such as wiring diagrams and technical
data (both in German and English), inspection certificates and the operation
instructions when entering the order number.
Serial number
10
Table 2: Description of serial number (with example)
MD123451405
1st+2nd position: Assembly in week
Week 0505
3rd+4th position:Year of production
Year of production: 201414
All other positions
Internal number for unambiguous product identificationMD12345
Page 11
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Identification
Actuator terminal plan
AUMA power class for
switchgear
Data Matrix code
9th position after TPA: Position transmitter version
0 = Without position transmitter
A, B, J, K, L, N, R,T = Potentiometer
C, D, E, G, H, M, P, S, U = Electronic position transmitter
The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g. A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for.The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate. For the assignment of the AUMA po w er classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to an y power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
When registered as authorised user, you may use the AUMA Support App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number of serial number.
Figure 4: Link to the App store:
Control
2.2.Short description
Multi-turn actuator
Actuator controls
Local con-
trols/AUMA CDT
Intrusive - Non-Intrusive
Table 3: Control examples (indications on controls name plate)
DescriptionInput signal
Control via HART interfaceHART
HART/24 V DC
Control via HART interface and control voltage for OPEN - CLOSE
Control via digital inputs (OPEN, STOP, CLOSE)
Definition in compliance with EN ISO 5210:
A multi-turn actuator is an actuator which transmits to the valve a torque for at least
one full revolution. It is capable of withstanding thrust.
AUMA multi-turn actuators are driven by an electric motor and are capable of
withstanding thrust in combination with output drive type A. For manual operation,
a handwheel is provided. Switching off in end positions may be either by limit or
torque seating. Controls are required to operate or process the actuator signals.
The AUMATIC actuator controls are used to operate AUMA actuators and are supplied
ready for use.The controls may be mounted directly to the actuator or separately
on a wall bracket.
When set to local control, it is possible to
●
operate the actuator via the local controls (push buttons and display) and perf orm
settings (contents of these instructions).
●
read in or out data or modify and save settings via the AUMA CDT software
(accessories), using a computer (laptop or PC).The connection between computer and AUMATIC is wireless via Bluetooth interface (not included in these
instructions).
●
Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.
●
Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, actuator and controls
housings do not have to be opened. For this purpose, the actuator is equipped
with an MWG (magnetic limit and torque transmitter), also supplying analogue
torque feedback signals/torque indication and analogue position feedback signals/position indication.
11
Page 12
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Transport, storage and packaging ACExC 01.2 Intrusive HART
3.Transport, storage and packaging
3.1.Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→
Do NOT stand below hovering load.
→
Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→
Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→
Actuators mounted to gearboxes: Attach ropes or hooks f or the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→
Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2.Storage
Long-term storage
3.3.Packaging
Danger of corrosion due to inappropriate storage!
→
Store in a well-ventilated, dry room.
→
Protect against floor dampness by storage on a shelf or on a wooden pallet.
→
Cover to protect against dust and dirt.
→
Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
→
The AUMATIC actuator controls must NOT be stored below –30 °C.
If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1.Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2.At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show , apply ne w corrosion protection.
Our products are protected by special packaging for transport when leaving the
factory .The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
12
Page 13
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Assembly
4.Assembly
4.1.Mounting position
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
4.2.Handwheel fitting
InformationFor transport purposes, handwheels from a diameter of 400 mm are supplied separ-
ately.
Figure 5: Handwheel
[1]Spacer
[2]Input shaft
[3]Handwheel
[4]Circlip
1.If required, fit spacer [1] onto input shaft [2].
2.Slip handwheel [3] onto input shaft.
3.Secure handwheel [3] using the circlip [4] supplied.
4.3.Multi-turn actuator: mount to valve/gearbox
Danger of corrosion due to damage to paint finish and condensation!
→
Touch up damage to paint finish after work on the device.
→
After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.3.1.Output drive types B, B1 – B4 and E
●
Application
Design
For rotating, non-rising valve stem
●
Not capable of withstanding thrust
Output drive bore with keyway:
●
Types B1 – B4 with bore according to EN ISO 5210
●
Types B and E with bore according to DIN 3210
●
Later change from B1 to B3, B4, or E is possible.
13
Page 14
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Assembly ACExC 01.2 Intrusive HART
Figure 6: Output drive
[1]Output drive types B, B1 – B4, E and C
[2]Output drive sleeve/output drive plug sleve with bore and keyway
[3]Circlip
InformationSpigot at flanges should be loose fit.
4.3.1.1. Multi-turn actuator (with output drive types B1 – B4 or E): mount to valve/gearbox
1.Check if mounting flanges fit together.
2.Check whether bore and keyway match the input shaft.
3.Apply a small quantity of grease to the input shaft.
4.Place multi-turn actuator.
Information: Ensure that the spigot fits uniformly in the recess and that the
mounting faces are in complete contact.
5.Fasten multi-turn actuator with screws according to table.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
6.Fasten screws crosswise to a torque according to table.
Table 4: Tightening torques for screws
Tightening torque TA [Nm]Screws
Strength class 8.8Threads
25M8
51M10
87M12
214M16
431M20
4.3.2.Output drive type A
●
Application
Output drive for rising, non-rotating valve stem
●
Capable of withstanding thrust
InformationTo adapt the actuators to output drive types A av ailab le on site with flanges F10 and
F14 (year of manufacture: 2009 and earlier), an adapter is required.The adapter
can be ordered from AUMA.
14
Page 15
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Assembly
4.3.2.1. Stem nut: finish machining
This working step is only required if stem nut is supplied unbored or with pilot
✔
bore.
Figure 7: Design of output drive type A
[1]Stem nut
[2]Bearing
[2.1] Bearing race
[2.2] Bearing rim
[3]Spigot ring
1.Remove spigot ring [3] from output drive.
2.Remove stem nut [1] together with bearings [2].
3.Remove bearing races [2.1] and bearing rims [2.2] from stem nut [1].
4.Drill and bore stem nut [1] and cut thread.
Information: When fixing in the chuck, make sure stem nut runs true!
5.Clean the machined stem nut [1].
6.Apply sufficient Lithium soap EP multi-purpose grease to bearing rims [2.2] and
bearing races [2.1], ensuring that all hollow spaces are filled with grease.
8.Re-insert stem nut [1] with bearings [2] into output drive.
Information:Ensure that dogs or splines are placed correctly in the keyway of
the hollow shaft.
9.Screw in spigot ring [3] until it is firm against the shoulder.
15
Page 16
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Assembly ACExC 01.2 Intrusive HART
4.3.2.2. Multi-turn actuator (with output drive type A): mount to valve
Figure 8: Assembly with output drive type A
[1]Valve stem
[2]Output drive type A
[3]Screws to actuator
[4]Valve flange
[5]Screws to output drive
1.If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2.Check if the flange of output drive type A matches the valve flange [4].
3.Apply a small quantity of grease to the valve stem [1].
4.Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5.Turn output drive type A until alignment of the fixing holes.
6.Screw in fastening screws [5], however do not completely tighten.
7.Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
The flanges are flush with each other if properly engaged.
➥
8.Adjust multi-turn actuator until alignment of the fixing holes.
9.Fasten multi-turn actuator with screws [3].
10. Fasten screws [3] crosswise with a torque according to table.
Table 5: Tightening torques for screws
Tightening torque TA [Nm]Screws
Strength class 8.8Threads
11M6
25M8
51M10
87M12
214M16
431M20
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
16
Page 17
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Assembly
4.4.Accessories for assembly
4.4.1.Stem protection tube for rising valve stem
— Option —
Figure 9: Assembly of the stem protection tube
[1]Cap for stem protection tube
[2]Stem protection tube
[3]Sealing ring
1.Seal thread with hemp, Teflon tape, or thread sealing material.
2.Screw stem protection tube [2] into thread and tighten it firmly.
3.Push down the sealing ring [3] onto the housing.
4.Check whether cap for stem protection tube [1] is available and in perfect con-
dition.
4.5.Mounting positions of local controls
The mounting position of the local controls is selected according to the order. If , after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfav ourable position, the mounting position can be changed at a later date . F our
mounting positions are possible.
Figure 10: Mounting positions A and B
17
Page 18
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Assembly ACExC 01.2 Intrusive HART
Figure 11: Mounting positions C and D
4.5.1.Mounting positions: modify
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Before opening, ensure that there is no explosive gas and no voltage.
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
→
Do not jam cover during fitting.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→
Earth both operators and devices.
1.Loosen screws and remove the local controls.
2.Check whether O-ring is in good condition, correctly insert O-ring.
3.Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→
Turn local controls by a maximum of 180°.
→
Carefully assemble local controls to avoid pinching the cables.
Failure to observe this warning can result in death, serious injury , or property damage.
→
The electrical connection must be carried out exclusively by suitably qualified
personnel.
→
Prior to connection, observe basic information contained in this chapter.
→
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan
Permissible networks
(supply networks)
Protection on site
The pertaining wiring diagram/terminal plan (both in German and English) is attached
to the device in a weather-proof bag, together with these operation instructions. It
can also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
The controls (actuators) are suitable for for use in TN and TT networks with directly
earthed star point and a maximum voltage of 690 V AC. Use in IT networks is
permitted while observing the respective <Protection on site> for for maiximum supply
voltages of 600 V AC.
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
Table 6: Current consumption controls
Max. current consumptionMains voltage
–30 %±10 %Permissible variation of the mains voltage
1,200 mA750 mA100 to 120 V AC
750 mA400 mA208 to 240 V AC
400 mA250 mA380 to 500 V AC
400 mA200 mA515 to 690 V AC
Power supply for the
controls (electronics)
Safety standards
Table 7: Maximum permissible protection
Max. protectionRated powerSwitchgear
16 A (gL/gG)up to 1.5 kWReversing contactor A1
32 A (gL/gG)up to 7.5 kWReversing contactor A2
63 A (gL/gG)up to 11 kWReversing contactor A3
16 A (g/R) I²t<1,500A²sup to 1.5 kWThyristor B1
32 A (g/R) I²t<1,500A²sup to 3 kWThyristor B2
63 A (g/R) I²t<5,000A²sup to 5.5 kWThyristor B3
If controls are mounted separately from actuator (controls on wall brack et): Consider
length and cross section of connecting cable when defining the protection required.
Use appropriate insulation monitors when working in power installations, for e xample
an insulation monitor measuring the pulse code.
In case of external supply of the controls (electronics):The external power supply
must have a reinforced insulation against the mains voltage in accordance with IEC
61010-1 and may only be supplied by a circuit limited to 150 VA in accordance with
IEC 61010-1.
All externally connected devices shall comply with the relevant safety standards.
19
Page 20
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Electrical connection ACExC 01.2 Intrusive HART
Cable installation in ac-
cordance with EMC
Type of current, mains
voltage and mains fre-
quency
Signal and bus cables are susceptible to interference.
Motor cables are interference sources.
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●
Avoid long par allel paths with cab les being either susceptible to interf erence or
interference sources.
●
For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Figure 12: Motor name plate (example)
Connecting cables
HART cable recommend-
ation:
[1]Type of current
[2]Mains voltage
[3]Mains frequency (for 3-ph and 1-ph AC motors)
●
For device insulation, appropriate (v oltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cables with a minimum temperature range of +80 °C.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
Twisted wire pair, shielded.
For cable length <1 500 m: cross section min. 0.2 mm²
For cable length <1 500 m: cross section min. 0.5 mm²
We recommend selecting 0.75 mm² cross section. For smaller cable length cross
section, the cross section must be enlarged to min. 0.75 mm² using a wire end sleeve
if required and performing an appropriate concentric crimping.
Multiple-twisted pair cables must not be used.
Prior to installation, please note:
●
Connection is made as point-to-point topology.
●
Respect a distance of minimum 20 cm between HART cab les and other cables
if possible. If possible, the cab les should be laid in a separ ate , conductive, and
earthed cable tray.
●
Make sure that there are no potential differences between participants.
●
Maximum cable length depends on characteristics of devices connected (impedance), of cables used (cable capacity and resistance) and the impedance
of all devices installed between two end devices.
