Profibus
Modbus RTU
Modbus TCP/IP
Foundation Fieldbus
HART
Operation and settingManual
Page 2
Actuator controls
Table of contents ACV 01.2/ACVExC 01.2
Read operation instructions first.
●
Observe safety instructions.
Purpose of the document:
This document contains information for the commissioning, operation and maintenance staff. It is intended to
support local device operation and setting modifications.
Reference documents:
●
Operation instructions (Assembly, operation, commissioning) for actuator.
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
1.1.Basic information on safety
Standards/directives
Safety instructions/warn-
ings
Qualification of staff
AUMA products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and a EC
Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
They include among others:
●
Standards and directives such as: EN 60079 “Electrical apparatus f or explosiv e
gas atmospheres" –
-Part 14: Electrical installations in hazardous areas (other than mines).
-Part 17: Inspection and maintenance of electrical installations in hazardous
areas (other than mines).
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to av oid personal injury or property
damage.
Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitab ly qualified personnel ha ving been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Work performed in potentially explosiv e atmospheres is subject to special regulations
which have to be observed.The end user or contractor of the plant are responsible
for respect and control of these regulations, standards, and laws.
Commissioning
Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation
Protective measures
Prerequisites for safe and smooth operation:
●
●
●
●
●
The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance
Any device modification requires the consent of the manufacturer.
1.2.Range of application
AUMA actuator controls are e xclusively designed f or the operation of AUMA actuators .
Other applications require explicit (written) confirmation by the manufacturer.The
following applications are not permitted, e.g.:
●
●
No liability can be assumed for inappropriate or unintended use.
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
Only operate the device if it is in perf ect condition while observing these instructions.
Immediately report any faults and damage and allow for corrective measures.
Observe recognised rules for occupational health and safety.
Observe the national regulations.
Observance of these operation instructions is considered as part of the device's
designated use.
1.3.Warnings and notes
The following warnings draw special attention to saf ety-rele v ant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. F ailure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury . Ma y also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→
Measures to avoid the danger
→
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4.References and symbols
The following references and symbols are used in these instructions:
Information
The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
< >Reference to other sections
T erms in brack ets shown abov e refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
9
Page 10
Actuator controls
Identification ACV 01.2/ACVExC 01.2
2.Identification
2.1.Name plate
Figure 1: Arrangement of name plate
[1]Actuator controls name plate
Actuator controls name plate
Figure 2: Name plate for actuator controls (example)
(= manufacturer logo)
[1]Type designation
[2]Order number
[3]Serial number
[4]Actuator terminal plan
[5]Actuator controls terminal plan
[6]Mains/voltage range/frequency range
[7]Rated power of the ACV
[8]Permissible ambient temperature
[9]Enclosure protection
[10]Control
[11]Data Matrix code
Descriptions referring to name plate indications
Type designation
These instructions apply to the following devices types and sizes:
ACV 01.2 = Actuator controls for variable speed actuators
ACVEx 01.2 = Actuator controls for v ariable speed actuators, e xplosion-proof version
Order number
The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagrams and technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Description of serial number (with example 0516MD12345)
MD123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationMD12345
Position 9 after TPA: Position transmitter version
0 = Without position transmitter
A, B, J, K, L, N, R,T = Potentiometer
C, D, E, G, H, M, P, S, U = Electronic position transmitter
I, Q = MWG (magnetic limit and torque transmitter)
Table 2:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
24 V DC
48 V DC
60 V DC
115 V AC
Control voltage 24 V DC for OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 48 V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 60 V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 115 V A C f or OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Input current for setpoint control via analogue input0/4 – 20 mA
Data Matrix code
2.2.Short description
Actuator controls
Local controls/
AUMA CDT
Intrusive - Non-Intrusive
When registered as authorised user, you may use the AUMA Support App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 3: Link to the AUMA App:
For further software/apps refer to chapter <Service software> or to the Internet:
www.auma.com.
ACV 01.2/ACVExC 01.2 actuator controls are used to oper ate AUMA actuators and
are supplied ready for use.The actuator controls may be mounted directly to the
actuator or separately on a wall bracket.
The functions of ACV 01.2/ACVExC 01.2 actuator controls include standard valve
control in OPEN-CLOSE duty , positioning, process control, logging of operating data
right through to diagnostic functions.
Operation, setting, and display can be performed directly at the actuator controls.
When set to local control, it is possible to
●
operate the actuator via the local controls (push buttons and display) and perf orm
settings (contents of these instructions).
●
read in or out data or modify and save settings via AUMA CDT software (accessory), using a computer (laptop or PC).The connection between computer
and actuator controls is wireless via Bluetooth interface (not included in these
instructions).
●
Intrusive version (control unit: electromechanical):
Limit and torque setting is performed via switches in the actuator.
11
Page 12
Actuator controls
Identification ACV 01.2/ACVExC 01.2
●
Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, without removal of actuator or actuator controls covers. For this purpose, the actuator is equipped with
an MWG (magnetic limit and torque transmitter), also capable to supply analogue
torque feedback signals/torque indication and analogue position feedback signals/position indication at the actuator controls output.
12
Page 13
Actuator controls
ACV 01.2/ACVExC 01.2 Operation
3.Operation
3.1.Local actuator operation
Local actuator operation is performed using the local controls push buttons of actuator
controls.
Figure 4: Local controls
Information
[1]Push button for operation command in direction OPEN
[2]Push button STOP
[3]Push button for operation command in direction CLOSE
[4]Push button RESET
[5]Selector switch
Hot surfaces, e.g. possibly caused by high ambient temperatures or strong
direct sunlight!
Danger of burns
→
Check surface temperature and wear protective gloves, if required.
→
Set selector switch [5] to position Local control (LOCAL).
The actuator can now be operated using the push buttons [1 – 3]:
➥
-
Run actuator in direction OPEN: Press push button [1] .
-Stop actuator: Press push button STOP [2].
-
Run actuator in direction CLOSE: Press push button [3] .
The OPEN and CLOSE operation commands can be given either in push-to-run or
in self-retaining operation mode. For further information, please refer to <Push-torun operation or self-retaining local> chapter.
3.2.Actuator operation from remote
Risk of immediate actuator operation when switching on!
Risk of personal injuries or damage to the valve
→
If the actuator starts unexpectedly: Immediately turn selector switch to position
0 (OFF).
→
Check input signals and functions.
13
Page 14
Actuator controls
Operation ACV 01.2/ACVExC 01.2
→
Set selector switch to position Remote control (REMOTE).
Now, it is possible to operate the actuator via remote control, via operation
For actuators equipped with a positioner , it is possible to change ov er between OPEN
- CLOSE control (Remote OPEN-CLOSE) and setpoint control (Remote SET-
POINT). For further information, refer to chapter <Change-over between OPEN CLOSE control and setpoint control>.
3.3.Menu navigation via push buttons (for settings and indications)
Menu navigation for display and setting is made via the push buttons [1 – 4] of the
local controls.
Set the selector switch [5] to position 0 (OFF) when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
Figure 5:
[1–4] Push buttons or navigation support
[5]Selector switch
[6]Display
Table 3: Important push button functions for menu navigation
Push buttons
[1]
[2]
[3]
14
port on display
Up ▲
Down ▼
Ok
Save
Edit
Details
FunctionsNavigation sup-
Change screen/selection
Change values
Enter figures from 0 to 9
Change screen/selection
Change values
Enter figures from 0 to 9
Confirm selection
Save
Enter <Edit> menu
Display more details
Page 15
Actuator controls
ACV 01.2/ACVExC 01.2 Operation
Push buttons
[4] C
●
Backlight
The display is illuminated in white during normal operation. It is illuminated in
red in case of a fault.
●
The screen illumination is brighter when operating a push button. If no push
button is operated for 60 seconds, the display will become dim again.
3.3.1.Menu layout and navigation
Groups
The indications on the display are divided into 3 groups:
Figure 6: Groups
[1]Startup menu
[2]Status menu
[3]Main menu
Status menu and main menu are marked with an ID.
ID
Figure 7: Marking with ID
port on display
Setup
Esc
FunctionsNavigation sup-
Enter Main menu
Cancel process
Return to previous display
Group selection
Direct display via ID
S
ID starts with S = status menu
M
ID starts with M = main menu
It is possible to select between status menu S and main menu M:
For this, set selector switch to 0 (OFF), hold down push button C for approx. 2
seconds until a screen containing the ID M... appears.
Figure 8: Select menu groups
You return to the status menu if:
●
the push buttons on the local controls have not been oper ated within 10 minutes
●
or by briefly pressing C
When entering the ID within the main menu, screens can be displayed directly (without
clicking through).
15
Page 16
Actuator controls
Operation ACV 01.2/ACVExC 01.2
Figure 9: Direct display (example)
Display indicates in the bottom row:Go to
1.
Press push button Go to.
Display indicates:Go to menu M0000
2.
Use push buttons Up ▲Down ▼ to select figures 0 to 9.
3.
Press push button Ok to confirm first digit.
4.Repeat steps 2 and 3 for all further digits.
5.
To cancel the process: Press C Esc.
3.4.User level, password
User level
Password
The user level defines which menu items or par ameters can be displayed or modified
by the active user.
There are 6 different user levels.The user level is indicated in the top row:
Figure 10: User level display (example)
A password must be entered to allow par ameter modification.The display indicates:
Password 0***
A specific password is assigned to each user level and permits different actions.
Table 4:
User levels and authorisations
Authorisation/passwordDesignation (user level)
Observer (1)
Operator (2)
Maintenance (3)
Specialist (4)
Service (5)
AUMA (6)
Verify settings
No password required
Change settings
Default factory password: 0000
Reserved for future extensions
Change device configuration
e.g. type of seating, assignment of output contacts
Default factory password: 0000
Service staff
Change configuration settings
AUMA administrator
3.4.1.Password entry
16
1.
Select desired menu and hold down push button for approx. 3 seconds.
Display indicates the set user level, e.g Observer (1)
➥
2.
Press Up ▲to select a higher user level and press Ok to confirm.
Display shows:Password 0***
➥
3.
Use push buttons Up ▲ Down ▼ to select figures 0 to 9.
4.
Confirm first digit of password via push button Ok.
5.Repeat steps 1 and 2 for all further digits.
Having confirmed the last digit with Ok, access to all parameters within one
➥
user level is possible if the password entry is correct.
Page 17
Actuator controls
ACV 01.2/ACVExC 01.2 Operation
3.4.2.Password change
Only the passwords of same or lower user level may be changed.
Example:The user is signed in as Specialist (4).This authorises him or her to modify
the passwords between user levels (1) to (4).
Device configuration M0053
Service functions M0222
Change passwords M0229
Menu point Service functions M0222 is only visible if user level has been set to
Specialist (4) or higher.
Select main menu
Change passwords
1.Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
3.
Select parameter Change passwords either:
→
→
-
Display indicates:▶ Change passwords
-The user level is indicated in the top row (1 – 6), e.g.:
-For user level 1 (view only), passwords cannot be changed.To change passwords, you must change to a higher user level. For this, enter a password via
a parameter.
4.
For a user level between 2 and 6: Press push button Ok.
The display indicates the highest user level, e.g.:For user 4
➥
5.
Select user level via push buttons Up ▲ Down ▼ and confirm with Ok.
Display indicates:▶ Change passwords Password 0***
➥
6.
Enter current password (→ enter password).
Display indicates:▶ Change passwords Password (new) 0***
➥
7.
Enter new password (→ enter password).
Display indicates:▶ Change passwords For user 4 (example)
➥
8.
Select next user level via push buttons Up ▲ Down ▼ or cancel the process
via Esc.
click via the menu to parameter, or
via direct display: press and enter ID M0229
3.5.Language in the display
The AUMATIC actuator controls display is multilingual.
3.5.1.Language change
Display... M0009
Language M0049
Select main menu
1.Set selector switch to position 0 (OFF).
17
Page 18
Actuator controls
Operation ACV 01.2/ACVExC 01.2
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
3.
Change language
Press Ok.
Display indicates:▶ Language
➥
4.
Press Ok.
Display indicates the selected language, e.g.:▶ Deutsch
➥
5.The bottom row of the display indicates:
Language selection
→
→
6.
Press Edit.
Display indicates:▶ Observer (1)
➥
7.
Select user level via Up ▲ Down ▼ resulting in the following significations:
→
→
8.
Press Ok.
Display indicates:Password 0***
➥
9.
Enter password (→ enter password).
Display indicates:▶ Language and Save (bottom row)
➥
10.
Select new language via Up ▲ Down ▼ resulting in the following significations:
→
→
11.
Confirm selection via Save.
The display changes to the new language.The new language selection is saved.
➥
Save → continue with step 10
Edit → continue with step 6
black triangle:▶ = current setting
white triangle: ▷ = selection (not saved yet)
black triangle:▶ = current setting
white triangle: ▷ = selection (not saved yet)
When switching on the power supply, all LEDs on the local controls illuminate for
approx. 1 second.This optical feedback indicates that the v oltage supply is connected
to the controls and all LEDs are operable.
Figure 11: LED test
During the self-test, the language selection can be activated so that the selected
language is immediately indicated in the display. For this, set selector switch to
position 0 (OFF).
Activate language selection:
1.
Display indicates in the bottom row:Language selection menu? 'Reset'
2.Press push button RESET and hold it down until the following text is display ed
in the bottom line: Language menu loading, please wait.
Figure 12: Self-test
The language selection menu follows the startup menu.
Startup menu
The current firmware version is displayed during the startup procedure:
Figure 13: Startup menu with firmware version: 04.00.00–xxxx
If the language selection feature has been activated during the self-test, the menu
for selecting the display language will now be indicated. For further information on
language setting, please refer to chapter <Language in the display>.
Figure 14: Language selection
If no entry is made over a longer period of time (approx. 1 minute), the display
automatically returns to the first status indication.
4.2.Indications in the display
Status bar
The status bar (first row in the display) indicates the operation mode [1], the presence
of an error [2] and the ID number [3] of the current display indication.
19
Page 20
Actuator controls
Indications ACV 01.2/ACVExC 01.2
Figure 15: Information in the status bar (top)
[1]Operation mode
[2]Error symbol (only for faults and warnings)
[3]ID number: S = Status page
Navigation support
If further details or information are available with reference to the displa y, the following
indications Details or More appear in the navigation support (bottom display row).
Then, further information can be displayed via the push button.
Figure 16: Navigation support (bottom)
[1]shows list with detailed indications
[2]shows further available information
The navigation support (bottom row) is faded out after approx. 3 seconds. Press any
push button (selector switch in position 0 (OFF)) to fade in the navigation support.
4.2.1.Feedback indications from actuator and valve
Display indications depend on the actuator version.
Valve position (S0001)
This indication is only available if a position transmitter (potentiometer, EWG, RWG
or MWG) is installed in the actuator.
●
S0001 on the display indicates the valve position in % of the travel.
●
The bar graph display appears after approx. 3 seconds.
●
When issuing an operation command, an arrow indicates the direction
(OPEN/CLOSE).
Figure 17:Valve position and direction of operation
Das Erreichen der eingestellten Endlagen wird zusätzlich mit den Symbolen (ZU)
und (AUF) angezeigt.
Figure 18: End position CLOSED/OPEN reached
0%Actuator is in end position CLOSED
100% Actuator is in end position OPEN
The indication is only available if the actuator is equipped with an MWG (magnetic
limit and torque transmitter).
●
S0002 on the display indicates the torque applied at the actuator output.
●
The bar graph display appears after approx. 3 seconds.
Figure 19:Torque
Select unit
Display in percent
OPEN - CLOSE control
The push button allows to select the unit displayed (percent %, Newton metre Nm
or "foot-pound" ft-lb
Figure 20: Units of torque
100 % indication equals the max. torque indicated on the name plate of the actuator .
Example: SA 07.6 with 20 – 60 Nm.
●
100 % corresponds to 60 Nm of nominal torque.
●
50 % corresponds to 30 Nm of nominal torque.
