AudioCodes Mediant 800B, Mediant 800C, Mediant 800, Mediant 800A Hardware Installation Manual

Page 1
Hardware Installation Manual
AudioCodes Mediant™ Family of Media Gateways & Session Border Controllers (SBC)
Mediant 800 Media Gateway & Enterprise SBC (E-SBC)
Page 2
Page 3
Table of Contents
1 Introduction ....................................................................................................... 11
2 Unpacking the Device ...................................................................................... 13
3 Physical Description ........................................................................................ 15
3.1 Physical Dimensions and Operating Environment ................................................. 15
3.2 Front Panel Description .......................................................................................... 16
3.2.1 Ports and Buttons.................................................................................................... 16
3.2.2 LEDs Description .................................................................................................... 18
3.2.2.1 LAN Interface LEDs ................................................................................. 18
3.2.2.2 FXS LEDs ................................................................................................ 18
3.2.2.3 FXO LEDs ................................................................................................ 19
3.2.2.4 BRI LEDs ................................................................................................. 19
3.2.2.5 E1/T1 (PRI) LEDs .................................................................................... 20
3.2.2.6 STATUS LED ........................................................................................... 20
3.2.2.7 Power LEDs ............................................................................................. 21
3.3 Rear Panel Description .......................................................................................... 22
4 Mounting the Device ........................................................................................ 25
4.1 Desktop Mounting .................................................................................................. 25
4.2 Wall Mounting ......................................................................................................... 26
4.3 19-Inch Rack Mounting .......................................................................................... 28
4.3.1 Using a Pre-Installed Rack Shelf ............................................................................ 28
4.3.2 Using Mounting Brackets ........................................................................................ 29
5 Cabling the Device ........................................................................................... 31
5.1 Grounding and Surge Protection ............................................................................ 31
5.2 Connecting to LAN ................................................................................................. 33
5.3 Connecting to Analog Devices ............................................................................... 35
5.3.1 Connecting the FXS Interfaces ............................................................................... 35
5.3.2 Connecting the FXO Interfaces ............................................................................... 36
5.3.3 Connecting the FXS Analog Lifeline ....................................................................... 38
5.4 ISDN BRI Interfaces ............................................................................................... 39
5.4.1 Connecting to BRI Lines ......................................................................................... 39
5.4.2 Connecting PSTN Fallback for BRI Lines ............................................................... 40
5.5 Connecting ISDN E1/T1 Interfaces ........................................................................ 42
5.5.1 Connecting to ISDN PRI (E1/T1) Trunks ................................................................ 42
5.5.2 Connecting PSTN Fallback for E1/T1 Trunks ......................................................... 43
5.6 Connecting to a Computer for Serial Communication ............................................ 45
5.7 Connecting the OSN Server ................................................................................... 46
5.9 Connecting to Power .............................................................................................. 48
5.9.1 Connecting to AC Power ......................................................................................... 48
5.9.2 Connecting to DC Power ........................................................................................ 49
6 Maintenance – Replacing the Power Fuse ..................................................... 53
Page 4
Hardware Installation Manual 4 Document #: LTRT-10689
Mediant 800
List of Figures
Figure 3-1: Mediant 800B Front Panel................................................................................................... 16
Figure 3-2: Mediant 800C Front Panel .................................................................................................. 16
Figure 3-3: Mediant 800B Rear Panel ................................................................................................... 22
Figure 3-4: Mediant 800C Rear Panel ................................................................................................... 22
Figure 4-1: Rubber Foot Attached to Underside of Device.................................................................... 25
Figure 4-2: Attaching the Mounting Brackets to Chassis ....................................................................... 26
Figure 4-3: Attaching the Chassis with Mounting Brackets to Wall ....................................................... 27
Figure 4-4: Mounting Brackets ............................................................................................................... 29
Figure 4-5: Attaching the Mounting Brackets ........................................................................................ 29
Figure 5-1: Grounding the Device .......................................................................................................... 32
Figure 5-2: LAN Port-Pair Groups and Web Interface String Names .................................................... 33
Figure 5-3: Connecting the LAN Ports ................................................................................................... 34
Figure 5-4: RJ-11 Connector Pinouts for FXS Interface ........................................................................ 35
Figure 5-5: Connecting FXS Interfaces ................................................................................................. 36
Figure 5-6: RJ-11 Connector Pinouts for FXO Interface ....................................................................... 37
Figure 5-7: Connecting FXO Interfaces ................................................................................................. 37
Figure 5-8: RJ-11 Connector Pinouts for FXS Lifeline .......................................................................... 38
Figure 5-9: Cabling FXS Lifeline ............................................................................................................ 38
Figure 5-10: RJ-45 Connector Pinouts for BRI Ports ............................................................................ 39
Figure 5-11: Cabling BRI Ports .............................................................................................................. 40
Figure 5-12: RJ-45 Connector Pinouts for BRI PSTN Fallback ............................................................. 40
Figure 5-13: Cabling (Ports 1 and 2) PSTN Fallback ............................................................................ 41
Figure 5-14: RJ-48c Connector Pinouts for E1/T1 ................................................................................ 42
Figure 5-15: Cabling E1/T1 Ports .......................................................................................................... 42
Figure 5-16: RJ-48c Connector Pinouts for E1/T1 PSTN Fallback ....................................................... 43
Figure 5-17: Cabling PRI Ports for PSTN Fallback ............................................................................... 44
Figure 5-18: Cabling Serial Interface ..................................................................................................... 45
Figure 5-19: Cabling OSN Server Ports ................................................................................................ 47
Figure 5-20: Connecting to the Power Supply ....................................................................................... 49
Figure 5-21: Connecting DC Power Plug to DC Inlet ............................................................................ 50
Figure 5-22: Plugging AC Power Cord into AC/DC Adaptor ................................................................. 51
Figure 6-1: Opening the Fuse Cavity ..................................................................................................... 53
Figure 6-2: Removed Power Fuse ......................................................................................................... 54
Page 5
List of Tables
Table 3-1: Physical Dimensions and Operating Environment ............................................................... 15
Table 3-2: Front Panel Description ........................................................................................................ 16
Table 3-3: LAN LEDs Description .......................................................................................................... 18
Table 3-4: FXS LEDs Description .......................................................................................................... 18
Table 3-5: FXO LEDs Description ......................................................................................................... 19
Table 3-6: BRI LEDs Description ........................................................................................................... 19
Table 3-7: E1/T1 LEDs Description ....................................................................................................... 20
Table 3-8: STATUS LED Description .................................................................................................... 20
Table 3-9: POWER LED Description ..................................................................................................... 21
Table 3-10: AC PWR LED Description .................................................................................................. 21
Table 3-11: DC PWR LED Description .................................................................................................. 21
Table 3-12: Rear Panel Description ....................................................................................................... 22
Table 5-1: RJ-45 Connector Pinouts for GbE/FE .................................................................................. 33
Table 5-2: OSN Server Platforms .......................................................................................................... 46
Table 5-3: AC Power Specifications ...................................................................................................... 48
Table 5-4: DC Power Specifications ...................................................................................................... 49
Table 6-1: Allowed Fuses for the Device ............................................................................................... 53
Page 6
Hardware Installation Manual 6 Document #: LTRT-10689
Mediant 800
This page is intentionally left blank.