5.2.Connecting via Ex plug/socket connector with screw-type terminals (KP, KPH)
5.2.1.Terminal compartment: open
Figure 13: Ex plug/socket connector KPH
[1]Cover
[2]Screws for cover
[3]O-ring
[4]Terminal compartment
[5]Terminal board
5.2.2.Cable connection
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws [2] and remove cover [1].
Terminal compartment [4] is designed for explosion protection Ex e (increased
➥
safety).The flameproof compartment (type of protection Ex d) remains hereby
closed.
2.Insert cable glands with Ex e approv al and of size suitable f or connection cables.
The enclosure protection IP… stated on the name plate is only ensured if suit-
➥
able cable glands are used. Example: Name plate shows enclosure protection
IP68.
3.Seal cable entries which are not used with approved plugs suitable for the re-
quired protection type.
4.Insert the wires into the cable glands.
Table 8: Cross sections and tightening torques
Power terminals (U1, V1, W1)
PE connection
Control contacts (1 to 38)
(flexible or solid)
(flexible or solid)
Tightening torquesCross sectionsType
2 Nm(1.5)1) 2.5 – 6 mm²
1 Nm0.75 – 1.5 mm²
21
Page 22
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Electrical connection ACExC 01.2 Intrusive HART
with small clamp washers1)
Danger of corrosion: Damage due to condensation!
→
After mounting, commission the device immediately to ensure that heater minimises condensation.
1.Remove cable sheathing in a length of 120 – 140 mm.
2.Strip wires.
→
Controls max. 8 mm, motor 12 mm
3.For flexible cables: Use end sleeves according to DIN 46228.
4.Connect cables according to order-related wiring diagram.
Information: Two wires for each connection permitted.
→
When using motor cables with a cross section of 1.5 mm²: Use small clamp
washers for connection to terminals U1, V1, W1 and PE (the small clamp
washers are provided in the electrical connection cover).
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth conductor.
5.Tighten protective earth firmly to PE connection
Figure 14: PE connection
[1]PE connection, control cable
[2]PE connection, motor cable
InformationSome actuators are equipped with an additional motor heater.The motor heater
[1]Cover
[2]Screws for cover
[3]O-ring
[4]Terminal compartment
[5]Terminal board
1.Clean sealing faces of cover [1] and housing.
2.Check whether O-ring [3] is in good condition, replace if damaged.
3.Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
4.Fit cover [1] and fasten screws [2] evenly crosswise.
5.Fasten cable glands with the specified torque to ensure the required enclosure
protection.
23
Page 24
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Electrical connection ACExC 01.2 Intrusive HART
5.3.Connecting via Ex plug/socket connector with terminal blocks (KES)
5.3.1.Terminal compartment: open
Figure 16: Ex plug/socket connector: left KES, right KES flameproof
[1]Cover
[2]Screws for cover
[3]O-ring
[4]Terminal compartment: Type of protection Ex e
[5]Terminal compartment: Type of protection Ex d
[6]Frame
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws [2] and remove cover [1].
Terminal compartments [4] and [5] are designed either in type of protection Ex
➥
e (increased safety) or in type of protection Ex d (flameproof enclosure). Hereby,
the flameproof interior compartment of the actuator (Ex d) remains closed.
2.Insert cable glands with Ex e approval and suitable for connection cables.
The enclosure protection IP… stated on the name plate is only ensured if suit-
➥
able cable glands are used. Example: Name plate shows enclosure protection
IP68.
3.Seal cable entries unused cable entries with approved plugs suitable for the
required protection type.
4.Remove cable sheathing and insert the wires into the cable glands.
5.Fasten cable glands with the specified torque to ensure required enclosure
protection.
DesignFigure 19: Design principle with wall bracket
[1]Wall bracket
[2]Connecting cables
[3]Electrical connection of wall bracket (XM)
[4]Electrical connection of actuator (XA)
[5]Electrical connection of controls (XK) – customer connector
Observe prior to connec-
tion
5.4.2.Parking frame
Application
●
Permissible length of connecting cables: max. 100 m.
●
If the actuator is equipped with a position transmitter (RWG): Connecting cables
must be available as shielded version.
●
Versions with potentiometer in the actuator are not suitable.
●
We recommend: AUMA cable sets LSW8-KES or LSW9-KP.
●
If the AUMA cab le set is not used: Use suitab le flexib le and screened connecting
cables.
●
When using connecting cables, e.g. of the heater or switch, requiring direct
wiring from the actuator to the XK customer connector (XA-XM-XK, refer to
wiring diagram), these connecting cables must be subject to an insulation test
in compliance with EN 50178. Connecting cab les of position transmitters (RWG,
IWG, potentiometer) do not belong to this group.They may not be subject to
an insulation test.
Parking frame for safe storage of a disconnected plug.
For protection against touching the bare contacts and against environmental
influences.
Figure 20: Parking frame and Ex plug/socket connector with screw-type terminals
(KP/KPH)
27
Page 28
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Electrical connection ACExC 01.2 Intrusive HART
Figure 21: Parking frame and Ex plug/socket connector with terminal blocks (KES)
5.4.3.Protection cover
Protection cover for plug compartment when plug is removed.
The open terminal compartment can be closed using a protective cover (not
illustrated).
5.4.4.Earth connection, external
The housing is equipped with an external earth connection (U-bracket) to connect
the device to the equipotential earth bonding.
Figure 22: Earth connection
28
Page 29
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Operation
6.Operation
Valve damage due to incorrect basic setting!
→
Prior to electrical operation of the actuator, the basic settings i.e. type of seating,
torque and limit switching have to be completed.
6.1.Manual operation
For purposes of setting and commissioning, in case of motor failure or power f ailure,
the actuator may be operated manually. Manual operation is engaged b y an internal
change-over mechanism.
6.1.1.Manual operation: engage
Damage at the motor coupling due to faulty operation!
→
Engage manual operation only during motor standstill.
1.Press push button.
2.Turn handwheel in desired direction.
→
To close the valve, turn handwheel clockwise:
Drive shaft (valve) turns clockwise in direction CLOSE.
➥
6.1.2.Manual operation: disengage
Manual operation is automatically disengaged when motor is started again.The
handwheel does not rotate during motor operation.
6.2.Motor operation
Perform all commissioning settings and the test run prior to motor operation.
✔
6.2.1.Local actuator operation
Local actuator operation is performed using the push buttons of the local controls of
the AC.
29
Page 30
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Operation ACExC 01.2 Intrusive HART
Figure 23: Local controls
[1]Push button for operation command in direction OPEN
[2]Push button STOP
[3]Push button for operation command in direction CLOSE
[4]Push button RESET
[5]Selector switch
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
→
Check surface temperature and wear protective gloves, if required.
→
Set selector switch [5] to position Local control (LOCAL).
The actuator can now be operated using the push buttons [1 – 3].
➥
-
Run actuator in direction OPEN: Press push button [1] .
-Stop actuator: Press push button STOP [2].
-
Run actuator in direction CLOSE: Press push button [3] .
InformationOPEN - CLOSE operation commands can be given either in push-to-run or in self-
retaining operation mode. In self-retaining mode, the actuator runs to the defined
end position after pressing the button, unless another command has been received
beforehand. For further information, please refer to Manual (Operation and setting).
6.2.2.Actuator operation from remote
→
Set selector switch to position Remote control (REMOTE).
Actuator control from Remote can be made either via the analogue setpoint
➥
indication (4 – 20 mA) or via digital HART commands.
6.3.Menu navigation via push buttons (for settings and indications)
Menu navigation for display and setting is made via the push buttons [1 – 4] of the
local controls.
30
Page 31
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Operation
Set the selector switch [5] to position 0 (OFF) when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
Figure 24:
Backlight
[1–4] Push buttons or navigation support
[5]Selector switch
[6]Display
Table 10: Important push button functions for menu navigation
Push buttons
[1]
[2]
[3]
[4] C
●
The display is illuminated in white during normal operation.The backlight turns
port on display
Up ▲
Down ▼
Ok
Save
Edit
Details
Setup
Esc
FunctionsNavigation sup-
Change screen/selection
Change values
Enter figures from 0 to 9
Change screen/selection
Change values
Enter figures from 0 to 9
Confirm selection
Save
Enter <Edit> menu
Display more details
Enter Main menu
Cancel process
Return to previous display
to red under fault conditions.
●
The screen illumination is brighter when operating a push button. If no push
button is operated for 60 seconds, the display will become dim again.
6.3.1.Menu layout and navigation
Groups
The indications on the display are divided into 3 groups:
31
Page 32
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Operation ACExC 01.2 Intrusive HART
Figure 25: Groups
[1]Startup menu
[2]Status menu
[3]Main menu
Status menu and main menu are marked with an ID.
ID
Figure 26: Marking with ID
S
ID starts with S = status menu
M
ID starts with M = main menu
Group selection
Direct display via ID
It is possible to select between status menu S and main menu M:
For this, set selector switch to 0 (OFF), hold down push button C for approx. 2
seconds until a screen containing the ID M... appears.
Figure 27: Select menu groups
You return to the status menu if:
●
the push buttons on the local controls have not been oper ated within 10 minutes
●
or by briefly pressing C
When entering the ID within the main menu, screens can be displayed directly (without
clicking through).
Figure 28: Direct display (example)
Display indicates in the bottom row:Go to
1.
2.
3.
4.Repeat steps 2 and 3 for all further digits.
5.
6.4.User level, password
User level
The user level defines which menu items or par ameters can be displayed or modified
by the active user.
There are 6 different user levels.The user level is indicated in the top row:
32
Press push button Go to.
Display indicates:Go to menu M0000
Use push buttons Up ▲ Down ▼ to select figures 0 to 9.
Press push button Ok to confirm first digit.
To cancel the process: Press C Esc.
Page 33
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Operation
Figure 29: User level display (example)
Password
6.4.1.Password entry
A password must be entered to allow par ameter modification.The display indicates:
Password 0***
A specific password is assigned to each user level and permits different actions.
Table 11: User levels and authorisations
Authorisation/passwordDesignation (user level)
Observer (1)
Operator (2)
Maintenance (3)
Specialist (4)
Service (5)
AUMA (6)
1.
Select desired menu and hold down push button for approx. 3 seconds.
Display indicates the set user level, e.g Observer (1)
➥
2.
Press Up ▲to select a higher user level and press Ok to confirm.
Display shows:Password 0***
➥
3.
Use push buttons Up ▲ Down ▼ to select figures 0 to 9.
4.
Confirm first digit of password via push button Ok.
Verify settings
No password required
Change settings
Default factory password: 0000
Reserved for future extensions
Change device configuration
e.g. type of seating, assignment of output
contacts
Default factory password: 0000
Service staff
Change configuration settings
AUMA administrator
5.Repeat steps 1 and 2 for all further digits.
Having confirmed the last digit with Ok, access to all parameters within one
➥
user level is possible if the password entry is correct.
6.4.2.Password change
Select main menu
Only the passwords of same or lower user level may be changed.
Example:The user is signed in as Specialist (4).This authorises him or her to modify
the passwords between user levels (1) to (4).
Device configuration M0053
Service functions M0222
Change passwords M0229
Menu point Service functions M0222 is only visible if user level has been set to
Specialist (4) or higher.
1.Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
33
Page 34
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Operation ACExC 01.2 Intrusive HART
3.
Change passwords
Select parameter Change passwords either:
→
→
-
Display indicates:▶ Change passwords
click via the menu to parameter, or
via direct display: press and enter ID M0229
-The user level is indicated in the top row (1 – 6), e.g.:
-For user level 1 (view only), passwords cannot be changed.To change passwords, you must change to a higher user level. For this, enter a password via
a parameter.
4.
For a user level between 2 and 6: Press push button Ok.
The display indicates the highest user level, e.g.:For user 4
➥
5.
Select user level via push buttons Up ▲ Down ▼ and confirm with Ok.
Display indicates:▶ Change passwords Password 0***
➥
6.
Enter current password (→ enter password).
Display indicates:▶ Change passwords Password (new) 0***
➥
7.
Enter new password (→ enter password).
Display indicates:▶ Change passwords For user 4 (example)
➥
8.
Select next user lev el via push b uttons Up ▲ Down ▼ or cancel the process
via Esc.
