AuCom EMX4i User Manual

Page 1
USER MANUAL
EMX4i Soft Starter
Page 2
Contents
CONTENTS
1. About This Manual ..................................... 3
1.1 Disclaimer ...................................................... 3
2. Caution Statements .................................. 4
2.2 Unexpected Operation .................................. 5
2.3 Avertissements à l'attention des clients
canadiens ........................................................ 6
3. System Design ........................................... 8
3.1 Feature List .................................................... 8
3.2 Model Code ..................................................... 9
3.3 Model Selection ............................................. 9
3.4 Current Ratings .......................................... 10
3.5 Dimensions and Weights .......................... 13
3.6 Physical Installation ................................... 14
3.7 Accessories ................................................. 14
3.8 Main Contactor ........................................... 15
3.9 Circuit Breaker ........................................... 15
3.10 Power Factor Correction ........................... 16
3.11 Short Circuit Protection Devices (SCPD) 16
3.12 IEC Coordination with Short Circuit
Protection Devices ..................................... 17
3.13 UL Coordination with Short Circuit
Protection Devices ..................................... 18
3.14 Fuse Selection for Type 2 Coordination .. 21
3.15 Specifications .............................................. 22
3.16 Disposal Instructions ................................. 23
4. Installation ............................................... 24
4.1 Command Source ...................................... 24
4.2 Setup Procedure Overview ....................... 24
4.3 Inputs ............................................................ 25
4.4 Outputs ......................................................... 27
4.5 Control Voltage ........................................... 28
4.6 Power Terminations .................................. 28
4.7 Typical Installation ..................................... 31
5. Setup Tools .............................................. 34
5.1 Set Date and Time ...................................... 34
5.2 Command Source ...................................... 34
5.3 Commissioning ........................................... 34
5.4 Run simulation ............................................ 35
5.5 Load/Save Settings .................................... 36
5.6 USB Save & Load ........................................ 36
5.7 Auto-Start/Stop ........................................... 38
5.8 Network Address ........................................ 38
5.9 Digital I/O State ........................................... 39
5.10 Analog I/O State .......................................... 39
5.11 Serial Number & Rating ............................ 39
5.12 Software Versions ....................................... 40
5.13 Thermistor Reset ........................................ 40
5.14 Reset Thermal Model................................. 40
6. Logs .......................................................... 41
6.1 Event Log ..................................................... 41
6.2 Counters ....................................................... 41
6.3 QR Code ........................................................ 41
7. Keypad and Feedback ............................. 42
7.1 The Keypad .................................................. 42
7.2 Remote Keypad ........................................... 43
7.3 Lighten/Darken the Display ...................... 43
7.4 Starter status LEDs .................................... 44
7.5 Displays ........................................................ 44
8. Operation ................................................. 46
8.1 Start, Stop and Reset Commands ............ 46
8.2 Command Override .................................... 46
8.3 Auto-Start/Stop ........................................... 46
8.4 PowerThrough ............................................ 47
8.5 Emergency Mode ........................................ 48
8.6 Auxiliary Trip ................................................ 48
8.7 Typical Control Methods ............................ 49
8.8 Soft Start Methods ...................................... 50
8.9 Stop Methods .............................................. 53
8.10 Pump Clean ................................................. 57
8.11 Reverse Direction Operation ..................... 57
8.12 Jog Operation .............................................. 58
8.13 Inside Delta Operation ............................... 59
8.14 Secondary Motor Set .................................. 60
9. Programmable Parameters .................. 61
9.1 Main Menu ................................................... 61
9.2 Altering Parameter Values ....................... 61
9.3 Adjustment Lock ......................................... 61
9.4 Parameter List ............................................ 62
9.5 1 Motor Details ............................................ 70
9.6 2 Motor Start/Stop ...................................... 71
710-14888-00C EMX4i User Manual 1
Page 3
CONTENTS
9.7 3 Motor Start/Stop-2 .................................. 74
9.9 5 Protection Levels ..................................... 80
9.10 6 Protection Action ..................................... 82
9.11 7 Inputs ......................................................... 86
9.12 8 Relay Outputs ........................................... 89
9.13 9 Analog Output .......................................... 91
9.14 10 Display ..................................................... 92
9.15 11 Pump Clean ............................................ 95
9.16 12 Communications Card ......................... 96
9.17 20 Advanced ................................................ 99
9.18 30 Pump Input Configuration ................. 100
9.19 31 Flow Protection ................................... 102
9.20 32 Pressure Protection ........................... 103
9.21 33 Pressure Control ................................. 104
9.22 34 Depth Protection ................................. 105
9.23 35 Thermal Protection ............................. 105
9.24 36 Pump Trip Action ................................. 106
10. Application Examples ............................ 108
10.1 Smart Card - Pump Control and
Protection .................................................. 108
10.2 Smart Card - Level Controlled Pump
Activation ................................................... 110
11. Troubleshooting .................................... 112
11.1 Protection Responses .............................. 112
11.2 Trip Messages ........................................... 112
11.3 General Faults .......................................... 121
2 EMX4i User Manual 710-14888-00C
Page 4
ABOUT THIS MANUAL
WARNING
CAUTION
NOTE
© 2018 AuCom Electronics Ltd. All Rights Reserved.
proving its products it reserves the right to modify or change the specification
of its products at any time without notice
text, diagrams, images and any other literary or artistic works

