Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
Scope of these instructions:
These instructions valid for multi-turn actuators of the type range
SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1 with
the actuator controls AM 01.1 / AM 02.1.
These operation instructions are only valid for “clockwise closing”,
i.e. driven shaft turns clockwise to close the valve.
Table of contentsPage
1.Safety instructions4
1.1Range of application4
1.2Electrical connection4
1.3Maintenance4
1.4Warnings and notes4
2.Short description5
3.Technical data6
4.Additional information to the wiring diagram legend9
5.Transport, storage and packaging10
5.1Transport10
5.2Storage10
5.3Packaging11
6.Mounting to valve/ gearbox12
7.Mounting positions of the local controls14
8.Electrical connection15
8.1Connection with AUMA plug/ socket connector (S, SH, SE)17
9.Manual operation19
10.Operation and indications of the local controls20
11.Opening the switch compartment22
11.1Removing the cover from the switch compartment22
11.2Pulling off the indicator disc (option)22
12.Setting the limit switching23
12.1Setting end position CLOSED (black section)23
12.2Setting end position OPEN (white section)23
12.3Checking the limit switches23
13.Setting the DUO limit switching (option)24
13.1Setting direction CLOSE (black section)24
13.2Setting direction OPEN (white section)24
13.3Checking the DUO limit switches24
14.Setting the torque switching25
14.1Setting25
14.2Checking the torque switches25
15.Test run26
15.1Checking the direction of rotation26
15.2Checking the setting of the limit switching27
15.3Checking the type of seating27
15.4Checking the PTC tripping device (option)27
16.Setting the potentiometer (option)29
2
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
Page
17.Setting the electronic position transmitter RWG (option)30
17.1Setting 2-wire system 4 – 20 mA and 3- /4-wire system 0 – 20 mA31
17.2Setting 3- / 4- wire system 4 – 20 mA32
18.Setting the mechanical position indicator (option)33
19.Closing the switch compartment33
20.Actuator controls AUMA MATIC34
20.1Functions of the diagnosis LEDs on the interface board (standard version)34
20.2Programming the logic board35
20.3EMERGENCY - OPEN and EMERGENCY - CLOSE signal (option)36
21.Electronic positioner (option)37
21.1Technical data37
21.2Setting37
21.2.1Setting type of signal39
21.2.2Setting actuator behavior on loss of signal40
21.3Positioner adjustment for end position CLOSED (standard version)41
21.4Positioner adjustment for end position OPEN (standard version)43
21.5Setting the sensitivity43
21.6Positioner adjustment for end position OPEN (inverse operation)45
21.7Positioner adjustment end position CLOSED (inverse operation)46
21.8Positioner in Split Range version (option)47
21.8.1Split Range: description of functions47
21.8.2Programming47
21.8.3Positioner adjustment for Split Range47
22.Timer (option)49
22.1Functions of the diagnosis LEDs (timer)49
22.2Setting start and end of stepping mode via DUO limit switching (option)50
22.3Setting ON and OFF times51
23.Fuses52
23.1Fuses within the actuator controls52
23.2Motor protection54
24.Enclosure protection IP 68 (option)55
25.Maintenance56
26.Lubrication56
27.Disposal and recycling56
28.Service57
29.Spare parts list Multi-turn actuator SA(R) 07.1 – SA(R) 16.160
30.Spare parts list controls AUMA MATIC62
Index63
Addresses of AUMA offices and representatives64
3
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
1.Safety instructions
1.1Range of application
AUMA actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves.
For other applications, please consult us. The manufacturer is not liable for any
possible damage resulting from use in other than the designated applications.
Such risk lies entirely with the user.
Observance of these operation instructions is considered as part of the controls’/ actuator’s designated use.
1.2Electrical connection
During electrical operation, certain parts inevitably carry lethal voltages. Work
on the electrical system or equipment must only be carried out by a skilled electrician themselves or by specially instructed personnel under the control and
supervision of such an electrician and in accordance with the applicable electrical engineering rules.