Operation commands (S0003)
The display S0003 indicates:
●
active operation commands, lik e e.g.: Operation in direction CLOSE or in direction OPEN
●
the actual value E2 as bar graph indication and as value between 0 and 100
%.
●
for setpoint control (positioner): setpoint E1
●
for stepping mode or for intermediate positions with operation profile: pivot
points and operation behaviour of pivot points
The navigation support (bottom row) is faded out after approx. 3 seconds and the
axis/axes for pivot point display are shown.
Active operation commands (OPEN, CLOSE, ...) are shown above the bar graph
display. The figure below shows the operation command in direction CLOSE.
Figure 21: Display for OPEN - CLOSE control
E2Actual position value
21
Page 22
Actuator controls
Indications ACV 01.2/ACVExC 01.2
Setpoint control
Pivot point axis
If the positioner is enabled and activated, the bar graph indication for E1 (position
setpoint) is displayed.
The direction of the operation command is displayed by an arrow above the bar
graph indication.The figure below shows the operation command in direction CLOSE.
Figure 22: Indication for setpoint control (positioner)
E1Position setpoint
E2Actual position value
The pivot points and their operation behaviour (operation profile) are shown on the
pivot point axis by means of symbols.
The symbols are only displayed if at least one of the f ollo wing functions is activ ated:
Operation profile M0294
Timer CLOSE M0156
Timer OPEN M0206
Figure 23: Examples: on the left pivot points (intermediate positions); on the right
stepping mode
Table 5: Symbols along the pivot point axis
Symbol
with operation profile
Stop during operation in direction
CLOSE
Stop during operation in direction
OPEN
OPEN and CLOSE
and CLOSE
4.2.2.Status indications according to AUMA classification
These indications are available if the parameter Diagnostic classific. M0539 is set
to AUMA.
Warnings (S0005)
If a warning has occurred, the display shows S0005:
●
the number of warnings occurred
●
a blinking question mark after approx. 3 seconds
Stepping modePivot point (intermediate position)
End of stepping modePivot point without reaction|
Start of stepping mode in direction
CLOSE
Start of stepping mode in direction
OPEN
–Stop during operation in directions
–Pause for oper ation in direction CLOSE
–Pause for oper ation in direction OPEN
–Pause for oper ation in directions OPEN
5.1.Status signals via output contacts (digital outputs)
Characteristics
5.1.1.Assignment of outputs
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
The output contacts (outputs DOUT 1 – 12) can be assigned to various signals.
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Default values:
Signal DOUT 1 = Fault
Signal DOUT 2 = End position CLOSED
Signal DOUT 3 = End position OPEN
Signal DOUT 4 = Selector sw. REMOTE
Signal DOUT 5 = Torque fault CLOSE
Signal DOUT 6 = Torque fault OPEN
Signal DOUT 7 = Thermal fault
Signal DOUT 8 = OPEN
Signal DOUT 9 = Limit switch CLOSED
Signal DOUT 10 = Limit switch OPEN
Signal DOUT 11 = Torque sw. CLOSED
Signal DOUT 12 = Torque sw. OPEN
Signal DOUT 1 M0109
Further setting values:
Refer to <Appendix>/<Selection overview for output contacts and indication lights>
5.1.2.Coding the outputs
The output signalsCoding DOUT 1 – Coding DOUT 12 can be set either to high
active or low active.
●
High active = output contact closed = signal active
●
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interfaceM0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1 = Low active
Coding DOUT 2 – Coding DOUT 12 = High active
5.2.Configurable status signals
The status signals described here are collective signals of various other signals. F or
configuration, the contained signals can be selected from a list and activated ( ) or
deactivated ( ) individually.
The status signals can either be assigned to a digital output (output contact) or to
an indication light (LED).
27
Page 28
Actuator controls
Signals (output signals) ACV 01.2/ACVExC 01.2
For detailed information on these signals, refer to <Fault signals and warnings>
chapter.
Configure status signals
Required user level:Specialist (4) or higher.
Device configuration M0053
Config. of signals M0860
Failure (configurable) M0879
Fault (Cfg) M0880
Warnings (Cfg) M0881
Not ready REMOTE (Cfg) M0882
A dot in the display indicated whether the signal is active or not.
Figure 32: Example
Black dot (●): Signal active
White dot (○): Signal not active
Activation/deactivation is switched on/off by push button Ok.
The actuator is equipped with a position transmitter.
Depending on the actuator equipment, different signals, such as travel, torque or
output speed can be recorded and issued as continuous values, e.g. 4 to 20 mA.
Actuator controls are equipped with up to two analogue outputs, AOUT1 and A OUT2.
Designation in the wiring diagram: AOUT 1.
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal AOUT 1 M0131
Default value: Actual position
Information
The signal range of the output (e.g. 0/4 – 20 mA) is set via a separate parameter
(Signal range AOUT1 M0129).
Setting values:
Not used
Actual position
Torque
28
Analogue output 1 is not assigned.
Position feedback of the valve position (actual position value E2)
Condition: Position transmitter installed in the actuator.
An adjustment to the end positions or the defined travel is not required. An automatic
adjustment is done via the end positions (LSC (WSR) and LSO (WOEL)).
For torque seating, the end positions OPEN and CLOSED of the limit switching
should be set as close as possible to the end positions of the valve to minimise the
deviation of the feedback.
Torque feedback E6
Condition: MWG position transmitter in actuator.
The zero point is in the centre of the selected output range (10 mA or 12 mA).The
torque in direction CLOSE is indicated with 0 – 10 mA or 4 – 12 mA, the torque in
direction OPEN with 10 – 20 mA or 12 – 20 mA. F or 127 % of the maxim um nominal
output torque, 0 or 4 mA are indicated in direction CLOSE, and 20 mA are indicated
in direction OPEN.
Figure 33: Actual torque value
–127 %= maximum nominal torque in end position CLOSED reached
+127 %= maximum nominal torque in end position OPEN reached
Input AIN 1
Input AIN 2
Speed target value
Temp. ctrls norm. ‰
Temp. ctrl unit norm ‰
Total accel. in %
5.3.2.Signal range of analogue output 1
Analogue value transmitted via AIN1 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0 – 20 mA) is connected to the analogue input
AIN 1.
Analogue value transmitted via AIN 2 (refer to wiring diagram) to the actuator.
Condition: An analogue signal (e.g. 0 – 20 mA) is connected to the analogue input
AIN 2.
Speed setpoint.
Actuator controls temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Control unit temperature (normalised) in per mil.
Condition: MWG position transmitter in actuator.
Total acceleration in percent of oscillation/vibration measurement 0 % = 0.000 g =
0/4 mA; 100 % = 4.000 g = 20 mA
Condition: MWG position transmitter in actuator.
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal range AOUT1 M0129
Default value: 0 - 20 mA
Setting values:
0 - 20 mA
4 - 20 mA
20 - 0 mA
20 - 4 mA
X to Y mA
5.3.3.Adjustment of analogue output 1
Analogue output 1 generates a 0 – 20 mA signal.
Analogue output 1 generates a 4 – 20 mA signal.
Analogue output 1 generates a 20 – 0 mA signal.
Analogue output 1 generates a 20 – 4 mA signal.
The signal range (X-Y) of the analogue output can be freely configured using two
parameters.
Initial values and end values of the signal range can be corrected by ± 10 % of the
maximum value range (20 mA)
Example: Parameter Signal range AOUT1 = 4 - 20 mA
The initial value (4 mA) can be adapted within a range of 2 mA to 6 mA.
29
Page 30
Actuator controls
Signals (output signals) ACV 01.2/ACVExC 01.2
The end value (20 mA) can be adapted within a range of 18 mA to 22 mA.
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Adjustment AOUT 1 M0544
0/4 mA (initial value) M0140
20 mA (final value) M0210
Designation in the wiring diagram: AOUT2.
Required user level:AUMA (6).
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal AOUT 2 M0132
Default value: Torque
Setting values:
Description see <Assignment of analogue output 1>.
5.3.5.Signal range of analogue output 2
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Signal range AOUT2 M0130
Default value: 0 - 20 mA
Setting values:
0 - 20 mA
4 - 20 mA
20 - 0 mA
20 - 4 mA
X to Y mA
5.3.6.Adjustment of analogue output 2
Analogue output 2 generates a 0 – 20 mA signal.
Analogue output 2 generates a 4 – 20 mA signal.
Analogue output 2 generates a 20 – 0 mA signal.
Analogue output 2 generates a 20 – 4 mA signal.
The signal range (X-Y) of the analogue output can be freely configured using two
parameters.
Initial values and end values of the signal range can be corrected by ± 10 % of the
maximum value range (20 mA)
Example: Parameter Signal range AOUT1 = 4 - 20 mA
The initial value (4 mA) can be adapted within a range of 2 mA to 6 mA.
The end value (20 mA) can be adapted within a range of 18 mA to 22 mA.
Required user level:Specialist (4) or higer.
Different operation modes (states) are available.The current operation mode is
indicated in the first line of the display:
Figure 34: Example: Operation mode Off
This chapter describes the characteristics of the different operation modes; the
respective functions are described in separate chapters.
6.1.Operation mode Off
The selector switch is in position 0 (OFF).
●
Characteristics
The indication in the top row of the display shows:Off
●
Electric operation is not possible (not even EMERGENCY operation).
●
The controls remain fully operative as far as signalling is concerned (controls’
power supply is maintained).
●
Push buttons C can be used for menu navigation via the display.
6.2.Operation mode Local
Selector switch is in position Local control (LOCAL).
●
Characteristics
The indication in the top row of the display shows:Local
●
In motor operation, the actuator can be controlled locally via the push buttons
(OPEN), STOP, (CLOSE).
●
Faults and warnings without automatic reset can be confirmed with the push
button RESET.
6.2.1.Push-to-run operation or self-retaining Local
Parameter Self-retaining Local M0076 determines the actuator operation behaviour
to operation commands via push buttons on local controls.
Customer settings M0041
Local controls M0075
Self-retaining Local M0076
Default value: OPEN and CLOSE
Setting values:
Off (push-to-run op.)
OPEN
CLOSE
Push-to-run operation activated, self-retaining off:
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received.The actuator stops if the operation command is cancelled.
In direction OPEN = self-retaining (in direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuator continues to run, even
if the operation command is cancelled (self-retaining).The actuator is either stopped
by the STOP command or if end position OPEN or an intermediate position OPEN
has been reached.
In direction CLOSE = self-retaining (in direction OPEN push-to-run operation):
32
Page 33
Actuator controls
ACV 01.2/ACVExC 01.2 Operation
After an operation command in direction CLOSE, the actuator continues to run, even
if the operation command is cancelled (self-retaining).The actuator is either stopped
by the CLOSE command or if end position CLOSED or an intermediate position
CLOSED has been reached.
OPEN and CLOSE
In directions OPEN and CLOSE = self-retaining:
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining).The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
Direct reversal of operation is not possib le. Operation commands in directions OPEN
or CLOSE must be stopped first by STOP command. Only then is an operation
command into the opposite direction allowed.
OPEN & CL w/o STOP
In directions OPEN and CLOSE = self-retaining without stop:
Direct reversal of operation is also possible without the STOP command. However,
operation can be stopped at any time by the STOP command.
6.3.Operation mode Remote
Selector switch is in position Remote control (REMOTE).
Characteristics
The indication in the top row of the display shows the set source of the operation
commands:
●
Remote (parallel interface)
●
Remote II (parallel interface, push button station)
Depending on the control, a distinction is made between:
●
OPEN-CLOSE control (operation mode Remote OPEN-CLOSE)
Control is made via binary operation commands OPEN, STOP, CLOSE.
●
Setpoint control (operation mode Remote SETPOINT):
Control via analogue operation commands, e.g. 4 – 20 mA.
●
Information
Binary signals (e. g. +24 V DC) via digital inputs are only recognised as valid
operation commands if the signal is present for at least 10 ms.
●
If a positioner or process controller is available, change-over between OPENCLOSE control (operation mode Remote OPEN-CLOSE) and setpoint control
(operation mode Remote SETPOINT) is possible. Refer to chapter <Changeover between OPEN-CLOSE control and setpoint control>.
6.3.1.Push-to-run operation or self-retaining Remote
Parameters Self-retaining Remote M0100, Self-retaining M01193 and Self-retaining
Remote II M0101 determine the operation behaviour of the actuator to binary
operation commands (OPEN, STOP, CLOSE), controlling the actuator “from Remote”
via the I/O interface.
Self-retaining = Off (push-to-run op.)
Self-retaining Remote II = OPEN and CLOSE
33
Page 34
Actuator controls
Operation ACV 01.2/ACVExC 01.2
Setting values for parameters,Self-retaining Remote M0100 and Self-retaining
Remote II M0101:
Off (push-to-run op.)
Push-to-run operation activated, self-retaining off:
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received.The actuator stops if the operation command is cancelled.
OPEN
In direction OPEN = self-retaining (in direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuator continues to run, even
if the operation command is cancelled (self-retaining).The actuator is either stopped
by the STOP command or if end position OPEN or an intermediate position OPEN
has been reached.
CLOSE
In direction CLOSE = self-retaining (in direction OPEN push-to-run operation):
After an operation command in direction CLOSE, the actuator continues to run, even
if the operation command is cancelled (self-retaining).The actuator is either stopped
by the CLOSE command or if end position CLOSED or an intermediate position
CLOSED has been reached.
OPEN and CLOSE
In directions OPEN and CLOSE = self-retaining:
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining).The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
Direct reversal of operation is not possib le. Operation commands in directions OPEN
or CLOSE must be stopped first by the STOP command.. Only then is an operation
command into the opposite direction allowed.
OPEN & CL w/o STOP
In directions OPEN and CLOSE = self-retaining without stop:
Direct reversal of the operation direction without STOP command is possible.
Direct reversal of operation is also possible without the STOP command. However,
operation can be stopped at any time by the STOP command.
6.4.Operation mode EMERGENCY
See also: Failure function <EMERGENCY behaviour>
●
Characteristics
The indication in the top row of the display shows:EMERGENCY
●
The operation mode EMERGENCY is initiated by the EMERGENCY signal.
●
The actuator performs an EMERGENCY operation. For example, the actuator
moves to a predefined EMERGENCY position (i.e. end position OPEN or end
position CLOSED).
●
As long as the EMERGENCY signal is present, the actuator does not respond
to any other operation commands (EMERGENCY signal has top priority).
The actuator can start immediately when switching on!
Risk of personal injuries or damage to the valve.
→
Ensure that the EMERGENCY signal is present when switching on.
→
Should the actuator start unexpectedly: Immediately set selector s witch to position 0 (OFF).
6.5.Operation mode EMERGENCY stop
See also: Failure function <EMERGENCY stop function>
Condition
An EMERGENCY stop button (latching) is either located on the electrical connection
or outside.
●
Characteristics
The indication in the top row of the display shows:EMCY stop
●
In an emergency, the EMERGENCY stop button can be used to interrupt the
power supply of the motor control (contactors or thyristors).
●
Operation mode EMERGENCY stop supersedes all other operation modes.
34
Page 35
Actuator controls
ACV 01.2/ACVExC 01.2 Operation
●
A new operation command can only be executed once the pressed EMERGENCY stop button is released and operation mode EMERGENCY Stop is
cancelled using a Reset command.
●
Once operation mode EMERGENCY Stop is cancelled (Reset command),
analogue operation commands present (e.g. 0/4 – 20 mA) will immediately be
executed.
6.6.Operation mode Disabled
See also: Application function <Local controls:enable>
●
Characteristics
The indication in the top row of the display shows:Disabled
●
The operation via the push buttons on the local controls is disabled.
●
Operation mode Disabled is possible in selector switch positions LOCAL and
OFF.
Table 7: Functions depending on the selector switch position:
●
The Enable Local is used for disabling or enabling via a digital input.
6.7.Operation mode Service
Conditions:
Set selector switch = position Local control (LOCAL) or Remote contr ol (REMOTE).