6.5.Language in the display
The AUMATIC display is multilingual.
6.5.1.Language change
Display... M0009
Language M0049
Select main menu
Change language
1.Set selector switch to position 0 (OFF).
2.
➥
3.
➥
4.
➥
5.The bottom row of the display indicates:
6.
➥
7.
8.
➥
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
Press Ok.
Display indicates:▶ Language
Press Ok.
Display indicates the selected language, e.g.:▶ Deutsch
→
→
Save → continue with step 10
Edit → continue with step 6
Press Edit.
Display indicates:▶ Observer (1)
Select user level via Up ▲ Down ▼ resulting in the following significations:
→
→
black triangle:▶ = current setting
white triangle: ▷ = selection (not saved yet)
Press Ok.
Display indicates:Password 0***
34
Page 35
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Operation
9.
Enter password (→ enter password).
Display indicates:▶ Language and Save (bottom row)
➥
10.
Language selection
Select new language via Up ▲ Down ▼ resulting in the following significations:
→
→
11.
Confirm selection via Save.
The display changes to the new language.The new language selection is saved.
➥
black triangle:▶ = current setting
white triangle: ▷ = selection (not saved yet)
35
Page 36
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Indications ACExC 01.2 Intrusive HART
7.Indications
7.1.Indications during commissioning
LED test
Language selection
When switching on the power supply, all LEDs on the local controls illuminate for
approx. 1 second.This optical feedback indicates that the v oltage supply is connected
to the controls and all LEDs are operable.
Figure 30: LED test
During the self-test, the language selection can be activated so that the selected
language is immediately indicated in the display. For this, set selector switch [5] to
position 0 (OFF).
Activate language selection:
1.
Display indicates in the bottom row:Language selection menu? 'Reset'
2.Press push button RESET and hold it down until the following te xt is displayed
in the bottom line: Language menu loading, please wait.
Figure 31: Self-test
Startup menu
The language selection menu follows the startup menu.
The current firmware version is displayed during the startup procedure:
Figure 32: Startup menu with firmware version: 04.00.00–xxxx
If the language selection feature has been activated during the self-test, the menu
for selecting the display language will now be indicated. For further information on
language setting, please refer to chapter <Language in the display>.
Figure 33: Language selection
If no entry is made over a longer period of time (approx. 1 minute), the display
automatically returns to the first status indication.
7.2.Indications in the display
Status bar
The status bar (first row in the display) indicates the operation mode [1], the presence
of an error [2] and the ID number [3] of the current display indication.
36
Page 37
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Indications
Figure 34: Information in the status bar (top)
[1]Operation mode
[2]Error symbol (only for faults and warnings)
[3]ID number: S = Status page
Navigation support
If further details or information are available with reference to the displa y, the following
indications Details or More appear in the navigation support (bottom display row).
Then, further information can be displayed via the push button.
Figure 35: Navigation support (bottom)
[1]shows list with detailed indications
[2]shows further available information
The navigation support (bottom row) is faded out after approx. 3 seconds. Press any
push button (selector switch in position 0 (OFF)) to fade in the navigation support.
7.2.1.Feedback indications from actuator and valve
Display indications depend on the actuator version.
Valve position (S0001)
This indication is only available if a position transmitter (potentiometer, RWG or
MWG) is installed in the actuator.
●
S0001 on the display indicates the valve position in % of the travel.
●
The bargraph display appears after approx. 3 seconds.
●
When issuing an operation command, an arrow indicates the direction
(OPEN/CLOSE).
Figure 36:Valve position and direction of operation
Reaching the preset end positions is additionally indicated via symbols (CLOSED)
and (OPEN).
Figure 37: End position CLOSED/OPEN reached
0%Actuator is in end position CLOSED
100% Actuator is in end position OPEN
37
Page 38
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Indications ACExC 01.2 Intrusive HART
Torque (S0002)
The indication is only available if the actuator is equipped with an MWG (magnetic
limit and torque transmitter).
●
S0002 on the display indicates the torque applied at the actuator output.
●
The bargraph display appears after approx. 3 seconds.
Figure 38:Torque
Select unit
Display in percent
OPEN - CLOSE control
The push button allows to select the unit displayed (percent %, Newton metre Nm
or "foot-pound" ft-lb
Figure 39: Units of torque
100 % indication equals the max. torque indicated on the name plate of the actuator .
Example: SA 07.5 with 20 – 60 Nm.
●
100 % corresponds to 60 Nm of nominal torque.
●
50 % corresponds to 30 Nm of nominal torque.
Operation commands (S0003)
The display S0003 indicates:
●
active operation commands, lik e e.g.: Operation in direction CLOSE or in direction OPEN
●
the actual value E2 as bargraph indication and as v alue between 0 and 100 %.
●
for setpoint control (positioner): setpoint E1
●
for stepping mode or for intermediate positions with operation profile: pivot
points and operation behaviour of pivot points
The navigation support (bottom row) is faded out after approx. 3 seconds and the
axis/axes for pivot point display are shown.
Active operation commands (OPEN, CLOSE, ...) are shown above the bargraph
display. The figure below shows the operation command in direction CLOSE.
Figure 40: Display for OPEN - CLOSE control
E2Actual position value
38
Page 39
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Indications
Setpoint control
Pivot point axis
If the positioner is enabled and activated, the bargraph indication for E1 (position
setpoint) is displayed.
The direction of the operation command is displayed b y an arrow above the barg raph
indication.The figure below shows the operation command in direction CLOSE.
Figure 41: Display for setpoint control (positioner)
E1Position setpoint
E2Actual position value
The pivot points and their operation behaviour (operation profile) are shown on the
pivot point axis by means of symbols.
The symbols are only displayed if at least one of the f ollo wing functions is activ ated:
Operation profile M0294
Timer CLOSE M0156
Timer OPEN M0206
Figure 42: Examples: on the left pivot points (intermediate positions); on the right
stepping mode
Table 12: Symbols along the pivot point axis
Symbol
with operation profile
Stop during operation in direction
CLOSE
Stop during operation in direction
OPEN
OPEN and CLOSE
and CLOSE
Stepping modePivot point (intermediate position)
End of stepping modePivot point without reaction|
Start of stepping mode in direction
CLOSE
Start of stepping mode in direction
OPEN
–Stop during operation in directions
–Pause for oper ation in direction CLOSE
–Pause for oper ation in direction OPEN
–Pause for oper ation in directions OPEN
Multiport valve positions (S0017)
In case of active multiport valve function, the display S0017 indicates a second
bargraph display with set positions (valve connections) above the actual position
value E2. Positions (P1, P2, ...) are displayed with a black triangle . Push buttons
are used to select positions. Both positions and the actual position v alue E2 are
displayed in degrees.
39
Page 40
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Indications ACExC 01.2 Intrusive HART
Figure 43: Status indication for multiport valve (example P4 = 180°)
P(P1, P2, ...) selected position (1, 2, ...)
(– –) no position selected
E2Actual position value
7.2.2.Status indications according to AUMA classification
These indications are available, if the parameter Diagnostic classific. M0539 is set
to AUMA.
Warnings (S0005)
If a warning has occurred, the display shows S0005:
●
the number of warnings occurred
●
a blinking question mark after approx. 3 seconds
Figure 44:Warnings
For further information, please also refer to <Corrective action>.
Not ready REMOTE (S0006)
The S0006 display shows indications of the Not ready REMOTE group.
If such an indication has occurred, the display shows S0006:
●
the number of indications occurred
●
a blinking crossbar after approx. 3 seconds
Figure 45: Not ready REMOTE indications
For further information, please also refer to <Corrective action>.
Fault (S0007)
If a fault has occurred, the display shows S0007:
●
the number of faults occurred
●
a blinking exclamation mark after approx. 3 seconds
40
Page 41
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Indications
Figure 46: Fault
For further information, please also refer to <Corrective action>.
7.2.3.Status indications according to NAMUR recommendation
These indications are available, if the parameter Diagnostic classific. M0539 is set
to NAMUR.
Out of Specification (S0008)
The S0008 indication shows out of specification indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0008:
●
the number of indications occurred
●
a blinking triangle with question mark after approx. 3 seconds
Figure 47: Out of specification
For further information, please also refer to <Corrective action>.
Function check (S0009)
The S0009 indication shows function check indications according to NAMUR
recommendation NE 107.
If an indication has occurred via the function check, the display shows S0009:
●
the number of indications occurred
●
a blinking triangle with a spanner after approx. 3 seconds
Figure 48: Function check
For further information, please also refer to <Corrective action>.
Maintenance required (S0010)
The S0010 indication shows maintenance indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0010:
●
the number of indications occurred
●
a blinking square with an oil can after approx. 3 seconds
41
Page 42
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Indications ACExC 01.2 Intrusive HART
Figure 49: Maintenance required
For further information, please also refer to <Corrective action>.
Failure (S0011)
The S0011 indication shows the causes of the failure indication according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0011:
●
the number of indications occurred
●
a blinking circle with a cross after approx. 3 seconds
Figure 50: Failure
For further information, please also refer to <Corrective action>.
7.3.Mechanical position indicator/running indication
— Option —
Mechanical position indicator:
●
Continuously indicates the valve position
(For complete travel from OPEN to CLOSED or vice versa, the indicator disc
[2] rotates by approximately 180° to 230°.)
●
Indicates whether the actuator is running (running indication)
●
Indicates that the end positions are reached (via indicator mark [3])
Figure 51: Mechanical position indicator
[1]Cover
[2]Indicator disc
[3]Mark
[4]Symbol for position OPEN
[5]Symbol for position CLOSED
42
Page 43
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Indications
7.4.Indication lights
Figure 52: Arrangement and signification of indication lights
[1]Marking with symbols (standard)
[2]Marking with figures 1 – 6 (option)
End position CLOSED reached (blinking: for operation in direction CLOSE)
1
2 Tc Torque fault CLOSE
Motor protection tripped
3
4 To Torque fault OPEN
End position OPEN reached (blinking: for operation in direction OPEN)
5
Bluetooth connection
6
Modify indication light assignment (indications)
Different indications can be assigned to LEDs 1 – 5.
Indication light 1 (left) = End p. CLOSED, blink
Indication light 2 = Torque fault CLOSE
Indication light 3 = Thermal fault
Indication light 4 = Torque fault OPEN
Indicat. light 5 (right) = End p. OPEN, blink
Signal interm. pos. = OPEN/CLOSED = Off
Further setting values:
Refer to Manual (Operation and setting).
43
Page 44
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Signals ACExC 01.2 Intrusive HART
8.Signals
8.1.Signals via HART
HART offers different feedback signals. Configuration is possible for both data
structure and data contents.
For details regarding feedbac k signals via HART interf ace, please ref er to the Manual
(Device integration) HART.
8.2.Status signals via output contacts (digital outputs)
Characteristics
8.2.1.Assignment of outputs
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1 – 6) can be assigned to various signals.
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
8.2.2.Encoding of outputs
●
●
Required user level:Specialist (4) or higher.
Signal DOUT 1 M0109
High active = output contact closed = signal active
Low active = output contact open = signal active
8.3.Analogue signals
Valve position
44
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
For further information on this topic, please refer to Manual (Operation and setting).
[1]Setting spindle: End position CLOSED
[2]Pointer: End position CLOSED
[3]Mark: End position CLOSED is set
White section:
[4]Setting spindle: End position OPEN
[5]Pointer: End position OPEN
[6]Mark: End position OPEN is set
9.5.1.End position CLOSED (black section): set
1.Engage manual operation.
2.Turn handwheel clockwise until valve is closed.
3.T urn handwheel by approximately half a turn (overrun) in the opposite direction.
4.Press down and turn setting spindle [1] with screw driver in direction of the
arrow and observe the pointer [2]:While a ratchet click is felt and heard, the
pointer [2] moves 90° every time.
5.If the pointer [2] is 90° from mark [3]: Continue turning slowly.
6.If the pointer [2] moves to mark [3]: Stop turning and release setting spindle.
The end position CLOSED setting is complete.
➥
7.If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.5.2.End position OPEN (white section): set
1.Engage manual operation.
