AUMA AM 01.1, AM 02.1, AMExB 01.1, AMExC 01.1 Operation Instructions Manual

Page 1
Actuator controls
Operation instructions
AUMA MATIC
AM 01.1/ AM 02.1
AMExB 01.1/ AMExC 01.1
Profibus DP
ISO 9001
Certificate Registration No.
12 100 4269 12 104 4269
Page 2
2
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Scope of these instructions These instructions are valid for multi-turn actuators of type ranges
SA(R) 07.1 – SA(R) 16.1 and SA(R)ExC 07.1 – SA(R)ExC 16.1 and for part-turn actuators of type ranges SG(R) 05.1 – SG(R) 12.1 and SGExC 05.1 – SGExC 12.1 with the controls AUMA MATIC AM 01.1/ AM 02.1 or AMExB 01.1 and AMExC 01.1 and Profibus DP interface.
Table of contents Page
1. Safety instructions 4
1.1 Range of application 4
1.2 Commissioning (electrical connection) 4
1.3 Maintenance 4
1.4 Warnings and notes 4
2. Short description 4
3. Transport and storage 5
4. General information about Profibus DP 5
4.1 Basic characteristics 5
4.2 Basic functions of Profibus DP 6
4.3 Transfer mode 6
4.4 Bus access 6
4.5 Communication 6
4.6 Functionality 6
4.7 Protection functions 6
4.8 Device types 6
5. Technical data 7
6. Design AUMA MATIC Profibus DP 10
7. Electrical connection 11
7.1 Power supply (standard) 11
7.2 Bus connection (standard) 12
7.3 Fitting the cover 13
7.4 Remote position transmitter 14
7.5 AUMA MATIC on wall bracket 14
7.6 Test run 14
7.7 Mains and bus connection for Ex-version with plug/ socket connector/ terminal board (KP) 15
7.8 Mains and bus connection for Ex-version with plug-in terminal connection (KES) 17
7.9 Redundant bus connection 18
7.10 Bus cables 19
7.11 Setting the Profibus DP address 20
8. Commissioning with controls 21
8.1 Introduction 21
8.2 Programming 21
8.3 Configuration of the Profibus DP interface of the AUMA MATIC 21
8.4 Communication start-up 22
8.5 Description of AUMA user parameters 22
9. Process representation input 29
9.1 Process representation input (default process representation) 30
10. Process representation output 34
10.1 Description of the output data 34
Page 3
3
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page
11. Description of actuator functions 36
11.1 Operation commands for OPEN/ CLOSE operation 36
11.2 Positioner 37
11.3 Stepping mode 38
12. Failure function 38
13. Description Profibus DP interface 39
13.1 Assignment of the customer inputs of the Profibus DP interface (option) 40
13.2 Assignment Profibus DP connection 41
13.3 Assignment positioner connections 41
13.4 Checking/ setting the switches on the logic board 42
14. Troubleshooting and corrective actions 43
14.1 Optical signals during operation 43
14.2 Actuator can not be controlled via Profibus DP 45
14.3 Position feedback does not function 48
14.4 Actuator is not switched off by the limit switch in direction CLOSE 48
14.5 Actuator stops immediately after start 48
14.6 Measuring the Profibus signals using an oscilloscope 48
15. Appendix A standard wiring diagram 49
15.1 Legend for standard wiring diagram 50
15.2 Additional information to the wiring diagram legend 50
16. Appendix B Proposed external wiring diagram 51
17. Appendix C GSD file 54
18. Appendix D Literature references 54
19. Appendix E Connecting the cable shield for the AUMA MATIC AMExB/ AMExC 01.1 54 Index 55 Addresses of AUMA offices and representatives 56
Page 4
1. Safety instructions
1.1 Range of application AUMA actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves and ball valves. For other applications, please consult us. The manufacturer is not liable for any possible damage resulting from use in other than the designated appli
­cations. Such risk lies entirely with the user. Observance of these operation instructions is considered as part of the controls’ designated use.
1.2 Commissioning (electrical connection)
During electrical operation, certain parts inevitably carry lethal voltages. Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of such an electrician and in accordance with the applicable electrical engineering rules.
1.3 Maintenance The maintenance instructions must be strictly observed, otherwise a safe
operation of the multi-turn actuator/ the controls is no longer guaranteed.
1.4 Warnings and notes Non-observance of the warnings and notes may lead to serious injuries or
damage. Qualified personnel must be thoroughly familiar with all warnings and notes in these operation instructions. Correct transport, proper storage, mounting, and installation, as well as careful commissioning are essential to ensure a trouble-free and safe operation. The following references draw special attention to safety-relevant proce­dures in these operation instructions. Each is marked by the appropriate pictograph.
This pictograph means: Note!
“Note” marks activities or procedures which have major influence on the correct operation. Non-observance of these notes may lead to consequen­tial damage.
This pictograph means: Electrostatically endangered parts!
If this pictograph is attached to a printed circuit board, it contains parts which may be damaged or destroyed by electrostatic discharges. If the boards need to be touched during setting, measurement, or for exchange, it must be assured that immediately before a discharge through contact with an earthed metallic surface (e.g. the housing) has taken place.
This pictograph means: Warning!
“Warning” marks activities or procedures which, if not carried out correctly, can affect the safety of persons or material.
2. Short description AUMA actuators have a modular design. Motor and gearing are mounted in
a common housing. The actuators are driven by an electric motor and controlled via the elec­tronic controls AUMA MATIC Profibus DP. The electronic controls are included in the scope of delivery.
4
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 5
3. Transport and storage
.
Transport to place of installation in sturdy packing.
.
Do not attach ropes or hooks to the handwheel for the purpose of lifting by hoist.
.
Store in well-ventilated, dry room.
.
Protect against floor dampness by storage on a shelf or on a wooden pallet.
.
Cover to protect against dust and dirt.
.
Apply suitable corrosion protection agent to bright surfaces.
4. General information about Profibus DP
For the exchange of information among automation systems and between automation systems and the connected decentral field devices, serial field­buses are mainly used today as the communication system. Thousands of applications have proved impressively that cost savings of up to 40 % in wiring, commissioning, and maintenance are achieved by using fieldbus technology. While in the past the fieldbuses used were often manufacturer specific and incompatible with other bus systems, the systems employed today are almost exclusively open and standardized. This means that the user does not depend on individual suppliers and can choose the best product at the most competitive price. Profibus DP is the leading open fieldbus system in Europe, which is also used successfully throughout the world. The application range includes automation in the areas of manufacturing, processing and building. Profibus DP is an international, open fieldbus which has been standardized in the fieldbus standard EN 50 170. This standardization ensures that the invest­ments of manufacturers and users are protected to the best possible degree and the independence of the manufacturer is guaranteed. These operation instructions cannot provide a general introduction into Profibus DP. For more information, please refer to the literature references in appendix D.
4.1 Basic characteristics Profibus DP defines the technical and functional features of a serial fieldbus
system allowing the interconnection of distributed, digital automation devices. Profibus DP distinguishes between master and slave devices. Profibus DP is designed for fast data transmission on the field level. Here, central control devices, such as a PLC or PC, communicate via a fast serial connection with peripheral field devices such as input/ output devices, valves, and actuators. The interchange of data among the field devices is realised on a cyclic basis. The respectively necessary communication functions are established by the Profibus DP basic functions according to EN 50 170.
Master devices control the data traffic on the bus. A master is allowed to send messages without an external request. Masters are also called ‘active devices’ in the Profibus protocol.
Slave devices such as AUMA Profibus DP actuators are peripheral devices. Typical slave devices are input/ output devices, valves, actuators and measuring transmitters. They do not have bus access, i.e. they may only acknowledge received messages or, at the request of a master, transmit messages to that master. Slaves are also called ‘passive devices’.
5
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page 6
4.2 Basic functions of Profibus DP
The master reads the input information from the slaves cyclically and writes the output information cyclically to the slaves. In addition to this cyclic data transfer of the process representation, Profibus DP also provides powerful functions for diagnostics and commissioning purposes. The data traffic is monitored through the monitoring functions on the master and slave side.
4.3 Transfer mode
.
RS-485 twisted pair cable or fibre optic cable.
.
AUMA actuators support baud rates up to 1.5 MBits/s
4.4 Bus access
.
Token-passing between the masters and polling between master and slave.
.
Mono-master or multi-master systems are possible.
.
Master and slave devices: max. 126 devices connected to one bus
4.5 Communication
.
Peer-to-peer (process data exchange [DATA EX]) or Multicast (control commands to all slaves).
.
Cyclic master-slave process data exchange (DATA EX) or acyclic master-master data transfer. Cyclic master-slave process data exchange (DATA EX) or acyclic master-master data transfer.
4.6 Functionality
.
Cyclic process data exchange (DATA EX) between DP master and DP slaves.
.
Dynamic activation or de-activation of individual DP slaves.
.
Checking the configuration of the DP slaves
.
Synchronisation of inputs and/ or outputs.
4.7 Protection functions
.
All messages are transmitted with Hamming Distance HD=4.
.
Watchdog timer at DP slaves.
.
Access protection for the inputs/ outputs of the DP slaves
.
Process data exchange (DATA EX) monitoring with configurable timer interval at the master.
.
Adjustable failure behaviour.
4.8 Device types
.
DP master class 2 (DPM2), e.g. programming/ configuration tools.
.
DP master class 1 (DPM1), e.g. central controllers such as PLC, PC.
.
DP slave, e.g. AUMA Profibus DP devices. Devices with binary or analogue inputs/ outputs, actuators, valves.
6
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 7
5. Technical data
7
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Features and functions
Power supply Standard voltages:
Special voltages:
External supply of the electronics (option)
24 V DC + 20 % / – 15 %, Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Switchgear Standard: Reversing contactors
2)
(mechanically and electrically interlocked)
for motor power up to 1.5 kW
Options: Reversing contactors
2)
(mechanically and electrically interlocked)
for motor power up to 7.5 kW Thyristor unit3)(recommended for modulating actuators)
for motor power up to 1.5 kW, 500 V AC with internal fuses
for motor power up to 5.5 kW, 500 V AC, external fuses required Control and output signals via Profibus DP interface Profibus DP interface with
additional inputs (option)
Profibus DP interface with 4 free 24 V DC inputs and 2 free 0/4 – 20 mA inputs. Signal transmission via fieldbus interface.
Local controls Standard: Selector switch LOCAL – OFF – REMOTE (lockable in all three positions)
Push buttons OPEN – STOP – CLOSE
3 indication lights:
End position CLOSED (yellow), collective fault signal (red),
End position open (green)
Option: Protection cover, lockable
Functions Standard Switch-off mode adjustable
Limit or torque seating for end position CLOSED
Overload protection against excessive torque over the whole travel
Phase failure monitoring with automatic phase correction
Push-to-run operation or self-retaining in LOCAL
Positioner4):
Nominal position value via Profibus DP interface Adjustable behaviour on loss of signal Adjustable sensitivity (dead band) and pause time
Motor protection evaluation Standard: For AM: Monitoring of the motor temperature in combination with
thermoswitches in the actuator motor
For AMExB/ AMExC: Monitoring of the motor temperature with PTC tripping
device in combination with PTC thermistors in the actuator motor
Options: Additional thermal overload relay in the controls in combination with
thermoswitches within the actuator
PTC tripping device in combination with PTC thermistors in the actuator motor Electrical connection Standard: For AM: AUMA plug/ socket connector with screw type connection
For AMExB/ AMExC: Ex-plug/ socket connector with terminal board
For further options and threads for cable entries, please refer to separate
technical data sheets
Special threads, other than standard mentioned above, possible
Control plug gold plated3)(sockets and pins)
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plug is removed) Overvoltage protection3)(option) Protection of the actuator and controls electronics against overvoltages on the fieldbus
cables of up to 4 kV
Wiring diagram (basic version) MSP 1B1-00-1-F18E1 KMS TP102/001
1) AC current only with AM 01.1/ AM 02.1 and AMExC 01.1 in combination with actuator SGExC
2) The lifetime guaranteed by the manufacturer amounts to min. 2 million cycles. If a higher number of switching cycles is to be expected, thyristor units with
virtually unlimited lifetime should be used
3) Only in combination with AM 01.1 and AM 02.1
4) Requires position transmitter (potentiometer or RWG) in actuator
Table 1: Profibus DP interface for actuator controls AM/ AMExB/ AMExC
3-phase AC
voltages/ frequencies
1-phase AC
1)
voltages/ frequencies
Volt 220 230 240 380 400 415 440 460 480 500 Volt 110,115,120 220,230,240
Hz 50 50 50 50 50 50 60 60 60 50 Hz 50/60 50/60
3-phase AC
voltages/ frequencies
1-phase AC
1)
voltages/ frequencies
Volts
525 575 660 690 208
Hz
50 50 50 50 60
Page 8
8
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Settings/ programming of the Profibus DP interface
Setting of the baud rate Automatic baud rate recognition Setting of the Profibus DP
address
The Profibus DP address is set via rotary switches
Commands and signals of the Profibus DP interface
Process representation output
(command signals)
OPEN, STOP, CLOSED
Nominal position value
4)
Process representation input (feedback signals)
End position OPEN, CLOSE Actual position value
4)
Selector switch in position LOCAL/ REMOTE Running indication
4)
(directional) Torque switch OPEN, CLOSED Limit switch OPEN, CLOSED Manual operation by handwheel
4)
or via local controls
Process representation input (fault signals)
Motor protection tripped Torque switch tripped in mid-travel One phase missing
Behaviour on loss of communication
The behaviour of the actuator is programmable: – running to end position OPEN or CLOSED – running to any intermediate position
4)
General data Profibus DP
Communication protocol Profibus DP according to EN 50 170-2 or DIN 19 245 Network topology Linear (BUS) structure. When using repeaters, tree structures can also be realised. Coupling
and uncoupling of devices during operation without affecting other devices is possible.