Display indicates in the first row:Service
●
Characteristics
The indication in the top row of the display shows:Service
●
For operation mode Service, a PC or laptop with AUMA CDT service software
is required. AUMA service uses this software (e.g. during commissioning or
maintenance) to perform settings at the actuator controls.
Information
In selector position Local control (LOCAL), press any push button to e xit the service
operation mode and to activate operation mode Local.
Selector switch is in position
Function during indication = Disabled
Actuator cannot be operated locallyLocal control (LOCAL)
Local menu operation not possible0 (OFF)
35
Page 36
Actuator controls
Basic settings for commissioning ACV 01.2/ACVExC 01.2
7.Basic settings for commissioning
Definition
Basic settings such as type of seating, torque and limit switching are required for
safe commissioning of the actuator controls together with the actuator . Basic settings
for display, such as date and time or display formats, can be changed, if required.
7.1.Type of seating for end positions
●
Function
Selection of the type of seating (according to valve manuf acturer's specifications)
-Limit seating in end position
-Torque seating in end position
●
For end positions OPEN and CLOSE, the following can be set individually:
Limit seating
The controls switch off the actuator in the end positions (OPEN/CLOSED) set via
limit switching.
For end position seating via limit switching, you have to account for the overrun of
the actuator. Overrun [1] is the tra v el from s witching off until complete standstill.The
overrun depends on the inertia of both the actuator and the valve and the delay time
of the controls.
Figure 35: Limit seating
PTripping position
[1]Overrun
The controls switch off the actuator in the end positions via torque switching.
For this the torque switching has to be set to the tripping torque specified by the
valve manuf acturer .When reaching the end position, the torque increases within the
valve seat. As soon as the set tripping torque is reached, the controls automatically
switch off the actuator.
In this context, the limit seating is used to signal that the limit switching will trip shortly
before reaching the end position.
7.1.1.Type of seating: set
Customer settings M0041
Torque seating
Valve damage due to incorrect setting!
→
The type of seating must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Type of seating M0012
End position CLOSED M0086
End position OPEN M0087
Default value: Limit
Setting values:
Limit
Torque
36
Seating in end positions via limit switching.
Seating in end positions via torque switching.
Page 37
Actuator controls
ACV 01.2/ACVExC 01.2 Basic settings for commissioning
Select main menu
Select parameter
CLOSE or OPEN
User login
1.Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
3.Select parameter either:
→
→
Display indicates:End position CLOSED
➥
4.
Use Up ▲ Down ▼ to select:
→
→
The black triangle ▶ indicates the current selection.
➥
5.
Press Ok.
Display indicates the current setting:Limit or Torque
➥
The bottom row of the display indicates either:
➥
-
Edit → continue with step 6
-
Save → continue with step 10
6.
Press Edit.
Display indicates:▶ Specialist (4)
➥
7.
Use Up ▲ Down ▼ to select user:
click via the menu to parameter, or
via direct display: Press and enter ID M0086 or M0087
▶ End position CLOSED
▶ End position OPEN
Information: Required user level: Specialist (4) or higher
Change settings
7.2.Torque switching
Conditions
Function
The symbols have the following meaning:
➥
-
black triangle:▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press Ok.
Display indicates:Password 0***
➥
9.
Enter password (→ enter password).
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
➥
of a black triangle ▶.
10.
Use Up ▲ Down ▼ to select new setting.
The symbols have the following meaning:
➥
-
black triangle:▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
11.
Confirm selection via Save.
The setting for the type of seating is complete.
➥
12.
Back to step 4 (CLOSED or OPEN): Press Esc .
MWG in actuator (non-intrusive version).
For torque switches within the actuator (intrusive version), the torque switching is
set as described in the operation instructions pertaining to the actuator.
●
Overload protection across full travel
●
Tripping in end positions (for torque seating)
●
Tripping in during manual operation also possible
37
Page 38
Actuator controls
Basic settings for commissioning ACV 01.2/ACVExC 01.2
●
Indication or setting either in percent %, Newton metre Nm or
in foot-pound ft-lb
Read more
<Torque monitoring> chapter
7.2.1.Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Select main menu
Select parameter
CLOSE or OPEN
User login
1.Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
3.Select parameter either:
→
→
Display indicates:Trip torque CLOSE
➥
4.
Use Up ▲ Down ▼ to select:
→
→
The black triangle ▶ indicates the current selection.
➥
5.
Press Ok.
Display shows the set value.
➥
The bottom row indicates: Edit Esc
➥
6.
Press Edit.
Display indicates:
➥
-
Specialist (4) → continue with step 7
-
in bottom row Up ▲ Down ▼ Esc → continue with step 11
7.
Use Up ▲ Down ▼ to select user:
click via the menu to parameter, or
via direct display: press and enter ID M0088.
▶ Trip torque CLOSE
▶ Trip torque OPEN
Information: Required user level: Specialist (4) or higher.
The symbols have the following meanings:
➥
-
black triangle:▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press Ok.
Display indicates:Password 0***
➥
38
Page 39
Actuator controls
ACV 01.2/ACVExC 01.2 Basic settings for commissioning
9.
Enter password (→ enter password).
Display shows the set value.
➥
The bottom row indicates: EditEsc
➥
10.
Press Edit.
11.
Change value
Enter new value for tripping torque via Up ▲ Down ▼.
Information: The adjustable torque range is shown in round brackets.
12.
Save new value via Save.
The tripping torque is set.
➥
13.
Back to step 4 (CLOSED or OPEN): Press Esc.
Information
The following f ault signals are issued if the torque setting performed has been reached
in mid-travel:
●
In the display of the local controls: Status indication S0007 Fault
Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed.The
acknowledgement is made:
1.either by an operation command in the opposite direction.
-
For Torque fault OPEN : Operation command in direction CLOSE
-
For Torque fault CLOSE : Operation command in direction OPEN
2.or, in case the torque applied is lower than the preset tripping torque:
7.3.Limit switching
Conditions
Electronic control unit with MWG in the actuator (non-intrusive version)
For an electro-mechanical control unit equipped with switches in the actuator (intrusiv e
version), the limit switches are set as described in the operation instructions.
Functions
●
●
7.3.1.Limit switching: set
Customer settings M0041
Select main menu
1.Set selector switch to position 0 (OFF).
-in selector switch position Local control (LOCAL) via push b utton RESET.
-in selector switch position Remote control (REMOTE):
-via a digital (I/O interface) with the Reset command if a digital input
is configured for RESET signal.
Tripping in end positions (limit seating)
Signalling the end positions (torque seating)
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Select parameter
2.Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates:▶ Display...
➥
3.Select parameter either:
→
→
Display indicates:Set end pos.CLOSED?
➥
click via the menu to parameter, or
via direct display: press and enter ID M0084.
39
Page 40
Actuator controls
Basic settings for commissioning ACV 01.2/ACVExC 01.2
4.
CLOSED or OPEN
User login
Use Up ▲ Down ▼ to select:
→
→
The black triangle ▶ indicates the current selection.
➥
5.
Press Ok.
The display indicates either:
➥
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 14
-
Specialist (4) → continue with step 6
6.
Use Up ▲ Down ▼ to select user:
▶ Set end pos.CLOSED? M0084
▶ Set end pos. OPEN? M0085
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
➥
-
black triangle:▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
7.
Press Ok to confirm to selected user.
Display indicates:Password 0***
➥
8.
Enter password (→ enter password).
The display indicates either:
➥
-
Set end pos.CLOSED? CMD0009 → continue with step 9
-
Set end pos. OPEN? CMD0010 → continue with step 14
Set end position
CLOSED CMD0009
9.Set again end position CLOSED:
10.
Press Yes to accept new end position setting.
Display indicates:End pos. CLOSED set!
➥
The left LED is illuminated (standard version) and thus indicates that the end
➥
position CLOSED setting is complete.
Set end position OPEN
CMD0010
Information
11. Make selection:
→
→
Edit → back to step 9: Set end position CLOSED "once again"
Esc → back to step 4; either set end position OPEN or exit the menu.
12. Re-set end position OPEN:
13.
Press Yes to accept new end position setting.
Display indicates:End pos. OPEN set!
➥
The right LED is illuminated (standard version) and thus indicates that the end
➥
position OPEN setting is complete.
14. Make selection:
→
→
Edit → back to step 9: Set end position OPEN "once again"
Esc → back to step 4; either set end position CLOSED or exit the menu.
If an end position cannot be set: Check the type of control unit in actuator.
40
Page 41
Actuator controls
ACV 01.2/ACVExC 01.2 Basic settings for commissioning
7.4.Date and time
After commissioning, we recommend checking and setting date and time. Date and
time are required for the event report function.
In case of a mains failure, date and time are stored.This data will only have to be
checked after a longer downtime.
Display... M0009
Date and time M0221
●
Information
7.5.Display formats
7.5.1.Date format
The date format, e.g. day/month/year, can be changed via the parameter Date
format M0310.
●
The time format, e.g. 12/24h can be changed via the parameter Time
format M0050.
The indications on the display can be represented in different f ormats: Country-specific
spellings, for example, can be accounted for.
The data can be represented in day/month/year or in year/month/day.
The time can be indicated in 12 or 24 hour format.
Display... M0009
Time format M0050
Default value: 24h
Setting values:
Indication of hour/minute/second in 12-hour format, example: 02:25:09 PM
Indication of hour/minute/second in 24-hour format, example: 14:25:09
The number format determines the sign for indicating the decimal places. Either a
decimal point or a decimal comma can be used to separate integral numbers and
decimal places.
xx.x
xx,x
Display... M0009
Number format M0231
Default values:
●
For English as display language = xx.x
●
For all other display languages = xx,x
Setting values:
Indication of the decimal places using a decimal point, example: 20.0 mA
Indication of the decimal places using a decimal comma, example: 20,0 mA
41
Page 42
Actuator controls
Basic settings for commissioning ACV 01.2/ACVExC 01.2
7.5.4.Torque unit
The torque can be indicated in different units.
Display... M0009
Torque unit M0051
Default value: Nm
Setting values:
Indication in Nm
Nm
ft-lb
7.5.5.Temperature unit
Indication in foot-pound
Indication in percent
%
The temperature unit can either be displayed in Celsius [C°] or Fahrenheit [°F].
Display... M0009
Temperature unit M0052
Default value: °C
Setting range: °C or °F
7.5.6.Position units
Function not active
Function active
The valve position (e.g. actual position, setpoint position) or other positions (e.g.
pivot points) are indicated in percent of the travel on the actuator controls display
(default setting).. By activating the par ameter Position, you may select other ph ysical
units instead of percent to represent the positions. Furthermore, both scaling and
maximum value may be adapted.The change-over affects all screens indicating a
position.This includes status pages such as S0001 S0003, but also the
representation of characteristics (e.g. position-time) as well as histograms.
Activate position unit
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Position M1206
Position activation M1207
Default value: Function not active
Setting values:
<Units of position> function deactivated. Position indications in the display (e.g. the
valve position S0001) are indicated in percent.
<Units of position> function activated. Position indications in the display are not
shown in percent but in the unit set for the values in parameter group Position.
Set max. value, scaling and unit
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Position M1206
Max. value at 100.0 % M1208
Scaling M1209
Unit M1210
Default values:
Max. value at 100.0 % = 1000
Scaling = 1 (Multiplikator für Einheit)
Unit = mA
42
Page 43
Actuator controls
ACV 01.2/ACVExC 01.2 Basic settings for commissioning
Setting ranges/values:
Max. value at 100.0 % = 1 – 1000
Scaling = 0.001 – 1000
Unit = mA; °C; bar; m³/h; m³/min; m; cm; mm; °
7.5.7.Process factor units
Process factors (e.g. process setpoint, actual process value ...) are shown in percent
of travel in the actuator controls displa y (def ault setting). By activ ating the parameter
Process factor, you may select other physical units apart from percent.The
change-over affects all screens indicating a process value.
Activate process factor units
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Process factor M1211
Proc. var. activation M1212
Default value: Function not active
Setting values:
Function not active
Function active
<Process factor units> deactivated. Position indications in the display are shown in
percent.
<Process factor units> activated. Position indications in the display are not shown
in percent but in the unit set for the values in parameter group Process factor.
Set max. value, scaling and unit
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Process factor M1211
Max. value at 100.0 % M1213
Scaling M1214
Unit M1215
Default values:
Max. value at 100.0 % = 1000
Scaling = 1 (multiplier for unit)
Unit = mA
Setting ranges/values:
Max. value at 100.0 % = 1 – 1000
Scaling = 0.001 – 1000
Unit = mA; °C; bar; m³/h; m³/min; m; cm; mm; °
7.5.8.Analogue working value units (AIN)
Activate working value units (AIN)
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Working values (AIN) M1216
Work. val. activ. (AIN) M1217
Function not active
Function active
Default value: Function not active
Setting values:
<Working value units (AIN)> function deactivated.
<Working value units (AIN)> function activated.
43
Page 44
Actuator controls
Basic settings for commissioning ACV 01.2/ACVExC 01.2
Set max. value, scaling and unit
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Working values (AIN) M1216
Max. value at 100.0 % M1217
Scaling M1218
Unit M1219
Default values:
Max. value at 100.0 % = 1000
Scaling = 1 (multiplier for unit)
Unit = mA
Setting ranges/values:
Max. value at 100.0 % = 1 – 1000
Scaling = 0.001 – 1000
Unit = mA; °C; bar; m³/h; m³/min; m; cm; mm; °
7.5.9.Analogue signal output units (AIN)
Function not active
Function active
Activate signal output units (AIN)
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Signal outputs (AIN) M1221
Sig. outp. activ. (AIN) M1222
Default value: Function not active
Setting values:
<Signal output units (AIN)> function deactivated.
<Signal output units (AIN)> function activated.
Set max. value, scaling and unit
Required user level:Specialist (4) or higher.
Display... M0009
Units M1205
Signal outputs (AIN) M1221
Max. value at 100.0 % M1223
Scaling M1224
Unit M1225
Default values:
Max. value at 100.0 % = 1000
Scaling = 1 (multiplier for unit)
Unit = mA
7.6.Contrast
44
Setting ranges/values:
Max. value at 100.0 % = 1 – 1000
Scaling = 0.001 – 1000
Unit = mA; °C; bar; m³/h; m³/min; m; cm; mm; °
The contrast can be used to adapt the display backlight (light or dark background).
Application functions are functions used to adapt the actuator controls to special
applications.This includes device functions, communication functions and device
information.
If they are enabled, these functions can be programmed by the user for his/her
specific task using parameters.
8.1.Speed functions
SAV/SARV actuators can be controlled via ACV actuator controls using individual
speed setpoints for operations in direction OPEN or CLOSE.This chapter describes
control in standard operation (operation modes Local and Remote). Settings and
behaviour in e.g. emergencies (operation mode EMERGENCY) as well as failure
behaviour (on loss of signal) are described together with the respective safety
functions.
8.1.1.Speed source for local operation and remote operation
The actuator speed for local operation (via local controls) and remote operation can
be provided from different speed sources.The speed can be set individually for each
operation direction (OPEN/CLOSE).The input signal of the respective speed source
can either be programmed as constant or variable speed value.
●
as constant, internal value (programmable speed)
●
as variable, external value (via analogue signal)
As a general rule, the speed source has already been set in the factory according
to the indications on the order.
Required user level:Specialist (4)
Internal 1 – Internal 4
2 DigIn: "Internal (1-4)"
Analogue input
Customer settings M0041
Speed functions M1699
Sp. source LOC OP M1700
Sp. source LOCAL CL M2039
Sp. source REM OP M1701
Sp. source REM CL M2040
Default value: Internal 1
Setting values:
The actuator is controlled with a constaant speed. F or this, f our programmable internal
speed values are available.The four internal speed values are programmed via
parameters Speed internal1 M1930 – Speed internal 4 M1933.
Speed selection via two external signals. F or this setting, changing between the f our
internally programmed, constant speeds (Internal 1 – Internal 4) is possible.
Two digital inputs have to be configured as control signals for speed selection.