2.Turn handwheel counterclockwise until valve is open.
3.T urn handwheel by approximately half a turn (overrun) in the opposite direction.
4.Press down and turn setting spindle [4] with screw driver in direction of the
arrow and observe the pointer [5]:While a ratchet click is felt and heard, the
pointer [5] moves 90° every time.
5.If the pointer [5] is 90° from mark [6]: Continue turning slowly.
6.If the pointer [5] moves to mark [6]: Stop turning and release setting spindle.
The end position OPEN setting is complete.
➥
7.If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
49
Page 50
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Actuators equipped with DUO limit switching contain two intermediate position
switches. One intermediate position may be set for each running direction.
Figure 55: Setting elements for limit switching
Black section:
[1]Setting spindle: Running direction CLOSE
[2]Pointer: Running direction CLOSE
[3]Mark: Intermediate position CLOSED is set
White section:
[4]Setting spindle: Running direction OPEN
[5]Pointer: Running direction OPEN
[6]Mark: Intermediate position OPEN is set
InformationAfter 177 turns (control unit for 1 – 500 turns/stroke) or 1,769 turns (control unit for
1 – 5,000 turns/stroke), the intermediate switches release the contact.
9.6.1.Running direction CLOSE (black section): set
1.Move valve in direction CLOSE to desired intermediate position.
2.If you override the tripping point inadvertently:Turn valve in opposite direction
and approach intermediate position again in direction CLOSE.
Information: Always approach the intermediate position in the same direction
as in later electrical operation.
3.Press down and turn setting spindle [1] with screw driver in direction of the
arrow and observe the pointer [2]:While a ratchet click is felt and heard, the
pointer [2] moves 90° every time.
4.If the pointer [2] is 90° from mark [3]: Continue turning slowly.
5.If the pointer [2] moves to mark [3]: Stop turning and release setting spindle.
The intermediate position setting in running direction CLOSE is complete.
➥
6.If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.6.2.Running direction OPEN (white section): set
1.Move valve in direction OPEN to desired intermediate position.
2.If you override the tripping point inadvertently: Mov e v alv e in opposite direction
and approach intermediate position again in direction OPEN (always approach
the intermediate position in the same direction as in later electrical operation).
3.Press down and turn setting spindle [4] with screw driver in direction of the
arrow and observe the pointer [5]:While a ratchet click is felt and heard, the
pointer [5] moves 90° every time.
4.If the pointer [5] is 90° from mark [6]: Continue turning slowly.
5.If the pointer [5] moves to mark [6]: Stop turning and release setting spindle.
The intermediate position setting in running direction OPEN is complete.
➥
6.If you override the tripping point inadvertently (ratchet click is heard after the
pointer has snapped): Continue turning the setting spindle in the same direction
and repeat setting process.
9.7.Test run
Perform test run only once all settings previously described have been performed.
9.7.1.Direction of rotation: check
1.Move actuator manually to intermediate position or to sufficient distance from
end position.
2.Set selector switch to position Local control (LOCAL).
3.Switch on actuator in running direction CLOSE and observe the direction of
rotation:
with indicator disc: step 4
without indicator disc: step 5 (hollow shaft)
→
Switch off before reaching the end position.
4.With indicator disc:
→
Observe direction of rotation.
The direction of rotation is correct, if actuator runs in direction CLOSE
➥
and indicator disc turns counterclockwise.
51
Page 52
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
1.Set selector switch to position Local control (LOCAL).
2.Operate actuator using push buttons OPEN, STOP, CLOSE.
The limit switching is set correctly if (default indication):
➥
-the yellow indication light/LED1 is illuminated in end position CLOSED
-the green indication light/LED5 is illuminated in end position OPEN
-the indication lights go out after travelling into opposite direction.
The limit switching is set incorrectly if:
➥
-the actuator comes to a standstill before reaching the end position
-one of the red indication lights/LEDs is illuminated (torque fault)
-
the status indication S0007 in the display signals a fault.
3.If the end position setting is incorrect: Reset limit switching.
4.If the end position setting is correct and no options (e.g. potentiometer , position
transmitter) are available: Close switch compartment.
9.7.3.Reference operation position feedback: perform
For actuators with position feedback (RWG, potentiometer), a reference operation
has to be performed once the limit switching setting was changed to ensure that the
position feedback (0/4 – 20 mA) supplies correct values:
Operate actuator electrically (via the push buttons OPEN and CLOSE of the
local controls) once to end position OPEN and once to end position CLOSED.
9.8.Potentiometer
— Option —
The potentiometer is used as travel sensor and records the valve position.
Setting elements
The potentiometer is housed in the actuator switch compartment.The switch
compartment must be opened to perform any settings. ➔ Refer to <Switch
compartment: open>.
Setting is made via potentiometer [1].
Figure 57:View on control unit
[1]Potentiometer
9.8.1.Potentiometer setting
InformationDue to the ratio of the reduction gearing, the complete resistance range/stroke is not
always covered.Therefore, external adjustment (setting potentiometer) must be
provided.
1.Move valve to end position CLOSED.
2.Turn potentiometer [1] clockwise to the stop.
End position CLOSED corresponds to 0 %
➥
End position OPEN corresponds to 100 %
➥
3.Turn potentiometer [1] slightly in opposite direction.
4.Perform fine-tuning of the zero point at external setting potentiometer (f or remote
indication).
9.9.Electronic position transmitter RWG
— Option —
The electronic position transmitter RWG records the valve position. On the basis of
the actual position value measured by the potentiometer (tra vel sensor), it generates
a current signal between 0 – 20 mA or 4 – 20 mA.
Technical data
Table 13: RWG 4020
Max. load R
Load influence
B
2-wire system3-wire or 4-wire systemData
a
1)
V
600 Ω
4 – 20 mA0 – 20 mA, 4 – 20 mAOutput current I
14 V DC + (I x RB), max. 30 V24 V DC (18 – 32 V)Power supply U
20 mA24 mA at 20 mA output currentMax. current consumption
(UV – 14 V)/20 mA
0.1 %/V0.1 %/VImpact of power supply
0.1 %/100 Ω0.1 %/(0 – 600 Ω)
53
Page 54
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Power supply possible via: AC, AM controls or external power supply1)
Depending on temperature range of the actuator: Refer to name plate2)
–60 °C to +80 °CAmbient temperature
5 kΩ
Setting elements
The RWG is housed in the actuator switch compartment.The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via three potentiometers [1], [2] and [3].
Figure 58:View on control unit when switch compartment is open
[1]Potentiometer (travel sensor)
[2]Potentiometer min. (0/4 mA)
[3]Potentiometer max. (20 mA)
[4]Measuring point (+) 0/4 – 20 mA
[5]Measuring point (–) 0/4 – 20 mA
The output current (measuring range 0 – 20 mA) can be checked at measuring points
[4] and [5].
9.9.1.Measuring range: set
For measuring range setting, voltage must be applied at the position transmitter.
1.Move valve to end position CLOSED.
2.Connect ammeter for 0 – 20 mA to measuring points [4 and 5].
3.Turn potentiometer [1] clockwise to the stop.
4.Turn potentiometer [1] slightly in opposite direction.
5.Turn potentiometer [2] clockwise until output current starts to increase.
6.T urn potentiometer [2] in opposite direction until the follo wing v alue is reached:
-for 0 – 20 mA approx. 0.1 mA
-for 4 – 20 mA approx. 4.1 mA
This ensures that the signal remains above the dead and live zero point.
➥
7.Move valve to end position OPEN.
8.Set potentiometer [3] to end value 20 mA.
9.Approach end position CLOSED again and check minimum value (0.1 mA or
4.1 mA). If necessary, correct the setting.
InformationIf the maximum value cannot be reached, the selection of the reduction gearing must
be checked.
9.10.Mechanical position indicator: set
— Option —
Fault in end position
Actuator runs to end stop although the limit switches work
properly.
Position transmitter RWG
Measurement range 4 – 20 mA
or maximum value 20 mA cannot
be set.
Limit and/or torque switches do
not trip.
turns/stroke of the actuator.
The overrun was not considered when setting
the limit switching.
The overrun is generated by the inertia of
both the actuator and the valve and the dela y
time of the controls.
turns/stroke of the actuator.
Switch is defective or switch setting is incorrect.
Exchange reduction gearing.Reduction gearing is not suitable for
Determine overrun: Ov errun = trav el cov ered
from switching off until complete standstill.
Set limit switching again considering the
overrun (turn handwheel back by the amount
of the overrun).
Exchange reduction gearing.Reduction gearing is not suitable for
Check setting, if required, reset end positions.
→ Check switches and replace them, if re-
quired.
Switch check
The red test buttons [1] and [2] are used for manual operation of the switches:
1.T urn test button [1] in direction of the TSC arrow:Torque switch CLOSED trips.
3.Turn test button [2] in direction of the TSO arrow:Torque switch OPEN trips.
If the actuator is equipped with a DUO limit switching (option), the intermediate
position switches (LSA and LSB) will be operated at the same time as the torque
switches.
1.Turn test button [1] in direction of the LSC arrow: Limit switch CLOSED trips.
2.Turn test button [2] in direction of the LSO arrow: Limit switch OPEN trips.
10.2.Fault indications and warning indications
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation.They only serve
for information purposes.
Collective signals include further indications which can be displayed via the
Details push button.
Table 15: Faults and warnings via status indications in the display
Warnings S0005
Not ready REMOTE S0006
Fault S0007
Collective signal 02:
Indicates the number of active warnings.
Collective signal 04:
Indicates the number of active signals.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
For indicated value > 0:Description/causeIndication on display
Press push button Details.
For details, refer to <Warnings and Out of
specification> table.
Press push button Details.
For details, ref er to <Not ready REMOTE and
Function check> table.
Press push button Details to display a list
of detailed indications.
For details, ref er to <Faults and F ailure> tab le.
57
Page 58
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Corrective action ACExC 01.2 Intrusive HART
For indicated value > 0:Description/causeIndication on display
Out of specification S0008
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Press push button Details.
For details refer to <Warnings and Out of
specification> table.
Actuator is operated outside the normal operation conditions.
Function check S0009
Collective signal 08:
Indication according to NAMUR recommendation NE 107
Press push button Details.
For details, ref er to <Not ready REMOTE and
Function check> table.
The actuator is being worked on; output signals are temporarily invalid.
Maintenance required S0010
Collective signal 09:
Indication according to NAMUR recommenda-
Press push button Details to display a list
of detailed indications.
tion NE 107
Recommendation to perform maintenance.
Failure S0011
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Press push button Details to display a list
of detailed indications.
For details, ref er to <Faults and F ailure> tab le.
Actuator function failure, output signals are
invalid
Table 16: Warnings and Out of specification
Config. warning
Internal warning
24 V DC external
Wrn on time running
Wrn on time starts
Failure behav. active
Wrn input AIN 1
Wrn input AIN 2
Wrn setpoint position
Op. time warning
Wrn controls temp.
Wrn motor temp.
Wrn gearbox temp.
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restrictions.
Collective signal 15:
Device warnings
The device can still be operated with restrictions.
controls has exceeded the power supply limits.
Warning on time max. running time/h ex-
ceeded
Warning on time max. number of motor starts
(starts) exceeded
The failure behaviour is active since all required setpoints and actual values are incorrect.
position
Possible causes:
Input signal for setpoint = 0 (signal loss)
The set time (parameter Perm.op. time,manual M0570) has been exceeded.The
preset operating time is exceeded for a complete travel from end position OPEN to end
position CLOSED.
high
RemedyDescription/causeIndication on display
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Check 24 V DC voltage supply.The external 24 V DC voltage supply of the
●
Check modulating behaviour of actuator.
●
Check parameter Perm. running time/h
M0356, re-set if required.
●
Check modulating behaviour of actuator.
●
Check parameter Permissible starts/h
M0357, re-set if required.
Verify signals:
●
Setpoint E1
●
Actual value E2
●
Actual process value E4
Check wiring.Warning: Loss of signal analogue input 1
Check wiring.Warning: Loss of signal analogue input 2
Check setpoint signal.Warning: Loss of signal of actuator setpoint
The warning indications are automatically
cleared once a new operation command is
executed.