Page 7
Notice
Information contained in this document is believed to be accurate and reliable at the time of printing. However, due to ongoing product improvements and revisions, AudioCodes cannot guarantee accuracy of printed material after the Date Published nor can it accept responsibility for errors or omissions. Updates to this document can be downloaded from
https://www.audiocodes.com/library/technical-documents.
This document is subject to change without notice.
Date Published: January-30-2019
WEEE EU Directive
Pursuant to the WEEE EU Directive, electronic and electrical waste must not be disposed of with unsorted waste. Please contact your local recycling authority for disposal of this product.
Customer Support
Customer technical support and services are provided by AudioCodes or by an authorized AudioCodes Service Partner. For more information on how to buy technical support for AudioCodes products and for contact information, please visit our website at
https://www.audiocodes.com/services-support/maintenance-and-support.
Stay in the Loop with AudioCodes
Abbreviations and Terminology
Each abbreviation, unless widely used, is spelled out in full when first used. Throughout this manual, unless otherwise specified, the term device refers to Mediant 800
Gateway and E-SBC.
Related Documentation
Document Name
SIP Release Notes
Mediant 800 Gateway and E-SBC User's Manual
CLI Reference Guide
Page 8
Hardware Installation Manual 8 Document #: LTRT-10689
Mediant 800
Notes and Warnings
Warning: Read and adhere to all warning statements in this document before installing
the device.
Warning: The device is an INDOOR unit and therefore, must be installed only indoors.
In addition, FXS and Ethernet port interface cabling must be routed only indoors and must not exit the building.
Note: Open source software may have been added and/or amended for this product.
For further information, please visit our website at
https://www.audiocodes.com/services-support/open-source/
or contact your
AudioCodes sales representative.
Caution Electrical Shock
Do not open or disassemble this device. The device carries high voltage and contact with internal components may expose you to electrical shock and bodily harm.
Warning: The device must be installed and serviced only by qualified service personnel.
Warning: The device must be installed ONLY in restricted access locations that are
compliant with ETS 300 253 guidelines where equipotential bonding has been implemented.
Warning: Disconnect the device from the mains and Telephone Network Voltage (TNV)
before servicing.
Document Revision Record
LTRT Description
10259 FXO warning statement.
10260 Power amperage updated.
10261 E1 cabling warning statement regarding STP.
10262 Max. power consumption.
10263 Power surge warnings; AC input current.
10265 Miscellaneous formatting.
10266 E1/T1 PSTN fallback added.
Page 9
LTRT Description
10267 AC power cable warning (Japanese).
10680 BRI cabling warning; LED label for console port; Status LED state typo.
10681 Download URL for CentOS driver
10682 Typo fixed re 19-inch rack mounting brackets.
10683 Logo updated; fallback updated.
10684 Lifeline splitter cable – not supplied
10685
Wall mounting added; Mediant 800C added; Mediant 800A removed; logos updated; CENTOS removed
10687
Power fuse updated; AC power rating updated; warnings added for grounding; cable type for LAN updated
10688 PRI PSTN fallback hardware note updated; OSN driver download note removed
10689 Logo updated on front panel.
Page 10
Mediant 800
Documentation Feedback
AudioCodes continually strives to produce high quality documentation. If you have any comments (suggestions or errors) regarding this document, please fill out the Documentation Feedback form on our website at https://online.audiocodes.com/documentation-feedback.
Page 11
Hardware Installation Manual 1. Introduction
1 Introduction
This document provides a hardware description of the Mediant 800 Gateway and E-SBC (hereafter referred to as device) and step-by-step procedures for mounting and cabling the device.
The device supports the following interfaces (customer ordered):
E1/T1 (PRI):
Mediant 800B: Up to 2 E1/T1 port interfaces (over single copper wire pair).
Mediant 800C: Up to 4 E1/T1 port interfaces
Up to 8 BRI ports (supporting up to 16 voice channels).
Up to 12 FXS port interfaces.
Up to 12 FXO port interfaces.
12 LAN Ethernet interfaces - up to 4 Gigabit Ethernet ports and up to 8 Fast Ethernet
ports. These ports operate in port-pair redundancy, providing up to 6 port-pair groups.
Open Solutions Network (OSN) server platform for hosting third-party applications
such as an IP PBX.
Power:
Mediant 800B: Single AC power inlet
Mediant 800C: Single AC power inlet, and a DC power inlet (optional, customer
ordered)
Notes:
Mediant 800 includes two hardware revisions which differ as follows:
Mediant 800B: Max. 2 E1/T1; AC power only Mediant 800C: Max. 4 E1/T1; AC and DC power (optional)
Hardware configurations may change without notice. Currently available hardware
configurations are listed in AudioCodes Price Book. For available hardware configurations, contact your AudioCodes sales representative.
The Fast Ethernet ports are available only on "pure" SBC Mediant 800 (i.e., without
PSTN / Gateway interfaces).
For software configuration, refer to the User's Manual.
Page 12
Mediant 800
This page is intentionally left blank.
Page 13
Hardware Installation Manual 2. Unpacking the Device
2 Unpacking the Device
Follow the procedure below for unpacking the carton in which the device is shipped.