The actuator speed is specified/modified externally via an analogue value (e.g. 0 –
20 mA).
An analogue input has to be defined as speed source.
Configuration of digital inputs for external speed selection
For setting of parameter Sp. source... = 2 DigIn: "Internal (1-4)" (external speed
selection)
According to the present description, two digital inputs have to be configured as
control signals to allow for external speed selection.
Required user level:Specialist (4)
Example
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use inputs DIN 5 and DIN 6 as control signals for external speed selection:
45
Page 46
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Parameter:Signal DIN 5 M0122 = Speed int. sel. bit 0
Parameter:Signal DIN 6 M0123 = Speed int. sel. bit 1
Information
Table 8:
Input signals (DIN) for external speed selection
Speed int. sel. bit 1Speed int. sel. bit 0
00
10
01
11
0 = low level (0 V DC or input open)
1 = high level (standard: +24 V DC)
Speed value for coding both digital inputs with “high active”1)
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 6 M0128), the input is either High active or Low active. Default
setting is High active.
Configuration of analogue input for speed
For setting of parameter Sp. source... = Analogue input.
An analogue input (AIN 1 or AIN 2) has to be configured as described to be able to
use an external (analogue) speed setpoint.
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Analogue inputs M0389
Signal AIN 1 M0135
Signal AIN 2 M0138
Example
Use analogue input AIN 1 for speed setpoint:
Parameter Signal AIN 1 M0135 = Interface speed
Information
The speed range for the analogue input is determined via parameters Speed rem.
min. M1936 and Speed rem. max M1937.
8.1.2.Speed for constant (internal) speed setpoint: set
For setting of parameter Sp. source... (internal speed setpoint)
If the actuator is controlled via an external speed source, the internal speed values
described here will not have an impact on the operation behaviour.
This setting is only effective if one of the speed sources is either set to Analogue
input or Fieldbus.
Customer settings M0041
Speed functions M1699
Speed rem. min. M1936
Speed rem. max M1937
Default values:
Speed rem. min. = 6 rpm (≙ 0/4 mA)
Speed rem. max = 60 rpm (≙ 20 mA)
Setting values:
Speed rem. min. = 6 ... 240 rpm (revolutions/minute)
Speed rem. max = 6 ... 240 rpm (revolutions/minute)
The adjustable speed range is indicated on the actuator name plate.
8.1.4.Speed reduction before reaching end positions OPEN/CLOSED (soft stop in end positions)
Prior to reaching the end position, the speed can be linearly reduced within a
programmable range.
Figure 36: Example of speed reduction in end positions
nCurrent speed in direction OPEN/CLOSE
n
Target speed for end positions
Z
Speed reduction range before end positions
Δ
Activate speed reduction before reaching end positions
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Speed red. range M1903
Function not active
Function active
Default value: Function active
Setting values:
<Speed reduction range> function deactivated.
<Speed reduction range> function activated.
Adjust speed reduction range before reaching end position
Within this range before reaching the end position, the current speed will be linearly
reduced to the target speed (parameter Target speed for red. M1905).
47
Page 48
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Information
If the current speed is lower than the target speed, the speed is increased to the
target speed!
Customer settings M0041
Speed functions M1699
Speed red. range M1906
Speed red. end pos. M1904
Default value: 5.0 %
Setting range: 0.0 ... 25.0 % (in % before reaching the end position, in relation to
the full travel)
Set target speed before reaching end position
The actuator runs to the end position at the target speed set by means of this
parameter.
Behaviour A: "Off", intermediate position is not signalled.
Behaviour B: Signal is active from reaching the pivot point (P) up to end position
OPEN (100 %)
C¯¯¯¯¯¯¯¯¯|_______O
Behaviour C: Signal is active from end position CLOSED (0 %) until reaching the
pivot point (P).
C_______|¯|_______O
Behaviour D: When passing the pivot point (P), a pulse signal is issued.
Figure 37: Signal behaviour (A to D) of the intermediate positions
Special characteristics of B, C and D
Behaviour of B and C:The signal is directly activated when reaching the set pivot
point (P).
Behaviour D: The signal is activated shortly before reaching the set pivot point (P).
The switch-on point is determined by pulse duration (+/– range around the pivot
point). Pulse dur ation depends on parameter Outer dead band M0148 and amounts
to 1.0 % of the travel for default setting.
Information
For behaviours B and C, the signal might be omitted if, e.g when using a positioner,
pivot point (P) is not fully reached due to the dead band. In this case, behaviour D
can be selected as the dead band is considered.
8.2.3.Hysteresis for intermediate positions: set
The hysteresis determines the tripping point of the signal.
Example
Parameter Pivot point 6 M0253 is set to 50.0 % of the travel.
Parameter Hysteresis 6 M0282 is set to 1.0 %.
49
Page 50
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Figure 38: Signal behaviour B, C, D for hysteresis = 1 %
P1
Switching on point(●)
P2
Switch-off point (○)
pTPulse duration = 2 times XT + hysteresis
Required user level:AUMA (6).
Customer settings M041
Intermediate positions M0143
Hysteresis M0267
Hysteresis 1 M0277
Default values: 0.5 % for all 8 positions
Setting range:0.0 % to 5.0 % of the travel (from OPEN to CLOSED)
Information
8.3.Operation profile (operation behaviour) for intermediate positions
Conditions
Characteristics
8.3.1.Operation profile: activate
For signal behaviour D , the v alue XT (Outer dead band M0148 parameter) determines
pulse duration pT and influences switch-on point P1.
Function <Positioner>, parameter Positioner M0158 = Function active (Required
user level:Specialist (4) or higher)
The function <Operation profile> can be used to define the operation behaviour of
the actuator when reaching an end position. Example:The actuator stops and only
continues its operation after another operation command.
This function is required in special applications to avoid water hammer , possib ly also
in combination with the timer.
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Operation profile M0294
Default value: Function not active
Setting values:
Function not active
Function active
8.3.2.Operation profile for intermediate positions (pivot points): set
50
Function <Operation profile> deactivated.
Function <Operation profile> activated.
When reaching an intermediate position, the operation behaviour of the actuator
may be set.
No intermediate stop, actuator continues the operation.
Off
●
Stop in OPEN
Stop in CLOSED
Stop in OPEN & CL.
Off time in OPEN
Off time in CLOSED
Off time in OPEN & CL.
Actuator stops at pivot point during operation in direction OPEN.
●
Another operation command must be issued to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
●
Actuator stops at pivot point during operation in direction CLOSE.
●
Another operation command must be issued to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
●
Actuator stops automatically upon reaching the pivot point.
●
Another operation command must be issued to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
Actuator stops at pivot point during operation in direction OPEN. If an operation
command in direction OPEN is present at the end of the pause time, the actuator
resumes operation into direction OPEN. If an operation command in direction CLOSE
is present during the pause time, the pause is aborted and operation into direction
CLOSE resumed.
When reaching the pivot point, the actuator stops during operation in direction CLOSE.
If an operation command in direction CLOSE is present at the end of the pause time,
the actuator resumes operation into direction CLOSE. If an operation command in
direction OPEN is present during the pause time, the pause is interrupted and
operation into direction OPEN resumed.
Actuator stops automatically upon reaching the pivot point. If an operation command
in direction OPEN or CLOSE is present at the end of the pause time, the actuator
resumes operation depending on the operation command.
Information
The actuator stops for each activated intermediate position for which operation behaviour Stop in OPEN, Stop in CLOSED or Stop in OPEN & CL. is assigned.
8.3.3.Off times for intermediate positions (pivot points): set
An off time can be defined for each pivot point.
If a pivot point is reached with the operation behaviour Off time in OPEN , Off time
in CLOSED or Off time in OPEN & CL., the actuator controls generate a signal during
off time:
Required user level:Specialist (4) or higher.
Customer settings M041
Intermediate positions M0143
Off times M0268
Off time 1 M0285
Default values: 00:01,0 min:s (1 second)
Setting ranges: 00:00.2 ... 30:00,0 min : s (0.2 seconds – 30 minutes)
8.4.Two-wire control
Conditions
Characteristics
Information
Operation mode Remote (Selector switch = position Remote control).
With the function <Two-wire control>, the actuator can be operated to end position
OPEN or CLOSED via a digital input.
In this function, the actuator only reacts to commands via the input OPEN / CLOSE.
Other inputs to which the operation commands OPEN, STOP, CLOSE were assigned,
do not have any function.
51
Page 52
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Execute operation commands via digital input:
Designation of digital input OPEN / CLOSE
(wiring diagram designation: OPEN/CLOSE
●
Default setting
Input OPEN / CLOSE = low level (0 V DC or input open):
Actuator runs in direction CLOSE.
●
Input OPEN / CLOSE = high level (standard: +24 V DC):
Actuator runs in direction OPEN.
Configuration of digital input
For the two-wire control, a digital input for the OPEN / CLOSE signal has to be
configured.
Required user level:Specialist (4)
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Use input DIN 5 for signal OPEN / CLOSE:
Parameter: Signal DIN 5 M0122 = OPEN/CLOSE
Information
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 6 M0128), the input is either High active or Low active. Default
setting is High active.
This function requires one of the following equipments within the actuator:
●
Electronic control unit (non-intrusive version)
●
Potentiometer
●
Electronic position transmitter EWG/RWG
Further conditions for the positioner operation mode:
●
Positioner enabled and activated.
●
Operation mode Remote (selector switch = position Remote control).
Characteristics
The positioner records setpoint position E1 and actual position value E2 for
comparison. Depending on the detected deviation, the actuator motor then runs in
direction OPEN or CLOSE.
●
Information
If the actuator is controlled via a setpoint (e.g. 0 – 20 mA), the status indication
S0003 on the display shows both setpoint position E1 and actual position v alue
E2.
●
If the status indication S0003 only shows actual position value E2, OPENCLOSE control is active and there is no setpoint control via the positioner. In
this case, you have to change-over to setpoint control first, refer to <Changeover between OPEN-CLOSE control and setpoint control> chapter.
8.5.1.Positioner: activate
Function not active
Function active
52
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Positioner M0158
Default value: Function not active
Setting values:
Function <Positioner> deactivated.
Function <Positioner> activated.
Adaptive positioning may reduce the number of starts and compensate for the o verrun
of the actuator.
Customer settings M0041
Positioner M0145
Adaptive behaviour M0147
Default value: Adaptive I
Setting values:
Adaptive behaviour switched off.
Off
Adaptive I
Adaptive behaviour for precise positioning (high positioning accuracy).
Due to the inertia of actuator and valve, the valv e position changes only slightly after
switching off the actuator (overrun).The positioner determines the resulting error
between setpoint and actual value for both directions and automatically adapts the
inner dead bands Xi and therefore switching point P2.
On the basis of the determined inner dead bands Xi and the set hysteresis
(parameters Posit. hyst. OPEN M0598 or Posit. hyst. CLOSE M0599), the outer
dead bands XT are automatically determined.
This reduces the error caused by the overrun after only a f e w oper ations and a high
positioning accuracy is achieved.
Figure 39: Positioner positioning behaviour
E1Target value
E2Actual value
P1Switch-on point
P2Switch-off point in direction OPEN
P3Setpoint reached
X
Max. error (outer dead band)
T
Xi1Overrun in direction OPEN (inner dead band OPEN)
Xi2Overrun in direction CLOSE (inner dead band CLOSE)
Adaptive II
Contrary to adaptive positioner 1, adaptive positioner 2 will not be subject to
oscillation.
8.5.3.Overrun (inner dead band): set manually
The inner dead band determines the switch-off point of the actuator and therefore
influences the overrun.
The inner dead band may be set individually for the directions OPEN and CLOSE.
Manual setting is only possible if the adaptive behaviour, parameter Adaptive
behaviour M0147 is switched off.
53
Page 54
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Customer settings M0041
Positioner M0145
Dead band OPEN M0234
Dead band CLOSE M0235
Default values: 0.5 % for dead band OPEN and CLOSED
Setting ranges: 0.0 – 10.0 % for dead band OPEN and CLOSED
●
Information
Inner dead bands may not be set wider than outer dead bands.
●
Inner dead bands may not be set too narrow as this may cause unnecessary
switching procedures (premature wear) or oscillation of the actuator.
.
8.5.4.Max. error variable (outer dead band): set manually
The outer dead band determines the switching-on point of the actuator.
The motor starts if the actual value (input signal E2) or a change in nominal value is
higher than the max. error variable determined by the outer dead band.
Manual setting is only possible if the adaptive behaviour, parameter Adaptive
behaviour M0147 switched off.
Customer settings M0041
Positioner M0145
Outer dead band M0148
Default value: 1.0 %
Setting range: 0.1 – 10.0 %
8.5.5.Dead time: set
The dead time prevents the operation to a new setpoint position within a
pre-determined time.
Customer settings M0041
Positioner M0145
Dead time M0149
Default value: 0.5 s
Setting range: 0.2 – 60.0 s (seconds)
Information
It must be ensured via the controls that the max. permissible number of starts of the
actuator is not exceeded.This can be achieved by setting the dead time to a sufficiently high value.
8.5.6.Hysteresis for positioner: set
The hysteresis determines the switching accuracy. It can be used to reduce the
number of starts for example.
This setting can only be made if the adaptive behaviour, parameter Adaptive
behaviour M0147 is set to Adaptive I.
Customer settings M041
Positioner M0145
Posit. hyst. OPEN M0598
Posit. hyst. CLOSE M0599
Default values: 0.5 % for OPEN and CLOSED
Setting range:0.0 % to 5.0 % of the travel (from OPEN to CLOSED)
8.5.7.Closing fully/opening fully (end position tolerance for setpoint)
If the end positions cannot be reached due to inaccurate analogue setpoint signals
(0/4 mA or 20 mA), a tolerance for the setpoint within the end position range can be
set. If the toler ance is exceeded or not reached, the actuator continues the oper ation
until the full end position has been reached.This ensures that the actuator opens
and closes fully.
Customer settings M0041
Positioner M0145
Tolerance CLOSE M0150
Tolerance OPEN M0151
Default values:
Tolerance CLOSE = 0.0 %
Tolerance OPEN = 100.0 %
Setting ranges: (in percent of the travel)
Tolerance CLOSE = 0.0 – 5.0 %
Tolerance OPEN = 95 – 100.0 %
8.5.8.Setting range: limit
Travel can be limited in directions OPEN and/or CLOSE.
This prevents end position(s) OPEN and/or CLOSED from being approached in
modulating duty.The actuator stops when reaching the set limit value.
For OPEN - CLOSE control (LOCAL or REMOTE OPEN-CLOSE operation mode),
this limitation is not active.The valve can then be run into the end positions either
via the local controls or from remote.
Function not active
Function active
Figure 40: Limitation of setting range
[1]Permissible actuator travel for setpoint control
[2]Permissible actuator travel for OPEN - CLOSE control
Activate limitation
Customer settings M0041
Positioner M0145
Limit setting range M0845
Default value: Function not active
Setting values:
Limitation deactivated.
Limitation activated.
Set limits
Customer settings M0041
Positioner M0145
Limit OPEN M0162
Limit CLOSE M0161
Default values:
Limit OPEN = 100.0 %
Limit CLOSE = 0.0 %
Setting ranges: 0.0 ... 100.0 % of travel
55
Page 56
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
8.5.9.Speed reduction before reaching setpoint position
Characteristics
Application
Function not active
Function active
The function adapts the setpoint depending on the error variable compared to the
setpoint. In case of a low error variable compared to the setpoint, the actuator runs
at low speed. For a high error variable, the actuator runs at maximum speed.The
maximum speed is then equal to the current speed.
For modulating duty with high positioning accuracy.
Activate speed reduction before reaching setpoint position
Required user level:Specialist (4) or higher.
Customer settings M0041
Positioner M0145
Speed red.before setp. M0835
Default value: Function active
Setting values:
<Speed reduction> function deactivated.
<Speed reduction> function activated.