●
Check valve.
●
Check parameter Perm.op. time, manual
M0570.
Measure/reduce ambient temperature.Temperature within controls housing too high
Check actuator sizing, correct accordingly.Temperature within motor winding too high
Check actuator sizing, correct accordingly.T emper ature within actuator gear housing too
or could not be started.
No actuator reaction to operation commands
within the set reaction time.
(no or insufficient Rx receive lev el) or RS-485
format error (incorrect bit(s))
(critical or permissible Rx receive level)
Limit value for torque warning in direction
OPEN exceeded.
Limit value for torque warning in direction
CLOSE exceeded.
Set time.Real time clock has not yet been set.
Replace button cell.Voltage of the RTC button cell is too low.
Check actuator (PVST settings).Partial Valve Strok e Test (PVST) could not be
Perform RESET or restart PVST.Partial Valve Strok e Test (PVST) was aborted
●
Check movement at actuator.
●
Check parameter Reaction time M0634.
Check/repair FO cables.Optical receiving signal (channel 1) incorrect
Check/repair FO cables.Warning: FO cable system reserve reached
Fit FO cable connection.W arning FO cable connection is not availab le.
Check parameter Wrn torque OPEN M0768,
re-set if required.
Check parameter Wrn torque CLOSE M0769,
re-set if required.
Table 17: Faults and Failure
Configuration error
Config. error REMOTE
Internal error
Torque fault CLOSE
Torque fault OPEN
Phase fault
Incorrect phase seq
Collective signal 11:
Configuration error has occurred.
Collective signal 22:
Configuration error has occurred.
Collective signal 14:
Internal error has occurred.
Torque fault in direction CLOSE
Torque fault in direction OPEN
●
When connecting to a 3-ph AC system and
with internal 24 V DC supply of the electronics: Phase 2 is missing.
●
When connecting to a 3-ph or 1-ph AC
system and with external 24 V DC supply
of the electronics: One of the phases L1,
L2 or L3 is missing.
The phase conductors L1, L2 and L3 are
connected in the wrong sequence.
Only applicable if connected to a 3-ph AC
system.
RemedyDescription/causeIndication on display
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
AUMA service
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Perform one of the following measures:
●
Issue operation command in direction
OPEN.
●
Set selector switch to position Local control (LOCAL) and reset fault indication via
push button RESET.
Perform one of the following measures:
●
Issue operation command in direction
CLOSE.
●
Set selector switch to position Local control (LOCAL) and reset fault indication via
push button RESET.
Test/connect phases.
Correct the sequence of the phase conductors
L1, L2 and L3 by exchanging two phases.
59
Page 60
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Corrective action ACExC 01.2 Intrusive HART
RemedyDescription/causeIndication on display
Mains quality
Thermal fault
Due to insufficient mains quality, the controls
cannot detect the phase sequence (sequence
of phase conductors L1, L2 and L3) within the
pre-set time frame provided for monitoring.
Motor protection tripped
●
Check mains voltage.
●
Check parameter Tripping time M0172,
extend time frame if required.
●
Cool down, wait.
●
If the fault indication display persists after
cooling down:
Set selector switch to position Local
-
control (LOCAL) and reset fault indication via push button RESET.
●
Check fuses.
Fault no reaction
Check movement at actuator.No actuator reaction to operation commands
within the set reaction time.
Table 18: Not ready REMOTE and Function check (collective signal 04)
RemedyDescription/causeIndication on display
Wrong oper. cmd
Sel. sw. not REMOTE
Service active
Disabled
EMCY stop active
EMCY behav. active
I/O interface
Handwheel active
Interlock
Interlock by-pass
PVST active
Collective signal 13:
Possible causes:
●
Several oper ation commands (e.g. OPEN
and CLOSE simultaneously , or OPEN and
SETPOINT operation simultaneously)
●
A setpoint is present and the positioner is
not active
●
For fieldbus: Setpoint exceeds 100.0 %
service software AUMA CDT.
Actuator is in operation mode Disabled.
The EMERGENCY stop switch has been operated.The motor control power supply (contactors or thyristors) is disconnected.
Operation mode EMERGENCY is active
(EMERGENCY signal was sent).
0 V are applied at the EMERGENCY input.
(parallel).
●
Check operation commands (send one
operation command only).
●
Set parameter Positioner to Function act-
ive.
●
Check setpoint.
Press push button Details to display a list
of individual indications.
For a description of the individual signals, refer
to Manual (Operation and setting).
Set selector switch to position REMOTE.Selector switch is not in position REMOTE.
Exit service software.Operation via service interface (Bluetooth) and
Check setting and status of function <Local
controls enable>.
●
Enable EMERGENCY stop switch.
●
Reset EMERGENCY stop state by means
of Reset command.
●
Detect cause for EMERGENCY signal.
●
Verify failure source.
●
Apply +24 V DC at EMERGENCY input.
Check I/O interface.The actuator is controlled via the I/O interface
Start motor operation.Manual operation is activated.
Check interlock signal.An interlock is active.
Check states of main and by-pass valve.By-pass function is interlocked.
Wait until PVST function is complete.Partial Valve Stroke Test (PVST) is active.
10.3.Fuses
10.3.1.Fuses within the actuator controls
Fuses used
F1/F2
60
Primary fuses on power supply unit
Power supply ≤ 500 V
Power supply > 500 V
AUMA art. no.F1/F2G fuse
6.3 x 32 mmSize
K002.2771 A T; 500 VReversing contactors
K002.2771 A T; 500 VThyristor units for motor power up to 1.5 kW
Thyristor units for motor power up to 3.0 kW
Thyristor units for motor power up to 5.5 kW
Internal 24 V DC supply
F3
AUMA art. no.F3G fuse according to IEC 60127-2/III
5 x 20 mmSize
K006.1062.0 A T; 250 VVoltage output (power supply unit) = 24 V
K006.1062.0 A T; 250 VVoltage output (power supply unit) = 115 V
Internal 24 V AC supply (115 V AC) for:
F4
●
Heater, switch compartment, reversing contactors control
●
PTC tripping device
●
for 115 V AC also control inputs OPEN - STOP - CLOSE
AUMA art. no.F4G-fuse according to IEC 60127-2/III
5 x 20 mmSize
K001.1841.25 A T; 250 VVoltage output (power supply unit) = 24 V
——Voltage output (power supply unit) = 115 V
Automatic reset fuse as short-circuit protection for external 24 V DC supply for
F5
customer (see wiring diagram)
Replace fuses F1/F2
InformationOnly valid for version with electrical connection of KES type.
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws [1] and remove plug/socket connector [2].
2.Pull fuse holder [3] out of pin carrier, open fuse cover and replace old fuses by
new ones.
Fuses F3/F4 (F1/F2): test /replace
InformationFor versions with electrical connection type KP/KPH, the fuses (F1/F2) are located
on the PSU board.
61
Page 62
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Corrective action ACExC 01.2 Intrusive HART
1.Loosen screws [1] and remove cover [2] on the rear of the actuator controls.
The power supply unit has measurement points (solder pins) allowing to perf orm
a resistance (continuity) measurement:
2.T o replace def ectiv e fuses:. Carefully loosen power supply unit [3] and pull out.
(The fuses are on the equipped part of the power supply board).
Cable damage due to pinching!
Risk of functional failures.
→
Carefully assemble power supply unit to avoid pinching the cables.
10.3.2.Motor protection (thermal monitoring)
In order to protect against overheating and impermissibly high surface temper atures
at the actuator, PTC thermistors or thermoswitches are embedded in the motor
winding.The thermoswitch is tripped as soon as the max. permissible winding
temperature has been reached.
The actuator is switched off and the following signals are given:
●
LED 3 (thermal fault) on the local controls is illuminated.
●
Status indication S0007 displays a fault.The fault Thermoswitch is displayed
when selecting Details.
The motor has to cool down before the operation can be resumed. Depending on
the parameter setting, the fault signal is either automatically reset or the f ault signal
has to be reset using the push button Reset in selector switch position LOCAL.
For further information to this topic, please refer to Manual (Operation and setting).
62
Page 63
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Servicing and maintenance
11.Servicing and maintenance
Damage caused by inappropriate maintenance!
→
Servicing and maintenance must be carried out exclusively by suitably qualified
personnel having been authorised by the end user or the contractor of the plant.
Therefore, we recommend contacting our service.
→
Only perform servicing and maintenance tasks when the device is switched off.
AUMA
Service & Support
AUMA off er extensiv e service such as servicing and maintenance as well as customer
product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com).
11.1.Preventive measures for servicing and safe operation
The following measures are required to ensure safe device operation:
6 months after commissioning and then every year
●
Carry out visual inspection:
Cable entries, cable glands, b lanking plugs, etc. have to be checked for correct
tightness and sealing.
Respect torques according to manufacturer's details.
●
Check fastening screws between actuator and gearbox/valve for tightness. If
required, fasten screws while applying the tightening torques as indicated in
chapter <Assembly>.
●
When rarely operated: Perform test run.
●
For devices with output driv e A: Press in Lithium soap EP m ulti-purpose grease
on mineral oil base at the grease nipple with a grease gun.
●
Lubrication of the valve stem must be done separately.
Figure 59: Output drive type A
[1]Output drive type A
[2]Grease nipple
Table 19: Grease quantities for bearing of output drive type A
1)
For grease at density r = 0.9 kg/dm³1)
For enclosure protection IP68
After continuous immersion:
●
Check actuator.
●
In case of ingress of water, locate leaks and repair, dry device correctly and
check for proper function.
11.2.Disconnection from the mains
If the device must be dismantled, e.g. for service purposes, it can be separated from
the mains without having to remove the wiring.
A 16.2A 14.2A 10.2A 07.2Output drive
5321.5Quantity [g]
63
Page 64
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Servicing and maintenance ACExC 01.2 Intrusive HART
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Before opening, ensure that there is no explosive gas and no voltage.
→
Handle cover and housing parts with care.
→
Joint surfaces must not be damaged or soiled in any way.
2.Remove plug/socket connector.
Hereby, cover [1] and terminal board [5] or frame [6] remain together.
➥
3.Seal open plug/socket connection, e.g. using AUMA protection cover and
parking frame.
4.Clean sealing faces at the cover and the housing.
5.Preserve joint surfaces with an acid-free corrosion protection agent.
6.Check whether O-ring [3] is in good condition, replace if damaged.
7.Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
8.Replace plug/socket connector and fasten screws evenly crosswise.
●
In the factory, the gear housing is filled with grease.
●
Grease change is performed during maintenance
-Generally after 4 to 6 years for modulating duty.
-Generally after 6 to 8 years if operated frequently (open-close duty).
-Generally after 10 to 12 years if operated rarely (open-close duty).
●
We recommend exchanging the seals when changing the grease.
64
Page 65
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Servicing and maintenance
●
No additional lubrication of the gear housing is required during operation.
●
Notes regarding the
maintenance
Check actuator visually. Ensure that no outside damage or changes are visible.
●
The electric connection cables must be without damage and wired correctly.
●
Do a thorough touch-up of possible damage to paint finish to prev ent corrosion.
Original paint in small quantities can be supplied by AUMA.
●
Cable entries, cable glands, plugs etc. have to be checked for correct tightness
and sealing. Consider torques according to manufacturer's details. If required,
replace the components. Only use components which have an EC type examination certificate.
●
Check whether Ex connections are fastened correctly.
●
Take care of possible discolouration of the terminals and wires.This would indicate an increased temperature.
●
For Ex housings, pay special attention to a possible collection of water.This
may originate from “breathing” due to severe temperature variations (e. g.
change of night and day), from damaged seals etc. Remov e any w ater immediately.
●
Check the flame path gaps of flameproof enclosures for dirt and corrosion.
●
Since the dimensions of all flameproof joints are strictly defined and inspected,
no mechanical work (such as grinding) shall be performed on them.The joint
surfaces have to be cleaned chemically (e. g. with Esso-Varsol).
●
Prior to fitting, preserve joint surfaces with an acid-free corrosion protection
agent (e. g. Esso Rust-BAN 397).
●
Ensure that all housing covers are handled carefully and that the seals are
checked.