To unpack the device:
1. Open the carton and remove packing materials.
2. Remove the chassis from the carton.
3. Check that there is no equipment damage.
4. Ensure that in addition to the chassis, the package contains the following items:
Four anti-slide bumpers for desktop installation
Two mounting brackets for 19-inch rack mounting
One AC power cord
(Mediant 800C only) one AC/DC power adaptor (optional, separate orderable
item)
5. Check, retain and process any documents.
If there are any damaged or missing items, notify your AudioCodes sales representative.
Page 14
Mediant 800
This page is intentionally left blank.
Page 15
3 Physical Description
This section provides a physical description of the device.
3.1 Physical Dimensions and Operating Environment
The device's physical dimensions and operating environment are listed in the table below:
Table 3-1: Physical Dimensions and Operating Environment
Physical Specification Description
Dimensions (H x W x D) 1U x 32 x 34.5 cm (12.6 x 13.6 inches)
Weight 2.5 kg (5.5 lbs.)
Environmental
Operational: 5 to 40°C (41 to 104°F) Storage: -25 to 85°C (-13 to 185°F) Humidity: 10 to 90% non-condensing
Page 16
Mediant 800
3.2 Front Panel Description
The front panel provides the telephony port interfaces, various networking ports, reset pinhole button, and LEDs.
3.2.1 Ports and Buttons
The device's front panel is shown in the figure below and described in the subsequent table.
Figure 3-1: Mediant 800B Front Panel
Figure 3-2: Mediant 800C Front Panel
Note: The figures above are used only as an example. The number and type of port
interfaces depends on the ordered model.
Table 3-2: Front Panel Description
Item # Label Description
1 Mediant 800B:
POWER /
STATUS
Mediant 800C:
AC PWR / DC
PWR / STATUS
Power and operating status LEDs. For more information, see Section
3.2.2 on page 18.
Page 17
Item # Label Description
2 FXS / FXO / BRI
/ PRI
Telephony port interfaces that can include one or a combination of the following, depending on the ordered model:
FXS port interfaces (RJ-11)
FXO port interfaces (RJ-11)
ISDN BRI port interfaces (RJ-45)
ISDN PRI (E1/T1) port interfaces (RJ-48)
Notes:
The FXS/FXO interfaces support loop-start signalling (indoor only).
For supported hardware configuration options, refer to the Release
Notes.
3 GE Up to four 10/100/1000Base-T (Gigabit Ethernet) LAN ports for
connecting IP phones, computers, or switches. These ports support the following features:
1+1 LAN port redundancy: These ports are grouped in pairs,
where one port is active and the other redundant. When a failure occurs in the active port, a switchover is done to the redundant port.
Half- and full-duplex modes Auto-negotiation
Straight or crossover cable detection
4 FE
Eight Fast Ethernet (10/100Base-TX) RJ-45 LAN ports for connecting IP phones, computers, or switches. The supported port features are the same as the GE ports (see Item #6 above).
Note: The Fast Ethernet ports are available only on "pure" SBC Mediant 800 (i.e., without PSTN / Gateway interfaces).
5 // Reset pinhole button for resetting the device and optionally, for
restoring the device factory defaults. To restore the device to factory defaults, do the following: With a paper clip or any other similar pointed object, press and hold down the Reset pinhole button for at least 12 seconds, but no more than 25 seconds.
6 CONSOLE RS-232 port (RJ-45) for serial communication.
7 USB/WWAN Two USB ports, used for various functionalities such as saving debug
captures to a USB storage device.
Page 18
Mediant 800
3.2.2 LEDs Description
The front panel provides various LEDs depending on the device's hardware configuration (e.g., the available telephony interfaces). These LEDs are described in the subsequent subsections.
3.2.2.1 LAN Interface LEDs
Each LAN port provides a LED (located on its left) for indicating LAN operating status, as described in the table below.
Table 3-3: LAN LEDs Description
LED
Color
LED
State
Description
Green On Ethernet link established.
Flashing Data is being received or transmitted.
- Off No Ethernet link.
3.2.2.2 FXS LEDs
Each FXS port provides a LED for indicating operating status, as described in the table below.
Table 3-4: FXS LEDs Description
LED
Color
LED
State
Description
Green On Phone is off-hooked.
Flashing Rings the extension line.
Red On
Error - malfunction in line or out of service due to Serial
Peripheral Interface (SPI) failure.
Disabled port initiated by user (using the CLI command,
analog-port-enable
)
- Off Phone is on hook.
- Off No power received by the device.
Page 19
3.2.2.3 FXO LEDs
Each FXO port provides a LED for indicating operating status, as described in the table below.
Table 3-5: FXO LEDs Description
LED
Color
LED
State
Description
Green On FXO line is off-hooked toward the PBX.
Flashing Ring signal detected from the PBX.
Red On
Error - malfunction in line or out of service due to Serial
Peripheral Interface (SPI) failure.
Disabled port initiated by user (using the CLI command,
analog-port-enable
)
- Off Line is on hook.
- Off No power received by the device.
3.2.2.4 BRI LEDs
Each BRI port provides a LED for indicating operating status, as described in the table below:
Table 3-6: BRI LEDs Description
Color State Description
Green On Physical layer (Layer 1) is synchronized (normal operation).
Red On Physical layer (Layer 1) is not synchronized.
- Off
Trunk is not active.
Page 20
Mediant 800
3.2.2.5 E1/T1 (PRI) LEDs
Each trunk port provides a LED for indicating operating status, as described in the table below:
Table 3-7: E1/T1 LEDs Description
Color State Description
Green On Trunk is synchronized (normal operation).
Red On Loss due to any of the following signals:
LOS - Loss of Signal LOF - Loss of Frame AIS - Alarm Indication Signal (the Blue Alarm) RAI - Remote Alarm Indication (the Yellow Alarm)
- Off Failure / disruption in the AC power supply or the power is currently not being supplied to the device through the AC power supply entry.
3.2.2.6 STATUS LED
The STATUS LED indicates the operating status, as described in the table below.
Table 3-8: STATUS LED Description
LED Color LED State Description
Green On
The device is operational and in Standalone mode (not in High-Availability mode).
Fast
Flashing
Initial rebooting stage. Software upgrade (.cmp file) in process (supported only
from Software Version 7.2).
Slow Flash HA mode - LED on Active device.
Slow-Fast
Flash
HA mode - LED on Redundant device.
Red On Boot failure.
Off Advanced rebooting stage.