Set speed reduction range
Range in relation to the setpoint, where the speed – depending on the deviation from
the setpoint – is either reduced or increased from the current speed to the "target
speed" (parameter Target speed at setp. M1939).
Customer settings M0041
Positioner M0145
Speed red. range M0836
Default value: 10.0 %
Setting range: 2.0 – 20.0 (deviation from the setpoint in %)
Set target speed before reaching setpoint position
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 4 M0126), the input is either High active or Low active. Default
setting of MODE input is Low active.
Change-over via digital input MODE
Switching behaviour for coding Low active:
(Default factory setting)
●
Input MODE = low level (0 V DC or input open) = Remote SETPOINT
The actuator reacts to a setpoint signal (e.g. 0/4 – 20 mA)
●
Input MODE = high level (standard: +24 V DC) = Remote OPEN-CLOSE:
The actuator reacts to operation commands OPEN, STOP, CLOSE.
8.5.11.Input of setpoint position
The setpoint position is generally led via input AIN1, but can also be led via AIN 2.
Required user level:AUMA (6).
Device configuration M0053
I/O interface M0139
Analogue inputs M0389
Signal AIN 1 M0135
Signal AIN 2 M0138
Default value AIN 1: Setpoint position
8.5.12.Input range of setpoint position
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue inputs M0389
Low limit AIN 1 M0133
High limit AIN 1 M0134
Default values:
Low limit AIN 1 = 0 mA
High limit AIN 1 = 20 mA
Setting values: 0 ... 20 mA
8.5.13.Split Range operation
●
Requirements
Function
<Positioner> function must be enabled and activated:
In Split Range operation, a setpoint position E1 can be shared by up to three
positioners. A typical application example is a pipeline with a bypass.The actuator
mounted on the bypass reacts in the lower limit (e.g. 0 – 10 mA), the actuator on the
main valve in the upper limit (e.g. 10 – 20 mA). If the setpoint position is within the
setpoint range defined for the individual actuator, the actuator behaviour will be
identical to standard positioner operation. If the setpoint position is higher or lower
than the upper or the lower limit of the setpoint range of the respective actuator, the
actuator will run to positions OPEN or CLOSED.
The upper and lower limit of the respective actuator is defined via the analogue input.
(<Input range of setpoint position>)
In addition, the upper and lower limit of the total target value (valid for all actuators
grouped in a split range operation).
Activate split range operation
Required user level:Specialist (4) or higher.
57
Page 58
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Device configuration M0053
Application functions M0178
Activation M0212
Split range operation M01650
Default value: Function not active
Setting values:
Function not active
Function active
<Split range operation> function deactivated.
<Split range operation> function activated.
Set total target value range
The set lower limit of total target value is used as f ailure source for failure beha viour
during split range operation. <Failure behaviour on loss of signal>
Customer settings M0041
Positioner M0145
Low limit target value M01651
High limit target value M01652
Default values:
Low limit target value = 0.0 mA
High limit target value = 20.0 mA
8.6.Process controller
Requirements
Characteristics
Setting ranges: 0.0 ... 20.0 mA
This function requires one of the following equipments within the actuator:
●
Electronic control unit with MWG (non-intrusive version)
●
Potentiometer
●
Electronic position transmitter EWG/RWG
Further conditions for the process controller operation mode:
●
Process controller enabled and activated.
●
Operation mode Remote (Selector switch = position Remote control).
The following figure illustrates the function of the process controller:
The process controller [2] receives the process setpoint E7 and the actual process
value E4 (e.g. from a sensor). On the basis of both values, the process controller
calculates the position setpoint E1 for positioner [3]. In turn, the positioner [3]
compares this target setpoint with the actual position value E2 of the valv e and issues
the operation commands (OPEN - CLOSE) for the actuator.
[1]Actuator controls
[2]Process controller
[3]Positioner
[4]Actuator
[5]Position transmitter e.g. EWG/RWG/MWG
[6]Sensor
[7]Valve
E1Position setpoint (internal)
E2Actual position value
E4Actual process value
E7Process setpoint
Application
8.6.1.Process controller activation
The process controller can be used to control pressure, flow or flow rates , flow lev els
and temperature.
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Process controller M0741
Default value: Function not active
Setting values:
Function not active
Function active
8.6.2.Process controller: set modulating behaviour
<Process controller> function deactivated.
<Process controller> function activated.
Three controller types are available to ideally adapt the modulating beha viour of the
process controller to the respective application.
59
Page 60
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Customer settings M0041
Process controller M0742
Modulating behaviour M0887
Default value: PI controller
Setting values:
P controller
P controller immediately reacts to a control deviation (i.e. actively) and amplifies the
input signal (error variable) proportionally to the set amplification. Setting parameter:
Proport. gain Kp M0744
Figure 42: Step response of P controller
P controller application
PI controller
PI controller application
PID controller
For uncritical closed-loop applications allowing to accept continuous error variab les
in the event of failures, e.g. pressure, flow, filling level and temperature control.
PI controllers consist of a P fraction immediately reacting to a control deviation and
an I fraction for chronological integration of the input signal (error variable). Due to
the additional time constant of the I fraction, the output value takes more time to
reach the target status (i.e. inertia of control loop response) whereas positioning
accuracy increases at the same time (lower control deviation). P arameters f or setting
the time constant: Reset time Ti M0745
Figure 43: Step response of PI controller
Quick control circuits not allowing continuous error variables, e.g. pressure,
temperature and ratio control.
Compared to the PI controller, the PID controller has an additional D fraction
accounting for changes in the error variable (change rate).The D fraction quickly
reacts to changes, even to minor control deviations with large output values.
Parameter for setting the D fraction:Rate time Td M0746
Figure 44: Step response of PID controller
PID controller use
8.6.3.Setpoint source (input for process setpoint)
For precise and highly dynamic control not allowing a continuous error variable.
In case of process setpoint signal loss, the actuator controls switch to the internal
setpoint 1. Parameter Internal setpoint 1 M0749
In case of process setpoint signal loss, the actuator controls switch to the internal
setpoint 2. Parameter Internal setpoint 2 M0750
In case of process setpoint signal loss, failure behaviour procedure is activated.
Parameter Failure behaviour M0378
In case of process setpoint signal loss, the last available process setpoint will still
be used as setpoint.
As standard, the valve is opened by the modulating actuator as soon as the actual
process value falls below the process setpoint. Depending on the process, it may,
however, be necessary that the valve closes as soon as the actual process value
falls below the process setpoint. In this case, the respectiv e par ameters are used to
set the process controller to inverse operation.
Customer settings M0041
Process controller M0742
Inverse operation M0748
Default value: Function not active
Setting values:
Function not active
Function active
Inverse operation is deactivated.
Inverse operation is activated.
8.6.6.Internal process setpoint
An internal process setpoint may be set with this parameter.The internal process
setpoint is used if:
●
Parameter Setpoint source M0743 is set to Internal setpoint or
●
Parameter Beh. setpoint failure M0747 is set to Internal setpoint 1 or Internal
setpoint 2.
The setting of the process controller largely depends on the area of controller
application. A PI controller suffices for most applications.
Procedure
1.Operate the controller as PI controller, i.e. set the parameters as follows:
-Proportional gain Kp = 1
-Reset time Ti = 1,000 s
-Rate time Td = 0
2.Double proportional gain Kp until the control loop starts to oscillate.
3.Reduce proportional gain Kp to 60 % of the set value.
4.Decrease reset time Ti until the error variable equals zero.
8.6.8.Proportional amplification Kp: set
In the event of an error variable, the P portion immediately (i.e. actively) changes
the position value proportionally to the error variable.
If a small error variable already requires a major valve position adjustment, the
proportional gain Kp must be increased.
Information
8.6.9.Reset time Ti: set
Information
If the reaction is too extreme (ov ershoot), the value must be reduced. If the reaction
is too weak, the value must be increased.
Customer settings M0041
Process controller M0742
Proport. gain Kp M0744
Default value: 1.0
Setting range: 0.1 ... 10.0
The reset time determines the I portion of the controller.The more inert a system,
the higher this value should be set.
●
Increase Ti in case of propensity for oscillation.
●
Decrease Ti if the reactions are excessively delayed.
●
Starting value for fast processes (e.g. pressure): 10 s
●
Starting value for slow processes (e.g. temperature): 1000 s
Customer settings M0041
Process controller M0742
Reset time Ti M0745
Default value: 1,000 s (seconds)
Setting range: 1 ... 1000 s
8.6.10.Rate time Td: set
Information
62
The rate time determines the D portion of the controller.Typically, no setting is
required here (= 0), since actuator and valve – due to the operating time – cannot
react abruptly to a sudden occurrence of an error variable.
●
Increase Td in case of propensity for oscillation.
●
Initial value for actuators: 0 s
Customer settings M0041
Process controller M0742
Rate time Td M0746
Default value: 0 s (seconds)
Setting range: 1 ... 100 s
8.6.11.Actual value source (input for actual process value)
Customer settings M0041
Process controller M0742
Actual value source M0756
Default value: I/O interface
Setting values:
I/O interface
The actual process value is defined via an analogue input (AIN 1 or AIN 2) of the
I/O interface.
8.6.12.Speed source for actual process value
The actuator speed for control via the actual process value can be specified by
different sources.
Customer settings M0041
Process controller M0742
Speed source PID M1968
Default value: Internal 1
Setting values:
Internal 1 – Internal 4
2 DigIn: "Internal (1-4)"
Analogue input
The actuator is controlled with a constant speed. F or this, f our programmable internal
speed values are available.The four internal speed values are programmed via
parameters Speed internal1 M1930 – Speed internal 4 M1933.
External speed selection. For this setting, tw o external signals may be used to change
between the four internally programmed, constant speeds (Internal 1 – Internal 4).
Two digital inputs have to be configured as control signals for speed selection.
The actuator speed is specified/modified externally via an analogue value (e.g. 0 –
20 mA). An analogue input has to be defined as speed source.
The speed range for the analogue input is determined via parameters Speed rem.
min. M1936 and Speed rem. max M1937.
8.7.Stepping mode
Conditions
Characteristics
This function requires one of the following equipments within the actuator:
●
Electronic control unit (non-intrusive version)
●
Potentiometer
●
Electronic position transmitter EWG/RWG
●
With stepping mode, the operating time can be increased for the entire or any
portion of the valve travel.
●
Stepping mode can be individually activated for the directions OPEN and
CLOSE.
63
Page 64
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Figure 45: Stepping mode
[1]Stepping range OPEN
[2]Stepping range CLOSE
P1Start of stepping mode
P2End of stepping mode
t1Operating time for normal operation
t2Operating time for stepping mode
t3Running time
t4Off time
8.7.1.Stepping mode: activate
Stepping mode can be individually activated for the directions OPEN and CLOSE.
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Timer CLOSE M0156
Timer OPEN M0206
Default value: Function not active
Setting values:
Function not active
Function active
Function <Stepping mode> deactivated.
Function <Stepping mode> activated.
8.7.2.Operation mode for stepping mode
Stepping mode can be activated via operation modes Local and/or Remote.
Customer settings M0041
Timer M0142
Step mode CLOSE M0157
Step mode OPEN M0207
Default value: Off both directions
Setting values:
Stepping mode is active in the operation modes:Remote, Remote II, Fieldbus
Stepping mode is active in the operation modes:Local, Service
Stepping mode is active in the operation modes:Remote, Remote II, Fieldbus, Local,
Service
The timer cannot be by-passed in <Operation mode EMERGENCY>.
Start and end of stepping mode can be individually set for both directions.
Customer settings M0041
Timer M0142
End stepping CLOSE M0152
Start stepping CLOSE M0153
Start stepping OPEN M0154
End stepping OPEN M0155
Default values:
End stepping CLOSE = 0.0 %
Start stepping CLOSE = 100.0 %
Start stepping OPEN = 0.0 %
End stepping OPEN = 100.0 %
Setting ranges:
End stepping CLOSE = 0.0 – 99.9 %
Start stepping CLOSE = 0.1 – 100.0 %
Start stepping OPEN = 0.0 – 99.9 %
End stepping OPEN = 0.1 – 100.0 %
8.7.4.On times and off times
On or off times can be set individually for directions OPEN and CLOSE.
Customer settings M0041
Timer M0142
On time CLOSE M0163
Off time CLOSE M0164
On time OPEN M0165
Off time OPEN M0166
Default values: 00:05.0 min : s (= 5 seconds; for all on and off times)
Setting ranges: 00:01.0 ... 00:05.00.0 min : s (= 1 second up to 30 minutes; for all
on and off times)
8.8.By-pass function
Application
Function
The by-pass function is used, e.g. for district heating pipelines. Under high pipeline
pressure, the gate valve of the main valve cannot be used, pressure compensation
via by-pass valve is therefore required.
Two MOVs – one main valve and a by-pass valve – are linked via enable signals
Bypass Sync In and By-pass Sync Out. Operation commands can only be e xecuted
if one of the two actuators sends the enable signal to the other. Release depends
on the end position.This ensures that only the following operation commands may
be executed:
●
The main valve can only be operated in directions OPEN or CLOSE if the bypass valve is in end position OPEN.
65
Page 66
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Figure 46: Function
Table 9: Main valve reaction to by-pass valve position.
Main valveBy-pass valve
Position
End position OPEN
Other position
In case of an operation command, the "Interlock by-pass" signal is sent (no release).1)
Enable signal
Bypass Sync OUT
(Default: +24 V DC
Low level (interlock)
(0 V DC or input open-circuit):
Release
(available operation commands)
in directions OPEN and CLOSEHigh level (release)
No operation possible
1)
EMERGENCY behaviour
Table 10: By-pass valve reactions to main valve position
By-pass valveMain valve
Position
End position
CLOSED
Other position
In case of an operation command in direction CLOSE, the "Interlock by-pass" signal is sent (no re-
1)
lease).
Enable signal
Bypass Sync OUT
(Standard: +24 V DC)
Low level (interlock)
(0 V DC or input open-circuit):
Release
(available operation commands)
in directions OPEN or CLOSEHigh level (release)
In direction OPEN or CLOSE
1)
The emergency behaviour of the by-pass function has the same characteristics as
the <EMERGENCY behaviour> function with the following differences:
In an EMERGENCY situation, both controls receive the EMERGENCY signal at the
same time.This signal starts the EMERGENCY operation specially defined for the
by-pass function. (Parameter EMCY operation M0204 is therefore not available in
the <EMERGENCY behaviour> function).
EMERGENCY operation procedure
1.By-pass valve is opened first.
2.Once the by-pass valve is fully opened, the main valve is closed.
3.Once the main valve is fully closed, the by-pass valve is fully opened.
Signal DIN 5 M0122 = By-pass Sync In
(wiring diagram designation: BYPASS SYNC IN)
●
Signal DIN 6 M0121 = EMERGENCY
(wiring diagram designation: NOT/EMERGENCY)
Information
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 6 M0128), the input is either High active or Low active. Default
setting is High active.
Configuration of digital output
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Example
Use output DOUT6 for signal Bypass Sync Out:
Parameter: Signal DOUT 6 M0111
Setting value: Bypass Sync Out (wiring diagram designation:BYPASS SYNC
OUT)
8.8.1.Bypass function: activate
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
By-pass function M0941
Default value: Function not active
Setting values:
Function not active
Function active
Bypass function deactivated.
Bypass function activated.
8.8.2.By-pass application: configure
The actuators for the two MOVs (valves) have to be configured according to their
application (main or by-pass valve).
Customer settings M0041
By-pass function M0942
By-pass application M0943
Default value: Main valve
Setting values:
Main valve
By-pass valve
Actuator for main valve.
Actuator for by-pass valve.
8.9.Automatic deblocking
Requirements
This function requires one of the following equipments within the actuator:
●
●
This function CANNOT be combined with the functions listed below:
●
●
Electronic control unit
Electronic position transmitter EWG/RWG
By-pass function
Operation profile
67
Page 68
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
●
If the setting range was limited for the positioner (parameter Limit setting
range M0845 = Function active)
For actuator controls in SIL version, we DISADVISE using the automatic deblocking
function.