Transmission medium Twisted, shielded copper cable according to EN 50 170 Profibus DP interface EIA-485 (RS485) Transmission speed/
cable length
Device types DP master class 1, e.g. central controllers such as PLC, PC, ...
DP master class 2, e.g. programming/ configuration tools DP slave, e.g. devices with digital and/ or analog inputs/ outputs such as actuators, sensors
Number of devices 32 devices without repeater, with repeater expandable to 126 Bus access Token-passing between the masters and polling for slaves.
Mono-master or multi-master systems are possible.
Supported Profibus DP functions Cyclic data exchange, sync mode, freeze mode, fail-safe mode
Service conditions
Enclosure protection according to EN 60 529
Standard: IP 67 (when mounted) Options: IP 68
5)
DS3)Terminal compartment additionally sealed against interior (double sealed)
Corrosion protection Standard: KN Suitable for installation in industrial units, in water or power plants
with a low pollutant concentration
Options: KS Suitable for installation in occasionally or permanently aggressive
atmosphere with a moderate pollutant concentration (e.g. wastewater treatment plants, chemical industry)
KX Suitable for installation in extremely aggressive atmosphere with high
humidity and high pollutant concentration
KX-G Same as KX, however aluminium-free version (outer parts)
3) Only in combination with AM 01.1 and AM 02.1
4) Requires position transmitter (potentiometer or RWG) in actuator
5) For version in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended
Baud rate (kbit/s)
Max. cable length (segment
length) without repeater
Possible cable length with repea­ter
(total network cable length)
9.6
19.2
45.45
93.75
187.5 500
1,500
1,200 m 1,200 m 1,200 m 1,200 m 1,000 m
400 m 200 m
approx. 10 km approx. 10 km approx. 10 km approx. 10 km approx. 10 km
approx. 4 km approx. 2 km
Page 9
9
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Finish coating Standard: Two-component iron-mica combination
Option: Special primer/ special finish coat (customer’s choice)
Colour Standard: Silver-grey (DB 701, similar to RAL 9007)
Option: Other colours than standard colour are possible on request
Ambient temperature AM 01.1/ AM 02.1:
Standard: – 25 °C to + 70 °C Options: – 40 °C to + 70 °C, low temperature version
– 50 °C to + 70 °C, extreme low temperature version incl. heating system – 60 °C to + 70 °C, extreme low temperature version incl. heating system
AMExB/ AMExC: Standard: – 20 °C to + 40 °C Options: – 40 °C to + 40 °C, low temperature version
– 50 °C to + 40 °C, extreme low temperature version incl. heating system
Vibration resistance
6)
according to IEC 60 068-2-6
1 g, from 10 Hz to 200 Hz (Only actuator with controls. Not valid in combination with gearboxes)
Gewicht approx. 7 kg (with AUMA plug/ socket connector)
approx. 12 kg (including Ex-plug/ socket connector with terminal board)
Accessories
Wall bracket
7)
AUMA MATIC mounted separately from the actuator, including plug/ socket connector. Connecting cables on request. Recommended for high ambient temperatures, difficult access, or in case of heavy vibrations during service.
Other information
EU Directives Electromagnetic Compatibility (EMC): (89/336/EEC)
Low Voltage Directive: (73/23/EEC) Machinery Directive: (98/37/EC)
Reference documents Product description “Actuator controls AUMA MATIC”
Dimension sheets Multi-turn actuators/ part-turn actuators with integral controls AUMA MATIC”
6) Resistant to vibrations during start-up or for failures of the plant. However, a fatigue strength may not be derived from this
7) Cable length between actuator and AUMA MATIC max. 100 m. Not suitable for version with potentiometer in the actuator. Instead of the potentiometer, an RWG has to be used in the actuator
Page 10
6. Design AUMA MATIC Profibus DP
The AUMA MATIC Profibus DP by AUMA represents the ideal controls for connecting multi-turn actuators of the SA range and part-turn actuators of the SG range to Profibus DP.
The integral controls AUMA MATIC Profibus DP consist of the following modules:
.
Profibus DP interface. The interface links the Profibus DP data with the internal electronics.
.
The logic board links the signals of the actuator with the local controls and the Profibus DP interface and controls the reversing contactors or the thyristors.
.
Local controls with selector switch, push buttons, and indication lights. The selector switch is used to select the control devices for local control LOCAL – 0 REMOTE for remote control. The push buttons (OPEN) – Stop (CLOSE) are used for the electric operation of the actuator on site.
.
Plug/ socket connectors for easy mounting of the AUMA MATIC Profibus DP on the actuators.
.
Signal and control board with primary fuses, relays for conversion of the local control commands into electrical signals, and indication lights as an option.
.
Switchgear: Reversing contactors or thyristors for motor controls.
.
Profibus DP connection board with terminals for the Profibus DP cable and the termination resistor for bus termination.
Actuators which have already been installed can be retrofitted for Profibus DP b
y exchanging the controls AUMA MATIC for controls AUMA MATIC
Profibus DP.
10
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Figure A: AUMA MATIC Profibus DP
Switchgear
Power supply unit
Logic board
Profibus DP interface
Plug/ socket connector
to the actuator
Local controls
Selector switch
Signal and control board
Profibus DP
connection board
Electrical connection with
AUMA plug/ socket connector
Page 11
7. Electrical connection
.
Work on the electrical system or equipment must only be carried out by a skilled electrician himself or by specially instructed personnel under the control and supervision of such an electrician and in accordance with the applicable electrical engineering rules.
.
Installation regulations for Profibus DP must be observed for the wiring. (For literature references, please refer to appendix D)
Make sure to respect electromagnetic compatibility (EMC) when installing cables: Signal and b
us cables are susceptible to interference. Electric power cables,
in particular motor cables, are interference sources.
.
Lay cables being susceptible to interference or sources of interference at the highest possible distance from each other.
.
The interference immunity of signal and bus cables increases if the cables are laid close to the ground potential.
.
If possible, avoid laying long cables and make sure that they are installed in areas being subject to low interference.
.
Avoid long parallel paths with cables being either susceptible to interfe­rence or interference sources.
7.1 Power supply (standard) F
or explosion-proof version (type designation: AMExB/ AMExC), please
refer to page 15 or page 17.
.
Check whether type of current, supply voltage, and frequency comply with motor data (refer to name plate at motor).
.
Loosen bolts (50.01) (figure B-1) and remove connection housing.
.
Loosen screws (51.01) and remove socket carrier (51.0) from plug cover (50.0).
.
Insert cable glands suitable for connecting cables. (The enclosure protection stated on the name plate is only ensured if suit­able cable glands are used).
.
Seal cable entries which are not used with suitable plugs.
.
Connect cables according to order-related wiring diagram. The wiring diagram applicable to the actuator is attached to the handw­heel in a weather-proof bag, together with the operation instructions. In case the wiring diagram is not available, it can be obtained from AUMA (state commission no., refer to name plate) or downloaded directly from the Internet (www.auma.com).
A special parking frame (figure B-2) for protection against touching the bare contacts and against en
vironmental influences, in case the electrical
connection has been removed, is available.
11
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Figure B-1: Connection
50.0
50.01
51.0
51.01
Figure B-2: Parking frame (accessory)
Parking frame
Technical data Motor power connections1)Protective earth Control terminals
No. of contacts max. 6 (3 are used) 1 (leading contact) 50 pins / sockets Marking U1, V1, W1, U2, V2, W2 according to VDE 1 to 50 Connecting voltage max. 750 V 250 V Nominal current max. 25 A
16 A Type of customer connection Screws Screw for ring lug Screws Cross section max. 6 mm
2
6 mm
2
2.5 mm
2
Material: Pin/ socket carrier Polyamide
Polyamide Polyamide
Contacts Brass (Ms)
Brass (Ms)
Brass, tin plated or gold plated (option)
1)Suitable for copper wires. For aluminium wires, please contact AUMA
Table 2: Technical data AUMA plug/ socket connector for bus connection
Page 12
7.2 Bus connection (standard) For explosion-proof version (type designation: AMExB/ AMExC), please
refer to page 15 or page 17. For version with FO (fibre optics), please refer to separate operation instruc
-
tions “AUMA MATIC AM 01.1/ AM 02.1 FO connection”.
.
Connect bus cable. Refer to figures C-1 and C2.
The termination resistors for channel 1 and channel 2 (options) are switched in via s
witches (S1) and (S2). Both switches are supplied in position ‘OFF’. Only switch on the termination resistors (position ‘ON’) if the actuator is the final device in the Profibus segment.
Only switch on the termination resistors (position ’ON’) if the actuator is the final device within the Profibus DP segment.
12
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
S1
ON Bus termination channel 1 ON OFF Bus termination channel 1 OFF
S2
ON Bus termination channel 2 ON (option) OFF Bus termination channel 2 OFF (option)
Table 3: Switch positions of S1 and S2
Figure C-1: Connection board (standard)
S1
Bus termination
channel 1
Connection
channel 1
Screening
S2 Bus termination channel 2 (option)
Connection channel 2 (redundant)
Screening
X1
P/B
N/A
N/A
5V
P/B
GND
B
A
B
Figure C-2: Connection (standard)
from previous / to next
Profibus DP device
channel 1
Page 13
7.3 Fitting the cover After connection:
.
Insert the socket carrier (51.0) into the plug cover (50.0) and fasten it with screws (51.01).
.
Clean sealing faces at the plug cover and the housing.
.
Check whether O-ring is in good condition.
.
Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.
.
Replace plug cover (50.0) and fasten bolts (50.01) evenly crosswise.
.
Fasten cable glands with the specified torque to ensure the required enclosure protection.
13
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
from previous/ to next
Profibus DP device
channel 1
Profibus
cable
AUMA
labelling at the
connection
SUB-D 9 plug pin
(for other
Profibus devices)
Colour
A N/A 8 green B P/B 3 red
Table 4: Assignment of Profibus cable
Figure C-3: Connection board (for overvoltage protection)
X1
1234
Figure C-4: Connection for overvoltage protection
x1 x2
Page 14
7.4 Remote position transmitter For the connection of remote position transmitters (potentiometer, RWG)
screened cables must be used.
7.5 AUMA MATIC on wall bracket The AUMA MATIC can also be mounted separately from the actuator on a
wall bracket.
.
For the connection of actuator and AUMA MATIC on wall bracket, use suit­able flexible and screened connecting cables. (Preconfectioned cables can be obtained from AUMA on request)
.
Permissible cable distance between actuator and AUMA MATIC amounts to a max. of 100 m.
.
Versions with potentiometer in the actuator are not suitable. Instead of the potentiometer, an RWG has to be used in the actuator.
.
Connect the wires in correct phase sequence. Check direction of rotation before switching on.
7.6 Test run P
erform test run. Please refer to the operation instructions pertaining to the
actuator (multi-turn actuator SA(R) ... / part-turn actuator SG ...).
Check limit and torque switching:
Check limit and torque switching, electronic position transmitter RWG or potentiometer (option) and re-set where appropriate. The settings are described in the operation instructions pertaining to the actuator (multi-turn actuator SA(R) ... part-turn actuator SG ... ).