Page 21
3.2.2.7 Power LEDs
The power LEDs depend on the Mediant 800 model.
3.2.2.7.1 Power LED
The POWER LED indicates the power supply status, as described in the table below.
Table 3-9: POWER LED Description
LED
Color
LED
State
Description
Green On Power is received by the device.
- Off No power received by the device.
Note: The POWER LED is applicable only to Mediant 800B.
3.2.2.7.2 AC PWR LED
The AC PWR LED indicates the AC power supply status, as described in the table below.
Table 3-10: AC PWR LED Description
Color State Description
Green On AC power is received by the device.
- Off No power received by the device.
Note: The AC PWR LED is applicable only to Mediant 800C.
3.2.2.7.3 DC PWR LED
The DC PWR LED indicates the DC power supply status, as described in the table below.
Table 3-11: DC PWR LED Description
Color State Description
Green On DC power is received by the device.
- Off No power received by the device.
Note: The DC PWR LED is applicable only to Mediant 800C.
Page 22
Mediant 800
3.3 Rear Panel Description
The device's rear panel is shown in the figure below and described in the subsequent table.
Figure 3-3: Mediant 800B Rear Panel
Figure 3-4: Mediant 800C Rear Panel
Note: The figures above are used only as an example. The Open Network Solution
(OSN) server ports are a customer ordered item and depend on the ordered OSN server platform.
Table 3-12: Rear Panel Description
Item # Label Description
1 OSN USB Three USB ports (Standard-A type) for connecting computer
peripherals (e.g., mouse and keyboard). These are used when implementing the OSN.
Note: These ports are available only if the device is equipped with the OSN server (customer ordered).
2 OSN VGA 15-Pin DB-type female VGA port for connecting to a monitor
(screen). This port is used when implementing the OSN. Note: This port is available only if the device is equipped with the
OSN server (customer ordered).
3 - Reset button for resetting the OSN server.
4 GE 1
GE 2
10/100/1000Base-T Ethernet ports (RJ-45) for connecting directly to the OSN server. For example, one port can be connected to the LAN (to IP Phones) and the second port to the WAN interface (to an IP PBX).
Note: the number of ports depends on ordered OSN server platform (see Section 5.7 on page 46).
5
Protective earthing screw.
Page 23
Item # Label Description
6 Mediant 800B: 100-
240V~4A
50-60Hz
Mediant 800C: 100-
240V~1.5A
50-60Hz
3-Prong AC power supply entry.
7 DC IN 12V-10A DC power inlet for accepting a DC terminal block plug.
Note:
DC power is applicable only to Mediant 800C. Use only the AC/DC power adaptor that is supplied by
AudioCodes to connect the DC inlet.
Page 24
Mediant 800
This page is intentionally left blank.
Page 25
Hardware Installation Manual 4. Mounting the Device
4 Mounting the Device
The device can be mounted in one of the following ways:
Placed on a desktop – see Section 4.1 on page 25
Mounted on a wall – see Section 4.2 on page 26
Installed in a standard 19-inch rack – see Section 4.2 on page 26
Warning: Do not place any equipment directly on top of the device or adjacent to its
sides (at least 13-cm separation). In addition, if you are mounting the device in a 19-inch rack, ensure that at least a 3U separation is maintained between the device and other mounted devices or equipment.
4.1 Desktop Mounting
The device can be placed on a desktop when its four anti-slide bumpers (supplied) are attached to the underside of the device.
To attach the anti-slide rubber bumpers to the device:
1. Flip the device over so that its underside faces up.
2. Locate the four anti-slide grooves on the underside - one in each corner.
3. Peel off the adhesive, anti-slide rubber feet and stick one in each anti-slide groove.
Figure 4-1: Rubber Foot Attached to Underside of Device
4. Flip the device over again so that it rests on the rubber feet and place it in the required
position on a desktop.
Page 26
Mediant 800
4.2 Wall Mounting
The device can be mounted on a wall using side mounting brackets (separate orderable item).
To mount the device on a wall:
1. Using a Philips-head screwdriver, attach the mounting brackets (supplied) to both sides
of the chassis using the screws (supplied), as shown in the figure below. Each bracket is secured to the chassis using three screws.
Figure 4-2: Attaching the Mounting Brackets to Chassis
2. Mark the drilling locations of the four mounting holes on the wall. You can use the
chassis with the attached wall-mounting brackets as a template. For this two people are needed, one to hold the chassis and one to mark the holes. Hold the chassis so that the mounting brackets are flush against the wall. Make sure that the orientation of the chassis is correct –front panel facing up (toward the ceiling). Make sure that the chassis is horizontal with the floor (you can use a level). With a pencil, stencil the mounting brackets' keyholes on the wall.
3. Remove the chassis and place it on a horizontal surface.
4. Drill holes in the wall where you marked the keyholes.
Page 27
Hardware Installation Manual 4. Mounting the Device
5. Insert wall anchors (not supplied) of appropriate size into each drilled hole.
6. With one person holding the chassis flush against the wall with the mounting brackets'
keyholes aligned with the wall anchors, Philips pan-head wood screws of 20-mm length
(not supplied) to secure the brackets to the wall.
Figure 4-3: Attaching the Chassis with Mounting Brackets to Wall
Page 28
Mediant 800
4.3 19-Inch Rack Mounting
The device can be installed in a standard 19-inch rack by implementing one of the following mounting methods:
Placing it on a pre-installed shelf in a 19-inch rack – see Section 4.3.1 on page 28
Attaching it directly to the rack’s frame using the device's mounting brackets (supplied)
that need to be attached to the chassis – see Section 4.3.2 on page 29
Rack Mount Safety Instructions
When installing the chassis in a rack, implement the following safety instructions:
Elevated Operating Ambient Temperature: If installed in a closed or multi-unit
rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient temperature. Therefore, consideration should be given to installing the equipment in an environment with maximum ambient temperature (Tma) of 40°C (104°F).
Reduced Air Flow: Installation of the equipment in a rack should be such that
the amount of air flow required for safe operation on the equipment is not compromised.
Mechanical Loading: Mounting of the equipment in the rack should be such
that a hazardous condition is not achieved due to uneven mechanical loading.
Circuit Overloading: Consideration should be given to the connection of the
equipment to the supply circuit and the effect that overloading of the circuits might have on over-current protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
Reliable Earthing: Reliable earthing of rack-mounted equipment should be
maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g., use of power strips). For earthing the device, see Section 5.1 on page 31.
