SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Table of contents AC 01.1 Intrusive Modbus RTU
Read operation instructions first.
●
Observe safety instructions.
●
These operation instructions are part of the product.
●
Preserve operation instructions during product life.
●
Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff . It is intended
to support device installation and commissioning.
Reference documents:
●
Manual (Operation and setting) AUMATIC AC 01.1/ACExC 01.1 Modbus
●
Manual (Device integration Fieldbus) AUMATIC AC 01.1/ACExC 01.1 Modbus
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUSafety instructions
1.Safety instructions
1.1Basic information on safety
Standards/directives
Safety instructions/war-
nings
Qualification of staff
Commissioning
AUMA products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others applicable configuration guidelines for fieldbus
applications.
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to av oid personal injury or property
damage.
Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitab ly qualified personnel ha ving been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation
Protective measures
Prerequisites for safe and smooth operation:
●
●
●
●
●
●
The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance
T o ensure saf e device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
Only operate the device if it is in perf ect condition while observing these instructions.
Immediately report any faults and damage and allow for corrective measures.
Observe recognised rules for occupational health and safety.
Observe the national regulations.
During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prevent possible burns, we recommend checking the surface temperature using an appropriate thermometer and wearing protective gloves, if required, prior to working on the device.
The following applications are not permitted, e.g.:
●
Industrial trucks according to EN ISO 3691
●
Lifting appliances according to EN 14502
5
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Potentially explosive areas, with the exception of zone 22
●
Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information
These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the A TEX directiv e 94/9/EC.
The actuators are designed to meet enclosure protection IP 67 or IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
●
In compliance with the A TEX directiv e 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
●
The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temper ature.
●
The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are prerequisites for compliance with the maximum surface temperature of devices.
●
The connection plug may only be plugged in or pulled out when device is disconnected from the mains.
●
The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.
●
The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
●
The threaded plug (part no. 511.0) or the stem protection tube with protective
cap (part nos. 568.1 and 568.2) for sealing the hollow shaft must imperatively
be mounted to guarantee tightness and therefore the combustible dust hazard
protection.
●
As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the saf e oper ation of actuators.
1.4Warnings and notes
The following warnings draw special attention to saf ety-rele v ant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
6
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUSafety instructions
Indicates a potentially hazardous situation with a medium level of risk. F ailure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury . Ma y also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→
Measures to avoid the danger
→
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.5References and symbols
The following references and symbols are used in these instructions:
InformationThe term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
Step by step
Provides a detailed description of each step for setting/viewing the parameter.
Description of the parameter settings/indications
Describes the setting/viewing possibilities of a parameter.
< >Reference to other sections
T erms in brack ets shown abov e refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may quickly be found.
7
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Identification AC 01.1 Intrusive Modbus RTU
2.Identification
2.1Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1:Arrangement of name plates
[1]Actuator name plate
[2]Controls name plate
[3]Motor name plate
[4]Additional plate, e.g. KKS plate (Power Plant Classification System)
Data for identificationFigure 2:Actuator name plate
[1]Type and size of actuator
[2]Commission number
Figure 3:Controls name plate
[1]Type and size of the controls
[2]Commission number
[3]Wiring diagram
[4]Control
Type and size
8
These instructions apply to the following devices:
Multi-turn actuators for open-close duty: SA 07.1, 07.5, 10.1, 14.1, 14.5, 16.1
Multi-turn actuators for modulating duty: SAR 07.1, 07.5, 10.1, 14.1, 14.5, 16.1
AC 01.1 = Stellantriebs-Steuerung AUMATIC
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUIdentification
Commission number
Wiring diagram
Control
2.2Short description
Multi-turn actuator
Actuator controls
Local controls/COM-AC
Intrusive - Non-Intrusive
An order-specific commission number is assigned to each device.This commission
number can be used to directly download the wiring diagram, inspection records and
further information regarding the device from the Internet: http://www.auma.com.
The 7th position in the ACP wiring diagram indicates the type of feedback signals
from the actuator:
P = Potentiometer
R = RWG (electronic position transmitter)
Modbus RTU = Control via Modbus RTU interface.
Definition in compliance with EN ISO 5210:
A multi-turn actuator is an actuator which transmits to the valve a torque for at least
one full revolution. It is capable of withstanding thrust.
AUMA multi-turn actuators are driven by an electric motor and are capable of
withstanding thrust in combination with output drive type A. For manual operation,
a handwheel is provided. Switching off in end positions may be either by limit or
torque seating. Controls are required to operate or process the actuator signals.