For actuators with feedback signal (RWG, potentiometer), a reference operation has to be performed after having changed the setting.
Perform reference operation:
.
Run actuator electrically (via the push buttons OPEN and CLOSE of the local controls) once to the end position OPEN and once to the end posi­tion CLOSED.
.
If no reference operation is performed after changing the limit switching, the feedback signal via the bus is not correct. The bus signals the missing reference operation as warning (see page 32).
14
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Figure C-5: AM on wall bracket
Connecting cable to actuator
Page 15
7.7 Mains and bus connection for Ex-version with plug/ socket connector/ terminal board (KP)
When working in potentially explosive areas, observe the European Standards EN 60079-14 “Electrical installations in hazardous areas” and EN 60079-17 “Inspection and mainten
-
ance of electrical installations in hazardous areas”.
For the Ex-plug/ socket connector (figure D-1), the electrical mains connec­tion is made after removing the plug cover (50.0) at the EEx e terminals of the terminal board (51.0). The flameproof compartment (type of protection EEx d) remains hereby closed.
.
Check whether type of current, supply voltage, and frequency correspond to motor data (refer to name plate at motor).
.
Loosen bolts (50.01) (figure D-1) and remove plug cover.
.
Insert cable glands with “EEx e” approval and of size suit­able for connecting cables. For the recommended cable glands refer to appendix E, page 54. (The enclosure protection stated on the name plate is only ensured if suitable cable glands are used).
.
Seal cable entries which are not used with suitable plugs.
.
Maximum 2 wires with the same cross section may be con­nected to one terminal.
.
Remove cable sheathing in a length of 120 – 140 mm. Strip wires: Controls max. 8 mm, motor max. 12 mm.
For stranded wires use end-sleeves according to DIN 46228.
.
Connect bus cable. Refer to figures (D-4 or D-5). The termination resistor for channel 1 is connected through linking the terminals 1 – 4 and 3 – 2 (standard). Only connect the termination resistor if the actuator is the final device in the Profibus segment.
.
Connect screen largely to the cable glands. For the recommended cable glands refer to appendix E, page 54.
If the actuator must be taken from the valve, e.g. for service purposes, it can be separ
ated from the mains without having to remove the wiring (figure D-2). For this purpose, the screws (51.02) are removed and the plug/ socket connector is pulled off. Plug cover (50.0) and terminal board (51.0) remain together.
Flameproof enclosure! Before opening, ensure that no explosive gas and no voltage is present.
A special parking frame (figure D-3) for protection against touching the bare contacts and against environmental influences is available.
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
15
Figure D-1: Connection
50.0
50.01
51.0
Figure D-2: Disconnection from the mains
50.0
51.0
51.02
Figure D-3: Parking frame (accessory)
Parking frame
Page 16
16
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Figure D-4: Bus connection for channel 1 (standard)
Another bus device follows the actuator
Actuator is final bus device
from previous Profibus DP device channel 1
to next Profibus DP device channel 1
Technical data Motor power connections
1)
Protective earth Control terminals
No. of contacts max. 3 1 (leading contact) 38 pins/ sockets Marking U1, V1, W1 1 to 24, 31 to 50 Connecting voltage max. 550 V 250 V Nominal current max. 25 A 10 A Type of customer connection Screws Screws Screws Cross section max. 6 mm
2
6 mm
2
1.5 mm
2
Material: Pin/ socket carrier Araldite/ Polyamide Araldite/ Polyamide Araldite/ Polyamide Contacts Brass (Ms) Brass (Ms) Brass (Ms) tin-plated
1) Suitable for copper wires. For aluminium wires, please contact AUMA.
Table 5: Technical data Ex plug/socket connector with terminal board for explosion-proof actuators
Page 17
7.8 Mains and bus connection for Ex-version with plug-in terminal connection (KES)
When working in potentially explosive areas, observe the European Standards EN 60079-14 “Electrical installations in hazardous areas” and EN 60079-17 “Inspection and mainten
-
ance of electrical installations in hazardous areas”.
The bus connection is realised via terminals (figure E-1) The terminal compartment is designed for explosion protection “EEx e” (increased safety). The controls AUMA MATIC (type of protection EEx d) remain closed.
.
Loosen bolts (1) (figure E-1) and remove terminal cover.
.
Insert cable glands with “EEx e” approval and of size suit­able for connecting cables. For the recommended cable glands refer to appendix E, page 54. (The enclosure protection stated on the name plate is only ensured if suitable cable glands are used).
.
Seal cable entries which are not used with suitable plugs.
Cross sections for connection:
Control
cables: max. 2.5 mm² Motor connection: max. 10 mm², Suitable bus cables, see page 19.
.
Connect bus cable to channel 1 according to configuration of the termi­nals (figure E-2). The termination resistor for channel 1 is connected through linking the terminals 1 – 2 and 3 – 4.
.
Only connect the termination resistors if the actuator is the final device in the Profibus segment.
17
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Figure E-1: Plug-in terminal connection
Terminal cover
Terminals
Terminal board
Figure E-2: Terminal configuration for Ex connection (KES)
Another bus device follows the actuator
Previous Next Profibus DP device Profibus DP device
Actuator is final bus device
Previous Profibus DP device
Page 18
7.9 Redundant bus connection AUMA Profibus DP devices can be connected with a second (redundant)
Profibus cable. If the bus on channel 1 fails, e. g. through cable break, the slave automatically switches to channel 2.
This cable redundancy may only be applied after previous integration test using the desired process control system!
.
For versions with AUMA plug/ socket connector (subclause 7.2):
Connect redundant bus cable to channel 2in the same way as channel 1 (refer to connection diagram figure C-2).
.
For Ex-version with plug/ socket connector / terminal board (KP) (subclause 7.7):
Connect cable B to terminal 6, cable A to terminal 7. The termination resistor for channel 2 is connected through linking the terminals 5 – 6 and 7 – 8.
.
For Ex-version with plug-in terminal connection KES) (subclause 7.8):
Connect cable B to terminal 6, cable A to terminal 7 (figure E-2). The termination resistor for channel 2 is connected through linking the terminals 5 – 6 and 7 – 8.
The setting of the redundant bus connection is realised via the parameters 4 and 5 (see page
23).
18
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 19
7.10 Bus cables Only cables according to standard DIN 19245 or EN 50170-2, cable type A,
may be used for Profibus DP wiring.
A maximum of up to 32 Profibus devices may be connected in one segment. If more devices are to be connected to one Profibus network, several segments must be connected with repeaters. The bus cable must be laid at a distance of at least 20 cm from other cables. It should be laid in a separate, conductive and earthed cable trunking. It must be ensured that there are no potential differences between the indivi­dual devices on the Profibus (perform a potential compensation).
Cable specification cable type A for Profibus DP
Characteristic impedance: 135 to 165 Ohm, at a frequency
of 3 to 20 Mhz. Cable capacity: < 30 pF per meter Core diameter > 0.64 mm Core cross section: > 0.34 mm², corresponds to AWG 22 Loop resistance: < 110 Ohm per km Screening: Copper shielding braid or shielding braid and
shielding foil
19
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Transmission rate in kBit/s
93.75
187,5 500 1500
Maximum segment length in m
1200 1000 400 200
Tabl e 6
Figure F: Example: Profibus with one segment
Bus termination switched on
Bus termination switched on
Profibus DP board
AUMA MATIC Profibus DP
Connection board
2-wire cable
Controls (master)
Page 20
7.11 Setting the Profibus DP address
The bus address is set on the Profibus DP interface board.
.
Loosen screws and remove cover (figure G-1)
.
Set the required bus address using rotary switches S2 and S3 (figure G-2). (Factory setting: slave address 2)
Switch (S3) for setting the units digit. Switch (S2) for setting the tens digit.
Example: The address ‘65’ is set as follows: (S3) to position 5 = (5 * 1 = 5) (S2) to position 6 = (6 * 10 = 60)
20
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Figure G-1
Screws
Profibus DP interface board
Figure G-2: Profibus DP interface board
Rotary switch S3 Rotary switch S2
Page 21
8. Commissioning with controls
8.1 Introduction When commissioning a Profibus DP network, the devices on the Profibus DP
must be parameterized and configured with the programming software of the controls (Profibus configurator). The programming software first reads the GSD file (General Station Data) of the individual actuators. The GSD file contains information about the proper­ties of the device which are needed by the master. The GSD file can be downloaded from the Internet website www.auma.com. Afterwards, the user can configure and program the instrument at the Profibus DP for the programming software of the process control system. This information is then stored in the controls (DP master) and sent to the actuators (DP slaves) each time communication is started. The control is executed via the process representation input and output bytes. If a configuration with consistent data is chosen, special functional elements for the control of the Profibus DP slaves must be used with some PLCs.
8.2 Programming The parameterization is partly determined in the Profibus standard, e.g. a bit
for switching bus monitoring on and off (watchdog). The AUMA Profibus DP control can additionally receive up to 100 bytes of ‘user parameters’, in which AUMA specific parameters can be set. The AUMA specific parameters are divided into 50 parameters with 2 bytes each per parameter. The parameters can be changed via the programming soft­ware of the controls. New programming software supports the setting of the parameters via text and a menu selection. When using older software, the values of the parameters must be entered using hexadecimal numbers. The meaning of the individual AUMA specific parameters is explained in subclause 8.5.
8.3 Configuration of the Profibus DP interface of the AUMA MATIC
During configuration, selection is made of how many input and output bytes for each device are reserved in the controls’ memory. Additionally it is deter­mined if the data is processed consistently or non-consistently.
Only the number of bytes determined in the configuration is transferred between DP master and DP slave.
The following configurations are possible with AUMA Profibus DP actuators:
All these configurations (except 1 In, 1 Out) can be selected as consistent or non-consistent
The number of input bytes states how many of the maximum 16 bytes the DP slave sends to the DP master. The number of output bytes states how many of the maximum 8 bytes the DP master sends to the DP slave.
21
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Number of input bytes Number of output bytes
11 21 22 44 61 62 64
84 12 4 16 8
Tabl e 7:
Page 22
If, for example, the configuration with 8 bytes input is selected, only the first 8 bytes are sent from the DP slave to the DP master. In this case, the master does not have access to bytes 9 to 12. This way, the DP master saves memory space since it only has to reserve 8 input bytes for the actuator. The data of the AUMA actuators should be consistently processed by the DP master. This ensures that the value of a 2 byte variable (position trans­mitter, analogue customer input) does not change after the reading out of the first byte and, thus, does not distort the value. If a master does not offer the possibility to use consistent configurations by means of the process control system, a non-consistent configuration can be chosen. The values for the position transmitter and the analogue customer inputs can then be transferred in 1 byte format (parameter 2 = 0).
8.4 Communication start-up When the DP master is switched on, it first sends a parameter and configu-
ration telegram to each DP slave. If parameters and configuration are correct, the DP slave enters the ‘Data Exchange’ mode to exchange process data between the controls and the slave. Then, the DP master can control the DP slave and read its current state via the process representa­tion. If communication is interrupted (e.g. due to switching off the slave or the breaking of the Profibus cable), it is automatically resumed by the DP master, once the origin of the fault has been eliminated.
8.5 Description of AUMA user parameters
The AUMA specific parameter are set by means of the GSD file.
Parameter 1 “Position transmitter” [Stellungsgeber]
Default value (standard setting): 1 0: The actuator is not equipped with a position transmitter. 1: Actuator is equipped with a potentiometer without RWG. 2: Actuator is equipped with an RWG0–20mA.
For this position transmitter, the signal interruption monitoring is not acti­vated.
3: Actuator is equipped with an RWG4–20mA.
For this position transmitter, the signal interruption monitoring is activated.
Parameter 2 “Measured data coding position transmitter” [Messwertkodierung Stellungsgeber]
Default value: 0 0: 0 to 100 percent, resolution amounts to 1 %
The position transmitter value is indicated in process representation input in byte 4. Byte 3 is fixed to the value 0. The setpoint is realised via byte 4 of process representation output. Byte 3 must be set to 0.
1: 0 to 1000 per mil, resolution amounts to 0.1 %
The position transmitter value is read using bytes 3 and 4 of process representation input. The setpoint is realised via bytes 3 (high byte) and 4 (low byte) of process representation output.
Parameter 3 "Reversing prevention in ms" [Reversiersperre in ms]
Parameter for setting the pause time in between a change of direction. If necessary, adjust the value to the mechanics to prevent destruction caused by excessively fast changes of direction.