1.3Maintenance
The maintenance instructions (refer to page 56) must be observed, otherwise a
safe operation of the actuator is no longer guaranteed.
1.4Warnings and notes
Failure to observe the warnings and notes may lead to serious injuries or damage. Qualified personnel must be thoroughly familiar with all warnings and notes
in these operation instructions.
Correct transport, proper storage, mounting and installation, as well as careful
commissioning are essential to ensure a trouble-free and safe operation.
During operation, the multi-turn actuator warms up and surface temperatures
> 140 °F may occur. Check the surface temperature prior to contact in order to
avoid burns.
The following references draw special attention to safety-relevant procedures in
these operation instructions. Each is marked by the appropriate pictograph.
This pictograph means: Note!
“Note” marks activities or procedures which have major influence on the correct
operation. Non-observance of these notes may lead to consequential damage.
This pictograph means: Electrostatically endangered parts!
If this pictograph is attached to a printed circuit board, it contains parts which
may be damaged or destroyed by electrostatic discharges. If the boards need to
be touched during setting, measurement, or for exchange, it must be assured
that immediately before a discharge through contact with a grounded metallic
surface (e.g. the housing) has taken place.
This pictograph means: Warning!
“Warning” marks activities or procedures which, if not carried out correctly, can
affect the safety of persons or material.
4
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
2.Short description
AUMA multi-turn actuators of the type range SA 07.1 – SA 30.1/SAR 07.1 –
SAR 30.1 are driven by an electric motor and controlled by the actuator controls AUMA MATIC AM 01.1/ AM 02.1, which is included in the scope of delivery.
A handwheel is provided for manual operation.
The limitation of travel is realized via limit switches in both end positions. Torque
seating is also possible in both end positions. The type of seating is determined
by the valve manufacturer.
Both the multi-turn actuator and the controls have a modular design, i.e. they
are designed in accordance with the principle of a modular construction system.
This means that each actuator or each controls are individually manufactured
and combined for a specific valve automation task. An order-specific commission number, printed on the name plate, is assigned to each actuator/ controls.
Commissioning
Please note that for low temperature versions (– 58 °F), the controls requires a
heat-up time.
This heat-up time is applicable in case the actuator and the controls are not live
and have cooled down to ambient temperature. In case commissioning has to
be performed under these conditions, the following heat-up times have to be
observed:
60 min. at – 58 °F
80 min. at – 76 °F
Figure A: Heat-up time chart
t [min.]
80
70
60
50
40
30
20
10
0
0–14–4
–22
–40–76
–58
ϑ [°F]
5
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
3.Technical data
Features and functions
Type of duty
MotorsStandard:3-ph AC asynchronous motor, type IM B9 according to IEC 34
Insulation classStandard:F, tropicalized
Motor protectionStandard:Thermoswitches (NC)
Self-lockingYes, for output speeds from 5.6 to 108 rpm
Limit switchingCounter gear mechanism for end positions CLOSED and OPEN
Torque switchingInfinitely adjustable torque switching for direction OPEN and CLOSE
Position feedback signal,
analogue (options)
Mechanical position indicator
(option)
Running indication (option)Blinker transmitter
Heater in switch compartmentStandard:Resistance type heater with 5 W, 24 V DC
Motor heater (option)SA(R) 07.1 – 10.1:12.5 W
Manual operationManual drive for setting and emergency operation, handwheel does not rotate during electrical operation.