4.3.1 Using a Pre-Installed Rack Shelf
The procedure below describes how to place the device on a pre-installed shelf in a 19-inch rack.
To mount the device on a pre-installed shelf in the rack:
1. Before installing it in the rack, ensure that you have a pre-installed rack shelf on which
the device can be placed.
2. Place the device on the pre-installed shelf in the rack.
Page 29
Hardware Installation Manual 4. Mounting the Device
4.3.2 Using Mounting Brackets
The procedure below describes how to mount the device in a 19-inch rack. Rack mounting involves placing the device on a pre-installed rack shelf (not supplied) and then securing the device to the rack frame using mounting brackets (supplied).
Figure 4-4: Mounting Brackets
To mount the device in a 19-inch rack using mounting brackets:
1. Attach the two mounting brackets (supplied) to each side of the device's chassis, using
the supplied screws, as shown in the figure below:
Figure 4-5: Attaching the Mounting Brackets
2. Place the device on a pre-installed shelf in the rack.
3. Attach the ends of the mounting brackets (that you installed in Step 1) to the vertical
track of the rack's frame, using standard 19-inch rack bolts (not supplied).
Page 30
Mediant 800
This page is intentionally left blank.
Page 31
5 Cabling the Device
This chapter describes the cabling of the device.
5.1 Grounding and Surge Protection
The device must be connected to earth (grounded) using an equipment-earthing conductor.
Protective Earthing
The equipment is classified as Class I EN60950 and UL60950 and must be earthed at all times.
Finland: "Laite on liltettava suojamaadoituskoskettimilla varustettuun pistorasiaan."
Norway: "Apparatet rna tilkoples jordet stikkontakt." Sweden: "Apparaten skall anslutas till jordat uttag."
Grounding and Power Surge Protection
The device must be installed only in telecommunication sites / centers in
compliance with ETS 300-253 requirements "Earthing and Bonding of Telecommunication Equipment in Telecommunication Centers".
Prior to installation, earth loop impedance test must be performed by a certified
electrician to ensure grounding suitability at the power outlet intended to feed the unit. It is essential that the impedance will be kept below 0.5 ohms!
Proper grounding is crucial to ensure the effectiveness of the lightning protection,
connect the device permanently to ground (as described in the procedure below). The device's grounding screw must be connected to the equipotential grounding bus bar located in the Telecommunication rack or installation site, using a wire of 6 mm2 surface wire. If the device is installed in a rack with other equipment, the rack must be connected to the equipotential grounding bus bar of the Telecommunication room, using a stranded cable with surface area of 25 mm2. The length of this cable must be as short as possible (no longer than 3 meters).
The device does not include primary telecom protection! When the FXO telephone
lines are routed outside the building, additional protection - usually a 350V three­electrode Gas Discharge Tube (GDT) as described in ITU-T K.44 - must be provided at the entry point of the telecom wires into the building (usually on the main distribution frame / MDF), in conjunction with proper grounding. The center pin of the GDT (MDF grounding bar) must be connected to the equipotential grounding bus bar of the Telecommunication room.
Failing to install primary surge protectors and failing to comply with the grounding
instructions or any other installation instructions, may cause permanent damage to the device!
As most of the installation is the responsibility of the customer, AudioCodes can
assume responsibility for damage only if the customer can establish that the device does not comply with the standards specified above (and the device is within the hardware warranty period).
The device complies with protection levels as required by EN 55024/EN 300386.
Higher levels of surges may cause damage to the device.
To protect against electrical shock and fire, use a minimum of 26-AWG wire size to
connect the FXO ports.
Page 32
Mediant 800
Warning:
To avoid electric shock and/or damage to ports due to over-voltage phenomena,
you must connect the device to a reliable ground using the grounding termination located on the device's rear panel.
When the device is powered only from the 12V DC supply (utilizing the external
power adaptor), the device is not grounded!
Ground the device prior to connecting the telephony port interfaces (FXO, FXS,
E1/T1 and BRI).
When powering off the device, prior to disconnecting the ground cable at the rear
panel ((if required), remove all telephony interface cables.
To ground the device:
1. Connect an electrically earthed strap of 16 AWG wire (minimum) to the chassis'
grounding screw (located on the rear panel), using the supplied washer and fasten the wire securely using a 6-32 UNC screw.
Figure 5-1: Grounding the Device
2. Connect the other end of the strap to a protective earthing. This should be in accordance
with the regulations enforced in the country of installation.
Page 33
5.2 Connecting to LAN
The device provides up to four 10/100/1000Base-T (Gigabit Ethernet) RJ-45 ports and up to eight 10/100Base-TX (Fast Ethernet) RJ-45 ports for connection to the LAN. These Ethernet ports can operate in pairs (groups) to provide 1+1 port redundancy. In each pair, one port serves as the active port while the other as standby. When the active port fails, the device switches to the standby port.
Notes:
The type and number of Ethernet ports depends on ordered hardware
configuration.
The Fast Ethernet ports are available only on "pure" SBC Mediant 800 (i.e., without
PSTN / Gateway interfaces).
By default, the Ethernet ports are grouped into pairs as shown in the figure below. You can change this port assignment, including assigning only a single port to an Ethernet Group. For more information, refer to the User's Manual.
Figure 5-2: LAN Port-Pair Groups and Web Interface String Names
These ports support half- and full-duplex modes, auto-negotiation, and straight or crossover cable detection.
Cable specifications:
Cable: Category 5e or Category 6 shielded twisted pair (STP) straight-through
Connector Type: RJ-45
Connector Pinouts:
Table 5-1: RJ-45 Connector Pinouts for GbE/FE
Pin Signal Name
1
Ethernet signal pair (10/100/1000Base-T)
2
3
Ethernet signal pair (10/100/1000Base-T)
6
4
Ethernet signal pair (1000Base-T)
5
7
Ethernet signal pair (1000Base-T)
8
Page 34
Mediant 800
Pin Signal Name
Shield Chassis ground
To connect the device to the LAN:
1. Connect the RJ-45 connector on one end of the Ethernet cable to one of the device's
Ethernet ports, labeled GE (for Gigabit Ethernet ports) and FE (for Fast Ethernet ports).