1. About This Manual

Indicates a hazard that may cause personal injury or death.
Indicates a hazard that may damage the equipment or installation.

1.1 Disclaimer

The examples and diagrams in this manual are included solely for illustrative purposes.
The information contained in this manual is subject to change at any time and without prior notice. In no event will responsibility or liability be accepted for direct,
Provides helpful information.
indirect or consequential damages resulting from the use or application of this equipment.
As AuCom is continuously im
appearing in this document are protected by copyright. Users may copy some of the material for their personal reference but may not copy or use material for any other purpose without the prior consent of
AuCom Electronics Ltd. AuCom endeavours to ensure that the information contained in this document
including images is correct but does not accept any liability for error, omission or differences with the
710-14888-00C EMX4i User Manual 3
. The
finished product.
Page 5
CAUTION STATEMENTS
NOTE
FOR YOUR SAFETY
WARNING – ELECTRICAL SHOCK RISK
SHORT CIRCUIT

2. Caution Statements

Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read and understand all instructions in this manual prior to installing, operating or maintaining the equipment, to follow good electrical practice including applying appropriate personal protective equipment and to seek advice before operating this equipment in a manner other than as described in this manual.
The EMX4i is not user serviceable. The unit should only be serviced by authorised service personnel. Unauthorised tampering with the unit will void the product warranty.
• The STOP function of the soft starter does not isolate dangerous voltages
from the output of the starter. The soft starter must be disconnected by an approved electrical isolation device before accessing electrical connections.
• Soft starter protection features apply to motor protection only. It is the
user’s responsibility to ensure safety of personnel operating machinery.
• The soft starter is a component designed for integration within an
electrical system; it is therefore the responsibility of the system designer/user to ensure the system is safe and designed to comply with relevant local safety standards.

2.1 Electrical shock risk

The voltages present in the following locations can cause severe electric shock and may be lethal:
• AC supply cables and connections
• Output cables and connections
• Many internal parts of the starter
The EMX4i is not short circuit proof. After severe overload or short circuit, the operation of the EMX4i should be fully tested by an authorised service
4 EMX4i User Manual 710-14888-00C
agent.
Page 6
CAUTION STATEMENTS
GROUNDING AND BRANCH CIRCUIT PROTECTION
WARNING – ACCIDENTAL STARTS
WARNING – STARTER MAY START OR STOP UNEXPECTEDLY
WARNING – DISCONNECT MAINS BEFORE ACCESSING STARTER OR LOAD
CAUTION – MECHANICAL DAMAGE FROM UNEXPECTED RESTART
It is the responsibility of the user or person installing the EMX4i to provide proper grounding and branch circuit protection according to local electrical safety codes.