The AUMATIC actuator controls are used to operate AUMA actuators and are supplied
ready for use.The controls may be mounted directly to the actuator or separately
on a wall bracket.
The functions of the AUMATIC controls include standard valve control in OPEN CLOSE duty, positioning, process control, logging of operating data, diagnostic
functions right through control via fieldbus.
Operation, setting, and display can be performed on site directly at the controls or
alternatively from REMOTE via a fieldbus interface.
On site it is possible to
●
Operate the actuator via the local controls (push buttons and display) and perform settings (contents of these instructions).
●
Read in or out data or modify and save settings via the COM-A C softw are (option), using a computer (laptop or PC). Depending on the version, the connection between computer and AUMATIC can be made with cable (infra-red interface) or without cable (Bluetooth interf ace) (not included in these instructions).
●
Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.
●
Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, actuator and controls
housings do not have to be opened. For this purpose, the actuator is equipped
with an MWG (magnetic limit and torque transmitter), also supplying analogue
torque feedback signals/torque indication and analogue position feedback signals/position indication.
9
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Transport, storage and packaging AC 01.1 Intrusive Modbus RTU
3.Transport, storage and packaging
3.1Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→
Do NOT stand below hovering load.
→
Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→
Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→
Actuators mounted to gearboxes: Attach ropes or hooks f or the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→
Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2Storage
Long-term storage
3.3Packaging
Danger of corrosion due to inappropriate storage!
→
Store in a well-ventilated, dry room.
→
Protect against floor dampness by storage on a shelf or on a wooden pallet.
→
Cover to protect against dust and dirt.
→
Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
→
The AUMATIC actuator controls must NOT be stored below –30 °C.
If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1.Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2.At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show , apply ne w corrosion protection.
Our products are protected by special packaging for transport when leaving the
factory .The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
10
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUAssembly
4.Assembly
4.1Mounting position
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
4.2Handwheel fitting
InformationFor transport purposes, handwheels from a diameter of 400 mm are supplied sepa-
rately.
Damage at the change-over mechanism due to incorrect assembly!
→
Only pivot change-over lever manually.
→
Do NOT use extensions as lever for operation.
→
First engage manual operation correctly, then mount handwheel.
1.Manually lift the red change-over lev er while slightly turning the shaft back and
forth until manual operation engages.
The manual operation is correctly engaged if the change-over le ver can be lifted
➥
by approx. 85°.
2.Attach handwheel over the red change-over lever then on to the shaft.
3.Release change-over lever (should snap back into initial position by spring action, if necessary, push it back manually).
4.Secure handwheel using the circlip supplied.
11
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Assembly AC 01.1 Intrusive Modbus RTU
4.3Multi-turn actuator: mount to valve/gearbox
Danger of corrosion due to damage to paint finish and condensation!
→
Touch up damage to paint finish after work on the device.
→
After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.3.1Output drive types B, B1 – B4 and E
●
Application
Design
For rotating, non-rising valve stem
●
Not capable of withstanding thrust
Output drive bore with keyway:
●
Types B1 – B4 with bore according to ISO 5210
●
Types B and E with bore according to DIN 3210
●
Later change from B1 to B3, B4, or E is possible.
Figure 6:Output drives
[1]Output drive types B1/B2 and B
[2]Hollow shaft with keyway
[3]Output drive types B3/B4 and E
[4]Output drive sleeve/output drive plug sleve with bore and keyway
InformationSpigot at flanges should be loose fit.
4.3.1.1Multi-turn actuator (with output drive types B1 – B4 or E): mount to valve/gearbox
1.Check if mounting flanges fit together.
2.Check whether bore and keyway match the input shaft.
3.Apply a small quantity of grease to the input shaft.
4.Place multi-turn actuator.
Information: Ensure that the spigot fits uniformly in the recess and that the
mounting faces are in complete contact.
5.Fasten multi-turn actuator with screws according to table.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
12
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUAssembly
6.Fasten screws crosswise to a torque according to table.
Table 1:Tightening torques for screws
Tightening torque TA [Nm]Screws
Strength class 8.8Threads
25M8
51M10
87M12
214M16
431M20
4.3.2Output drive type A
●
Application
Output drive for rising, non-rotating valve stem
●
Capable of withstanding thrust
4.3.2.1Stem nut: finish machining
This working step is only required if stem nut is supplied unbored or with pilot
✔
bore.