Unexpected starting of actuator!
When using automatic deblocking with le vel-controlled operation command ev aluation,
unexpected starting of actuator into the wrong direction might occur when trying to
eliminate a double-sided torque fault (torque faults in directions OPEN and CLOSE
are present at the same time).
→
Use automatic deblocking only in combination with edge controlled operation
command evaluation (parameter Com. eval. REMOTE M1709).
Characteristics
8.9.1.Automatic deblocking function: activate
In case of torque switch tripping in intermediate position (i.e. prior to reaching the
end position), the actuator automatically attempts to reach the end position by
operation into the opposite direction and executing the actual operation command
once again.
The torque fault signal is suppressed during automatic deblocking. Should torque
switching trip again once automatic deblocking is complete , the actuator is s witched
off and actuator controls signal a torque fault.
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
MPV function M1679
Default value: Function not active
Setting values:
Function not active
Function active
8.9.2.Operation time for operation in opposite direction: set
Function deactivated.
Function activated.
The actuator controls remember the first seating position and operates the actuator
for the set operation time into opposite direction.
Required user level:Specialist (4) or higher.
Customer settings M0041
Automatic deblocking M1680
Oper. time opposite M1681
Default value: 3 s
Setting ranges: 1 ... 60 s (seconds)
Tolerance range (+/-) for original torque seating position, within which a torque fault
will be signalled after unsuccessful automatic deblocking.
Required user level:Specialist (4) or higher.
Customer settings M0041
Automatic deblocking M1680
Tolerance range M1683
Default value: 10 %
Setting ranges: 5 ... 30 % (percentage of operating time into opposite direction)
8.10.Synchronous link
Application
Function
Synchronous link means synchronous electrical operation of two actuators (master
actuator/slave actuator) without mechanical link.The synchronous link function can
be used to operate two gate valves within a weir, for example.
Two MOVs – one main valve and a secondary valve – are linked via four signals.
End position OPEN/CLOSED , selector switch Remote, de viation too high and f ailure
as well as possible speed correction for synchronous operation are signalled or
controlled via the main valve.
Figure 47: Function
Example
Information
Configuration of digital inputs of the main valve
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Input DIN5 for Syn. link End pos. In signal = secondary valve has reached end
position CLOSED.
Input DIN6 for Syn. link Remote In signal = selector switch of secondary valve is in
position REMOTE.
Input DIN7 for Sync. link Ready In signal = secondary valve signals Ready state.
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 6 M0128), the input is either High active or Low active. Default
setting is High active.
69
Page 70
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Configuration of analogue inputs of the main valve
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue inputs M0389
Example
Use input AIN1 for Setpoint position signal:
Parameter: Signal AIN 1 M0135
Setting value: Setpoint position (Wiring diagram designation:AIN 1 SETPOINT)Use input AIN2 for Syn. link Position In signal:
Parameter: Signal AIN 2 M0138
Setting value: Syn. link Position In (Wiring diagram designation: ELSH In)
Configuration of analogue input of the main valve
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue outputs M0335
Output AOUT 1 for Speed target value signal:
Parameter: Signal AOUT 1 M0131
Setting value:Speed target value (Wiring diagram designation:SPEED SETPOINT)
Configuration of analogue input of the secondary valve
Required user level:Specialist (4) or higher.
Device configuration M0053
I/O interface M0139
Analogue inputs M0389
Example
8.10.1.Synchronous link function: activate
Use input AIN1 for Setpoint position signal:
Parameter: Signal AIN 1 M0135
Setting value: Setpoint position (Wiring diagram designation:AIN 1 SETPOINT)
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Synchronous link M1789
Default value: Function not active
Setting values:
Permitted difference between actual position value of the master actuator and the
slave actuator. A fault signal will be issued when exceeding the value set here.
The heater system is generally used for low temperature (in lo w temperature version
up to –60 °C). For an installed heater system, the other heaters (control unit, motor
heater) will also be connected to the heater system.
Wiring diagram designation: R5 H
Marking of variants within the wiring diagram code (position 11)
●
B = 115 V AC or 230 V AC externally supplied
●
C, E, H = internally supplied via actuator controls
The heater system is temperature-controlled.The heater system will automatically
be activated for a temperature range between –5 °C and –10 °C and ensures that
the temperature within the controls housing does not fall below –20 °C.
8.11.2.Heater on control unit (actuator)
Characteristics
For AUMA actuators with AC actuator controls, a resistance type heater is installed
on the control unit (within actuator switch compartment).
The heater minimises condensation within the actuator switch compartment.
Wiring diagram designation: R1 H
Marking within the wiring diagram code: position 11 = A – H
Information
The proper function of the heater can be monitored. For further information, refer to
<Heater system/heater monitoring>.
Information
Activate/deactivate heater on control unit
The heater on the control unit of the actuator can be activated/deactivated.
Activation/deactivation can either be permanent or automatically when
exceeding/falling short of defined temperature values. An electronic control unit
(MWG) is required for automatic setting.
If the heater is deactivated, heater monitoring is also deactivated (parameter Heatermonitor)!
Required user level:Specialist (4).
Device configuration M0053
71
Page 72
Actuator controls
Application functions ACV 01.2/ACVExC 01.2
Actuator M0168
Heater control unit M1338
Default value: On
Setting values:
Heater is deactivated.
Off
Heater is activated.
On
Auto
8.11.3.Motor heater
Heater is automatically activated/deactivated by the actuator controls:
●
For temperatures e xceeding +40 °C within the switch compartment = deactivated
●
For temperatures of less than +35 °C within the s witch compartment = activated
The motor heater minimises condensation within the motor and improves the start-up
behaviour for extremely low temperatures.
Wiring diagram designation: R4 H
Marking within the wiring diagram code: position 11 = D (motor heater externally
Failure functions are started by certain events and lead to a defined action of the
controls or the actuator. A failure operation can be started by a manual action (e.g.
pressing an EMERGENCY stop button). In general, a failure operation is automatically
started by a fault signal from a monitoring function (e.g. loss of signal).
Prevention of impermissible operation states such as: Operation command in direction
OPEN, actuator still runs in direction CLOSE due to the delay time.
The reversing pre vention time (off-time between tw o operation commands in opposite
direction) prevents a restart for a defined interval once the motor has switched off.
Parameters and instructions for setting
Required user level:AUMA (6).
Device configuration M0053
Switchgear M0173
Revers. prevent. time M0174
Default value: 0.3 s seconds
Setting range: 0.1 … 30.0 s seconds
9.2.Failure behaviour on loss of signal
Characteristics
The failure behaviour can be used to define A C reaction to loss of signal or a defectiv e
signal.
Only in operation mode Remote will the failure behaviour react to a signal loss. In
operation modes Local or Off, there will be no reaction.
9.2.1.Failure behaviour initiation on loss of signal
Required user level:Specialist (4) or higher.
Customer settings M0041
Failure behaviour M0378
Signal loss beh. M0379
Default value: Good signal first
Setting values:
Good signal first
Immediately active
The <Failure behaviour> is only initiated if the monitored signal fails (falling edge).
This setting ensures that if the signal is missing, the actuator will not start when
switching on (Good signal first).
The <Failure behaviour> is immediately initiated if the monitored signal is missing
(is not present).
For the setting Immediately active:
The actuator can start immediately when switching on!
Risk of personal injuries or damage to the valve.
→
Ensure that the signal set under parameter Source M0385 is present when
switching on.
→
Should the actuator start unexpectedly: Immediately set selector s witch to position Local control (LOCAL) or 0 (OFF).
9.2.2.Failure source (failure reason) for a failure operation: set
Customer settings M0041
Failure behaviour M0378
Source M0385
73
Page 74
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
Default value: I/O interface
Setting values:
I/O interface
The failure behaviour is initiated in case of setpoint loss (setpoint position, process
setpoint, actual process value).
The monitoring depends on the preset setpoint range, e.g.:
●
Setpoint = 4 – 20 mA, E1 lower than 3.7 mA = loss of signal
●
Setpoint = 10 – 20 mA, E1 lower than 9.7 mA = loss of signal
●
Information
For a setpoint range of 0 – 20 mA , monitoring is not possible.
●
Actuator controls will only respond to a setpoint signal loss, if a signal is present
at the MODE input, i.e. actuator controls are in operation mode Remote SETPOINT (setpoint control).
9.2.3.Failure operation (reaction of the actuator) on loss of signal
The failure operation determines which action is executed by the actuator once the
failure behaviour is initiated.
Customer settings M0041
Failure behaviour M0378
Failure operation M0384
STOP
CLOSE
OPEN
Approach position
Execute last CMD
Information
Default value: STOP
Setting values:
The actuator stops in the current position.
The actuator runs to end position CLOSED.
The actuator runs to end position OPEN.
The actuator runs to the predetermined position. Conditions:
●
The function <Positioner> is activated.
●
Parameter Source M0385 is set to I/O interface
The actuator executes the last operation command before it is stopped.
If the last operation command was a setpoint definition via analogue input (AIN 1/AIN
2), the lower limit of the setpoint position is used (parameter Low limit AIN 1/Lowlimit AIN 2).The actuator is operated to the defined end position, usually end position
CLOSED.
Behaviour depending on the selector switch position:
Once the failure operation is triggered, the defined position is approached. If the
actuator is then moved to another position (e.g. by manual operation), it will try to
perform the set failure operation while the selector switch is in position Remotecontrol (REMOTE).
To prevent a new approach to the failure position during manual operation, the selector switch must be set to position Local control (LOCAL) or 0 (OFF) prior to
operating the handwheel.
9.2.4.Failure position: define
If the failure operation Approach position is set, the actuator moves to the failure
position indicated here.
Required access level:Specialist (4) or higher.
Customer settings M0041
Failure behaviour M0378
Fail.pos.OPEN CLOSE M0387
Default value: 50.0 %
Setting range: 0.0 ... 100.0 % (from end position OPEN to CLOSED)
The adjustable speed range is indicated on the actuator name plate.
9.2.6.Delay time: set
A failure operation is only perf ormed once the delay time has expired.This prevents
a short-term loss of signal, which does not have an effect on the process, from directly
starting a failure operation
The EMERGENCY behaviour can be used to determine the actuator behaviour in
an emergency.
●
The function <EMERGENCY behaviour> is initiated by the EMERGENCY signal.
●
The actuator performs a defined EMERGENCY operation. For example, the
actuator moves to a predefined EMERGENCY position (i.e. end position OPEN
or end position CLOSED).
●
As long as the EMERGENCY signal is present, the actuator does not respond
to any other operation commands (EMERGENCY signal has top priority).
●
After initiating the EMERGENCY behaviour, binary operation commands (via
digital inputs) may have to be sent again.
For the function <EMERGENCY behaviour>, a digital input for the signal
EMERGENCY has to be available and configured.
Configuration of digital input
Example
Information
Required access level:Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use input DIN 4 for signal EMERGENCY:
Parameter: Signal DIN 4 M0118
Setting value: EMERGENCY (wiring diagram designation: EMERGENCY)
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 4 M0126), the input is either High active or Low active. For safety
reasons, the EMERGENCY signal input is generally set to Low active.
75
Page 76
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
Perform EMERGENCY operation via digital input
Switching behaviour for coding Low active:
●
Input EMERGENCY = low level (0 V DC or input open-circuit)
EMERGENCY operation is initiated.
●
Input EMERGENCY = high level (standard: +24 V DC)
No EMERGENCY operation
9.3.1.EMERGENCY behaviour: activate
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
EMCY behaviour M0589
Default value: Function not active
Setting values:
Function not active
Function active
Function <EMERGENCY behaviour> deactivated.
Function <EMERGENCY behaviour> activated.
For activated EMERGENCY behaviour:
The actuator can start its operation due to an EMERGENCY signal.
Risk of personal injuries or damage to the valve.
→
For commissioning and maintenance work: Set selector switch to position 0
(OFF). Motor operation can only be interrupted in this selector switch position.
→
Should the actuator start unexpectedly: Immediately set selector s witch to position 0 (OFF).
Information
EMERGENCY behaviour must be completely configured during first activation.This
means the setting of the following parameters must be adapted to the required actuator behaviour in particular: Failure reaction EMCY EMCY source EMCY operation
mode EMCY operation EMCY position
9.3.2.EMERGENCY failure reaction
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Failure reaction EMCY M0203
Default value: Good signal first
Setting values:
Good signal first
Immediately active
The <EMERGENCY behaviour> is initiated as soon as the EMERGENCY signal
changes from high to low. Example: for binary EMERGENCY input of +24 V DC to
0 V.This prevents the <EMERGENCY behaviour> from being initiated immediately
once the actuator controls are switched on and no EMERGENCY signal is present.
The <EMERGENCY behaviour> is initiated by a low le vel at the EMERGENCY signal.
For this setting, the EMERGENCY signal has to have a high level before switching
on the actuator controls; otherwise <EMERGENCY beha viour> is initiated immediately
after switching on.
The actuator can start immediately when switching on!
Risk of personal injuries or damage to the valve.
→
Ensure that the EMERGENCY signal is present when switching on.
→
Should the actuator start unexpectedly: Immediately set selector s witch to position 0 (OFF).
9.3.3.Failure source (failure reason) for an EMERGENCY operation: set
Customer settings M0041
EMCY behaviour M0198
EMCY source M0591
Default value: I/O interface
Setting values:
I/O interface
Active interface
The EMERGENCY signal is present as binary signal (standard: +24 V DC) at a digital
input. If this v oltage (i. e. the signal) is no longer present, the EMERGENCY behaviour
is initiated.
If active interface fails, the EMERGENCY behaviour is initiated; e.g. when changing
the command source the failure source for the EMERGENCY signal also fails.
9.3.4.Operation mode for EMERGENCY behaviour
The EMERGENCY behaviour can be activated for the operation modes Remote
and/or Local
Customer settings M0041
EMCY behaviour M0198
EMCY operation mode M0202
Default value: Remote only
Setting values:
Remote only
Remote and local
Information
9.3.5.EMERGENCY operation
EMERGENCY behaviour is active in the operation modes:RemoteRemote II Fieldbus
EMERGENCY behaviour is active in the operation modes:Remote, Remote II,
Fieldbus, Local, Service
In the operation mode Off (selector switch position 0), no emergency operation is
performed.
The EMERGENCY operation determines which action is executed by the actuator
once the EMERGENCY behaviour is initiated.
Customer settings
EMCY behaviour
EMCY operation
STOP
CLOSE
OPEN
Approach EMCY pos.
Default value: STOP
Setting values:
The actuator stops in the current position.
The actuator runs to end position CLOSED.
The actuator runs to end position OPEN.
The actuator runs to the predetermined position.
77
Page 78
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
9.3.6.EMERGENCY position
If the EMERGENCY operation Approach EMCY pos. is set, the actuator moves to
the EMERGENCY position entered here.
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
EMCY position M0232
Default value: 0.0 %
Setting range: 0.0 … 100.0 % (from end position OPEN to CLOSED)
9.3.7.EMERGENCY speed
Speed for an EMERGENCY operation.
Required user level:Specialist (4) or higher.
If the EMERGENCY signal initiates an EMERGENCY operation, the stepping mode
can be by-passed during this operation.
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass timer M0201
Default value: Off
Setting values:
No by-pass of stepping mode.
Off
Stepping mode is by-passed.
On
9.3.11.Operation profile: by-pass
If the EMERGENCY signal initiates an EMERGENCY operation, the set operation
profile (operation behaviour) can be by-passed during this operation.
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass operat.profile M0596
Default value: Off
Setting values:
No by-pass of operation profile.
Off
The operation profile is by-passed.
On
9.3.12.Interlock: by-pass
If the Interlock function is activated, you may by-pass this function during
EMERGENCY operation to prevent that an enable command must be issued to
perform EMERGENCY operation.
Required user level:Specialist (4) or higher.
Customer settings M0041
Default value: Off
Setting values:
By-pass mode is deactivated. Interlock function is e v en activ e during EMERGENCY
Off
operation.