Connection to controlsAUMA plug/ socket connector with screw type connection
Output drive typesA, B1, B2, B3, B4 according to EN ISO 5210
1)
Standard:SAShort time duty S2 - 15 min
SARIntermittent duty S4 - 25 %
Option:SAShort time duty S2 - 30 min
SARIntermittent duty S4 - 50 %
Intermittent duty S5 – 25 %
Option:Special motors
Option:H, tropicalized
Option:PTC thermistors (according to DIN 44082)
for 1 to 500 turns per stroke (optional for 1 to 5,000 turns per stroke)
Standard:Tandem switch (2 NC and 2 NO) for each end position
Options:Single switch (1 NC and 1 NO) for each end position,
switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position,
switches galvanically isolated
Intermediate position switch (DUO limit switching),
adjustable for any intermediate position
Standard:Single switch (1 NC and 1 NO) for each direction
Options:Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated
Potentiometer or 0/4 – 20 mA (RWG)
For further details, see separate data sheet
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Options:Self-regulating PTC heater, 5 – 20 W
24 – 48 V AC/DC, 110 – 250 V AC/DC or 380 – 400 V AC
SA(R) 14.1 – 16.1:25 W
SA(R) 25.1 – 30.1:50 W
Option:Handwheel lockable
A, B, D, E according to DIN 3210
C according to DIN 3338
Special output drives: AF, AK, AG, IB1, IB3
Power supply, mains frequency
and current consumption
External supply of the
electronics (option)
Rated powerRefer to motor name plate
Overvoltage categoryCategory III
1) Based on 68 °F ambient temperature and at an average load with running torque according to Technical data SA or SAR
For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the nominal voltage: ± 10 %
Permissible variation of the mains frequency: ± 5 %
Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 600 mA
208 to 240 V AC = max. 300 mA
380 to 500 V AC = max. 150 mA
24 V DC + 20 % / – 15 %,
Observe current consumption of the controls
Note: The controls is designed for the rated power of the actuator
6
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
SwitchgearStandard:Reversing contactors2)(mechanically and electrically interlocked)
for motor power up to 1.5 kW
Options:Reversing contactors
2)
(mechanically and electrically interlocked)
for nominal motor current up to 18 A (OPEN - CLOSE- duty)
or 16 A (modulating duty)
Thyristor unit3)(recommended for modulating actuators)
for motor power up to 1.5 kW, 500 V AC with internal fuses
for motor power up to 5.5 kW, 500 V AC, external fuses required
ControlStandard:Control inputs 115 V AC, OPEN - STOP - CLOSE (via opto-isolator,
with one common), current consumption: approx. 10 mA per input
Observe min. duration of impulse for modulating actuators
Option:Control inputs 24 V DC, OPEN - STOP - CLOSE (via opto-isolator,
with one common), current consumption: approx. 15 mA per input
Output signalsStandard:5 output relays with gold-plated contacts:
4 potential-free NO contacts with one common:
max. 250 V AC, 0.5 A (resistive load)
Standard configuration:
End position OPEN, end position CLOSED, selector switch REMOTE,
selector switch LOCAL
1 potential-free change-over contact, max. 250 V AC, 0.5A (resistive load)
for collective fault signal
Standard configuration:
Torque fault, phase failure, motor protection tripped
Option:Signals in connection with positioner:
End position OPEN, end position CLOSED
(requires tandem switch within actuator)
Selector switch REMOTE, selector switch LOCAL via 2
nd
level
selector switch
1 potential-free change-over contact, max. 250 V AC, 0.5A (resistive load)
for collective fault signal:
Torque fault, phase failure, motor protection tripped
Voltage outputStandard:Auxiliary voltage 115 V AC, max. 30 mA for supply of the control inputs,3),
galvanically isolated from internal voltage supply
Option:Auxiliary voltage 24 V DC, max. 50 mA for supply of the control inputs,
galvanically isolated from internal voltage supply
Local controlsStandard:Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
Push buttons OPEN - STOP - CLOSE
3 indication lights:
End position CLOSED (red), collective fault signal (yellow), end position OPEN (green)
Option:Protection cover, lockable
FunctionsStandard:Switch-off mode adjustable
Limit or torque seating for end position OPEN and end position CLOSED
Overload protection against excessive torques over the whole travel
Excessive torque (torque fault) can be excluded from collective fault signal
Phase failure monitoring with automatic phase correction
Push-to-run operation or self-retaining in REMOTE
Push-to-run operation or self-retaining in LOCAL
Blinker transmitter signal of actuator can be switched on or off (option)
Options:Positioner
4)
:
Nominal position value via analogue input E1 = 0/4 – 20 mA
Adjustable behavior on loss of signal
Adjustable sensitivity (dead band) and pause time
Split Range operation
Motor protection evaluationStandard:Monitoring of the motor temperature in combination with thermoswitches
in the actuator motor
Options:Additional thermal overload relay in the controls in combination with thermoswitches
within the actuator
PTC tripping device in combination with PTC thermistors in the actuator motor
Electrical connectionStandard:AUMA plug/ socket connector with screw type connection
Options:Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed)
2) The lifetime guaranteed by the manufacturer amounts to min. 2 million cycles. If a higher number of switching cycles is to be expected, thyristor units with virtually
unlimited lifetime should be used
3) Not possible in combination with PTC tripping device
4) Requires position transmitter (potentiometer or RWG) in actuator
7
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
Threads for cable glandsStandard:NPT-threads
Options:Pg-threads, G-threads
Wiring diagramWiring diagram according to commission number included in delivery
Further options for version with RWG in the actuator
IP 67-DS (Double Sealed)
IP 68-DS (Double Sealed)
(Double Sealed = additional protection of the interior of the housing
against ingress of dust and dirt when removing the plug)
Corrosion protectionStandard:KNSuitable for installation in industrial units, in water or power plants
with a low pollutant concentration
Options:KSSuitable for installation in occasionally or permanently aggressive
atmosphere with a moderate pollutant concentration
(e.g. in wastewater treatment plants, chemical industry)
KXSuitable for installation in extremely aggressive atmosphere
with high humidity and high pollutant concentration
KX-G Same as KX, however aluminium-free version (outer parts)
Finish coatingStandard:Two-component iron-mica combination
Standard colorStandard:AUMA silver-grey (similar to RAL 7037)
Option:Other colors are possible on request
Ambient temperatureStandard:SA:– 25 °C to + 70 °C
SAR:– 25 °C to + 60 °C
Options:– 40 °C to + 60 °C/ – 40 to 140 °F, low temperature version
– 50 °C to + 60 °C/ – 75 to 140 °F, extreme low temperature version
incl. heating system
– 60 °C to + 60 °C/ – 75 to 140 °F, extreme low temperature version
incl. heating system
Vibration resistance
according to IEC 60 068-2-6
1 g, from 10 Hz to 200 Hz
Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may
not be derived from this.
Applies to actuator with actuator controls, not valid in combination with gearboxes
LifetimeSA 07.1 – 10.1: 20,000 operations (OPEN - CLOSE - OPEN) with 30 turns per stroke
SA 14.1 – 16.1: 15,000 operations (OPEN - CLOSE - OPEN) with 30 turns per stroke
SA 25.1 – 30.1: 10,000 operations (OPEN - CLOSE - OPEN) with 30 turns per stroke
SAR 07.1 – 10.1: 5 million operations/ starts
SAR 14.1 – 16.1: 3.5 million operations/ starts
SAR 25.1 – 30.1: 2.5 million operations/ starts
6)
6)
6)
WeightMulti-turn actuator:Refer to Technical data SA/ SAR
Actuator controls:Approx. 7 kg (including AUMA plug/ socket connector)
Accessories
Wall bracket
7)
AUMA MATIC mounted separately from the actuator, including plug/ socket connector.
Connecting cables on request.
Recommended for high ambient temperatures, difficult access, or in case of heavy vibrations
during service.