●
All cable and motor protection components have to be checked.
●
If defects impairing the safety are detected during maintenance, repair measures
have to be initiated without delay.
●
Any kind of surface coating for the joint surfaces is not permitted.
●
When exchanging parts, seals etc. only original spare parts shall be used.
11.4.Disposal and recycling
Our devices have a long lifetime. However, they have to be replaced at one point in
time.The devices have a modular design and may, therefore, easily be separated
and sorted according to materials used, i.e.:
●
●
●
●
The following generally applies:
●
●
●
electronic scrap
various metals
plastics
greases and oils
Greases and oils are hazardous to water and must not be released into the
environment.
Arrange for controlled waste disposal of the disassembled material or for separate recycling according to materials.
Observe the national regulations for waste disposal.
65
Page 66
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Technical data ACExC 01.2 Intrusive HART
12.Technical data
InformationThe following technical data includes standard and optional features. For detailed
information on the customer-specific version, refer to the order-related data sheet.
The technical data sheet can be downloaded from the Internet at www.auma.com
in both German and English (please state the order number).
12.1.Technical data Multi-turn actuators
Features and functions
Standard version (ATEX):
●
II 2G Ex de IIC (IIB, IIB+H2) T4 (T3) Gb
●
II 2D Ex tb IIIC T130°C (T190°C) Db IP68
●
II 2G c IIC T4
Standard version (IECEx):
●
Ex de IIC (IIB, IIB+H2) T4 (T3) Gb
●
Ex tb IIIC T130°C (190°C) Db IP68
Short-time duty S2 - 15 min (multi-turn actuators for open-close duty)
Intermittent duty S4 - 25 % (multi-turn actuators for modulating duty)
Short-time duty S2 - 30 min (multi-turn actuators for open-close duty)
Intermittent duty S4 - 50 % (multi-turn actuators for modulating duty)
3-ph AC asynchronous motor, type IM B9 according to IEC 60034Standard:Motors
1-phase AC motor, type IM B9 according to IEC 60034
DC shunt motor, type IM B14 according to IEC 60034
DC compound motor, type IM B14 according to IEC 60034
F, tropicalizedStandard:Insulation class
H, tropicalizedOption:
3-phase and 1-phase AC current motors: PTC thyristors (according to DIN 44082)
DC motors:Without
Thermoswitches (NC) in the actuator and in the thermal overload relay of controlsOption:
110 – 120 V AC, 220 – 240 V AC or 400 V AC (externally supplied)Voltages:Motor heater (option)
Handwheel lockable
Handwheel stem extension
Power tool for emergency operation with square 30 mm or 50 mm
EC type examination certificate
Mains voltage, mains frequency
Self-locking
Manual operation
Indication for manual operation
(option)
Standard:Explosion protection
For actual version, refer to actuator name plate
DEKRA 11 ATEX 0008 X
DEKRA 12 ATEX 0143 X
IECEx DEK 12.0022 X
Standard:Type of duty
Option:
For nominal voltage and 40 °C ambient temperature and at average load with 35 % of the
max. torque
Option:
Refer to motor name plate
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 % (for 3-phase and 1-phase AC current)
Category III according to IEC 60364-4-443Overvoltage category
Standard:Motor protection
Self-locking: Output speeds up to 90 rpm (50 Hz), 108 rpm (60 Hz)
NOT Self-locking: Output speeds up to 125 rpm (50 Hz), 150 rpm (60 Hz)
Multi-turn actuators are self-locking, if the valve position cannot be changed from standstill
while torque acts upon the output drive.
Power depending on the size 12.5 – 25 W
Manual drive for setting and emergency operation, handwheel does not rotate during elec-
trical operation.
Option:
Indication whether manual operation is active/not active via single switch (1 change-over
contact)
66
Page 67
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Technical data
Features and functions
B1 according to EN ISO 5210Standard:Valve attachment
A, B2, B3, B4 according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Single switches (1 NC and 1 NO) for each end position, not galv anically isolatedStandard:
Tandem switches (2 NC and 2 NO) for each end position, switches galvanically
isolated
Triple switches (3 NC and 3 NO) for each end position, switches galvanically
isolated
Intermediate position switch (DUO limit switching), adjustable for any position
Single switches (1 NC and 1 NO) for each direction, not galvanically isolatedStandard:
Tandem switches (2 NC and 2 NO) for each direction, switches galvanically
isolated
Self-regulating PTC heater, 5 – 20 W, 110 – 250 V AC/DCStandard:Heater in switch compartment
24 – 48 V AC/DC or 380 – 400 V ACOptions:
Electromechanical control unit
Limit switching
logue (option)
(option)
Option:
Special output drive types: AF, AK, AG, B3D, ED, DD, IB1, IB3
A prepared for permanent lubrication of stem
Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 2 to 500 (standard) or 2 to 5,000 (option)
Options:
Torque switching adjustable for directions OPEN and CLOSETorque switching
Options:
Potentiometer or 0/4 – 20 mA (EWG/RWG)Position feedback signal, ana-
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSEDMechanical position indicator
Blinker transmitter (option for modulating actuators)Running indication
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with AM
or AC actuator controls.
Technical data for limit and torque switches
2 x 106 startsMechanical lifetime
Silver plated contacts:
24 V AC/DCU min.
250 V AC/DCU max.
20 mAI min.
I max. AC current
I max. DC current
Gold plated contacts
Technical data for blinker transmitter
Silver plated contacts:
I max. AC current
5 A at 250 V (resistive load)
3 A at 250 V (inductive load, cos phi = 0.6)
0.4 A at 250 V (resistive load)
0.03 A at 250 V (inductive load, L/R = 3 µs)
7 A at 30 V (resistive load)
5 A at 30 V (inductive load, L/R = 3 µs)
5 VU min.
30 VU max.
4 mAI min.
400 mAI max.
107 startsMechanical lifetime
10 V AC/DCU min.
250 V AC/DCU max.
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi ≈ 0.8)
0.25 A at 250 V (resistive load)I max. DC current
67
Page 68
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Technical data ACExC 01.2 Intrusive HART
Technical data for handwheel activation switches
106 startsMechanical lifetime
Silver plated contacts:
12 V DCU min.
250 V ACU max.
3 A at 250 V (inductive load, cos phi = 0.8)I max. AC current
3 A at 12 V (resistive load)I max. DC current
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
Installation altitude
to EN 60529
Vibration resistance according
to IEC 60068-2-6
Finish coating
Lifetime
≤ 2 000 m above sea level
> 2,000 m above sea level, on request
–40 °C to +40/ 60 °CStandard:Ambient temperature
Options:
–50 °C to +40 °C/+60 °C (1-phase AC motors)
–60 °C to +40 °C/+60 °C (3-phase AC motors)
For exact version, refer to actuator name plate.
Standard:Enclosure protection according
IP68
For special motors differing enclosure protection: refer to name plate.
DS Terminal compartment additionally sealed against interior (double sealed)Option:
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: Maximum 8 m head of water
●
Duration of continuous immersion in water: Maximum 96 hours
●
Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For actual version, refer to actuator name plate.
Pollution degree 4 (when closed) according to EN 50178Pollution degree
2 g, from 10 to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this.Valid for multi-turn actuators in version AUMA NORM (with
AUMA plug/socket connector, without actuator controls). Not valid in combination with
gearboxes.
Standard:Corrosion protection
KS: Suitable for installation in industrial units, in water or power plants with a
low pollutant concentration as well as for installation in occasionally or permanently aggressive atmosphere with a moderate pollutant concentration (e.g. w aste
water treatments plants, chemical industry)
Option:
KX: Suitable for installation in extremely aggressive atmospheres with high humidity and high pollutant concentration
KX-G : same as KX, however aluminium-free version (outer parts)
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Technical data
12.2.Technical data Actuator controls
Features and functions
Standard version (ATEX):
●
II 2G Ex de IIC (IIB, IIB+H2) T4 (T3) Gb
●
II 2D Ex tb IIIC T130°C (T190°C) Db IP68
Standard version (IECEx):
●
Ex de IIC (IIB, IIB+H2) T4 (T3) Gb
●
Ex tb IIIC T130°C (190°C) Db IP68
Reversing contactors (mechanically and electrically interlocked) f or A UMA power
classes A1/A2
Reversing contactors (mechanically and electrically interlocked) f or A UMA power
class A3
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating
actuators) for AUMA power classes B1 and B2
Signal transmission is made via HART interface
OPEN, STOP, CLOSE, EMERGENCY control inputs
I/O interface for selecting the control type (HART or additional binary OPEN, STOP,
CLOSE input signals)
24 V DC, current consumption: approx. 10 mA per inputStandardVoltage and current values of
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
115 V DC, current consumption: approx. 15 mA per input
115 V AC, current consumption: approx. 15 mA per input
Power supply
Mains frequency
External supply of the electronics (option)
Current consumption
Control and feedback signals
HART interface
with additional input signals
(option)
the optional additional inputs
Standard:Explosion protection
For actual version, refer to actuator name plate
In combination with SAEx: DEKRA 11ATEX0008 XEC type examination certificate
Refer to name plates at controls and motor
Permissible variation of mains voltage: ±10 %
Permissible variation of mains voltage: ±30 % (option)
Permissible variation of mains frequency: ±5 %
24 V DC +20 % / –15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
External power supply must have reinf orced insulation against mains voltage in accordance
with IEC 61010-1 and may only be supplied by a circuit limited to 150 VA in accordance with
IEC 61010-1.
Current consumption of the controls depending on mains voltage:
For permissible variation of mains voltage of ±10 %:
●
100 to 120 V AC = max. 740 mA
●
208 to 240 V AC = max. 400 mA
●
380 to 500 V AC = max. 250 mA
●
515 to 690 V AC = max. 200 mA
For permissible variation of mains voltage of ±30 %:
●
100 to 120 V AC = max. 1,200 mA
●
208 to 240 V AC = max. 750 mA
●
380 to 500 V AC = max. 400 mA
●
515 to 690 V AC = max. 400 mA
Category III according to IEC 60364-4-443Overvoltage category
The controls are designed for the rated motor power, refer to motor name plateRated power
Standard:Switchgear
Options:
Reversing contactors are designed f or a lif etime of 2 million starts. For applications requiring
a high number of starts, we recommend using thyristor units.
For the assignment of AUMA power classes, please refer to electrical data on actuator.
Via HART interface
Device class: Actuator
Analogue 4 – 20 mA setpoint with digital HART communication
All input signals must be supplied with the same potential.
Via HART interfaceStatus signals
69
Page 70
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Technical data ACExC 01.2 Intrusive HART
Features and functions
HART interface
with additional output signals
(option)
Bluetooth
Communication interface
Additional output signals (only available in combination with additional input signals)
Binary output signals
●
6 programmable output contacts:
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive load)
-
Standard assignment: End position CLOSED, end position OPEN, selector switch
REMOTE, torque fault CLOSE, torque fault OPEN
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
-
Standard assignment: Collectiv e fault signal (torque fault, phase f ailure, motor protection tripped)
●
6 programmable output contacts:
5 change-over contacts with one common, max. 250 V AC, 1 A (resistive load)
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
-
●
6 programmable output contacts:
6 potential-free change-over contacts without one common, per contact max. 250 V
-
AC, 5 A (resistive load)
All binary output signals must be supplied with the same potential.
Analogue output signal for position feedback
●
Galvanically isolated position feedback E2 = 0/4 – 20 mA (load max. 500 Ω)
Standard:Voltage output
Auxiliary voltage 24 V DC, max. 100 mA f or supply of control inputs, galv anically
isolated from internal voltage supply
Option:
Auxiliary voltage 115 V AC , max. 30 mA for supply of control inputs , galvanically
isolated from internal voltage supply
Not possible in combination with PTC tripping device
Standard:Local controls
●
Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
●
Push buttons OPEN, STOP, CLOSE, RESET
Local STOP
-
The actuator can be stopped via push button Stop of local controls if the
selector switch is in position REMOTE. Not activated when leaving the
factory.