By-pass mode is activated. Interlock function is deactivated during EMERGENCY
On
operation.
9.3.13.Local stop: by-pass
EMCY behaviour M0198
By-pass Interlock M0668
If activated, you ma y by-pass Local Stop function during an EMERGENCY operation
to prevent interruption of EMERGENCY operation b y pressing the push button ST OP.
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass Local STOP M0682
Default value: Off
Setting values:
79
Page 80
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
By-pass mode is deactivated. Local Stop function is ev en active during EMERGENCY
Off
operation.
By-pass mode is activated. Local Stop function is deactiv ated during EMERGENCY
On
operation.
9.3.14.Delay time for EMERGENCY operation
An EMERGENCY operation is only performed once the delay time has expired.
Consequently , a short-term signal failure will not hav e an impact on the process and
will not immediately initiate an EMERGENCY operation.
Required user level:Specialist (4) or higher.
Customer settings M0041
EMCY behaviour M0198
Delay time M0804
Default value: 00:01.00 min : s
Setting range: 00:00.0 ... 30:00.0 min : s
9.4.Enabling local controls
●
Application
Characteristics
Condition
Protection against unauthorised operation via local controls
●
Protection against unauthorised parameter setting via local controls
The selector switch functions LOCAL and/or OFF may be enabled or disabled.
For the function <Enable local controls>, a digital input for the signal Enable Local
has to be available and configured.
Configuration of digital input
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Information
9.4.1.Enabling function: activate
Use input DIN 5 for signal Enable Local:
Parameter: Signal DIN 5 M0122
Setting value: Enable Local (wiring diagram designation: Enable LOCAL)
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 5 M0127), the input is either High active or Low active. Default
setting is High active.
Enable/disable local controls via digital input
Switching behaviour for coding High active:
●
Input Enable Local = high level (standard: +24 V DC):
Operation via local controls enabled
●
Input Enable Local = low level (0 V DC or input open):
Operation via local controls disabled
Function not active
80
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Enable LOCAL M0631
Default value: Function not active
Setting values:
Function <Local controls: enable from REMOTE> deactivated.
Function <Local controls: enable from REMOTE> activated.
9.4.2.Enabling function behaviour
The enable behaviour determines which selector switch functions (LOCAL, OFF)
require an additional enable signal.
Required user level:Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Enable LOCAL M0628
Default value: Sel. sw. Local
Setting values:
Sel. sw. Local
Sel. sw. Local + Off
Information
Disabling or enabling is only effective in operation mode LOCAL (selector switch is
in position Local control). If no enab le signal is present, oper ation via push b uttons
on the local controls is disabled and the display shows the f ollowing signal:Disabled.
Disabling or enabling is effective in operation modes LOCAL and OFF (selector
switch positions Local control and 0). If no enable signal is present, operation via
push buttons on the local controls is disabled and the display shows the following
signal: Disabled.
If the <Priority REMOTE> function is also activated, the two functions should have
different setting values. In case of identical setting values, e.g.Sel. sw. Local + Off,
the <Enable local controls> function will have no function, since the actuator controls
will be exclusively in operation mode REMOTE if the enable signal is missing.
9.5.Priority REMOTE
Characteristics
Application
Condition
Example
Information
A control signal can provide REMOTE control with priority over actuator operation
via local controls (irrespective of the selector switch position)
This function uses the same input signal as the <Enabling local controls> function.
No changing possibility via selector switch from LOCAL
For the <Priority REMOTE> function, a digital input for the signal Enable Local has
to be available and configured.
Configuration of digital input
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use input DIN 5 for signal Enable Local:
Parameter: Signal DIN 5 M0122
Setting value: Enable Local (wiring diagram designation: Enable LOCAL)
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 5 M0127), the input is either High active or Low active. Default
setting is High active.
Priority REMOTE via digital input
Switching behaviour for coding High active:
●
Input Enable Local = high level (standard: +24 V DC):
Operation via local controls enabled
●
Input Enable Local = low level (0 V DC or input open):
Priority REMOTE: Operation via local controls disabled
9.5.1.Priority REMOTE: activate
Required user level:Specialist (4) or higher.
81
Page 82
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
Device configuration M0053
Application functions M0178
Activation M0212
Priority REMOTE M0770
Default value: Function not active
Setting values:
Function not active
Function active
<Priority REMOTE> function is deactivated.
<Priority REMOTE> function is activated.
9.5.2.Priority REMOTE behaviour
This function determines which selector switch functions (LOCAL, OFF) require an
additional enable signal.
Required user level:Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Priority REMOTE M0773
Default value: Sel. sw. Local
Setting values:
Sel. sw. Local
Priority of control from REMOTE is only effective in oper ation mode LOCAL (selector
switch is in position Local control). If no enab le signal is present, operation via push
buttons on the local controls is disabled, the actuator can be controlled from REMO TE
and the controls indicate the symbol in the status line of the display (menu S0001).
Sel. sw. Local + Off
Priority of control from REMOTE is effective in operation modes LOCAL and OFF
(selector switch positions Local control and 0). If no enable signal is present,
operation via push buttons on the local controls is disabled, the actuator can be
controlled from REMOTE and the controls indicate the symbol in the status line
of the display (menu S0001).
9.6.Interlock (enabling operation commands)
●
Characteristics
An operation command will only be executed if an additional enable signal for
the operation command is present.
●
Enabling may be activ ated or deactivated individually for operation commands
OPEN and CLOSE.
●
Enabling can be set for the different operation modes.
Condition
For the function <Interlock>, a digital input for the signal Enable OPEN has to be
available and configured.Enable CLOSE
Configuration of digital input
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Example
Use input DIN 5 to enable operation commands in direction CLOSE:
Parameter: Signal DIN 5 M0122
Setting value: Enable CLOSE (wiring diagram designation:Interlock CLOSE)
Information
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 5 M0127), the input is either High active or Low active. Default
setting is High active.
Default value: Function not active
Setting values:
Function not active
Function active
Function <Interlock (enable operation commands)> deactivated.
Function <Interlock (enable operation commands)> activated.
9.6.2.Failure source of Interlock enable signal: set
Customer settings M0041
Interlock M0664
Interlock source M1013
Default value: Active comm. source
Setting values:
Active comm. source
Signals for enabling operation commands are sent via the active interface. I.e.
changing the command source also changes the failure source of the enable signal.
Interface
The enable signal for the operation commands must be configured as binary signal
(default: +24 V DC) at a digital input (parameter: Enable OPEN/Enable CLOSE).
9.6.3.Operation mode for interlock
The additional enable signal can be activated for different operation modes.
Customer settings M0041
Interlock M0664
Oper. mode Interlock M0665
Default value: Off both directions
Setting values:
Interlock is off.
Off
Remote
Local
Remote and local
Interlock is active in operation modes:RemoteRemote II Fieldbus
Interlock is active in operation modes:Local, Service
Interlock is active in operation modes:Remote, Remote II, Fieldbus, Local, Service
9.6.4.Interlock behaviour (running direction)
The Interlock behaviour determines which selector switch functions (LOCAL, OFF)
require an additional enable signal.
Required user level:Specialist (4) or higher.
Customer settings M0041
Interlock M0664
Running dir. Interlock M0666
Default value: OPEN and CLOSE
83
Page 84
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
Setting values:
OPEN
CLOSE
OPEN and CLOSE
The enable signal is only required for operation commands in direction OPEN.
The enable signal is only required for operation commands in direction CLOSE.
The enable signal is required for operation commands in directions OPEN and
CLOSE.
9.7.Local Stop
●
Characteristics
The function Local Stop can be used to stop an operation from Remote locally
with the push button STOP.
●
All operation commands are interrupted.
Information
After releasing push button STOP, an oper ation command which might still be present
will become active immediately.
9.7.1.Behaviour
Required user level:Specialist (4) or higher.
Customer settings M0041
Local controls M0075
Local STOP M0627
Default value: Off
Setting values:
Push button STOP can only interrupt an operation in operation mode Local (selector
Off
switch = position Local control).
Sel.sw.Local + Remote
In the operation modes Local, Remote, Remote II, EMERGENCY and Service, push
button STOP interrupts an operation.
Information
In operation mode Disabled, an interruption is NOT possible.
9.8.EMERGENCY stop function
Conditions
An EMERGENCY stop button (latching) is either located on the electrical connection
or outside.
●
Characteristics
In an emergency, the EMERGENCY stop button can be used to interrupt the
power supply. Possibly available operation commands will be reset via self-retaining.
●
The indication in the top row of the display shows:EMCY stop
Figure 48: EMERGENCY stop button on the electrical connection
●
Information
The EMERGENCY stop button is reserved for operation in the event of an
emergency. For maintenance work, the mains supply of the actuator controls
has to be switched off and protected against accidental switching on.
●
The EMERGENCY stop push button is not availab le for e xplosion-proof versions,
but only for weatherproof versions of the actuator controls.
After having unlocked the EMERGENCY stop button, a possibly active operation
command will NOT immediately be re-activated, b ut only respective ackno wledgement
by the operator.This resets the EMERGENCY stop status.
The acknowledgement is made:
●
via the RESET push button in selector switch position Local contr ol (LOCAL).
●
via a digital input from Remote. Assignment: RESET
9.9.Partial Valve Stroke Test (PVST)
Characteristics
Requirements
Example
The Partial Valve Stroke Test (PVST) is used to check the function of both actuator
and actuator controls. During this test, the function of the valve is tested by means
of partial opening or closing within a defined period of time without interrupting the
process. After successful testing, actuator controls operate the actuator to its initial
position.
If the test was not successful, actuator controls will generate the following signals:
PVST fault PVST abort For monitoring the PVST, these signals must be evaluated
by a PLC.
●
Position transmitter in the actuator
●
Function <Positioner> activated.
●
If the actuator is in safe state (caused by the f ailure beha viour), the test will not
be performed.
●
The test can only be performed during OPEN - CLOSE control. For setpoint
control (modulating duty), a test cannot be performed.
For the change-ov er, a digital input for the signal Execute PVST has to be available
and configured.
Configuration of digital input
Required user level:Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use input DIN 5 for Execute PVST signal :
Parameter: Signal DIN 4 M0118
Setting value: Execute PVST (wiring diagram designation: ESD)
Information
The logic for the digital inputs may be in verted. Depending on the parameter setting
(e.g.Coding DIN 4 M0126), the input is either High active or Low active. For safety
reasons, the Execute PVST signal input is generally set to Low active.
Execute PVST via digital input
Switching behaviour for coding Low active:
●
Input Execute PVST = low level (0 V DC or input open)
No test
●
Input Execute PVST = high level (standard: +24 V DC):
Test is initiated
Execute PVST manually via push buttons of the local controls
Required user level:Specialist (4) or higher.
Device configuration M0053
Service functions M0222
Execute PVST M0850
The actuator is within the set stepping range.The initial position depends on the
settings of the following parameters:PVST behaviour M0853, PVST stroke M0854
85
Page 86
Actuator controls
Failure functions ACV 01.2/ACVExC 01.2
Information
9.9.1.PVST: activate
Function not active
Function active
9.9.2.PVST source: set
PVST can be aborted by sending a Reset command:
●
local (manual), in selector switch position local operation, via push button
Reset.
●
From Remote, in selector switch position Remote control via a digital input.
Assignment: RESET
Required user level:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
PVST M0851
Default value: Function not active
Setting values:
<PVST> function deactivated.
<PVST> function activated.
Customer settings M0041
PVST M0852
PVST source M1139
Default value: Active interface
Setting values:
Active interface
Signals for triggering a PVST are sent via the active interface, i.e. changing the
command source also changes the failure source of the PVST.
I/O interface
Signals for triggering a PVST must be configured as binary signals (default: +24 V
DC) at a digital input.
9.9.3.Operation mode for PVST
Required user level:Specialist (4) or higher.
Customer settings M0041
PVST M0852
PVST operation mode M0889
Default value: Stroke
Setting values:
Stroke
End position test
9.9.4.Behaviour for PVST: define
Stroke controlled PVST; operation across defined stroke (parameter PVST stroke)
within a defined time (parameter PVST monitoring). In this operation mode, the PVST
can be started in any valve position (even outside the end position).
Operating time controlled PVST; operation within a defined time (parameter PVSToperating time) after leaving an end position. In this operation mode , PVST can only
be started from one of the end positions.
The test can be performed in direction OPEN or direction CLOSE.
During stroke controlled PVST execution (par ameter PVST operation mode M0889
= Stroke), this parameter determines the partial stroke for a PVST.
Usually, the valve stroke amounts to 10 to 15 %.The amount of the partial stroke
depends on process requirements and the required diagnostic coverage rate.
The monitoring functions signal a warning or a fault as soon as a certain value is
outside the permissible range. Faults generally cause an actuator shutdown.
Torque monitoring has the following functions:
●
Valve overload protection against excessive torques (leads to switching off)
●
Torque warning before overload protection tripping (only in combination with
electronic control unit in the actuator)
Overload protection
Once the overload protection trips (torque exceeds set tripping torque), the actuator
is stopped.
The controls generate a fault indication if:
●
the excessive torque occurs between end positions
●
the excessive torque occurs in the end positions and limit seating is set.
The fault indication is shown in the display
●
Status indications: S0007 Fault or S0011 Failure
-
Details: Torque fault CLOSE or Torque fault OPEN
The fault has to be acknowledged before the operation can be resumed:
1.either by an operation command in the opposite direction.
-
For Torque fault CLOSE : Operation command in direction OPEN
-
For Torque fault OPEN : Operation command in direction CLOSE
Requirements
2.or, in case the torque applied is lower than the preset tripping torque after tripping:
-via the RESET push button in selector switch position Local control
(LOCAL).
Depending on the version, tripping torques for overload protection are either set via
switches in the actuator or via software parameters in the controls . For the settings,
refer to <Torque switching> chapter.
Torque warning
Actuator with electronic control unit (MWG).
The torque warning can be used e.g. for self-monitoring or for anticipating
maintenance requirements.
Customer settings M0041
Torque switching M0013
Wrn torque CLOSE M0769
Wrn torque OPEN M0768
Default value: 80 %
Setting range: 20 ... 100 % of the set nominal torque
When exceeding the set limit values, the actuator is not stopped, however, the
controls generate a warning signal:
●
Status indications: S0005Warnings or S0008Out of specification
-
Details: Torque wrn CLOSE or Torque wrn OPEN
10.1.1.Torque by-pass
By means of the torque by-pass, the torque monitoring is deactivated for a defined
(short) time. During this interval, the full actuator torque may be used, for example,
to release the actuator from a jammed end position or any other jammed position.
89
Page 90
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2
Valve damage due to excessive torque!
→
Only apply torque by-pass with the consent of the valve manufacturer.
Torque by-pass: activate
Customer settings M0041
Torque switching M0013
Torque by-pass M0092
Default value:Function not active
Setting values:
Function active
Function not active
The torque by-pass is activated.
The torque by-pass is deactivated.
Time interval for torque by-pass
During the time interval set here, the torque monitoring is deactivated.
Customer settings M0041
Torque switching M0013
Torque by-pass [s] M0205
Default value: 0.0 s
Setting range: 0.0 ... 5.0 s seconds
Information
10.1.2.Torque limitation of torque by-pass
Condition
If torque by-pass is activated, the interval should be longer than the set time period
for reversing prevention time to ensure torque by-pass will also be effective in the
event of reversal of operation.
For activated torque by-pass, the torque monitoring (parameter Torqueby-pass M0092) is deactivated for a defined (short) time. By activating the torque
limitation, torque monitoring will be activated again, but not in relation to the set
tripping torque, howev er not in relation to a torque peak which can be set separately
by menas of this function.
Electronic control unit with MWG in the actuator (non-intrusive version)
Activate torque limitation
Customer settings M0041
Torque switching M0013
Torque limitation M1805
Default value:Function not active
Setting values:
Function active
Function not active
The torque limitation of the torque by-pass is activated.