Product description “Actuator controls AUMA MATIC”
Dimension sheets SA/ SAR “...with integral controls AUMA MATIC”
Technical data sheets AM 01.1/AM 02.1
Technical data sheets SA/ SAR
Electrical data sheets SA/ SAR
5) For 3-phase asynchronous motors in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended. Additionally, for enclosure protection
IP 68, we recommend to use the double sealed terminal compartment DS. For special motors, the enclosure protection according to the name plate applies
6) The lifetime of modulating actuators depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To reach the
longest possible maintenance and fault-free operation time, the number of starts per hour chosen should be as low as permissible for the process
7) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the potentiometer, an RWG has
to be used in the actuator
8
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
4.Additional information to the wiring diagram legend
Information A:
A running indication is possible if blinker transmitter (S5) is installed
(opening and closing of contacts).
Direction CLOSE:Connections X
Direction OPEN:Connections X
Contacts remain closed in end position.
When connected to an external PLC, the blinking signal can be switched off via
the DIP-switches (table 4, page 35).
Information B:
The type of seating in the end positions is determined by the valve manufacturer. The setting is done at the programming switches S1-2 and S3-2
(see page 35). The tripping of a torque switch in an intermediate position
switches off the actuator and causes a fault signal.
The limit switches serve for signalization when switching off by torque seating.
They need to be set so that the appropriate switch is tripped shortly before
reaching the end position. If the torque switch trips before the limit switch, the
actuator is switched off and a fault signal is generated.
For further programming possibilities, e.g. self-retaining in operation mode
REMOTE, see table 4, page 35.
6 - XK7
K
6 - XK8
K
Information D:
The following faults are registered and can be transmitted to the control room as
a potential-free collective fault signal:
- Power failure
- Phase failure
- Motor protection tripped
- Torque switch tripped in mid-travel.
This signal can be switched off on the logic board, see table 4, page 35.
Information E:
Input signals according to DIN 19 240.
The nominal operation current of inputs X
2, XK3, and XK4 amounts to
K
10 – 15 mA. If the internal voltage 24 V DC is used for remote control, it must
only be connected via potential-free contacts.
Information F:
In case of wrong phase sequence, the running direction is automatically
adjusted. In case of a phase failure, the actuator stops. The fault is indicated at
LED V14 on the interface board (see page 34). For collective fault signal, see
information D.
Information G:
Potential-free contacts are available for signals. The internal control voltage
(X
11 / + 24 V and XK5 / – 24V) must not be used for external lamps, relays,
K
etc.
Please note that this information only pertains to point to point
drawings.
9
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
5.Transport, storage and packaging
5.1Transport
.
For transport to place of installation, use sturdy packaging.
.
Do not attach ropes or hooks to the handwheel for the purpose of lifting by
hoist.
.
If multi-turn actuator is mounted on valve, attach ropes or hooks for the purpose of lifting by hoist to valve and not to multi-turn actuator.
Fitting the handwheel:
For transport purposes, handwheels from a diameter of 400 mm are supplied
separately.
Engage manual operation prior to mounting the handwheel! If
the manual operation is not engaged, damage can occur at the
change-over mechanism.
.
Engage manual operation (figure B-1):
Manually lift the red change-over lever while slightly turning the shaft back and
forth until manual operation engages. The manual operation is correctly
engaged if the change-over lever can be lifted by approx. 85°.
Manual force is sufficient for operating the change-over lever. It
is not necessary to use an extension. Excessive force may
damage the change-over mechanism.
.
Install handwheel over the red change-over lever on to the shaft (figure B-1).
.
Release change-over lever (should snap back into initial position by spring
action, figure B), if necessary, push it back manually.
.
Secure handwheel using the snapring supplied.
5.2Storage
Figure B-1
85°
.
Store in well-ventilated, dry room.
.
Protect against floor dampness by storage on a shelf or on a wooden pallet.
.
Cover to protect against dust and dirt.
.
Apply suitable corrosion protection agent to uncoated surfaces.