Figure 5-3: Connecting the LAN Ports
2. Connect the other end of the cable to the Gigabit Ethernet network (for the GE ports)
and/or Fast Ethernet network (for the FE ports).
3. For 1+1 LAN protection, repeat steps 1 and 2 for the standby port, but connect it to
another network (in the same subnet).
Note: If you are implementing LAN port-pair redundancy, make sure that each port in
the Ethernet Group is connected to a different network (but in the same subnet).
Page 35
5.3 Connecting to Analog Devices
This section describes how to connect the device to analog equipment.
5.3.1 Connecting the FXS Interfaces
The procedure below describes how to cable the device's FXS interfaces.
Warnings:
The device is an INDOOR unit and therefore, must be installed only indoors.
FXS port interface cabling must be routed only indoors and must not exit the
building.
Make sure that the FXS ports are connected to the appropriate, external devices;
otherwise, damage to the device may occur.
FXS ports are considered TNV-2.
Notes:
FXS interfaces are a separate orderable item.
FXS is the interface replacing the Exchange (i.e., the CO or the PBX) and connects
to analog telephones, dial-up modems, and fax machines. The FXS is designed to supply line voltage and ringing current to these telephone devices. An FXS VoIP
device interfaces between the analog telephone devices and the Internet.
Cable specifications:
Cable: Standard straight-through RJ-11-to-RJ-11 telephone cable
Connector Type: RJ-11
Connector Pinouts:
Figure 5-4: RJ-11 Connector Pinouts for FXS Interface
Page 36
Mediant 800
To connect the FXS interfaces:
1. Connect one end of an RJ-11 cable to the FXS port (labeled FXS).
Figure 5-5: Connecting FXS Interfaces
2. Connect the other end of the cable to the required telephone interface (e.g., fax machine,
dial-up modem, and analog POTS telephone).
5.3.2 Connecting the FXO Interfaces
The procedure below describes how to cable the device's FXO interfaces.
Warnings:
The device does not include primary telecom protection! When the FXO telephone
lines are routed outside the building, additional protection - usually a 350V three­electrode Gas Discharge Tube (GDT) as described in ITU-T K.44 - must be provided at the entry point of the telecom wires into the building (usually on the main distribution frame / MDF), in conjunction with proper grounding. The center pin of the GDT (MDF grounding bar) must be connected to the equipotential grounding bus bar of the Telecommunication room.
To protect against electrical shock and fire, use a minimum 26-AWG wire to
connect FXO ports to the PSTN.
Ensure that the FXO ports are connected to the appropriate, external devices;
otherwise, damage to the device may occur.
FXO ports are considered TNV-3.
Notes:
FXO interfaces are a separate orderable item.
FXO is the interface replacing the analog telephone and connects to a Public
Switched Telephone Network (PSTN) line from the Central Office (CO) or to a Private Branch Exchange (PBX). The FXO is designed to receive line voltage and ringing current, supplied from the CO or the PBX (similar to an analog telephone). An FXO VoIP device interfaces between the CO/PBX line and the Internet.
Page 37
Cable specifications:
Cable: 26 AWG min
Connector Type: RJ-11
Connector Pinouts:
Figure 5-6: RJ-11 Connector Pinouts for FXO Interface
To connect the FXO interfaces:
1. Connect one end of an RJ-11 cable to the FXO port (labeled FXO).
Figure 5-7: Connecting FXO Interfaces
2. Connect the other end of the cable to the required telephone interface: (e.g., telephone
exchange analog lines or PBX extensions).
Page 38
Mediant 800
5.3.3 Connecting the FXS Analog Lifeline
The device supports Analog Lifeline. If the device loses power, for example, due to a power outage or the unplugging of its power cable, it automatically routes calls from a POTS telephone ("lifeline" phone), connected to an FXS port, to the PSTN (instead of the IP network).
The Lifeline is provided by FXS Port # 1. This port connects to the analog POTS phone and the PSTN / PBX using a splitter cable (not supplied). The Lifeline splitter connects pins 1 and 4 to another source of an FXS port, and pins 2 and 3 to the POTS phone.
Notes:
The lifeline splitter cable is a separate orderable item.
Analog Lifeline cabling is applicable only if the device is ordered with FXS
interfaces.
The number of supported Lifelines depends on the device’s hardware configuration.
For the combined FXS/FXO configuration, one Lifeline is available; for the 12-FXS
configuration, up to three Lifelines are available.
Cable specifications:
Cable: Splitter cable with RJ-11 connector on one end and two RJ-11 jacks (plugs) on
the other end
Connector Type: RJ-11
Connector Pinouts:
Figure 5-8: RJ-11 Connector Pinouts for FXS Lifeline
To cable the FXS Lifeline:
1. Connect the lifeline splitter to FXS Port 1.
2. On the lifeline splitter cable, do the following:
a. Connect the analog telephone to Port A. b. Connect an analog PSTN line to Port B.
Figure 5-9: Cabling FXS Lifeline
Page 39
5.4 ISDN BRI Interfaces
This section describes how to cable the BRI interfaces.
5.4.1 Connecting to BRI Lines
The device provides up to four BRI S/T ports. These ports connect to ISDN terminal equipment such as ISDN telephones. Each BRI port can be configured either as termination equipment/user side (TE) or network termination/network side (NT). Up to eight terminal equipment (TE) devices can be connected per BRI S/T port, using an ISDN S-bus that provides eight ISDN ports. When configured as NT, the BRI port drives a nominal voltage of 38 V with limited current supply of up to 100 mA.
Warning:
BRI port cabling must be routed only indoors and must not exit the building.
To protect against electrical shock and fire, use a 26 AWG min wire to connect the
BRI ports to the PSTN.
Note: BRI interfaces are a separate orderable item.
Cable specifications:
Cable: 26 AWG min.
Connector Type: RJ-45
Connector Pinouts:
Figure 5-10: RJ-45 Connector Pinouts for BRI Ports
Page 40
Mediant 800
To connect the BRI ports:
1. Connect the BRI cable to the device's BRI RJ-45 port.
2. Connect the other end of the cable to your ISDN telephone or PBX/PSTN switch.
Figure 5-11: Cabling BRI Ports
5.4.2 Connecting PSTN Fallback for BRI Lines
The device supports PSTN Fallback for BRI lines. If the device loses power, for example, due to a power outage or the unplugging of its power cable, it automatically routes calls from the Tel side to the PSTN (instead of the IP network).