The actuator will be stopped during the by-pass interval and a torque fault will be
generated once the permitted torque peak has been exceeded.
The torque limitation of the torque by-pass is deactivated.
There is no torque monitoring. During the by-pass interval, no torque fault will be
In order to protect against overheating and impermissibly high temperatures at the
actuator, PTC thermistors or thermoswitches are embedded in the motor winding.
The thermoswitch is tripped as soon as the max. permissible winding temperature
has been reached.
The actuator is switched off and the following signals are given:
●
LED 3 (motor protection trippped) on the local controls is illuminated.
●
Status indication: S0007Fault or S0011 Failure
-
Details: Thermal fault
The motor has to cool down before the operation can be resumed.
Depending on the parameter setting (motor protection behaviour), the fault signal is
either automatically reset or the fault signal has to be acknowledged manually.
Manual acknowledgement can be made:
●
in selector switch position Local control (LOCAL) via push button RESET.
●
in selector switch position Remote control (REMO TE) via a digital (I/O interface)
with the RESET command if a digital input is configured for RESET signal.
In addition, the actuator controls cyclically (once per day) check the motor protection
monitoring for its proper function. If this check fails, the controls generate the fault
indication: IE mot. prot. monitor
Motor protection behaviour
Required user level:AUMA (6).
Device configuration M0053
Actuator M0168
Motor prot. mode M0169
Default values:
Non-explosion-proof actuators = Auto
Explosion-proof actuators = Reset
Setting values:
Auto
Reset
10.3.Type of duty monitoring (motor starts and running time)
Automatic reset after the motor has cooled down.
Not possible for explosion-proof version.
Manual reset.
Once the motor has cooled down, the fault has to be ackno wledged (reset) manually
as described above.
If required the thermal overload relay has to be reset manually.To this end, remove
the cover on the back of actuator controls and oper ate the reset button on the thermal
overload relay.
This function monitors the permissible type of duty (e.g. S2 - 15 min) of the actuator .
For this, controls monitor possible excess of
●
permissible motor starts (cycles) per hour
●
permissible running time (on-time) per hour
If any of these values has been e xceeded, the actuator will howe v er not be stopped,
but the following warning signals are issued.
●
Status indications: S0005 or S0008
-
Details: Wrn op.mode starts
91
Page 92
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2
●
Status indications: S0005 or S0008
-
Details: Wrn op.mode run time
The warning signals will automatically be cleared if the permissible motor starts per
second or the permissible running time per hour are no longer reached.
The operational info logger records the number of excesses (warnings) as well as
the number of motor starts and motor running times.
Asset Management M1231
Operational info M0177
Operational info M0188
On time warning 1 M0325 contains total number of all on time warnings.
On time warning 2 M0326 contains maximum duration of on time warning
Example:
Due to excess of defined starts/h or defined running time/h, the AC issues in total 4
on time warnings: two for 5 min, once for 10 min, once for 17 min. Afterwards the
operating data counters contain the following values:
On time warning 1 M0325 = 37 min = total of all periods (5+5+10+17 min)
On time warning 2 M0326 = 17 min = longest period
Figure 49: Example
Function not active
Function active
[1]Running time/h
[2]Starts/h
[3]On time warning
Activate on time monitoring
Required user level:Specialist (4) or higher.
Customer settings M0041
Duty type monitoring M0355
Duty type monitoring M0358
Default value: Function not active
Setting values:
Function <On-time monitoring> deactivated.
Function <On-time monitoring> activated.
This function allows the monitoring of the operating time of the actuator. If the actuator
needs longer than the set time to move from end position OPEN to end position
CLOSED, a warning is signalled (the actuator is not stopped):
●
Status indication S0005Warnings
-
Details: Op. time warning
The warning indication is automatically cleared once a new operation command is
executed.
When the actuator moves from an intermediate position to an end position, the set
monitoring time for the whole stroke is assigned in relation to the remaining
stroke/travel.
Operation mode: activate
Required access level:Specialist (4) or higher.
Customer settings M0041
Oper. time monitoring M0568
Operation mode M0569
Default value: Off
Setting values:
The operating time monitoring is switched off
Off
Manual
The operating time monitoring is switched on.The permissible operation time is set
via parameter Perm.op. time, manual M0570.
Operating times can be displayed via Asset Management. Ref er to <Display operating
times>
10.5.Reaction monitoring
The actuator controls monitor whether the actuator moves after receiving an operation
command.
If no reaction is recorded at the output drive of the actuator within a set time, either
a warning or a fault signal is generated depending on the setting:
●
●
In the event of a fault signal, the fault has to be acknowledged to be able to resume
the operation.The acknowledgement is made:
●
●
In case of operation from an intermediate position, reaction monitoring will only be
performed if the actuator is equipped with a position feedback.
Oper. time monitoring M0568
Perm.op. time, manual M0570
Status indications: S0005Warnings or S0008Out of specification
-
Details: Wrn no reaction
Status indications: S0007Fault or S0011Failure
-
Details: Fault no reaction
in selector switch position Local control (LOCAL) via push button RESET.
in selector switch position Remote control (REMO TE) via a digital (I/O interface)
with the RESET command if a digital input is configured for RESET signal.
93
Page 94
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2
Activate switching off for reaction time error
Required user level:Specialist (4) or higher.
Customer settings M0041
Reaction monitoring M0632
Actuator behaviour M0633
Default value: No cut-off
Setting values:
No cut-off
Cut-off
The reaction monitoring only issues a warning.
The reaction monitoring issues a fault signal, the actuator is stopped.
Set reaction time
Customer settings M0041
Reaction monitoring M0632
Reaction time M0634
Default value: 15.0 s
Setting range: 15.0 ... 300.0 seconds (0 seconds up to 5 minutes)
10.6.Motion detector
Requirements
Characteristics
Information
10.6.1.Motion detector: activate
Position transmitter in the actuator.
The motion detector checks whether the actuator moves even without operation
command (e.g. in manual operation or if there is no self-retaining).
Controls identify motion if the actuator moves more than the pre-set tra vel diff erence
within the predefined recording time. Controls signal: Output drive rotates
Parameters for motion detection have a direct impact on reaction monitoring.
Required user level:Specialist (4) or higher.
Customer settings M0041
Motion detector M0676
Motion detector M0675
Default value: Function active
Setting values:
Function not active
Function active
10.6.2.Detection time dt
Monitoring is deactivated.
Monitoring is activated.
Required user level:Specialist (4) or higher.
Customer settings M0041
Motion detector M0676
Detect. time dt M0677
Detect. time dt (MWG) M0681
Default values:
Detect. time dt (for potentiometer/EWG/RWG within actuator) = 00:05.0 min:s ( 5
seconds)
Detect. time dt (MWG) (for MWG within actuator) = 00:00.5 min:s (0.5 seconds)
Setting ranges:
Detect. time dt = 00:01.0 ... 30:00.0 min:s (minutes:seconds)
Detect. time dt (MWG) = 00:00.1 ... 00:02.0 min:s (minutes:seconds)
Electronic control unit within the actuator (non-intrusive version).
The actuator controls monitor vibration by means of an acceleration sensor at the
MWG.
If certain limits are exceeded or fallen short of, the actuator controls either send a
warning or a fault signal.
Parameters for setting limit values
Required user level:Specialist (4).
Device configuration M0053
Monitoring functions M0645
Vibration alarm level M1657
Vibration alarm time M1658
Vibration alarm level M1657
Limit value (at sensor) for triggering the acceleration alarm (warning).
Default value:1.000 g
Setting range: 0.5000 ... 4.000 g
Information
Vibration alarm time M1658
Interval during which the vibration limit must be exceeded until the vibration alarm
is triggered (fault signal).
Default value:0.1 s (seconds)
Setting range: 0.1 ... 10.0 s
The acceleration values of oscillation/vibration measurement can either be displa yed
or sent to an analogue output. Refer to <Oscillation/vibration indication>.
95
Page 96
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2
10.8.Monitoring of electronics power supply
AC actuator controls monitor the following voltages and signals a warning (refer to
<Fault signals and warnings> chapter):
●
Auxiliary voltage 24 V DC, e.g for supplying the control inputs
●
Voltage 24 V AC for controlling the reversing contactors, for thermoswitches
and heater within the actuator and for generating the 115 V AC auxiliary voltage
for the customer (option)
●
Internal 24 V DC power supply of the electronics components (within the controls
and in the actuator)
●
External 24 V DC supply of the electronics (option)
Activate monitoring of auxiliary voltage 24 V DC
Required user level:Specialist (4).
Device configuration .
Monitoring functions M0645
Monitor 24 V DC cust. M0650
Default value: Function not active
Setting values:
Function not active
Monitoring is deactivated.
Monitoring is activated. Should the auxiliary voltage 24 V DC f or supplying the control
On
inputs fail, a warning will be issued.
Activate monitoring of external supply 24 V DC
Required user level:Specialist (4).
Device configuration M0053
Monitoring functions M0645
Monitor 24 V DC ext. M0649
Default value: Function not active
Setting values:
Function not active
10.9.Temperature monitoring
Characteristics
Conditions:
Information
Monitoring is deactivated.
Monitoring is activated. Should the external supply 24 V DC fail, a warning will be
On
issued.
If the respective sensors are installed in the devices, the actuator controls monitor
different temperatures.
If certain temperature limits are exceeded or fallen short of, the controls either send
a warning or a fault signal.
●
for temperature within the control unit of the actuator: MWG (magnetic limit and
torque transmitter)
●
For motor temperature: additionally temperature sensor (PT 100) in the motor
●
For gear housing temperature: additionally temperature sensor (PT 100) in the
gearing
Current device temperatures can also be displayed. Refer to <Display device temperatures>.
10.10.Heater system/heater monitoring
The heater system within the actuator controls housing and the heater on the control
unit (within the switch compartment of the actuator) can be monitored. If the monitoring
is activated the follo wing warning will be generated if the heater system or the heater
(circuit = interrupted) fails:
In the display of the local controls, status indication S0005Warnings
-
Details: Internal warningWrn heater
For further information on the heater system and the heater refer to separate <Heater
system and heater> chapter.
Activate heater system monitoring
Heater system monitoring monitors all connected heaters for failure.
Required user level:Specialist (4).
Device configuration M0053
Monitoring functions M00645
Monitor heat. system M0647
Default value: Function not active
Setting values:
Function not active
Function active
Heater monitoring is deactivated.
Heater monitoring is activated.
Activate heater control unit monitoring
Information
Function not active
Function active
Information
If a heater system is installed within the actuator controls, heater monitoring is not
activated/deactivated via this parameter, but via Monitor heat. system M0647 parameter of the heater system.
Required user level:Specialist (4).
Device configuration M0053
Actuator M0168
Heater monitor M0646
Default value: Function not active
Setting values:
Heater monitoring is deactivated.
Heater monitoring is activated. If the heater fails, a warning will be issued.
Monitoring can only be made once the heater is activated (parameter Heater controlunit).
Set reaction time for heater monitoring
Heater monitoring will only respond once a fault persists longer than the set monitoring
time. Short-time faults occurring for less than the set monitoring time are not signalled
as warning.
The controls verify whether sub-assemblies mounted in actuators and controls
correspond to the desired version.
In case incorrect sub-assemblies are mounted or if sub-assemblies are missing the
controls either send a warning or a fault signal.
For detailed information on this indication refer to <Fault signals and warnings>
chapter.
97
Page 98
Actuator controls
Monitoring functions ACV 01.2/ACVExC 01.2
10.12.Phase failure monitoring
Conditions:
Characteristics
Information
Information
Phase failure monitoring is only valid f or connections to 3-phase AC po wer supplies.
For versions with 1-phase AC or DC, phase failure monitoring is not possible.
The actuator controls monitor phase L2 If phase L2 is missing for a certain time
interval, the actuator controls still can send and receive signals and generate a fault
indication. Since the actuator controls are supplied via phases L1 and L3, the two
phases cannot be monitored. In case L1 or L3 fails, the actuator controls are
inoperable and the actuator stops.
In case of phase L2 loss during motor operation, this does not necessarily lead to
an immediate standstill of the actuator.The reason is that the rotating motor generates
the missing phase itself.This leads, however, to a reduction of the motor output
torque. If the applied torque is sufficient for valve operation, the missing phase L2
is only detected when switching off (e.g. in an end position) and the Phase fault fault
signal is generated as a consequence.
Configuration of tripping time
Required user level:Specialist (4) or higher.
Device configuration M0053
Phase monitoring M0170
Tripping time M0172
Default value: 10.0 s
Setting range: 1.0 – 300.0 s
Faults in supply v oltage (e.g. voltage drops) do not generate a fault signal during the
adjustable tripping time.
98
Page 99
Actuator controls
ACV 01.2/ACVExC 01.2 Functions: activate and enable
11.Functions: activate and enable
11.1.Activate functions
Via menu Activation M0212, functions can be switched on (activated) or off
(deactivated).
Required user level for enabling/disabling:Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Information
Some functions require enabling. Only enabled functions are visible and can be activated or deactivated.
Enabling requiredMenuFunction
M0156Timer CLOSE
M0206Timer OPEN
M0158Positioner
M0294Operation profile
M0741Process controller
M0573Bluetooth
M0631Enable LOCAL
M0770Priority REMOTE
M0790Auto change-over I/O
M0663Interlock
M0851PVST
M0941By-pass function
M1136Maintenance signals
M1137Maintenance interval
M1197Limit switch. via CDT
M1650Split range operation
M1679Automatic deblocking
M1789Synchronous link
M1709Com. eval. REMOTE
No
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
Yes
No
11.2.Enable functions
Information
Via menu Enabling M0179, optional functions can be enabled or disabled.
This menu is visible in the display from user level Specialist (4).
In user level Specialist (4), an additional activation password (depending on the
serial number) is required for enabling the function.The activation password can
only be assigned and generated by the AUMA service.
99
Page 100
Actuator controls
Service functions ACV 01.2/ACVExC 01.2
12.Service functions
The functions described here may only be changed by the AUMA service or by
authorised and trained personnel.
Menu item Service functions is only visible, if user level Specialist (4) or higher is
selected.
12.1.Direction of rotation
Characteristics
Information
This function allows changing the direction of rotation for actuator with 3-phase AC
motors.
The direction of rotation indicates the direction into which the drive shaft rotates
around its own axis.The view is on the top of the actuator. Distinction is made
between clockwise and counterclockwise rotation.
●
When changing from clockwise closing to counterclockwise closing or vice
versa, only the direction of rotation of the motor is changed.The change-over
requires further action:
-The wiring diagram designation is marked on the actuator controls name
plate. In case of a change, a ne w name plate with the ne w wiring diagram
number has to be requested from AUMA.
-The wiring diagram number is stored in the electronic device ID (parameter
Wiring diagram actuator M0060).The ID has to be adapted to the new
designation once conversion is complete.
-The actuator mounted to the controls must be configured for the set direction of rotation. Subsequent con version from cloc kwise closing to counterclockwise closing is possible using an AUMA conversion kit.
Parameters and instructions for setting
Setting the direction of rotation using parameters is only possible for actuators with
electronic control unit/MWG (Non-intrusive version).
Valve damage due to incorrect direction of rotation!
→
For 3-phase AC motors, the rotation direction of the actuator must match the
rotation direction of the valve.
Clockwise rotation
Counterclockwise rot.
12.2.Factory setting
Required user level:AUMA (6).
Device configuration M0053
Actuator M0168
Closing rotation M0176
Default value: Clockwise rotation
Setting values:
The motor is controlled with a clockwise rotating field with the following sequence:
L1-U1, L2-U2, L3-U3 (clockwise closing).
The motor is controlled with a counterclockwise rotating field with the following
sequence: L1-U3, L2-U2, L3-U1 (counterclockwise closing).
The factory setting corresponds to the delivery state of the actuator controls.
When converting the controls e.g. by the AUMA service, a new factory setting can
be generated to adapt the modified configuration.
Former factory settings can be restored.
Generate new factory setting
Required user level:Service (5) or higher.
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.