If multi-turn actuators are to be stored for a long time (more than 6 months), the
following points must be observed additionally:
.
Prior to storage: Protect uncoated surfaces, in particular the output drive parts
and mounting surface, with long-term corrosion protection agent.
.
Check for corrosion approximately every 6 months. If first signs of corrosion
show, apply new corrosion protection.
Figure B-2
10
After mounting, connect actuator immediately to electrical
system, so that the heater prevents condensation.
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
5.3Packaging
Our products are protected by special packaging for the transport ex works. The
packaging consists of environmentally friendly materials which can easily be
separated and recycled.
We use the following packaging materials: wood, cardboard, paper, and Polyurethane foam. For the disposal of the packaging material, we recommend recycling and collection centers.
11
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
6.Mounting to valve/ gearbox
.
Prior to mounting the multi-turn actuator must be checked for
damage. Damaged parts must be replaced by original spare
parts.
.
After mounting to valve/ gearbox, touch up any possible damage to paint finish.
The multi-turn actuator leaves the factory in position CLOSED (limit switch
CLOSED tripped).
.
Check if mounting flange fits the valve/ gearbox.
Spigot at flanges should be loose fit!
The output drive types B1, B2, B3, or B4 (figure B-3) are delivered with bore
and keyway (usually according to ISO 5210).
Figure B-3
Output drive type B1/B2
Plug sleeve
Output drive type B3/B4
Bore with keyway
For output drive type A (figure C-1), the internal thread of the stem nut must
match the thread of the valve stem. If not ordered explicitly with thread, the stem
nut is unbored or with pilot bore when delivered. For finish machining of stem
nut, refer to next page.
.
Check whether bore and keyway match the input shaft of valve/ gearbox.
.
Thoroughly degrease mounting faces at multi-turn actuator and valve/ gear-
box.
.
Apply a small quantity of grease to input shaft of valve/gearbox.
.
Place actuator on valve/gearbox and fasten. Fasten bolts
(quality min. grade 5, refer to table 1) evenly crosswise.
Table 1: Standard dry fastening torque for bolts
UNC bolts – grade 5TA(ft lbs.)
5
- 1819
16
3
- 1633
8
1
- 1378
2
5
- 11155
8
3
- 10255
4
Conversion factor: 1 Nm corresponds to 1.3529 ft lbs.
12
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
Finish machining of stem nut (output drive type A):
Figure C-1
Output drive type A
Stem nut
80.3
80.01/80.02
80.2
The output drive flange does not have to be removed from the actuator.
.
Remove spigot ring (80.2, figure C-1) from mounting flange.
.
Take off stem nut (80.3) together with thrust bearing (80.01) and thrust bearing races (80.02).
.
Remove thrust bearing and thrust bearing races from stem nut.
.
Drill and bore stem nut and cut thread.
When fixing in the chuck, make sure stem nut runs true!
.
Clean the machined stem nut.
.
Apply Lithium soap EP multi-purpose grease to thrust bearing and races, then
place them on stem nut.
.
Re-insert stem nut with thrust bearings into the mounting flange. Ensure that
dogs are placed correctly in the slots of the hollow shaft.
.
Screw in spigot ring until it is firm against the shoulder.
.
Press Lithium soap EP multi-purpose grease on mineral oil base into the
grease nipple with a grease gun (for quantities, please refer to table):
Table 2: Grease quantities for output drive type A
Output
drive
Qty
1) For greases with a density ρ = 0.9 kg/dm³3; conversion factor: 1 oz corresponds to 28.35 g
Protection tube for rising valve stem
.
Seal thread with hemp, Teflon tape, or thread sealing material.
.
Screw protection tube (1) into thread (figure C-2) and tighten it firmly.
.
Push down the sealing (2) to the housing.
.
Check whether cap (3) is available and without damage.