●
6 indication lights:
End position and running indication CLOSED (yellow), torque fault CLOSE
-
(red), motor protection tripped (red), torque fault OPEN (red), end position
and running indication OPEN (green), Bluetooth (blue)
●
Graphic LC display, illuminated
Options:
●
Special colours for the 5 indication lights:
End position CLOSED (green), torque fault CLOSE (blue), torque fault
-
OPEN (yellow), motor protection tripped (white), end position OPEN (red)
Bluetooth class II chip, version 2.0 with a range up to 10 m in industrial en vironments. Supports
the SPP Bluetooth profile (Serial Port Profile).
Programming software:
AUMA CDT, commissioning and diagnostic tool for Windows-based PCs, PDAs and smartphones
Standard:Application functions
●
Switch-off mode adjustable
Limit or torque seating for end positions OPEN and CLOSED
-
●
Torque by-pass, adjustable up to 5 seconds (no torque monitoring during
start-up time)
●
Start and end of stepping mode as well as ON and OFF times (1 to 1,800
seconds) can be set individually for directions OPEN and CLOSE.
●
Any 8 intermediate positions between 0 and 100 %, reaction and signal behaviour programmable
●
Positioner
Position setpoint via HART interface
-
Automatic adaptation of dead band (adaptive behaviour selectable)
-
Change-over between OPEN - CLOSE control and setpoint control via
-
HART interface
Option:
●
PID controller with adaptive positioner , 0/4 – 20 mA inputs for process setpoint
and actual process value
70
Page 71
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Technical data
Features and functions
●
EMERGENCY operation, behaviour programmable
Digital input low active
-
Reaction can be selected: Stop , run to end position CLOSED , run to end
-
position OPEN, run to intermediate position
Torque monitoring can be by-passed during EMERGENCY operation.
-
●
Local STOP
The actuator can be stopped via push button Stop of local controls if the
-
selector switch is in position REMOTE. Not activated when leaving the
factory.
Motor running time, number of starts, torque switch trippings in end position CLOSED,
limit switch trippings in end position CLOSED , torque switch trippings in end position
OPEN, limit switch trippings in end position OPEN, torque faults CLOSE, torque f aults
OPEN, motor protection trippings
Status signals according to NAMUR recommendation NE 107: "Failure", "Function
check", "Out of specification", "Maintenance required"
3 torque characteristics (torque-travel characteristic) f or opening and closing directions
can be saved separately. Torque characteristics stored can be shown on the display.
PTC tripping device in combination with PTC thermistors within actuator motorStandard:Motor protection evaluation
Additional thermal overload relay in controls combined with thermoswitches
within actuator
Monitoring functions
Diagnostic functions
Standard:Safety functions
●
Valve overload protection (adjustable), results in switching off and generates fault signal
●
Motor temperature monitoring (thermal monitoring), results in switching off and generates
fault indication
●
Monitoring the heater within actuator, generates warning signal
●
Monitoring of permissible on-time and number of starts (adjustable), generates warning
signal
●
Operation time monitoring (adjustable), generates warning signal
●
Phase failure monitoring, results in switching off and generates fault signal
●
Automatic correction of rotation direction upon wrong phase sequence (3-ph AC current)
●
Electronic device ID with order and product data
●
Operating data logging: A resettable counter and a lifetime counter each for:
-
●
Time-stamped event report with history for setting, operation and faults:
-
●
Torque characteristics
-
Options:
Options:
Refer to name plateWiring diagram
Setting/programming the HART interface
Setting the HART address
The HART address is set via HART command 6 or alternatively via the display of AC 01.2
controls (default value: 0)
Ex plug/socket connector with screw-type terminals (KP)Standard:Electrical connection
●
Ex plug/socket connector with terminal blocks (KES), increased safety Ex e
●
Ex plug/socket connector with terminal blocks (KES), flameproof enclosure
Ex d
Metric threadsStandard:Threads for cable entries
Pg-threads, NPT-threads, G-threadsOptions:
71
Page 72
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Technical data ACExC 01.2 Intrusive HART
Commands and signals of the HART interface
Output data
Feedback signals
Fehlermeldungen
Device class: "Actuator"
Supported control types:
●
Loop Current Mode activated:
Analogue 4 – 20 mA control signal for position setpoint
●
Loop Current Mode deactivated:
Digital HART commands for position setpoint (0 – 100.0 %) or for discrete operation in
directions OPEN and CLOSE
End positions OPEN, CLOSED
Position setpoint
Actual torque value, requires magnetic limit and torque transmitter (MWG) in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Device Status Informationen
●
Field Device Status
●
Device Specific Status
●
Extended Device Status Information
●
Standardized Status
●
Analog Channel Saturated
●
Analog Channel Fixed
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
72
Page 73
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Technical data
General HART data
HART according to IEC 61158 and IEC 61784 (CPF 9)Communication protocol
Point-to-point wiringNetwork topology
FSK (Frequency Shift Key) modulated to 4 – 20 mA setpoint signal
●
Input impedance: 250 Ω.The impedances of other HART devices connected within the
loop (parallel or in series) must be within the HART specification.
●
Point-to-point wiring
●
Signal range: 4 – 20 mA
●
Working range: 2 – 22 mA
●
Minimum operation voltage: 7 V (at 22 mA)
●
Integrated reverse polarity protection
Refer to HART specificationHART cable specification
Internal power supply of HART interface via actuator controls (apart from HART supply
voltage, no other supply required)
Manufacturer name: AUMA
Manufacturer ID: 0x607C
HART protocol revision: 7.4
Number of device variables: 12
Model name: AUMATIC AC 01.2/ACExC 01.2
Device type code: 0xE1FD
●
Universal Commands
●
Common Practice Commands:
Command 33 (Read Device Variables)
-
Command 40 (Enter/Exit Fixed Current Mode)
-
Command 42 (Perform Device Reset)
-
Command 45 (Trim Loop Current Zero)
-
Command 46 (Trim Loop Current Gain)
-
Command 50 (Read Dynamic Variable Assignments)
-
Command 79 (Write Device Variable)
-
Command 95 (Read Device Communication Statistics)
-
●
Device Specific Commands:
Command 128 (Write Operation Command)
-
Command 131 (Read Software Version)
-
Command 132 (Reset to Factory Default)
-
Command 133 (Reset Operational Data)
-
Command 134 (Reset HART Configuration)
-
Command 160 (Read Parameter)
-
Command 161 (Write Parameter)
-
Command 162 (Read Process Data)
-
Service conditions
Installation altitude
Indoor and outdoor use permissibleUse
Any positionMounting position
≤ 2 000 m above sea level
> 2,000 m above sea level, on request
–25 °C to +40 °C/+60 °CStandard:Ambient temperature
–60 °C to +40 °C/+60 °C, extreme low temperature versionOptions:
Low temperature versions incl. heating system for connection to e xternal power
supply 230 V AC or 115 V AC.
For exact version, refer to actuator controls name plate.
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
73
Page 74
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Technical data ACExC 01.2 Intrusive HART
Service conditions
Enclosure protection according
to EN 60529
EN 60664-1 (VDE 0110-1)
Vibration resistance according
to IEC 60068-2-6
Finish coating
IP68 with AUMA 3-phase AC motor/1-phase AC motor
Terminal compartment additionally sealed against interior (double sealed)
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: Maximum 8 m head of water
●
Duration of continuous immersion in water: Maximum 96 hours
●
Up to 10 operations during continuous immersion
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed)Pollution degree according to
1 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength
may not be derived from this. Not valid in combination with gearboxes.
Standard:Corrosion protection
KS: Suitable for installation in industrial units, in water or power plants with a
low pollutant concentration as well as for installation in occasionally or permanently aggressive atmosphere with a moderate pollutant concentration (e.g. w aste
water treatments plants, chemical industry)
Option:
KX: Suitable for installation in extremely aggressive atmospheres with high humidity and high pollutant concentration
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Other colours are possible on request.Option:
Accessories
Wall bracket
Further information
EU Directives
AC 01.2 mounted separately from the actuator , including plug/soc ket connector. Connecting
cable on request.
Recommended for high ambient temperatures, difficult access, or in case of hea vy vibr ation
during service.
Cable length between actuator and AC 01.2 max. 100 m. Not suitab le f or v ersion with potentiometer in the actuator. Instead of the potentiometer, the actuator has to be equipped with
an electronic position transmitter. Cable length for non-intrusive version with MWG in the
actuator max. 100 m. Requires separate data cable for MWG.
AUMA CDTProgramming software for PC
approx. 12 kg (including Ex-plug/socket connector and terminal board)Weight
ATEX Directive: 94/9/EC
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Spare parts
13.Spare parts
13.1.Multi-turn actuators SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 with Ex plug/socket connector and screw-type terminals (KP, KPH)
75
Page 76
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Spare parts ACExC 01.2 Intrusive HART
Information: Please state device type and our order number (see name plate) when ordering spare parts. Only
original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
no.
079.0
501.0
(SA/SAR 07.2 – SA/SAR 16.2 for VD
motor)
type terminals (KP, KPH)
TypeDesignationRef.
no.
554.0Sub-assemblyTorque lever017.0
558.0Sub-assemblyOutput drive wheel for limit switching023.0
559.0-1Sub-assemb lyDrive wheel for limit switching024.0
559.0-2Sub-assemb lyLocking plate025.0
566.1Sub-assemblyEx plug/socket connector with screw-
Stem protection tube (without cap)568.1Washer – Power terminal501.4
Cap for stem protection tube568.2Sub-assemblyPin carrier (without pins)502.1
V-seal568.3Sub-assemblyPin for controls505.0
Stem nut type A575.1Sub-assemblyPin for motor506.0
Pin for motor coupling583.1Sub-assemb lyThreaded plug511.0
Radial seal for output drive type A with
ISO
TypeDesignationRef.
Sub-assemblyScrew plug539.0Sub-assemblyHollow shaft003.0
Sub-assemblyHandwheel with ball handle542.0Sub-assemblyDrive shaft005.0
Sub-assemblyOutput drive type B1/B3/B4/E549.0Motor coupling005.1
Sub-assemblyMechanical position indicator553.0Sub-assemblyPlanetary gearing for manual drive009.0
Sub-assemblySocket carrier for motor plug/socket
Sub-assemblyPotentiometer for position transmitter556.0Gear segment018.0
Sub-assemblyPotentiometer without slip clutch556.1Crown wheel019.0
Sub-assemblyHeater557.0Sub-assemblyDrive pinion II for torque switching022.0
Sub-assemblyBlinker transmitter including pins at
Sub-assemblyControl unit with torque switching
Sub-assemblyControl unit with magnetic limit and
Sub-assemblySwitch stack for direction OPEN560.0-1Sub-assemblyWire for protective earth058.0
Sub-assemblySwitch stack for direction CLOSE560.0-2Sub-assemblyMotor (VD motor incl. ref. no. 079.0)070.0
Sub-assemblySwitch for limit/torque560.1Sub-assemblyPlanetary gearing for motor drive
Sub-assemblyPosition transmitter EWG/RWG566.0Sub-assemblyCover500.0
Sub-assemblyPotentiometer for RWG without slip
Sub-assemblyPosition transmitter board for RWG566.2Screw – Control terminal501.1
Sub-assemblyWires for RWG566.3Washer – Control terminal501.2
Sub-assemblySlip clutch for potentiometer567.1Screw – Power terminal501.3
Sub-assemblyMotor coupling on motor shaft583.0Sub-assemblyCover for electrical connection507.0
Sub-assemblyRetaining spring for motor coupling584.0Sub-assemblyOutput drive type A (without stem nut)514.0
SetSeal kit, smallS1Sub-assemblyOutput drive type D516.0
SetSeal kit, largeS2
76
Page 77
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Spare parts
13.2.Actuator controls A UMA TIC ACExC 01.2 with Ex plug/socket connector and scre w-type terminals
(KP, KPH)
77
Page 78
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Spare parts ACExC 01.2 Intrusive HART
Information: Please state device type and our order number (see name plate) when ordering spare parts. Only
original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
Sub-assemblyEx plug/socket connector with screw-type terminals (KP, KPH)501.0
Screw for control terminal501.1
Washer for control terminal501.2
Screw for power terminal501.3
Washer for power terminal501.4
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Spare parts
13.3.Actuator controls AUMATIC ACExC 01.2 with Ex plug/socket connector and terminal blocks
(KES)
79
Page 80
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Spare parts ACExC 01.2 Intrusive HART
Information: Please state device type and our order number (see name plate) when ordering spare parts. Only
original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation in these instructions.