Default value: 200 lowest value:100 (0.1s) maximum value: 1000 (1 s)
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
22
Page 23
Parameter 4 “Redundancy” [Redundanz]
Default value: 0 0: no cable redundancy (only the first channel is used for communication). 1: cable redundancy switched on (first and second channel cabled)
The watchdog must be activated, otherwise the parameter record is rejected by the DP slave.
Parameter 5 “Time for channel changing in 0.1 s” [Zeit für Kanalwechsel in 0,1 s]
Indicates the time after which the channel is changed if no process data exchange (DATA EX) takes place (no ‘Data Exchange’ or DP-Fail-Safe state). This parameter is only effective if the cable redundancy (parameter 4) is switched on.
Default value: 50 lowest value: 50 (5 s) maximum value: 6000 (10 min)
Parameter 6 “Failure behaviour”[Sicherheitsverhalten]
Failure operation on failure of connection (no status Data_Exchange or DP fail-safe). The parameters set in the most recent connection also apply to the failure behaviour after an interruption in the voltage supply. If the parameter is set to the values 1 or 2, the watchdog must be activated, otherwise the para­meter record is rejected by the DP slave.
Default value: 0 0: Failure behaviour switched off (parameters 7, 8, 9 are insignificant) 1: Simple failure behaviour switched on.
A failure operation will only be started if a connection to the master (process data exchange [DATA EX]) has already been available.
2: Extended failure behaviour switched on.
If extended failure behaviour is switched on, a failure opera­tion can be initiated immediately after the actuator has been switched on.
Parameter 7 “Delay time for failure operation 0.1s” [AusloesZeitSicherheitsfahrt 0,1 s]
Delay time for failure operation in 0.1 s. Indicates the down time of process data exchange after which a failure operation will be started. If the exchange is restored during this time, no failure operation will be performed.
Default value: 30 lowest value: 0 (actuator reacts immediately) maximum value: 12,000 (actuator reacts after 20 minutes)
Parameter 8 “Failure operation” [Sicherheitsfahrt]
Default value: 0 0: Actuator remains in its position (STOP). 1: Actuator runs CLOSE. 2: Actuator runs OPEN. 3: Actuator runs to failure position (refer to parameter 9).
If no position transmitter is installed (Parameter 1 = 0), value 3 is not permitted. In this case, the parameter record is rejected.
23
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page 24
Parameter 9 “Failure position in per mil” [Sicherheitsposition in Promille]
Actuator runs to the pre-set failure position. This parameter is only effective if parameter 8 (failure operation) is set to value 3, and if parameter 6 (failure behaviour) is not 0.
Default value: 0 lowest value: 0 (end position CLOSED) maximum value: 1000 (end position OPEN)
Parameter 10 “Output speed failure operation percentage” [Drehzahl Sicherheitsfahrt Proz]
Running speed applied to approach failure position. Only effective in combination with variable speed AUMA actuators, type AS, ASR. Only effective if parameter 8 (failure operation) and parameter 6 (failure behaviour) are not set to 0.
Default value: 100 lowest value: 0 (minimum output speed) maximum value: 100 (maximum output speed)
For detailed descriptions of parameters 11 to 14, please refer to subclause 11.2
Parameter 11 “Dead time positioner in 0.1 s” [Totzeit Stellungsregler in 0,1 s]
Indicates the dead time which has to be maintained between two motor starts. In case the Profibus DP Master issues a command before that time, the AUMA MATIC delays the actuator reaction until dead time has expired.
The controls must ensure that the maximum number of motor starts of the actuator is not exceeded.
Default value: 0 minimum value: 0 (actuator reacts immediately) maximum value: 600 (actuator delays reaction by 1 minute max.)
Parameter 12 “Overrun direction OPEN in per mil” [Nachlauf Richtg AUF in Promille]
The motor is switched off as soon as the distance between the actuator position and the nominal position reaches this value. This is only valid for operations in direction OPEN. This parameter must be smaller than the value in parameter 14 (max. error in per mil).
Default value: 5 minimum value: 0 (no overrun in direction OPEN) maximum value: 100 (10 % overrun in direction OPEN)
Parameter 13 “Overrun direction CLOSE in per mil” [Nachlauf Richtg ZU in Promille]
The motor is switched off as soon as the distance between the actuator position and the nominal position reaches this value. This is only valid for operations in direction CLOSE. This parameter must be smaller than the value in parameter 14 (max. error in per mil).
Default value: 5 minimum value: 0 (no overrun in direction CLOSE) maximum value: 100 (10 % overrun in direction CLOSE)
24
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 25
Parameter 14 “Max. error in per mil” [max. Regelabweichung in Promille]
The actuator will only be restarted if the distance between the nominal posi
­tion and the actual position is higher than this value. Corresponds to the outer dead band. This parameter must be higher than the values of parameter 12 (overrun in direction OPEN) and parameter 13 (overrun in direction CLOSE).
The parameter must be set sufficiently high to ensure a stable function of the positioner. If the value is set too low, the actuator moves continuously around the nominal value which will result in reducing the life time of the actuator.
Default value: 10 minimum value: 1 (0.1 % error). maximum value: 100 (10 % error).
Parameter 15 "Proportional operation active" [Proportionalfahrt aktiv]
Soft start/ soft stop is only possible together with variable speed actuators (type AS, ASR). This parameter has no influence on non-variable speed actuators.
Default value: 0 0: no soft start/ soft stop (proportional operation) 1: soft start/ soft stop (proportional operation)
Parameter 15 – 19 reserved for variable output speed actuators of types AS, ASR with motor controls AUMA VARIOMATIC.
Parameter 16 “Proportional range Stop in per mil” [ProportBereich Stop in Promille]
Proportional range of the nominal position in per mil (soft stop). If the difference between nominal and actual actuator position is smaller than this value, the running speed will decrease proportionally to the diffe­rence in nominal/ actual position. This allows the nominal position to be “gently” reached. Only effective if parameter 15 (proportional operation active) and parameter 1 (position transmitter) are not set to 0.
Default value: 100 minimum value: 0 (soft stop ineffective) maximum value: 1000 (soft stop over the whole travel)
Parameter 17 “Stop speed in percent” [Stopgeschwindigeit in Prozent]
Default value: 0 minimum value: 0 (actuator moves to nominal position with min. speed) maximum value:100 (actuator moves to nominal position with max speed).
Running speed with which the nominal position will be approached. Only effective if parameter 15 (proportional operation active) and parameter 1 (position transmitter) are not set to 0.
Parameter 18 "Proportional range start in per mil" [ProportBereich Start in Promille]
Proportional range of the start position in per mil (soft start) If the difference between start position and actual actuator position is smaller than this value the running speed will increase proportionally to the difference in nominal/ actual position. This causes the actuator to “gently” leave the start position. Only effective if parameter 15 (proportional opera
-
tion active) and parameter 1 (position transmitter) are not set to 0.
Default value: 40 minimum value: 0 (soft start ineffective) maximum value: 1000 (soft start over the whole travel)
25
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page 26
Parameter 19 “Starting speed in percent” [Startgeschwindigkeit in Prozent]
Running speed used to leave the start position. Only effective if parameter 15 (proportional operation active) and parameter 1 (position transmitter) are not set to 0.
Default value: 50 minimum value: 0 (minimum starting speed) maximum value: 100 (maximum starting speed)
Parameter 20 “Start analogue 2 in 0.1 mA” [Anfang Analog 2 in 0,1 mA]
Current value at which the measuring range of analogue 2 input (option) begins. This value must be smaller than the value in parameter 21 (end analogue 2 in 0.1 mA). If a sensor with a 4..20 mA signal is connected to analogue 2, the value must be set to 40.
Default value: 0 minimum value: 0 (value for sensor with 0-20 mA output) maximum value: 150
Parameter 21 “End analogue 2 in 0.1 mA” [Ende Analog 2 in 0,1 mA]
Current value at which the measuring range of analogue 2 input (option) ends. This value must be higher than the value in parameter 20 (start analogue 2 in 0.1 mA).
Default value: 200 minimum value: 50 maximum value: 200 (value for sensor with 0 – 20 mA or 4 – 20 mA output)
Parameter 22 "Coding analogue 2" [Kodierung Analog 2]
Default value: 0 0: 0 to 100 percent 1: 0 to 1000 per mil 2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
Parameter 23 “Start analogue 3/4 in 0.1 mA” [Anfang Analog 3/4 in 0,1 mA]
Default value: 0 minimum value: 0 (value for sensor with 0 – 20 mA output) maximum value: 150
Current value at which the measuring range of analogue 3/4 input begins. This value must be smaller than the value in parameter 24 (end analogue 3/4). If a sensor with a 4..20 mA signal is connected to analogue 3/4, the value must be set to 40.
Parameter 24 “End analogue 3/4 in 0.1 mA”[Ende Analog 3/4 in 0.1 mA]
Default value: 200 minimum value: 50 maximum value: 200 (value for sensor with 0 – 20 mA or 4 – 20 mA output)
Current value at which the measuring range of analogue 3/4 input ends. This value must exceed the value in parameter 23 (start analogue 3/4).
Parameter 25 “Coding analogue 3/4” [Kodierung analog 3/4]
Default value: 0 0: 0 to 100 percent 1: 0 to 1000 per mil 2: 0 to 1023 (raw value of analogue-digital converter, not standardised)
26
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 27
The stepping mode increases the number of starts of the actuator. It must be ensured that the maximum number of starts will equally not be exceeded when operating in step
-
ping mode.
Parameter 26 "Stepping direction OPEN active" [Takt Richtung AUF aktiv]
This parameter is only effective if parameter 1 (position transmitter) is not 0. Otherwise the parameter record will be rejected.
Default value: 0 0: Stepping mode in direction OPEN switched off 1: Stepping mode in direction OPEN switched on
Parameter 27 “Stepping operating time OPEN in 0.1 s” [Takt Fahrzeit AUF in 0,1 s]
Stepping operating time direction OPEN in 0.1 s This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Default value: 10 minimum value: 1 (actuator runs 0.1 s per stepping period) maximum value: 36,000 (actuator runs 1 hour per stepping period)
Parameter 28 “Stepping pause time OPEN in 0.1 s” [Takt Pausenzeit AUF in 0,1 s]
Stepping pause time direction OPEN in 0.1 s This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Default value: 50 minimum value: 1 (actuator stationary 0.1 s per stepping period) maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 29 “Stepping start OPEN in per mil” [Takt Anfang AUF in Promille]
Start of stepping distance in direction OPEN. Indication of position in per mil This value must be smaller than the value in parameter 30 (stepping end OPEN in per mil). Otherwise, the parameter record will be rejected. This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Default value: 0 minimum value: 0 (stepping mode in direction OPEN begins at 0, end position CLOSED) maximum value: 999
Parameter 30 “Stepping end OPEN in per mil” [Takt Ende AUF in Promille]
End of stepping distance in direction OPEN. Indication of position in per mil This value must be higher than the value in parameter 29 (stepping start OPEN in per mil). Otherwise, the parameter record will be rejected. This parameter is only effective if parameter 26 (stepping direction OPEN active) is not 0.
Default value: 1000 minimum value: 1 maximum value: 1000 (Stepping mode in direction OPEN ends at position
1000, end position OPEN)
Parameter 31 “Stepping direction CLOSE active” [Takt Richtung ZU aktiv]
This parameter is only effective if parameter 1 (position transmitter) is not 0. Otherwise, the parameter record will be rejected.
Default value: 0 0: Stepping mode in direction CLOSE switched off 1: Stepping mode in direction CLOSE switched on
27
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page 28
Parameter 32 “Stepping operating time CLOSE in 0.1 s” [Takt Fahrzeit ZU in 0,1 s]
Operating time for stepping mode in direction CLOSE. Indication in 0.1 seconds. This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0.
Default value: 10 minimum value: 1 (actuator runs 0.1 s per stepping period) maximum value: 36000 (actuator runs 1 hour per stepping period)
Parameter 33 “Stepping pause time CLOSE in 0.1 s” [Takt Pausenzeit ZU in 0,1 s]
Pause time for stepping mode in direction CLOSE. Indication in 0.1 seconds This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0. Otherwise, the parameter record will be rejected.
Default value: 50 minimum value: 1 (actuator stationary 0.1 s per stepping period) maximum value: 36,000 (actuator stationary 1 hour per stepping period)
Parameter 34 “Stepping start CLOSE in per mil” [Takt Anfang ZU in Promille]
Default value: 1000 minimum value: 1 maximum value: 1000 (Stepping mode in direction CLOSE starts at position 1000, end position OPEN)
Start of stepping distance in direction CLOSE. Indication of position in per mil. This value must be higher than the value in parameter 35 (stepping end CLOSE in per mil). Otherwise, the parameter record will be rejected. This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0.