PSTN Fallback is supported if the device houses one or more BRI modules, where each BRI module provides two or four spans.
In the event of a PSTN fallback, the BRI module's metallic relay switch automatically connects line Port 1 (I) to Port 2 (II) of the BRI module.
For example, if a PBX trunk is connected to Port 1 and the PSTN network is connected to Port 2, when PSTN Fallback is activated, calls from the PBX are routed directly to the PSTN through Port 2.
Warning:
BRI port cabling must be routed only indoors and must not exit the building.
To protect against electrical shock and fire, use a 26 AWG min wire to connect the
BRI ports to the PSTN.
Cable specifications:
Cable: 26 AWG min.
Connector Type: RJ-45
Connector Pinouts:
Figure 5-12: RJ-45 Connector Pinouts for BRI PSTN Fallback
Page 41
To connect the BRI line interfaces for 1+1 PSTN Fallback:
1. Connect line 1 to a PBX.
2. On the same BRI module, connect line 2 to the PSTN.
Figure 5-13: Cabling (Ports 1 and 2) PSTN Fallback
Notes:
PSTN Fallback is supported only on BRI interfaces.
PSTN Fallback is supported only between ports on the same BRI module.
This PSTN Fallback feature has no relation to the PSTN Fallback Software
Upgrade Key.
Page 42
Mediant 800
5.5 Connecting ISDN E1/T1 Interfaces
This section describes how to cable the PRI interfaces.
5.5.1 Connecting to ISDN PRI (E1/T1) Trunks
The procedure below describes the cabling of the device's E1/T1 (PRI) trunk interfaces.
Warning:
PRI port cabling must be routed only indoors and must not exit the building.
To protect against electrical shock and fire, use a 26 AWG min wire to connect T1
or E1 ports to the PSTN.
To comply with EMC rules and regulations, use shielded twisted pair (STP) cables
for E1 interfaces.
Note: PRI interfaces are a separate orderable item.
Cable specifications:
Cable: STP cable of 26 AWG min.
Connector Type: RJ-48c
Connector Pinouts:
Figure 5-14: RJ-48c Connector Pinouts for E1/T1
To connect the E1/T1 trunk interface:
1. Connect the E1/T1 trunk cable to the device’s E1/T1 port.
2. Connect the other end of the trunk cable to your PBX/PSTN switch.
Figure 5-15: Cabling E1/T1 Ports
Page 43
5.5.2 Connecting PSTN Fallback for E1/T1 Trunks
The device supports PSTN Fallback for E1/T1 lines. If the device loses power, for example, due to a power outage or the unplugging of its power cable, it automatically routes calls that are received from the Tel side (e.g., PBX) directly to the PSTN (instead of to the IP network).
Support for PSTN fallback:
Mediant 800B: PSTN Fallback is supported only when using a module with dual
E1/T1 ports. In the event of a PSTN fallback, the module's metallic relay switch automatically connects Port #1 with Port #2 to route calls between the Tel and PSTN side.
Mediant 800C: In the event of a PSTN fallback, the module's metallic relay switch
automatically connects Port #1 with Port #2 (and Port #3 with Port #4 for the four E1/T1 port module) to route calls between the Tel and PSTN side. These ports must be on the same module.
Warning:
PRI port cabling must be routed only indoors and must not exit the building.
To protect against electrical shock and fire, use a 26 AWG min. wire to connect the
PRI ports to the PSTN.
To comply with EMC rules and regulations, use shielded twisted pair (STP) cables
for E1 interfaces.
Cable specifications:
Cable: STP cable of 26 AWG min.
Connector Type: RJ-48c
Connector Pinouts:
Figure 5-16: RJ-48c Connector Pinouts for E1/T1 PSTN Fallback
Page 44
Mediant 800
To connect the PRI ports for PSTN Fallback:
1. Connect one of the PRI ports to the PBX.
2. Connect the second PRI port to the PSTN.
Figure 5-17: Cabling PRI Ports for PSTN Fallback
Note: It does not matter which PRI port connects to which Tel entity (i.e., PBX or PSTN).
Page 45
5.6 Connecting to a Computer for Serial Communication
The device provides an RS-232 serial interface port on its front panel for serial communication with a PC.
Cable specifications:
Connector Type: RJ-45
Cable: RJ-45 to DB-9 cable adaptor
To connect the device's serial interface to a computer:
1. Connect the RJ-45 cable connector to the device's serial port, labeled CONSOLE.
2. Connect the other end of the cable to the COM1 or COM2 RS-232 communication port
on your PC.
Figure 5-18: Cabling Serial Interface
Page 46
Mediant 800
5.7 Connecting the OSN Server
The device may be ordered with an embedded, Open Network Solution (OSN) platform for hosting third-party services such as an IP PBX. The OSN modules are located on the device's rear panel.
The table below lists available, orderable OSN server platforms:
Table 5-2: OSN Server Platforms
OSN
Platform
CPU Memory Storage Interfaces
OSN2
2
nd
Generation Intel Core Celeron
1.6 GHz
2 or 4 GB HDD 500 GB
Two external Gigabit Ethernet Internal Gigabit Ethernet Three USB 2.0 via Connection
Module
VGA
OSN4 3rd Generation
Intel Core i7 Quad Core
16 GB
ECC DDR3
HDD (500 GB) or SSD (240 GB)
Two external Gigabit Ethernet Internal Gigabit Ethernet Three USB 2.0 via Connection
Module
VGA
OSN5
Intel Atom N2800
1.86 GHz Dual Core
2G HDD 500 GB
One external Gigabit Ethernet Internal Gigabit Ethernet Three USB 2.0 via Connection
Module
VGA
Notes:
The OSN server platform is a customer ordered feature and thus, the OSN
interface ports, located on the rear panel are available only when the device is purchased with the OSN server.
The OSN server also provides an internal interface connection to the Mediant 800
LAN switch. In other words, instead of using the Gigabit Ethernet port on the rear panel, you can use the LAN port #1 located on the front panel for connecting to the OSN server.
The table above lists the currently available OSN platforms. This list may change
without notice. To check for any updated information on available OSN platforms, contact your AudioCodes sales representative.