Figure C-2: Protection tube for rising valve stem
A 07.2 A 10.2 A 14.2 A 16.2A 25.2 A 30.2A 35.2 A 40.2A 48.2
1)
1.5 g2 g3 g5 g10 g14 g20 g25 g30 g
3
1
2
13
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
7.Mounting positions of the local controls
The mounting position of the local controls is designed according to the order. If,
after mounting the actuator to the valve or the gearbox on site, the local controls
is in an unfavorable position, the mounting position can easily be changed at a
later date.
Four mounting positions are possible:
Figure D-1: Mounting position A
Actuator
Figure D-3: Mounting position C
Figure D-2: Mounting position B
Actuator
Figure D-4: Mounting position D
14
Actuator
Changing the mounting position
.
Disconnect actuator from the mains before opening.
.
Turn local controls by a maximum of 180°, rotate circuit board
accordingly!
.
Ensure that the wires are neither twisted nor jammed.
.
Loosen 4 bolts and remove the local controls.
.
Turn local controls in one of the four positions and re-place on the actuator,
rotate circuit board accordingly.
.
Clean sealing faces of housing and cover.
.
Check whether O-ring is in good condition.
.
Replace cover on switch compartment and fasten bolts evenly crosswise.
Actuator
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
8.Electrical connection
Work on the electrical system or equipment must only be
carried out by a skilled electrician themselves or by specially
instructed personnel under the control and supervision of such
an electrician and in accordance with the applicable electrical
engineering rules.
Wiring diagram
The terminal plan applicable to the actuator is placed inside the terminal compartment, the operation instructions are attached to the handwheel in a
weather-proof bag.
External fuse
For short-circuit protection and for protecting the actuator, fuses and disconnect
switches have to be provided by the customer.
The current values for sizing the switch can be derived from the current consumption of the motor plus the current consumption of the controls.
Motor current consumption:
Refer to name plate on motor (nominal current).
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
The maximum permissible fuse for controls with a rated power of 1.5 kW is 16 A
(gL/ gG), and for controls with a rated power of 7.5 kW, the value amounts to 32
A (gL/ gG).
Cable installation in accordance with EMC
Signal and bus cables are susceptible to interference.
Motor cables are interference sources.
.
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
.
The interference immunity of signal and bus cables increases if the cables are
laid close to the ground potential.
.
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
.
Avoid long parallel paths with cables being either susceptible to interference
or interference sources.
.
For the connection of remote position transmitters (potentiometer, RWG),
screened cables must be used.
Heater
As standard, the control unit of the actuator is equipped with a heater to prevent
condensation within the actuator. Unless ordered otherwise, the heater is internally supplied. For external supply (option), the heater always has to be
connected.
Some actuators are optionally equipped with an additional motor heater. The
motor heater is always externally supplied and has to be connected according
to the wiring diagram.
15
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
Actuator controls on wall bracket (accessory)
For version on wall bracket, please observe the following:
Figure E: AUMA MATIC on wall bracket
Connecting cables
to actuator
.
Versions with potentiometer in the actuator are not suitable. Instead of the
potentiometer, an RWG has to be used in the actuator
.
Permissible cable distance between actuator and AUMA MATIC amounts to a
maximum of 100 m.
.
Factory supplied cables for the connection between actuator and AUMA
MATIC on wall bracket can be obtained from AUMA on request.
In case non factory supplied cables are used, the following additionally has to
be observed:
.
Use suitable flexible and screened connecting cables.
.
Connect the wires in correct phase sequence.
Check the direction of rotation before switching on (see page 26)
Subsequent mounting of the actuator controls on the actuator
In case the actuator and the actuator controls have different commission numbers (refer to name plates), the designations of the terminal plan and the wiring
diagram (KMS . . .) have to match for both devices.