Parameter 35 “Stepping end CLOSE in per mil” [Takt Ende ZU in Promille]
End of stepping distance in direction CLOSE. Indication of position in per mil. This value must be higher than the value in parameter 34 (stepping start CLOSE in per mil). This parameter is only effective if parameter 31 (stepping direction CLOSE active) is not 0. Otherwise, the total parameter record will be rejected.
Default value: 0 minimum value: 0 (stepping mode in direction CLOSE ends at position 0, end position CLOSED) maximum value: 999
Parameters 36 to 50 are spare parameters [Reserveparameter]
They are reserved for extensions.
Default value: 0 Value range: 0 to 65535
28
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 29
9. Process representation input
Via the process representation input, the master (controls) can read the state of the slave (actuator).
Grey bits are collective signals. They contain the results of a disjunction (OR operation) of other information.
To ensure that the actuator gives a correct end position signal after power failure in end position CLOSED/ OPEN, we recommend to evaluate the information LSC (WSR)/ LSO (WOEL) (bit 5/4 in byte 2) for the end position signal CLOSED/ OPEN.
29
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Logical signals
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Wrong command
Selector not remote
Thermal fault
Mains failure
Torque fault CLOSE
Torque fault OPEN
Clear state
--
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Failure 24 V supply
Channel 2 active
Loss of transm. signal
Potentiometer fault
Hardware fault
No reference operation
--
--
--
Analog 3/4 loss
Analog 2 loss
--
Dig. input 3
Dig. input 2
Dig. input 1
Dig. input 0
Fault signals
Warning signals
Physical operation
Options
High byte
1 customer analog input
(wiring diagram design. analog 2)
st
Low byte
1 customer analog input
(wiring diagram design. analog 2)
st
High byte
2 customer analog input
(wiring diagram design. analog 3/4)
nd
Low byte
2 customer analog input
(wiring diagram design. analog 3/4)
nd
Spare Spare Spare Spare
Byte1:
Actuator signals
Thermal fault
Mains failure
Remote sw. position
Local sw. position
LSO (WOEL)
LSC (WSR)
TSO (DOEL)
TSC (DSR)
Byte 2:
Byte 7:
Byte 3: E2 Actual position
Byte 6:
Byte 5:
Byte 4: E2 Actual position
Byte 8:
Byte16
Byte15
Byte14
Byte13
Byte12: 2 analog input
nd
Byte 11: 2 analog input
nd
Byte 10: 1 analog input
st
Byte 9: 1 analog input
st
Local CLOSE
Local OPEN
Remote CLOSE
Remote OPEN
Start stepping mode
Operation pause
Proport. operation
Rev.prev./ dead time
Actual position (high byte)
(position transmitter)
Actual position (low byte)
(position transmitter)
Fault ind.
Warning ind.
Running CLOSE
Running OPEN
Setpoint reached
CLOSED position
OPEN position
--
Page 30
9.1 Process representation input (default process representation)
Byte 1: Logical signals
Important signals from the ac
-
tuator concerning errors, war
-
nings, operations:
30
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Bit Designation Value Description
0
OPEN position
Limit seating in end positi
-
on OPEN
1 Limit switch in direction OPEN operated.
0 other
1
CLOSED position
Limit seating in end positi­on CLOSED
1 Limit switch in direction CLOSE operated
0 other
CLOSED po­sition
Torque sea­ting in end position CLOSED
1
Torque switch and limit switch in direction CLOSE operated.
0 other
2
Setpoint reached
1
The setpoint is within max. error variable (outer dead band). Signal occurs only if Profibus DP master has set the Setpoint reached bit.
0 other
3
1
(reserved for extensions)
0
4
Running OPEN
1
Operation command (OPEN or SETPOINT) from Pro­fibus DP in direction OPEN is executed. For operati­on in stepping mode, this signal is also active during an off-time, the dead time, and the reversing preventi­on.
0 No operation is carried out via Profibus DP.
5
Running CLOSE
1
Operation command (CLOSE or SETPOINT) from Profibus DP in direction CLOSE is executed. For ope­ration in stepping mode, this signal is also active du­ring an off-time, the dead time, and the reversing pre­vention.
0 No operation is carried out via Profibus DP.
6
Warning ind.
1
One or several warnings have occurred. Collective signal: Contains the result of a disjunction
(OR operation) of all bits of the byte “Warning sig­nals” (page 33).
0
No warnings are active (all bits of the warnings can­celled).
7
Fault ind.
1
One or several faults have occurred so that the ac­tuator can no longer be controlled via Profibus DP (at least one bit set in fault byte).
Collective signal: Contains the result of a disjunction (OR operation) of all bits of the byte “Fault signals” (page 31 cont’d)
0
No faults are active (all bits are cancelled in fault byte).
Page 31
Byte 2: Actuator signals
Basic signals originating from the logic
Byte 3: E2 Actual position (high byte) (position transmitter) Byte 4: E2 Actual position (low byte) (position transmitter)
Bytes 3 and 4 are used to transmit the actual actuator position (requires position transmitter within actuator). The actual position can be transmitted either as a value between 0 – 100 (percent) or 0 – 1000 (per mil). For 0 – 100 (per cent), the consistency does not have to be regarded in the trans­mission and only the low byte must be regarded. The change-over between 0 – 100 and 0 – 1000 is realised via a parameter in the GSD file (default setting: transmission in 0 – 100 format).
Byte 5: Fault signals
The actuator is not ready for remote operation. As soon as one of these signals is set, bit 7 of byte 1 will alsobe set)
31
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Bit Designation Value Description
0
Thermal fault
1 A thermal fault (motor protection) has occurred.
0 No thermal fault has occurred.
1
Mains failure
1 A mains failure has occurred, e.g. phase error.
0 No mains failure has occurred.
2
Remote sw. position
1 Selector switch in position REMOTE.
0 Selector switch not in position REMOTE.
3
Local sw. position
1 Selector switch in position LOCAL.
0 Selector switch not in position LOCAL.
4
LSO (WOEL)
1 Limit switch OPEN left operated.
0 Limit switch OPEN left not operated.
5
LSC (WSR)
1 Limit switch CLOSE right operated.
0 Limit switch CLOSE right not operated.
6
TSO (DOEL)
1 Torque switch OPEN left operated (storing).
0 Torque switch OPEN left not operated.
7
TSC (DSR)
1 Torque switch CLOSE right operated (storing).
0 Torque switch CLOSE right not operated.
Bit Designation Value Description
0
Wrong com-
mand
1
Indicates the fact that several operation commands were received simultaneously via Profibus DP (e.g. Re­mote OPEN and Remote CLOSE simultaneously or Re­mote CLOSE/ Remote OPEN and Remote SETPOINT (nominal) simultaneously) or that the max. value for a nominal position has been exceeded (setpoint > 1000).
0 Operation commands correct
1
Selector not
remote
1 Selector switch: position LOCAL or OFF
0 Selector switch: position REMOTE
2
Thermal fault
1
Motor protection has tripped; remedy: resetting local controls via selector switch position RESET after the motor has cooled off.
0 other
3
Mains failure
1 Loss of one phase or incorrect phase sequence.
0 other
4
Torque fault
CLOSE
1
Torque fault OPEN occurred (only torque or torque be
-
fore limit, according to type of seating); remedy: reset
-
ting using counter command
0 other
5
Torque fault
OPEN
1
Torque fault CLOSED occurred (only torque or torque before limit, according to type of seating); remedy: re
-
setting using counter command
0 other
Page 32
Byte 6: Warning signals
Warning signals serve only in­formation purposes and do not interrupt or cancel an ope­ration (as opposed to faults). As soon as one of these sig­nals is set, bit 6 of byte 1 will be set simultaneously.
Byte 7: Physical operation
32
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Bit Designation Value Description
6
Clear state
1 Indicates that a telegram Global Control Clear was
sent via the Profibus DP (the bit can only be deleted with a telegram Global Control Operate). In this state, the actuator can not be operated from REMOTE.
0
7
1
not assigned (reserved for extensions)
0
Bit Designation Value Description
0
Failure 24 V
supply
1 Failure 24 V supply voltage.
0 other
1
Channel 2
active
1 Actuator uses channel 2 for communication.
0 other
2
Loss of
transm.
signal
1
Signal interrupted at position transmitter RWG: For re­cognition purpose, parameter 1 must be set to value 3 (RWG 4 – 20 mA).
0 other
3
Potentio-
meter fault
1
Potentiometer fault: in end position CLOSED a value is measured being higher than the one in end position OPEN.
0 other
4
Hardware
fault
1
Hardware fault: If this bit is set, the Profibus board must be checked/ replaced.
0 other
5
No reference
operation
1
No reference operation: The values of the position transmitter cannot be used as long as the reference operation (end position OPEN, en position CLOSED) has not been performed. A nominal ope­ration is not possible.
0 other
6
1
Not assigned (reserved for extensions)
0
7
1
Not assigned (reserved for extensions)
0
Bit Designation Value Description
0
Rev.prev./ dead time
1
Reversing prevention/ dead time warning: The actuator does not start as long as reversing prevention or dead time is still active. The bit is set if a run command is available which cannot be executed immediately. The bit is cancelled as soon as the actuator starts.
0 other
1
Proport. operation
1
Proportional section reached (soft start or soft stop) ac­tive. Only possible together with adjustable output speed actuators of the type ranges AS, ASR with AUMA VARIOMATIC Profibus DP.
0 other
2
Operation pause
1 Operation pause
0 other
3
Start step
-
ping mode
1
Indicates that the actuator is within the stepping range during active stepping mode. Conditions: position trans
-
mitter is provided, stepping mode is active, remote ope
-
ration is being performed.
0 other
Page 33
Byte 8: Options
Digital inputs and loss of signal at analogue inputs
Byte 9: High byte first analogue customer input (wiring diagram designation analogue 2) Byte 10: Low byte first analogue customer input (wiring diagram designation analogue 2)
The data content of bytes 9 and 10 depends on parameter 22; with the default value (0 – 100 percent), only the low byte is used.
Byte 11: High byte second analogue customer input (wiring diagram designation analogue 3/4) Byte 12: Low byte second analogue customer input (wiring diagram designation analogue 3/4)
The data content of bytes 11 and 12 depends on parameter 25; with the default value (0 – 100 percent), only the low byte is used.
Byte 13 to 16: reserved for extensions
33
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Bit Designation Value Description
0
Dig. input 0
1 Digital input no. 1 = 1 (switch closed)
0 Digital input no. 1 = 0 (switch open)
1
Dig. input 1
1 Digital input no. 2 = 1 (switch closed)
0 Digital input no. 2 = 0 (switch open)
2
Dig. input 2
1 Digital input no. 3 = 1 (switch closed)
0 Digital input no. 3 = 0 (switch open)
3
Dig input 3
1 Digital input no. 4 = 1 (switch closed)
0 Digital input no. 4 = 0 (switch open)
4—
1
not assigned (reserved for extensions)
0
5
Analog 2 loss
1
Signal interrupted at analogue input 2 (first free analo­gue input) i.e. the measured value is more than 0.2 mA lower than the set minimum value.
0 no signal interruption analogue input 2 detected
6
Analog 3/4 loss
1
Signal interrupted at analogue input 3/4 (second free analogue input) i.e. the measured value is more than
0.2 mA lower than the set minimum value.
0 no signal interruption analogue input 3/4 detected
7—
1
not assigned (reserved for extensions)
0
4
Remote OPEN
1
Remote operation via Profibus in direction OPEN (re
­mote operation bit for logic board set and movement of potentiometer detected). Signalling of this bit requires a position transmitter.
0 other
5
Remote CLOSE
1
Remote operation via Profibus in direction CLOSE (re
­mote operation bit for logic board set and movement of potentiometer detected). Signalling of this bit requires a position transmitter.
0 other
6
Local OPEN
1
Actuator runs locally in direction OPEN (local controls or handwheel).
Signalling of this bit requires a position transmitter.
0 other
7
Local CLOSE
1
Actuator runs locally in direction CLOSE (local controls or handwheel). Signalling of this bit requires a position transmitter.
0 other
Page 34
10. Process representation output
Via the process representation output, the master (controls) can control the slave (actuator).
In order to perform remote operations, the selector switch of local controls must be set to ‘Remote control’.
Only one operation bit may be set at byte 1. If several operation bits are set at the same time, the actuator stops and signals the fault “Wrong command”.