Figure 7:Design of output drive type A
[1]Stem nut
[2]Bearing
[2.1] Bearing race
[2.2] Bearing rim
[3]Spigot ring
1.Remove spigot ring [3] from output drive.
2.Remove stem nut [1] together with bearings [2].
3.Remove bearing races [2.1] and bearing rims [2.2] from stem nut [1].
4.Drill and bore stem nut [1] and cut thread.
Information: When fixing in the chuck, make sure stem nut runs true!
5.Clean the machined stem nut [1].
6.Apply sufficient Lithium soap EP multi-purpose grease to bearing rims [2.2] and
bearing races [2.1], ensuring that all hollow spaces are filled with grease.
8.Re-insert stem nut [1] with bearings [2] into output drive.
Information:Ensure that dogs or splines are placed correctly in the keyway of
the hollow shaft.
9.Screw in spigot ring [3] until it is firm against the shoulder.
13
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Assembly AC 01.1 Intrusive Modbus RTU
4.3.2.2Multi-turn actuator (with output drive type A): mount to valve
Figure 8:Assembly with output drive type A
[1]Valve stem
[2]Output drive type A
[3]Screws to actuator
[4]Valve flange
[5]Screws to output drive
1.If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2.Check if the flange of output drive type A matches the valve flange [4].
3.Apply a small quantity of grease to the valve stem [1].
4.Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5.Turn output drive type A until alignment of the fixing holes.
6.Screw in fastening screws [5], however do not completely tighten.
7.Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
The flanges are flush with each other if properly engaged.
➥
8.Adjust multi-turn actuator until alignment of the fixing holes.
9.Fasten multi-turn actuator with screws [3].
10. Fasten screws [3] crosswise with a torque according to table.
Table 2:Tightening torques for screws
Tightening torque TA [Nm]Screws
Strength class 8.8Threads
11M6
25M8
51M10
87M12
214M16
431M20
14
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUAssembly
4.4Accessories for assembly
4.4.1Stem protection tube for rising valve stem
— Option —
Figure 9:Assembly of the stem protection tube
[1]Cap for stem protection tube
[2]Stem protection tube
[3]Sealing ring
1.Seal thread with hemp, Teflon tape, or thread sealing material.
2.Screw stem protection tube [2] into thread and tighten it firmly.
3.Push down the sealing ring [3] onto the housing.
4.Check whether cap for stem protection tube [1] is available and in perfect con-
dition.
4.5Mounting positions of local controls
The mounting position of the local controls is selected according to the order. If , after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfav ourable position, the mounting position can be changed at a later date . F our
mounting positions are possible.
Figure 10:Mounting positions A and B
15
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Assembly AC 01.1 Intrusive Modbus RTU
Figure 11:Mounting positions C and D
4.5.1Mounting positions: modify
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws and remove the local controls.
2.Check whether O-ring is in good condition, correctly insert O-ring.
3.Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→
Turn local controls by a maximum of 180°.
→
Carefully assemble local controls to avoid pinching the cables.
4.Fasten screws evenly crosswise.
16
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUElectrical connection
5.Electrical connection
5.1Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury , or property damage.
→
The electrical connection must be carried out exclusively by suitably qualified
personnel.
→
Prior to connection, observe basic information contained in this chapter.
→
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan
Protection on site
The pertaining wiring diagram/terminal plan (in German and English language) is
attached to the device in a weather-proof bag, together with these operation
instructions. It can also be obtained from A UMA (state commission no ., refer to name
plate) or downloaded directly from the Internet (www.auma.com).
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
Table 3:Current consumption controls
Max. current consumptionMains voltage
650 mA100 to 120 V AC (±10 %)
325 mA208 to 240 V AC (±10 %)
190 mA380 to 500 V AC (±10 %)
500 mA, filter capacitor 2,200 µF24 V DC (+10 %/-15 %) and AC motor
750 mA, filter capacitor 2,200 µF24 V DC (+10 %/–10 %) and DC motor
Table 4:Maximum permissible protection
max. protectionRated powerSwitchgear
16 A (gL/gG)up to 1.5 kWReversing contactor A1
32 A (gL/gG)up to 7.5 kWReversing contactor A2
63 A (gL/gG)up to 11 kWReversing contactor A3
16 A (g/R) I²t<1,500A²sup to 1.5 kWThyristor
32 A (g/R) I²t<1,500A²sup to 3 kWThyristor
63 A (g/R) I²t<5,000A²sup to 5.5 kWThyristor
Power supply for the
controls (electronics)
Safety standards
Cable installation in ac-
cordance with EMC
If controls are mounted separately from actuator (controls on wall brack et): Consider
length and cross section of connecting cable when defining the protection required.