16
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
8.1Connection with AUMA plug/ socket connector (S, SH, SE)
Figure F-1: Version SH (standard)Figure F-2: Version SFigure F-3: Version SE
Before mains connection
Check whether type of current, supply voltage, and frequency comply with
motor data (refer to name plate at motor):
VD00 63-4/45
Art. No.: Z006.413
3 ~ 480V60Hz
0.09 kW
Y 0.60A
Current type/mains voltage/mains frequency
Opening the terminal compartment
.
Loosen bolts (1) and remove cover (figure G).
.
Loosen screws (2) and remove socket carrier from cover.
.
Insert cable glands suitable for connecting cables
(The enclosure protection stated on the name plate is only ensured if suitable
cable glands are used.).
NEMA 4X
Thermal protection: Th
Insulation class: F
.
Seal cable entries which are not used with suitable plugs.
Figure G: Opening the terminal compartment
Cover
(1)
Enclosure protection
Cable gland and
screw plug
in enclosure protection
according to name plate
Socket carrier
(2)
17
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
Connecting the cables
.
Connect cables according to order-related wiring diagram.
All PE conductors have to be tightened firmly to the PE connection
(symbol:) using either ring lugs (flexible cables), or lugs (solid cables) (figure H).
Each time the PE connection has been disconnected, it has to
be ensured that the PE conductors are firmly connected.
Figure H: PE connection
Closing the terminal compartment
.
Insert socket carrier into the cover and fasten with screws (2) (figure G).
.
Clean sealing faces at the cover and the housing.
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
.
Replace cover and fasten bolts (1) evenly crosswise.
.
Fasten cable glands with the specified torque to ensure the required enclosure protection.
Parking frame, protection cover (accessories)
A special parking frame (figure J) for protection against touching the exposed
contacts and against environmental influences is available.
The open terminal compartment can be closed using a protective cover
(not illustrated).
Screw
Washer
Circlip
Protective earth with ring lugs/lugs
PE connection
Socket carrier
18
Figure J: Parking frame (accessory)
Parking frame
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructionswith actuator controls AUMA MATIC AM 01.1 / AM 02.1
9.Manual operation
The actuator may be operated manually for purposes of setting and commis
sioning and in case of motor failure or power failure.
Manual operation is engaged by an internal change-over mechanism.
Engaging manual operation
.
Lift up change-over lever in the center of the handwheel to approx. 85°, while
slightly turning the handwheel back and forth until manual operation engages
(figure K-1).
Figure K-1
Manual force is sufficient for operating the change-over lever. It
is not necessary to use an extension. Excessive force may
damage the change-over mechanism.
.
Release change-over lever (should snap back into initial position by spring
action, figure K), if necessary, push it back manually.
Figure K-2
-
Operating the change-over lever while the motor is running
(figure L-1) can lead to increased wear at the change-over
mechanism.
Figure L-1Figure 13-2
.
Turn handwheel into desired direction (figure 13-2).
Disengaging manual operation
Manual operation is automatically disengaged when motor is started again.
The handwheel does not rotate during motor operation.
19
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
t
t
with actuator controls AUMA MATIC AM 01.1 / AM 02.1Operation instructions
10.Operation and indications of the local controls
Figure M: Local controls
Push buttons
Selector switch
Selector switch
0
I
I
Indication lights
Position OFF (0):
- No remote control possible
- No local control possible
- Actuator remains ready for signalization
signalization (the controls’ power supply is maintained)
III
Test
III
Test
0
I
I
Position Local control (I):
The actuator can be operated locally via the push buttons
OPEN - STOP - CLOSE.
0
I
I
Position Remote control (II):
The actuator can be controlled from remote, e.g. via the control room.
0
I
Position Test (III):
II
Test PTC tripping device (refer to page 27)
Only available in combination with motor protection
III
(PTC thermistor).
Rese
Yellow indication light (fault) is illuminated.
0
I
Position Reset (III):
II
Reset fault signal (yellow indication light) after the motor pro
tection has tripped (refer to page 54).
III
Only available in combination with motor protection
Rese
-
(PTC thermistor).
20
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.