10.1 Description of the output data
Byte 1: Commands
Bits0–2areused to transmit operation commands to ac­tuator. Only one of these bits may be set at any given time. If Remote SETPOINT is set, the value of the nominal positi­on (byte 3 and byte 4) is used. Bits3–7arereserved for futu­re extensions and must re­main set to 0.
34
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit
0
Spare Spare Spare Spare
Speed
Setpoint position high byte
Setpoint position low byte
Remote SETPOINT
Remote OPEN
Remote CLOSE
Command
Byte 1:
Byte 8
Byte 7
Byte 6
Byte 5
Byte 4: E1 Setpoint
Byte 3: E1 Setpoint
Byte 2: E3 Output speed
Bit Designation Value Description
0
Remote
OPEN
1 Running OPEN
0 Not running OPEN
1
Remote
CLOSED
1 Running CLOSE
0 Not running CLOSE
2
Remote
SETPOINT
1
Running to setpoint Can only be set if a position transmitter e.g. potentio-
meter/ RWG (options) is available.
0 Not running to setpoint.
3
- -
1
Not assigned (reserved for extensions)
0
4
- -
1
Not assigned (reserved for extensions)
0
5
- -
1
Not assigned (reserved for extensions)
0
6
- -
1
Not assigned (reserved for extensions)
0
7
- -
1
Not assigned (reserved for extensions)
0
Page 35
Byte 2: E3 Output speed: This byte is only effective in combination with variable output speed actua
-
tors type AS and ASR.
Value range: 0..100: Minimum output speed: 0 (actuator runs with min. set output speed) Maximum output speed: 100 (actuator runs with max. set output speed)
Byte 3: E1 Setpoint (high byte) Byte 4: E1 Setpoint (low byte)
The setpoint can be transmit­ted either as a value between 0 – 100 (percent) or 0 – 1000 (per mil). For the 0 – 100 scaling, the consisten­cy does not have to be consi­dered in the transmission and only the low byte must be eva­luated. The change-over bet­ween 0 – 100 and 0 – 1000 is realised via a parameter in the GSD file via parameter 2 “Measured data coding positi­on transmitter”. According to this programming, different maximum values apply. When these limits are exceeded, the actuator stops and signals the fault “Wrong command”.
Bytes 5 to 8: reserved for extensions, must be set to 0.
35
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Condition Value
Parameter 2 (measured data coding position transmitter) = 0
This byte must be set to 0.
Parameter 2 (measured data coding position transmitter) = 1
This byte indicates the low byte of the setpoint (0...1000 per mil).
Byte 3: High Byte of setpoint position 0...1000
Condition Value
Parameter 2 (measured data coding position transmitter) = 0
Setpoint position 0...100
Parameter 2 (measured data coding position transmitter) = 1
This byte indicates the low byte of the setpoint (0...1000 per mil).
Byte 4: Low Byte of setpoint position 0...100 or position 0...1000
Page 36
11. Description of actuator functions
11.1 Operation commands for OPEN/ CLOSE operation
Operation commands are determined by the operation command bits and the nominal value (setpoint) of the Profibus process representation output. Only one command bit may be set at any given time. If several command bits are set, no operation is performed and the fault signal ‘Wrong command’ is given. To avoid placing too much strain on the mechanics the actuator is equipped with a (programmable) delay when changing direction (reversing preven­tion).
The following operation command bits are required for OPEN/ CLOSE operation:
Remote OPEN Remote CLOSE
Remote operation OPEN/ STOP
Remote OPEN = 1 The actuator runs in direction OPEN. Remote OPEN = 0 The actuator stops.
The actuator is switched off automatically if the end position OPEN (limit switch LSO [WOEL] is reached. Occurring faults (thermal failure, phase failure, torque failure) stop the operation.
Remote operation CLOSE/ STOP
Remote CLOSED = 1 The actuator runs to position CLOSED. Remote CLOSED = 0 The actuator stops.
The actuator is switched off automatically if the end position CLOSED is reached (limit switch LSC [WSR] for limit seating or LSC [WSR] and TSC [DSR] for torque seating). Occurring faults (thermal failure, phase failure, torque failure) stop the operation.
Remote operation to setpoint position/ STOP
The positioner can only function if the actuator is equipped with a position transmitter, e.g. potentiometer/ RWG (option).
Remote SETPOINT = 1 The actuator moves to the set nominal value. Remote SETPOINT = 0 The actuator stops.
The setpoint must be indicated in % or in ‰ (depending on the AUMA user parameter 2 “Measured data coding position transmitter” within the GSD file). Occurring faults (thermal failure, phase failure, torque failure) stop the operation via the positioner.
With a setpoint of 0 % (0 ‰), the actuator runs to the end position CLOSED. With a setpoint of 100 % (1000 ‰) the actuator runs to the end position OPEN. In case the setpoint is more than 100 % (1000 ‰) , no operation is performed and the fault signal “Wrong command” is given.
36
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 37
11.2 Positioner The positioner is activated via the bit ‘Remote SETPOINT”.
The positioner is a three-position-controller. Via the ‘SETPOINT’ position in the process representation input, the nominal value of the position is trans
­mitted cyclically to the actuator as nominal variable (cycle time = bus cycle time DP). The positioner integrated in the actuator controls AUMA MATIC provides the position signal for controlling the motor depending on the nominal and actual position value. The feedback signal (actual value of actuator position) is produced internally within the actuator.
The position transmitter compares the nominal value of the position set in the controls to the locally measured actual value of the position. If the diffe­rence between nominal value and actual value is higher than the max. error (parameter 14), the positioner drives the motor, depending on the error, either in direction OPEN or direction CLOSE.
Overrun (inner dead band) The inner dead band determines the switching-off point of the actuator.
The tripping point in both directions can be set via the parameters 12 and 13 (page 24), so that the actuator stops as close as possible to the nominal value.
Max. error (outer dead band)
The outer dead band determines the switching-on point of the actuator. If the actual position or a change of the nominal value is higher than the max. permissible error set with parameter 14 (page 25), the motor is started.
The parameter must be set sufficiently high to ensure a stable function of the positioner. If the value is set too low, the number of starts is likely to be increased Thus, the end of the lifetime of the actuator and valve will be reached sooner.
Dead time The dead time prevents the operation to a new nominal position within a
pre-determined time. The time can be between 0 and 1 minute and is set in parameter 11.
The controls must ensure that the maximum number of motor starts of the actuator is not exceeded. This can be achieved by setting the parameter 11 to a sufficiently high value.
For further information on the positioner, please refer to the operation instructions pertaining to the actuator (multi-turn actuator SA(R).../ part-turn actuator SG... with AUMA MATIC AM...).
37
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
50 %
100 %
0%
50,5 %
49 %
49,5 %
51 %
Figure H: Modulating duty: nominal operation to 50 %
OPEN
Setpoint
CLOSED
Motor is switched off
Max. error = 1 %
Setpoint reached
Overrun
Page 38
11.3 Stepping mode Stepping mode requires a position transmitter (option).
The stepping mode lengthens the operating time for part of or for the whole travel.
Setting operation and pause times
The operation and pause times (stepping times) in opening or closing direc­tion are set with the parameters 27 to 33. An individual operation and pause time can be set for each direction.
Indication of operation in stepping mode
The states of the operation in stepping mode are indicated by the bits 2 and 3 in byte 7 of the process representation output.
12. Failure function The failure function allows the start of failure operations in case of special
events, e.g. when the communication between the actuator and the master is interrupted. This function is set with the parameters 6 to 10.
The failure function can only be set off when the watchdog function is acti­vated within the master.
If the actuator is in the failure function, the set failure position is approached via a failure operation. If the actuator is then moved to another position (e.g. by manual operation), it will try to perform the set failure action while the selector switch is in posi­tion REMOTE.
To prevent a new approach to the failure position during manual operation, the selector switch (local controls) must be switched to position ‘LOCAL’ or ‘OFF’ before operating the handwheel.
The following events can trigger the failure function:
.
The connection to the master is interrupted.
.
The master enters the Clear state and sends:
either a) global control telegrams with the content Clear. or
b) data telegrams with the length 0 (DP fail safe mode).
As soon as the cause for triggering the failure mode is eliminated (connec­tion restored, master in Operate state), the operation commands from the master can be executed again.
38
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 39
13. Description Profibus DP interface
S1.1 When using the external analogue input X11 AI 3/4, the switch S1.1 must be
in position AI 3.
S1.2 Switch for setting the position feedback via position transmitter potentiome-
ters/ RWG (option). S1.2 = V:
If the actuator is equipped with a potentiometer without RWG, this
switch must be in position ‘V’. S1.2 = mA:
Switch may only be in this position if an RWG is installed in the actuator. If the actuator is equipped with an RWG (0-– 20 mA or 4 – 20 mA), this switch must be in position ‘mA’.
S2/S3 Rotary switches for Profibus address setting.
These two switches are used to set the address of the actuator within the Profibus DP network. Only addresses from 0 to 125 may be allocated.
S2 Rotary switch for setting the unit digit. S3 Rotary switch for setting the tens digit.
S4 Switch for setting the end position seating in end position CLOSED.
(In end position OPEN, switching off is always via limit seating) This switch is used to inform the Profibus DP board about the type of seating is to be used to operate the actuator in end position CLOSED (limit seating or torque seating). The end position seating is set in the factory according to the details given in the order.
The setting of the end position seating in end position CLOSED must be the same on the Profibus DP board (switch S4) and on the logic board (switch S1-2, figure J, page 42).
S4 = LIMIT:
If the switch is in position ‘LIMIT’ (left, no dot visible), the
actuator is in limit seating for end position CLOSED.
S4 = TORQUE:
If the switch is in position ‘TORQUE’ (right, dot visible), the
actuator is in torque seating for end position CLOSED.
39
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Figure J: Profibus DP interface board
S1.1
X8 PROFIBUS X11 AI ¾ X10 AI
S1.2
Rotary switch S3 Rotary switch S2
S4
S1.1 S1.2 S2 S3
AI 3
V
(with Potentiometer)
mA
(with RWG)
02
Table 8: Standard setting of Profibus DP interface board
Page 40
13.1 Assignment of the customer inputs of the Profibus DP interface (option)
X7 spare This plug provides pins for 4 digital customer inputs.
These signals are freely available inputs, which the micro-controller trans­mits into the process representation input (byte 8, bits 0 – 3). The inputs are galvanically isolated and internally connected to 0 V via pull-down resistors. In an unconnected state, a logical zero is transmitted. To set an input to logical one, 24 V DC must be applied (pins 5 or 6).
.
Proposed external wiring diagrams (appendix B of the operation instructions) for these signals must be obser­ved.
.
The bounce time of the connected switches should not be more than 1 ms.
X12 First analogue customer input (analogue 2).
An e
xternal 0/4- 20mA sensor for transmitting the measured values via the
Profibus can be connected to this input.
X11 Second analogue customer input (analogue 3/4)
A 0/4-20mA sensor for transmitting the measured values via the Profibus can be connected to this input.
If the switch S1.1 is on the left side in position AI 3, the pin 5 (AN 4) is connected to GND. Input AN 3 can be used in the same way as AN 2. If the switch is on the right side in position AI 3-AI 4, a differential measure­ment between AN 3 and AN 4 can be performed.
.
Potential-free differential measurement is not possible.
.
There is always a GND connection.
.
Proposed external wiring diagrams (appendix B) observed.
.
The inputs AN2, AN3, and AN4 do not have galvanic isola
­tion via opto-isolator. The maximum load of the 24 V through the sensors must not exceed 40 mA.
40
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Pin Description
1 R1: digital input 1 2 R2: digital input 2 3 R3: digital input 3 4 R4: digital input 4 5 + 24 V 6 + 24 V
Table 9: Digital inputs (galvanically isolated)
Pin Description
1 AN 2: analogue signal 0 – 20 mA 2 GND (system ground)
Table 10: Analogue inputs at plug X12 AI 2
Pin Description
1 + 24 V 2 GND (system ground) 3 GND (system ground) 4 AN 3+: analogue signal 0 – 20 mA (plus) 5 AN 4–: analogue signal 0 – 20 mA (minus) 6 GND (system ground)
Table 11: analogue inputs at plug X11 AI 3/4
Page 41
13.2 Assignment Profibus DP connection
X8 PROFIBUS The bus signals and the galvanically isolated voltage supply for the bus
termination, as well as the bus termination resistors located on the Profibus DP board are connected on this plug.