If the controls (electronics) are supplied externally with 24 V DC and DC motors (24
V DC, 48 V DC, 60 V DC, 110 V DC, 220 V DC) are used simultaneously, the 24 V
DC voltage supply for the controls should be ensured via the XK25/26 terminals,
separately from the power supply (U1, V1). In case of common supply using a single
cable (links from U1, V1 with XK25/26, for 24 V DC only !!!), short-term excess or
falling below the permissible voltage limits can be the consequence during s witching
(24 V DC +10 %/–10 %). Any possibly incoming operation commands are not
executed outside the admissible limit values.The controls briefly signal a fault
condition.
All externally connected devices shall comply with the relevant safety standards.
Signal and bus cables are susceptible to interference.
Motor cables are interference sources.
17
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Electrical connection AC 01.1 Intrusive Modbus RTU
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●
Avoid long par allel paths with cab les being either susceptible to interf erence or
interference sources.
●
For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains
voltage and mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
motor name plate.
Figure 12:Motor name plate (example)
Connecting cables
Bus cables
[1]Type of current
[2]Mains voltage
[3]Mains frequency (for 3-ph and 1-ph AC motors)
●
For device insulation, appropriate (v oltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cable with appropriate minimum rated temperature.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
Only cables complying with the recommendations of EIA 485 specifications should
be used for Modbus wiring.
Cable recommendation:
Impedance:
135 to 165 Ohm, at a measurement frequency between 3 and 20 MHz
Cable capacity:
Wire diameter
Wire cross section:
Loop resistance:
Screening:
< 30 pF per metre
> 0.64 mm
0.34 mm², corresponds to AWG 22
< 110 Ohm per km
CU shielding braid or shielding braid and shielding
foil
18
Prior to installation, please note:
●
Connect maximum 32 devices to one segment.
●
If more devices are to be connected:
-Connect several segments using repeaters.
●
Respect a distance of minimum 20 cm between the bus cable and other cab les.
●
If possible, bus cables should be laid in a separate, conductive, and earthed
cable tray.
●
Make sure to avoid potential differences between the individual devices on the
bus (perform an equipotential earth bonding).
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUElectrical connection
5.2Connection with AUMA plug/socket connector
Cross sections AUMA plug/socket connector:
InformationFor some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board at the motor.
5.2.1Terminal compartment: open
InformationThe bus connection can be separately accessed from the mains connection (refer
to <Bus terminal compartment: open>).
Figure 13:Mains connection AUMA plug/socket connector SD bus
[1]Connection housing
[2]Screws for connection housing
[3]O-ring
[4]Screws for socket carrier
[5]Socket carrier
[6]Cable entry for mains
[7]Blanking plug
[8]Cable gland (not included in delivery)
InformationBus operation is not interrupted when removing the connection housing [1].
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws [2] and remove connection housing [1].
2.Loosen screws [4] and remove socket carrier [5] from connection housing [1].
19
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Electrical connection AC 01.1 Intrusive Modbus RTU
3.Insert cable glands [8] suitable for connecting cables.
The enclosure protection IP... stated on the name plate is only ensured if suitab le
➥
cable glands are used. Example: Name plate shows enclosure protection IP
68.
4.Seal unused cable entries [6] with suitable blanking plugs [7].
5.Insert the cables into the cable glands [8].
5.2.2Cable connection
Observe permissible cross sections.
✔
1.Remove cable sheathing.
2.Strip wires.
3.For flexible cables: Use end sleeves according to DIN 46228.
4.Connect cables according to order-related wiring diagram.
In case of a fault: Hazardous voltage while protective earth conductor is NOT
connected!
Risk of electric shock.
→
Connect all protective earth conductors.
→
Connect PE connection to external protective earth conductor of connecting
cables.
→
Start running the device only after having connected the protective earth conductor.
5.Tighten PE conductors firmly to PE connection using ring lugs (flexible cab les)
or loops (rigid cables).
Figure 15:PE connection
[1]Socket carrier
[2]Screw
[3]Washer
[4]Lock washer
[5]Protective earth with ring lugs/loops
[6]
PE connection, symbol:
20
Danger of corrosion: Damage due to condensation!