Sub-assemblyCable conduit (actuator connection)532.0
Terminals for motor/controls533.0
Circlip535.1
Sub-assemblyEx plug/socket connector with terminal blocks (KES)573.0
SetSeal kitS
80
Page 81
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Certificates
14.Certificates
14.1.Declaration of Incorporation and EC Declaration of Conformity
81
Page 82
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Certificates ACExC 01.2 Intrusive HART
14.2.ATEX certificate
82
Page 83
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Certificates
83
Page 84
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
Certificates ACExC 01.2 Intrusive HART
84
Page 85
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART
85
Page 86
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART
86
Page 87
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive HART Index
F
Index
A
Accessories (electrical connection)
Accessories for assembly17
Actual value - indication on
display
Actuator controls terminal
plan
Actuator operation at the local
controls
Actuator operation from remote
Actuator terminal plan9 , 11
Ambient temperature9 , 9 , 68 , 73
Analogue signals44
Applications6
Assembly13
ATEX certificate82
C
Cable set26
Certificates81
26
38
29
30
9
Failure - indication on displa y42
Fault - indication on display40
Flange size10
Function check - indication on
41
display
Fuses60
H
Handwheel13
HART address46
I
Identification8
Indication lights43
Indications36
Indications on display36
Indicator disc42 , 54
Input current11
Input signal11
Inspection record10
Intermediate position indica-
43
tion via LEDs
Intermediate positions50
Intrusive11
Commissioning5
Commissioning (indications
36
on display)
Commission number9
Connecting cable26
Control9 , 11
Control voltage11
Corrective action57
Corrosion protection12 , 68 , 74
Current consumption19
L
Language in the display34
LEDs (indication lights)43
Limit switching48 , 52
Local actuator operation29
Local control29
Local controls29
Local setting30
Lubrication64
D
Data Matrix code11
Declaration of Incorporation81
Device type10
Digital outputs44
Direct display via ID32
Direction of rotation51
Directives5
Display (indications)36
Disposal65
DUO limit switching50
E
Earth connection28
EC Declaration of Conformity81
Electrical connection19
Electronic position transmitter53
EMC20
Enclosure protection9 , 9 , 68 , 74
Error - indication on display36
Explosion protection marking10
39
play
Position indicator54
Position transmitter11
Position transmitter RWG53
Potentiometer53
Power class9
Power class for switchgear11
Power supply19 , 20
Production, year10
Protection cover28
Protection on site19
Protective measures5
Q
Qualification of staff5
R
Range of application5
Recycling65
Reference operation52
Remote actuator operation30
Running indication42
RWG53
S
Safety instructions5
Safety instructions/warnings5
Serial number9 , 9 , 10
Service63
Service conditions73
Servicing63
Setpoint - indication on dis-
39
play
Short-circuit protection19
Signals44
Signals (analogue)44
Size10
Slave address46
Spare parts75
Speed9
Standards5
Status menu32
Status signals44
Stem nut15
Stem protection tube17
Storage12
Supply networks19
Support63
Support App11 , 11
Switch check57
T
Technical data66
Technical data for switches67
Terminal cross sections21 , 24
Terminal plan19
Test run51
Tightening torques21 , 24
Torque - indication on display38
Torque range9
Torque switching48
Transport12
Type (device type)10
Type designation9 , 9
Type of current20
Type of lubricant9
U
User level32
V
Valve position - indication on
37
display
Valve stem17
W
Wall bracket26
Warnings - indication on dis-
40
play
Wiring diagram10 , 19
Y
Year of production10
88
Page 89
AUMA worldwide
Europe
AUMA Riester GmbH & Co. KG
Plant Müllheim
DE 79373 Müllheim
Tel +49 7631 809 - 0
riester@auma.com
www.auma.com
Plant Ostfildern-Nellingen
DE 73747 Ostfildern
Tel +49 711 34803 - 0
riester@wof.auma.com
Service-Center Bayern
DE 85386 Eching
Tel +49 81 65 9017- 0
Riester@scb.auma.com
Service-Center Köln
DE 50858 Köln
Tel +49 2234 2037 - 900
Service@sck.auma.com
Service-Center Magdeburg
DE 39167 Niederndodeleben
Tel +49 39204 759 - 0
Service@scm.auma.com
AUMA-Armaturenantriebe Ges.m.b.H.
AT 2512 Tribuswinkel
Tel +43 2252 82540
office@auma.at
www.auma.at
AUMA BENELUX B.V. B. A.
BE 8800 Roeselare
Tel +32 51 24 24 80
office@auma.be
www.auma.nl
ProStream Group Ltd.
BG 1632 Sofia
Tel +359 2 9179-337
valtchev@prostream.bg
www.prostream.bg
OOO “Dunkan-Privod”
BY 220004 Minsk
Tel +375 29 6945574
belarus@auma.ru
www.zatvor.by
AUMA (Schweiz) AG
CH 8965 Berikon
Tel +41 566 400945
RettichP.ch@auma.com
AUMA Servopohony spol. s.r.o.
CZ 250 01 Brandýs n.L.-St.Boleslav
Tel +420 326 396 993
auma-s@auma.cz
www.auma.cz
GRØNBECH & SØNNER A/S
DK 2450 København SV
Tel +45 33 26 63 00
GS@g-s.dk
www.g-s.dk
IBEROPLAN S.A.
ES 28027 Madrid
Tel +34 91 3717130
iberoplan@iberoplan.com
AUMA Finland Oy
FI 02230 Espoo
Tel +358 9 5840 22
auma@auma.fi
www.auma.fi
AUMA France S.A.R.L.
FR 95157 Taverny Cedex
Tel +33 1 39327272
info@auma.fr
www.auma.fr
AUMA ACTUATORS Ltd.
GB Clevedon, North Somerset BS21 6TH
Tel +44 1275 871141
mail@auma.co.uk
www.auma.co.uk
D. G. Bellos & Co. O.E.
GR 13673 Acharnai, Athens
Tel +30 210 2409485
info@dgbellos.gr
APIS CENTAR d. o. o.
HR 10437 Bestovje
Tel +385 1 6531 485
auma@apis-centar.com
www.apis-centar.com
Fabo Kereskedelmi és Szolgáltató Kft.
HU 8800 Nagykanizsa
Tel +36 93/324-666
auma@fabo.hu
www.fabo.hu
Falkinn HF
IS 108 Reykjavik
Tel +00354 540 7000
os@falkinn.is
www.falkinn.is
AUMA ITALIANA S.r.l. a socio unico
IT 20023 Cerro Maggiore (MI)
Tel +39 0331 51351
info@auma.it
www.auma.it
AUMA BENELUX B.V.
LU Leiden (NL)
Tel +31 71 581 40 40
office@auma.nl
NB Engineering Services
MT ZBR 08 Zabbar
Tel + 356 2169 2647
nikibel@onvol.net
AUMA BENELUX B.V.
NL 2314 XT Leiden
Tel +31 71 581 40 40
office@auma.nl
www.auma.nl
SIGUM A. S.
NO 1338 Sandvika
Tel +47 67572600
post@sigum.no
AUMA Polska Sp. z o.o.
PL 41-219 Sosnowiec
Tel +48 32 783 52 00
biuro@auma.com.pl
www.auma.com.pl
AUMA-LUSA Representative Office, Lda.
PT 2730-033 Barcarena
Tel +351 211 307 100
geral@aumalusa.pt
SAUTECH
RO 011783 Bucuresti
Tel +40 372 303982
office@sautech.ro
OOO PRIWODY AUMA
RU 141402 Khimki, Moscow region
Tel +7 495 221 64 28
aumarussia@auma.ru
www.auma.ru
OOO PRIWODY AUMA
RU 125362 Moscow
Tel +7 495 787 78 21
aumarussia@auma.ru
www.auma.ru
ERICHS ARMATUR AB
SE 20039 Malmö
Tel +46 40 311550
info@erichsarmatur.se
www.erichsarmatur.se
ELSO-b, s.r.o.
SK 94901 Nitra
Tel +421 905/336-926
elsob@stonline.sk
www.elsob.sk
Auma Endüstri Kontrol Sistemleri Limited
Sirketi
TR 06810 Ankara
Tel +90 312 217 32 88
info@auma.com.tr
AUMA Technology Automations Ltd
UA 02099 Kiev
Tel +38 044 586-53-03
auma-tech@aumatech.com.ua
Africa
Solution Technique Contrôle Commande
DZ Bir Mourad Rais, Algiers
Tel +213 21 56 42 09/18
stcco@wissal.dz
A.T.E.C.
EG Cairo
Tel +20 2 23599680 - 23590861
contactus@atec-eg.com
SAMIREG
MA 203000 Casablanca
Tel +212 5 22 40 09 65
samireg@menara.ma
MANZ INCORPORATED LTD.
NG Port Harcourt
Tel +234-84-462741
mail@manzincorporated.com
www.manzincorporated.com
89
Page 90
AUMA worldwide
AUMA South Africa (Pty) Ltd.
ZA 1560 Springs
Tel +27 11 3632880
aumasa@mweb.co.za
America
AUMA Argentina Rep.Office
AR Buenos Aires
Tel +54 11 4737 9026
contacto@aumaargentina.com.ar
AUMA Automação do Brazil ltda.
BR Sao Paulo
Tel +55 11 4612-3477
contato@auma-br.com
TROY-ONTOR Inc.
CA L4N 8X1 Barrie, Ontario
Tel +1 705 721-8246
troy-ontor@troy-ontor.ca
AUMA Chile Representative Office
CL 9500414 Buin
Tel +56 2 821 4108
aumachile@auma-chile.cl
Ferrostaal de Colombia Ltda.
CO Bogotá D.C.
Tel +57 1 401 1300
dorian.hernandez@ferrostaal.com
www.ferrostaal.com
Transcontinental Trading Overseas SA.
CU Ciudad Habana
Tel +53 7 208 9603 / 208 7729
tto@ttoweb.com
AUMA Región Andina & Centroamérica
EC Quito
Tel +593 2 245 4614
auma@auma-ac.com
www.auma.com
Corsusa International S.A.C.
PE Miraflores - Lima
Tel +511444-1200 / 0044 / 2321
corsusa@corsusa.com
www.corsusa.com
Control Technologies Limited
TT Marabella,Trinidad,W.I.
Tel + 1 868 658 1744/5011
www.ctltech.com
AUMA Actuators Middle East
BH 152 68 Salmabad
Tel +97 3 17896585
salesme@auma.com
Mikuni (B) Sdn. Bhd.
BN KA1189 Kuala Belait
Tel + 673 3331269 / 3331272
mikuni@brunet.bn
AUMA Actuators (China) Co., Ltd
CN 215499 Taicang
Tel +86 512 3302 6900
mailbox@auma-china.com
www.auma-china.com
PERFECT CONTROLS Ltd.
HK Tsuen Wan, Kowloon
Tel +852 2493 7726
joeip@perfectcontrols.com.hk
PT. Carakamas Inti Alam
ID 11460 Jakarta
Tel +62 215607952-55
auma-jkt@indo.net.id
AUMA INDIA PRIVATE LIMITED.
IN 560 058 Bangalore
Tel +91 80 2839 4656
info@auma.co.in
www.auma.co.in
ITG - Iranians Torque Generator
IR 13998-34411 Teheran
+982144545654
info@itg-co.ir
Trans-Jordan Electro Mechanical Supplies
JO 11133 Amman
Tel +962 - 6 - 5332020
Info@transjordan.net
AUMA JAPAN Co., Ltd.
JP 211-0016 Kawasaki-shi, Kanagawa
Tel +81-(0)44-863-8371
mailbox@auma.co.jp
www.auma.co.jp
DW Controls Co., Ltd.
KR 153-702 Gasan-dong, GeumChun-Gu,,
Seoul
Tel +82 2 2624 3400
import@actuatorbank.com
www.actuatorbank.com