Page 47
To connect to the OSN server:
1. Perform the following cabling procedures on the OSN server, located on the rear panel:
a. Connect computer peripherals (e.g., mouse and keyboard) to the USB ports
(Standard-A type) labeled USB.
b. Connect the USB storage device containing the operating system installation files
(Linux or Microsoft Windows) to one of the USB ports, labeled USB.
c. Connect a monitor using a 15-Pin D-type male connector to the VGA female port,
labeled VGA.
d. Connect to the network using an RJ-45 Ethernet cable connector to the Gigabit
Ethernet port/s (labeled GE 1 and GE 2).
Figure 5-19: Cabling OSN Server Ports
2. Connect the device to power.
3. Follow the operating system's installation instructions to install the operating system.
To reset the OSN server:
Insert a sharp-pointed object (such as a drawing pin) into the Reset pinhole and then
extract it after a second; the OSN server performs a reset.
Page 48
Mediant 800
5.9 Connecting to Power
The supported power type depends on the Mediant 800 hardware revision:
Mediant 800B: Only AC power
Mediant 800C: AC and DC redundant power. When both power supplies are used (AC
and DC), the device is powered from the AC power source only. The DC source starts feeding the device only upon an AC power outage.
Notes: For Mediant 800C, the device is always shipped with AC power support. DC
power is also available if the device is ordered with DC support (AC/DC power adaptor is provided).
5.9.1 Connecting to AC Power
The device receives power from a standard alternating current (AC) electrical outlet. The connection is made through the supplied AC power cord.
Table 5-3: AC Power Specifications
Physical Specification Value
Input Voltage Single universal AC power supply 100 to 240V
AC Input Frequency 50 to 60 Hz
AC Input Current
Mediant 800B: 4 A (max.)
Mediant 800C: 1.5 A (max.)
Max. Power Consumption
SBC Only (no PSTN): 27W Gateway (without OSN): 60W*
* Power consumption varies according to the assembled hardware configuration.
Warnings:
The device must be connected to a socket-outlet providing a protective earthing
connection.
To avoid electric shock or fire, use only the AC power cord that is supplied by
AudioCodes with the device.
For replacing the power fuse, see Section 6 on page 53.
ご注意
本製品に添付の電源ケーブルは、Mediant 800 Gateway & E-SBC に専用設計されてい るため、汎用性がありません. 本電源ケーブルを他の機器に使用されないよう、ご注 意ください.
Page 49
To connect the device to AC power:
1. Connect the plug of the AC power cord (supplied) to the device's AC power socket
(labeled 100-240V ~ 4A 50-60Hz), located on the rear panel.
Figure 5-20: Connecting to the Power Supply
2. Connect the plug at the other end of the AC power cord to a standard electrical outlet.
The POWER LED, located on the front panel, lights up green.
5.9.2 Connecting to DC Power
DC power is cabled using the AC/DC power adaptor (supplied) which is connected to a standard AC electrical wall outlet. Typically, the DC power source is used for power redundancy with the AC power source (see note below).
Notes:
DC power support is a separate orderable item.
When both power supplies are used (AC and DC), the device is powered from the
AC power source only. The DC source starts feeding the device only upon an AC power outage.
Table 5-4: DC Power Specifications
Physical Specification Value
Input Voltage 12VDC / 10A
Warning: Use only the AC/DC power adaptor that is provided by AudioCodes when
ordering DC power.
Page 50
Mediant 800
To connect the device for DC power:
1. Insert the male DC plug into the DC inlet connector located on the device's rear panel.
When inserting the DC plug, make sure that the latch faces up (see figure below). Make sure that the latch snaps into the inlet, indicating that the terminal block has been firmly plugged in.
Figure 5-21: Connecting DC Power Plug to DC Inlet
Page 51
2. Plug the female connector that is located on one end of the AC power cord (supplied),
into the AC/DC power adaptor.
Figure 5-22: Plugging AC Power Cord into AC/DC Adaptor
3. Plug the other end of the AC power cord (supplied) into a standard electrical wall outlet.
The device's DC PWR LED, located on the front panel, lights up green.
Page 52
Mediant 800
This page is intentionally left blank.
Page 53
Hardware Installation Manual 6. Maintenance – Replacing the Power Fuse
6 Maintenance – Replacing the Power Fuse
The device contains a fuse that protects the device from excessive AC current. The fuse is located on the rear panel, below the power socket. To replace the fuse, use only one of the following fuses described in the table below:
Table 6-1: Allowed Fuses for the Device
Manufacturer Manufacturer Part Number
LITTEFUSE 215 06.3 (6.3A/250V)
Caution
For continuous protection, replace only with the same fuse type and rating fuse.
Notes: The power fuse is applicable only to AC power.
To replace the fuse:
1. Unplug the power cord from the electrical outlet.
2. Using a small flathead screwdriver, gently pries open the fuse cavity as illustrated in the
figure below:
Figure 6-1: Opening the Fuse Cavity
Page 54
Mediant 800
3. Carefully remove the fuse from the fuse cavity.
Figure 6-2: Removed Power Fuse
4. Insert the new fuse securely into the fuse cavity until you hear a click sound.
5. Reconnect the power cord and verify that the power LED is lit green.
Page 55
Hardware Installation Manual 6. Maintenance – Replacing the Power Fuse
This page is intentionally left blank.
Page 56
International Headquarters
1 Hayarden Street,
Airport City
Lod 7019900, Israel
Tel: +972-3-976-4000
Fax: +972-3-976-4040
AudioCodes Inc.
200 Cottontail Lane,
Suite A101E,
Somerset, NJ 08873
Tel: +1-732-469-0880
Fax: +1-732-469-2298
Contact us: https://www.audiocodes.com/corporate/offices-worldwide
Website: https://www.audiocodes.com/
©2019 AudioCodes Ltd. All rights reserved. AudioCodes, AC, HD VoIP, HD VoIP Sounds Better, IPmedia, Mediant, MediaPack, What’s Inside Matters, OSN, SmartTAP, User Management Pack, VMAS, VoIPerfect, VoIPerfectHD, Your Gateway To VoIP, 3GX, VocaNom, AudioCodes One Voice and CloudBond are trademarks or registered trademarks of AudioCodes Limited. All other products or trademarks are property of their respective owners. Product specifications are subject to change without notice.
Document #: LTRT-10689
Loading...