→
After mounting, commission the device immediately to ensure that heater minimises condensation.
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUElectrical connection
InformationSome actuators are equipped with an additional motor heater.The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
5.2.3Terminal compartment: close
Figure 16:AUMA plug/socket connector SD bus
[1]Connection housing
[2]Screws for connection housing
[3]O-ring
[4]Screws for socket carrier
[5]Socket carrier
[6]Cable entry for mains
[7]Blanking plug
[8]Cable gland (not included in delivery)
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
→
Carefully fit socket carrier to avoid pinching the cables.
1.Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2.Clean sealing faces of connection housing [1] and housing.
3.Check whether O-ring [3] is in good condition, replace if damaged.
4.Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.Fit connection housing [1] and fasten screws [2] evenly crosswise.
6.Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.2.4Bus terminal compartment: open
The AUMA plug/soc ket connector (SD bus) is equipped with a connection board for
connecting the bus cables.When removing the cover [1] the connection board is
easily accessible.
21
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Electrical connection AC 01.1 Intrusive Modbus RTU
Figure 17:AUMA plug/socket connector SD bus
[1]Cover (bus terminal compartment)
[2]Screws for cover
[3]O-ring
[4]Cable entries for bus cables
[5]Blanking plug
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→
Earth both operators and devices.
1.Loosen screws [2] and remove cover [1].
2.Insert cable glands suitable for bus cables.
The enclosure protection IP… stated on the name plate is only ensured if suita-
➥
ble cable glands are used.
Example: Name plate shows enclosure protection IP 68.
➥
3.Seal unused cable entries [4] with suitable blanking plugs [5].
4.Insert the wires into the cable glands.
5.2.5Bus cables: connect
Versions
The bus connection described in this chapter applies to the following v ersions of the
connection board:
●
●
●
InformationFor loop redundancy, automatic termination is performed as soon as the AUMATIC
is connected to the power supply. When interrupting the power supply, e.g. after removing the AUMA plug/socket connector, both RS-485 loop segments are automatically connected to each other.
22
Standard version (1-channel)
Versions with overvoltage protection (up to 4 kV)
Versions for redundancy (2-channel)
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTUElectrical connection
Figure 19:Connection board (standard version)
[S1]Bus termination channel 1
[X1]
Channel 1, ↑ from the previous device
[X2]
Channel 1, ↓ to the next device
[X3]Shielding clamp
Figure 20:Connection boards (versions with overvoltage protection)
[A]Board for line topology
[B]Board for loop topology (loop redundancy)
[S1]Bus termination channel 1
[S2]Bus termination channel 2
[S3]Redundancy
[X1]
Channel 1: ↑ from the previous device ↓ to the next device
[X2]
Channel 2: ↑ from the previous device ↓ to the next device
[X3]Shielding clamps
23
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
Electrical connection AC 01.1 Intrusive Modbus RTU
Figure 21:Connection baords (versions for redundancy)
[A]Board for line topology
[B]Board for loop topology (loop redundancy)
[S1]Bus termination channel 1
[S2]Bus termination channel 2
[S3]Redundancy
[X1]
Channel 1: ↑ from the previous device
[X2]
Channel 1: ↓ to the next device
[X3]Shielding clamps
[X4]
Channel 2: ↑ from the previous device
[X5]
Channel 2: ↓ to the next device
Table 5:Functions for switches S1 – S3
Bus termination channel 1 ONONS1
Bus termination channel 1 OFFOFF
Bus termination channel 2 ON (option)ONS2
Bus termination channel 2 OFF (option)OFF
one fieldbus board1SPCS3
two fieldbus boards (redundancy, option)2SPC
InformationSwitches S1 and S2 are supplied in OFF position.
Connecting bus cables:
1.Connect cables.
Table 6:Assignment of fieldbus cables
Fieldbus cables
AUMA labelling at the
connection
fieldbus devices)
2.If the actuator is the final device in the bus segment:
2.1 Switching on the termination resistor for channel 1 using switch S1 (ON
position).
2.2 For component redundancy: Switching on the termination resistor for
channel 2 using switch S2 (ON position). Refer to table <Functions for
switches S1 – S3>.
Information: As soon as the termination resistors are switched on, the
connection to the next Fieldbus device is automatically interrupted to avoid
multiple terminations (not applicable for overvoltage protection).
3.Connect cable shield largely to shielding clamp [X3].
ColourSUB-D 9 plug pin (for other
green8N/AA
red3P/BB
24
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.