13.3 Assignment positioner connections
X10 AI 1 The signals required for the position transmitter potentiometer/ potentio-
meter with RWG are connected on this plug.
41
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Pin Description
1 Channel 1: B cable bus termination 2 Channel 1: A cable bus termination 3 Channel 2: A cable Profibus (redundant channel) 4 Channel 2: A cable Profibus (redundant channel) 5 GND float (Profibus ground) 6 + 5 V float (Profibus + 5 V)
Table 12: Plug assignment X8
Pin Description
1 + 5 V for potentiometer 2 AN 1: analogue signal from position transmitter 3 GND (system ground) 4 + 24V for RWG
Table 13: Plug assignment X10 AI 1
Page 42
13.4 Checking/ setting the switches on the logic board
The settings on the logic board are already made in the factory, according to the order details. The logic board is located below the Profibus DP board.
The setting of the end position seating in end position CLOSED must be the same on the Profibus DP board (switch S4, figure H, page 39) and on the logic board (switch S1-2).
42
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Figure K : Logic board
S3-2: Switching-off in end position OPEN. Switch position has no influence. When controlling via Profibus DP, switching-off is always realised by limit seating in end position OPEN
Position1: Switching-off by limit seating in end position CLOSED
Position 2: Switching-off by torque seating in end position CLOSED
S3-2
S1-2
S2-2
DIP switch S2-2 Programming
(ON = pressed)
Direction CLOSE
Direction OPEN
Self-retaining REMOTE
Self-retaining REMOTE
may not be used
Push-to-run operation REMOTE
Self-retaining LOCAL
Push-to-run operation LOCAL
Blinker transmitter (option)
Blinker transmitter must
be deactivated!
Blinker transmitter
deactivated
Torque error: torque switch trip­ping (in mid-travel) contained in collective fault signal (insignificant for fieldbus interface)
included not included
Tabl e 14
Page 43
14. Troubleshooting and corrective actions
14.1 Optical signals during operation
LED ‘SYSTEM OK’ (V1) This LED shows the correct voltage supply to the Profibus DP board.
Is continuously illuminated: Voltage supply connected to Profibus interface. Is blinking: No Eprom used or Eprom defective. Is not illuminated: No voltage at the DP interface.
LED (V2) This LED indicates a run command in direction OPEN.
Is continuously illuminated: Run command in direction OPEN is executed. Is not illuminated: No run command in direction OPEN active.
LED (V3) This LED indicates a run command in direction CLOSE.
Is continuously illuminated: Run command in direction CLOSE is being
executed.
Is not illuminated: No run command in direction CLOSE active.
LED ‘LocErr’ (V5) This LED indicates local faults in the actuator.
A fault with higher blinking frequency prevails over a fault with lower blinking frequency.
Blinking once: TH fault (Thermal fault) actuator has stopped,
motor overheating (motor protection).
Blinking 2 times: STE fault (electrical fault)
phase failure
Blinking 3 times: TSO (DOEL) fault (torque switch opening left)
Unexpected torque in direction OPEN.
Blinking 4 times: TSC (DSR) fault (torque switch closing right)
Unexpected torque in direction CLOSE.
Blinking 5 times: Supply voltage failure (24V)
Supply voltage of Profibus DP board is higher than 30 V or smaller than 18 V.
Blinking 6 times: Slave is in CLEAR state
43
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Figure L: Profibus DP interface board
V1 V2 V3 V4 V8 V7 V6 V5S1.2 S1.1
Page 44
LED ‘Data Ex’ (V8) When LED is illuminated, the Profibus DP board has entered the ‘Data
Exchange’ state. Only in this state, the actuator can be controlled by the DP master and the state of actuator can be read.
LED ‘State’ (V7) Is illuminated or not illuminated: Profibus DP board is not operational
Blinking once: Program on the Profibus DP board is being
executed.
Blinking twice: Actuator is in failure mode.
Regular blinking of the LED during operation indicates correct operation of the DP board.
LED ‘BusErr’ (V6) This LED shows bus related faults.
A fault with higher blinking frequency prevails over a fault with lower blinking frequency, continuous illumination covers all blinking signals.
Is continuously illuminated: setting of invalid address (higher than 125). Blinking once: No baud rate on bus. Blinking twice: Incorrect parameter data. Blinking 3 times: Incorrect configuration data.
44
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 45
14.2 Actuator can not be controlled via Profibus DP
45
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
LED ‘SYSTEM OK’ (V1) ?
Operation
via local controls
possible?
Voltage supply of
Profibus DP
board correct
Actuator cannot be controlled via Profibus DP
EPROM
installed on
board?
Profibus DP board defective
Exchange Profibus DP board
Install Profibus DP Eprom
Profibus DP board not supplied with voltage
Exchange Profibus DP board
Check voltage supply of AUMA MATIC Check fuses
continuously illuminated
is blinking is not illuminated
Ye s
No
Ye s
No
1
Page 46
46
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Voltage supply of
Profibus DP
board correct
Profibus DP slave not
in Data Exchange mode
Profibus DP
communication
correct
No baud rate
found
- Check master
- Check wiring
- Check bus connection
Master only functions on level 2. Does not try to program or configure
LED ’Bus Err’ (V6) ?
CheckProfibusDP master
Ye s
No
blinking once
not illuminated
Incorrect configuration data. Correct configuration in master
blinking three times
Incorrect parameter data. Correct parameter in master
blinking twice
1
2
Address on slave
set > 125
continuously illuminated
LED ‘DataEx’
illuminated
(V8)?
Page 47
47
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
LED
‘State’ (V7)
?
blinking once
blinking twice
Profibus DP
communication
correct
Thermo fault:
Motor overheating
LED ‘LocErr’ (V5) ?
blinking once
is not illuminated
blinking three times
blinking twice
Profibus DP
board does not
signal any fault
STE-fault:
power failure/
overcurrent
TSO fault:
Torque in
direction OPEN
Check mains connection
.
voltage. Poss. exchange power supply unit
Check supply
Eliminate cause of torque fault
Let motor cool off. Eliminate cause of overheating
Voltage
under 18V or
over 30V
TSC fault:
Torque in
direction CLOSE
blinking four times
blinking five times
Eliminate cause of torque fault
Operation
via local controls
possible?
Ye s
No
Check logic board motor controls motor
LED
or
illuminated?
No operation
command issued
by master
Check programming of controls
CheckProfibusDP board Check logic board
Ye s
No
2
Slave is in
failure mode
1)
clear function in master.
If necessary, switch off Auto-
slaves at the Profibus.
Slave is in
CLEAR state
Check all other programmed
blinking six times
1) see setting of AUMA user parameters 6, 7, 8, 9, and 10
Page 48
14.3 Position feedback does not function
.
Check, whether the voltage at plug (X10 AI1) on the Profibus DP board, pin 3 (-) and pin 2 (+) rises linearly when operating to OPEN position and falls linearly when operating to CLOSED position. The value for position CLOSED should be within the range 0 to 2 V. The value for position OPEN should be within the range 3 to 5 V. The voltage difference between CLOSED and OPEN should be more than 3V.
14.4 Actuator is not switched off by the limit switch in direction CLOSE
The actuator is set to torque seating. Set actuator to limit seating:
.
Set switch S4 (see figure H, page 39) on the Profibus DP board to position ‘LIMIT’.
.
Set switch S1-2 on the logic board (see page 42) to position 1.
14.5 Actuator stops immediately after start
.
Set switch S2-2 (blinker transmitter) on the logic board to position ‘ON’.
14.6 Measuring the Profibus signals using an oscilloscope
On the Profib
us board, the signal from Profibus channel 1 on plug (X8 Profibus, refer to page 41) pin 1 (P/B) and pin 2 (N/A) can be checked using a digital oscilloscope. The off-load voltage between pin 1 (+) and pin 2 (-) must be positive and within the range of 0.8 V and 1.4 V.
48
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Example for correct Profibus signal:
Example for incorrect Profibus Signal (Bus only terminated on one side):
Page 49
15. Appendix A Standard wiring diagram Legend page 50
Original wiring diagram and legend are delivered together with the actuator.
49
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Page 50
15.1 Legend for standard wiring diagram
15.2 Additional information to the wiring diagram legend
Information B:
Local controls
Information F:
Power supply board
Information H:
Profibus DP board
50
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
S 1 TSC Torque switch, closing, clockwise rotation
S 2
TSO (DOEL)
Torque switch, opening, counterclockwise rotation
S 3
LSC (WSR)
Limit switch, closing, clockwise rotation
S 4
LSO (WOEL)
Limit switch, opening, counterclockwise rotation
R 2 Potentiometer
F 1 Th Thermoswitch (motor protection)
R 1 H Heater
A 1.8 Profibus DP board
A 2 Logic board
A 8 Power supply board
A 13 Bus connection board
A 20 Signal and control board
F 1, F 2 Primary fuses for power supply unit
F 3, F 4 Secondary fuses
H 1 Indication light end position CLOSED
H 2 Indication light end position OPEN
H 3 Indication light FAULT
K 1, K 2 Reversing contactors
K 3, K4 Control relays for reversing contactors
S 11 Selector switch LOCAL – OFF – REMOTE
S 12.1
S 12.2
S 12.3
Push button OPEN
Push button STOP
Push button CLOSE
Page 51
16. Appendix B Proposed external wiring diagram
Digital and analogue inputs are optional.
The two customer analogue connections (AI 3/4 and AI 2) as well as the four digital customer inputs (Dig 1 ...4) are only provided (wired) by the factory if explicitly mentioned on the order. The 5th digit of the MSP number (refer to name plate) indicates if analogue connections are available. If the 5th digit is assigned to ‘0’, no external connections are available. If the 5th digit is assigned to ‘L’, the connections are provided.
51
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Connection of external sensors, 2-wire technology
Page 52
52
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Connection of external sensors, 3-wire technology
Page 53
53
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Connection of external sensors, 4-wire technology
Page 54
17. Appendix C GSD file GSD [Gerätestammdatei] stands for device master file. GSD is the so-called
device data sheet for Profibus devices. The GSD file, supplied by AUMA, contains a description of the Profibus DP interface. The descriptions and characteristics contained within the GSD file facilitate easy configuration of the actuator controls.
The GSD file can be downloaded from Internet
www.auma.com
18. Appendix D Literature references
1. As an introduction into Profibus DP: Manfred Popp: Profibus DP, Grundlagen, Tips und Tricks für Anwender. Hüthig Verlag, ISBN 3-7785-2676-6
2. Guidelines for the electrician: Aufbaurichtlinien Profibus DP/FMS Order No. 2.111 Available from: Profibus Nutzerorganisation Haid-und Neu-Str. 7 D-76131 Karlsruhe Phone +49-721 / 96 58 590 Fax +49-721 / 96 58 589 Http:/ www.profibus.com
19. Appendix E Connecting the cable shield for the AUMA MATIC AMExB/ AMExC 01.1
The shield of the fieldbus cable should be largely connected with the respective threads.
Recommended threads e.g. WAZU-EMV/EX supplied by Hugro (refer to www.hugro-gmbh.de).
54
Actuator controls AUMA MATIC AM/ AMExB/ AMExC Profibus DP Operation instructions
Page 55
55
Actuator controls AUMA MATIC AM/ AMExB/ AMExC
Operation instructions Profibus DP
Index
A
Actuator functions 36 AUMA plug/ socket connector 10
B
Basic functions 6 Basic signals 31 Blinker transmitter 42 Bus access 6 Bus cable 18 - 19 Bus connection 18
C
Cable capacity 19 Cable type 19 Characteristic impedance 19 Collective fault signal 42 Commissioning 21 Communication 6 Connection board 10,12 Controls 10 Core cross section (bus cable) 19 Core diameter (bus cable) 19 Corrosion protection 5
D
Dead band 30,37 Dead time 30,37 Device types 6
E
Electrical connection 4,11 End position seating 39 Error 30,43 Error variable 30
F
Failure function 38 Fault signals 31 Functionality 6
G
GSD file 54
H
Handwheel 38
I
Indication lights 10
L
Limit seating 30 Literature 54 Local controls 10 Loop resistance 19
M
Maintenance 4 Measuring the Profibus signals 48 Motor connection 17 Motor protection 31
N
Name plate 15
O
Operating time 38 Output speed E3 35 Overrun 24,37 Overvoltage protection 13
P
Parameter
Coding 26 Coding analogue 3/4 26 Dead time positioner 24 Delay time for
failure operation 23 End analogue 26 End analogue 3/4 in 0.1 mA 26 Failure behaviour 23 Failure operation 23 Failure position 24 Max. error 25 Measured data code 22 Output speed
failure operation 24 Overrun direction CLOSE 24 Overrun direction OPEN 24 Position transmitter 22 Proportional operation active 25 Proportional range Start 25 Proportional range Stop 25 Redundancy 23 Reversing prevention 22 Start analogue 26 Start analogue 3/4 in 0.1 mA 26 Starting speed 26 Stepping 27 Stepping direction
CLOSE active 27 Stepping end CLOSE
in per mil 28 Stepping end OPEN in per mil27 Stepping operating time
CLOSE in 0.1 s 28 Stepping operating time
OPEN in 0.1 s 27 Stepping pause time CLOSE
in 0.1 s 28 Stepping pause time OPEN
in 0.1 s 27 Stepping start CLOSE
in per mil 28 Stepping start OPEN
in per mil 27 Stop speed 25 Time for channel changing 23
Parking frame 15 Part-turn actuators 10 Phase failure 36 Plug/ socket connector 10,15 - 16 Position transmitter 36 Positioner 36 - 37 Power supply 11 Process representation 29,34 Programming 21 Protective functions 6 Push-to-run operation 42
R
Redundancy 23 Remote operation 34 Remote position transmitter RWG 14 Reversing contactors 10 RWG 36
S
Safety instructions 4 Screening (bus cable) 19 Selector switch 10 Self-retaining 42 Setpoint 22 Signals 30,43 Soft start 25 Soft stop 25 Stepping mode 27,38 Storage 5 Switching off 39,42 Switching-off point 37
T
Technical data 7 - 9,16 Termination resistors 10,12 Thyristors 10 Torque switching 14 Transfer mode 6 Transport 5 Trouble shooting and
corrective actions 43
U
User parameter 22
W
Wall bracket 14 Warning signals 32 Warnings 4,30 Wiring diagram 49
Informationen also available on the Internet:
Wiring diagram, GSD file, test records and further actuator information can be downloaded directly from the Internet by entering the order no. or Com. No. (see name plate). Our website: http://www.auma.com
Page 56
www.auma.com
AUMA Riester GmbH & Co. KG P. O . B o x 1 3 6 2 D - 79373 Müllheim Te l Fax riester@auma.com www.auma.com
+49 (0)7631/809-0 +49 (0)7631/809 250
+49 (0)711 / 34803 0 +49 (0)711 / 34803 34
AUMA Riester GmbH & Co. KG P. O . B o x 1 1 5 1 D - 73747 Ostfildern Te l Fax riester@wof.auma.com www.auma.com
For detailed information about AUMA products, please refer to the Internet:
ISO 9001
Certificate Registration No.
12 100 4269 12 104 4269
Y000.421/003/en/1.05
Europe
AUMA Riester GmbH & Co. KG
Factory Müllheim
DE-79373 Müllheim
Tel +49 7631 809 - 0 Fax +49 7631 809 - 250 riester@auma.com www.auma.com
Factory Ostfildern-Nellingen
DE-73747 Ostfildern
Tel +49 711 34803 - 0 Fax +49 711 34803 - 34 riester@wof.auma.com
Service Centre Cologne
DE-50858 Köln
Tel +49 2234 20379 - 00 Fax +49 2234 20379 - 99 Service@sck.auma.com
Service Centre Magdeburg
DE-39167 Niederndodeleben
Tel +49 39204 759 - 0 Fax +49 39204 759 - 19 Service@scm.auma.com
Service Centre Bavaria
DE-85748 Garching-Hochbrück
Tel +49 89 329885 - 0 Fax +49 89 329885 - 18 Riester@scb.auma.com
North Office, Ship building sector
DE-21079 Hamburg
Tel +49 40 791 40285 Fax +49 40 791 40286 Stephan.Dierks@auma.com
North Office, Industry
DE-29664 Walsrode
Tel +49 5167 504 Fax +49 5167 565 Erwin.Handwerker@auma.com
East Office
DE-39167 Niederndodeleben
Tel +49 39204 75980 Fax +49 39204 75989 Claus.Zander@auma.com
West Office
DE-45549 Sprockhövel
Tel +49 2339 9212 - 0 Fax +49 2339 9212 - 15 Karlheinz.Spoede@auma.com
SoutheWest Office
DE-69488 Birkenau
Tel +49 6201 373149 Fax +49 6201 373150 Dieter.Wagner@auma.com
Württemberg Office
DE-73747 Ostfildern
Tel +49 711 34803 80 Fax +49 711 34803 81 Siegfried.Koegler@wof.auma.com
Baden Office
DE-76764 Rheinzabern
Tel +49 7272 76 07 - 23 Fax +49 7272 76 07 - 24 Wolfgang.Schulz@auma.com
Power plant sector
DE-79373 Müllheim
Tel +49 7631 809 192 Fax +49 7631 809 294 Klaus.Wilhelm@auma.com
Büro Bavaria
DE-93356 Teugn/Niederbayern
Tel +49 9405 9410 24 Fax +49 9405 9410 25 Mathias.Jochum@auma.com
AUMA Armaturenantriebe GmbH
AT-2512 Tribuswinkel
Tel +43 2252 82540 Fax +43 2252 8254050 office@auma.at
AUMA (Schweiz) AG
CH-8965 Berikon
Tel +41 566 400945 Fax +41 566 400948 RettichP.ch@auma.com
AUMA Servopohony spol. s.r.o.
CZ-10200 Praha 10
Tel +420 272 700056 Fax +420 272 704125 auma-s@auma.cz
OY AUMATOR AB
FI-02270 Espoo
Tel +35 895 84022 Fax +35 895 8402300 auma@aumator.fi
AUMA France
FR-95157 Taverny Cédex
Tel +33 1 39327272 Fax +33 1 39321755 stephanie.vatin@auma.fr www.auma.fr
AUMA ACTUATORS Ltd.
GB- Clevedon North Somerset BS21 6QH
Tel +44 1275 871141 Fax +44 1275 875492 mail@auma.co.uk
AUMA ITALIANA S.r.l.
IT-20023 Cerro Maggiore Milano
Tel +39 0331-51351 Fax +39 0331-517606 info@auma.it www.auma.it
AUMA BENELUX B.V.
NL-2314 XT Leiden
Tel +31 71 581 40 40 Fax +31 71 581 40 49 office@benelux.auma.com
AUMA Polska
PL-41-310 Dabrowa Górnicza
Tel +48 32 26156 68 Fax +48 32 26148 23 R.Ludzien@auma.com.pl www.auma.com.pl
AUMA Priwody OOO
RU-141400 Moscow region
Tel +7 095 221 64 28 Fax +7 095 221 64 38 aumarussia@auma.ru www.auma.ru
ERICHS ARMATUR AB
SE-20039 Malmö
Tel +46 40 311550 Fax +46 40 945515 info@erichsarmatur.se www.erichsarmatur.se
GRØNBECH & SØNNER A/S
DK-2450 København SV
Tel +45 33 26 63 00 Fax +45 33 26 63 21 GS@g-s.dk www.g-s.dk
IBEROPLAN S.A.
ES-28027 Madrid
Tel +34 91 3717130 Fax +34 91 7427126 iberoplan@iberoplan.com
D. G. Bellos & Co. O.E.
GR-13671 Acharnai Athens
Tel +30 210 2409485 Fax +30 210 2409486 info@dgbellos.gr
SIGURD SØRUM A. S.
NO-1301 Sandvika
Tel +47 67572600 Fax +47 67572610 post@sigurd-sorum.no
INDUSTRA
PT-2710-297 Sintra
Tel +351 2 1910 95 00 Fax +351 2 1910 95 99 jpalhares@tyco-valves.com
MEGA Endüstri Kontrol Sistemieri Tic. Ltd. Sti.
TR-06460 Övecler Ankara
Tel +90 312 472 62 70 Fax +90 312 472 62 74 megaendustri@megaendustri.com.tr
Africa
AUMA South Africa (Pty) Ltd.
ZA-1560 Springs
Tel +27 11 3632880 Fax +27 11 8185248 aumasa@mweb.co.za www.auma.co.za
A.T.E.C.
EG- Cairo
Tel +20 2 3599680 - 3590861 Fax +20 2 3586621 atec@intouch.com
America
AUMA ACTUATORS INC.
US-PA 15317 Canonsburg
Tel +1 724-743-AUMA (2862) Fax +1 724-743-4711 mailbox@auma-usa.com www.auma-usa.com
AUMA Chile Respresentative Office
CL- La Reina Santiago de Chile
Tel +56 2 8214108 Fax +56 2 2778478 aumachile@adsl.tie.cl
LOOP S. A.
AR-C1140ABP Buenos Aires
Tel +54 11 4307 2141 Fax +54 11 4307 8612 contacto@loopsa.com.ar
Asvotec Termoindustrial Ltda.
BR-13190-000 Monte Mor/ SP.
Tel +55 19 3879 8735 Fax +55 19 3879 8738 atuador.auma@asvotec.com.br
TROY-ONTOR Inc.
CA-L4N 5E9 Barrie Ontario
Tel +1 705 721-8246 Fax +1 705 721-5851 troy-ontor@troy-ontor.ca
MAN Ferrostaal de Colombia Ltda.
CO- Bogotá D.C.
Tel +57 1 4 011 300 Fax +57 1 4 131 806 dorian.hernandez@manferrostaal.com www.manferrostaal.com
PROCONTIC Procesos y Control Automático
EC- Quito
Tel +593 2 292 0431 Fax +593 2 292 2343 info@procontic.com.ec
IESS DE MEXICO S. A. de C. V.
MX-C.P. 02900 Mexico D.F.
Tel +52 55 55 561 701 Fax +52 55 53 563 337 informes@iess.com.mx
Multi-Valve Latin America S. A.
PE- San Isidro Lima 27
Tel +511 222 1313 Fax +511 222 1880 multivalve@terra.com.pe
PASSCO Inc.
PR-00936-4153 San Juan
Tel +18 09 78 77 20 87 85 Fax +18 09 78 77 31 72 77 Passco@prtc.net
Suplibarca
VE- Maracaibo Estado, Zulia
Tel +58 261 7 555 667 Fax +58 261 7 532 259 suplibarca@intercable.net.ve
Asia
AUMA (INDIA) PRIVATE LIMITED
IN-560 058 Bangalore
Tel +91 80 2839 4655 Fax +91 80 2839 2809 info@auma.co.in www.auma.co.in
AUMA JAPAN Co., Ltd.
JP-210-0848 Kawasaki-ku, Kawasa­ki-shi Kanagawa
Tel +81 44 329 1061 Fax +81 44 366 2472 mailbox@auma.co.jp
AUMA ACTUATORS (Singapore) Pte Ltd.
SG-569551 Singapore
Tel +65 6 4818750 Fax +65 6 4818269 sales@auma.com.sg www.auma.com.sg
AUMA Middle East Rep. Office
AE- Dubai
Tel +971 4 3682720 Fax +971 4 3682721 auma@emirates.net.ae
PERFECT CONTROLS Ltd.
HK- Tsuen Wan, Kowloon
Tel +852 2493 7726 Fax +852 2416 3763 joeip@perfectcontrols.com.hk
DW Controls Co., Ltd.
KR-153-803 Seoul Korea
Tel +82 2 2113 1100 Fax +82 2 2113 1088/1089 sichoi@actuatorbank.com www.actuatorbank.com
AL-ARFAJ Eng. Company W. L. L.
KW-22004 Salmiyah
Tel +965 4817448 Fax +965 4817442 arfaj@qualitynet.net
BEHZAD Trading Enterprises
QA- Doha
Tel +974 4433 236 Fax +974 4433 237 behzad@qatar.net.qa
Sunny Valves and Intertrade Corp. Ltd.
TH-10120 Yannawa Bangkok
Tel +66 2 2400656 Fax +66 2 2401095 sunnyvalves@inet.co.th
Top Advance Enterprises Ltd.
TW- Jhonghe City Taipei Hsien (235)
Tel +886 2 2225 1718 Fax +886 2 8228 1975 support@auma-taiwan.com.tw www.auma-taiwan.com.tw
AUMA Beijing Representative Office
CN-100029 Beijing
Tel +86 10 8225 3933 Fax +86 10 8225 2496 mailbox@auma-china.com www.auma-china.com
Australia
BARRON GJM Pty. Ltd.
AU-NSW 1570 Artarmon
Tel +61 294361088 Fax +61 294393413 info@barron.com.au www.barron.com.au
2005-04-11
Loading...