2.2 Unexpected Operation

In some installations, accidental starts may pose an increased risk to safety of personnel or damage to the machines being driven. In such cases, it is recommended that the power supply to the soft starter is fitted with an isolating switch and a circuit-breaking device (eg power contactor) controllable through an external safety system (eg emergency stop, fault detector).
The EMX4i will respond to control commands from various sources, and could start or stop unexpectedly. Always disconnect the soft starter from mains voltage before accessing the starter or load.
The soft starter has built-in protections which can trip the starter in the event of faults and thus stop the motor. Voltage fluctuations, power cuts and motor jams may also cause the motor to trip.
The motor could restart after the causes of shutdown are rectified, which may be dangerous for personnel. Always disconnect the soft starter from mains voltage before accessing the starter or load.
The motor could restart after the causes of shutdown are rectified, which may be dangerous for certain machines or installations. In such cases, it is essential that appropriate arrangements are made against restarting after unscheduled stops of the motor.
710-14888-00C EMX4i User Manual 5
Page 7
CAUTION STATEMENTS
AVERTISSEMENT
AVERTISSEMENT – RISQUE DE CHOC ÉLECTRIQUE
PAR SÉCURITÉ
AVERTISSEMENT – DÉMARRAGES ACCIDENTELS

2.3 Avertissements à l'attention des clients canadiens

L'icône AVERTISSEMENT ci-contre signale les informations concernant des risques pouvant entraîner des blessures graves, voire mortelles. Pour votre sécurité, veuillez consulter les avertissements sur cette page ou demander une copie du présent manuel en français auprès de votre distributeur local.
Les zones suivantes sont soumises à des tensions pouvant provoquer des risques de chocs électriques graves, voire mortels :
• Raccordement et câbles d'alimentation AC
• Câbles et raccordements de sortie
• De nombreuses pièces internes du démarreur
• La fonction STOP du démarreur progressif n'isole pas des tensions
dangereuses de la sortie du démarreur. Le démarreur progressif doit être déconnecté par un dispositif d'isolement électrique approprié avant d'accéder aux connexions électriques.
• Les fonctions de protection du démarreur progressif ne concernent que
la protection du moteur. Il relève de la responsabilité de l'utilisateur d'assurer la sécurité des personnes travaillant sur les machines.
• Le démarreur progressif est un appareil conçu pour s'intégrer dans un
système électrique ; il relève donc de la responsabilité du concepteur ou de l'utilisateur de veiller à ce que ce système soit sûr et conçu selon les normes de sécurité locales en vigueur.
Dans certaines installations, des démarrages accidentels peuvent provoquer un risque supplémentaire pour la sécurité des personnes ou endommager les machines contrôlées. Dans de tels cas, il est recommandé de doter l'alimentation du démarreur progressif d'un interrupteur d'isolement et d'un coupe-circuit (par exemple, un disjoncteur) contrôlable à partir d'un système de sécurité externe (par exemple, un arrêt d'urgence, un détecteur de défaut).
6 EMX4i User Manual 710-14888-00C
Page 8
CAUTION STATEMENTS
AVERTISSEMENT – LE DÉMARREUR PEUT DÉMARRER OU S'ARRÊTER À TOUT MOMENT
AVERTISSEMENT – DÉCONNECTER L'ALIMENTATION PRINCIPALE AVANT D'ACCÉDER AU DÉMARREUR OU À LA CHARGE
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
L’EMX4i répond aux commandes de contrôle de différentes origines et peut par conséquent démarrer ou s'arrêter à tout moment. Toujours déconnecter le démarreur de la tension secteur avant d'accéder au démarreur ou à la charge.
Le démarreur progressif comporte des protections intégrées qui peuvent déclencher des mises en sécurité dans l'éventualité de défauts et ainsi arrêter le moteur. Des fluctuations de tension, des coupures d'alimentation et des blocages du moteur peuvent produire des mises en sécurité de celui-ci.
Le moteur pourrait redémarrer une fois que les causes de l'arrêt ont été résolues, ce qui pourrait mettre en danger le personnel. Toujours déconnecter le démarreur de la tension secteur avant d'accéder au démarreur ou à la charge.
Ne pas appliquer la tension du secteur au démarreur tant que tout le câblage n'est pas terminé.
Toujours appliquer la tension de commande avant (ou en même temps que) la tension secteur.
Lors du raccordement de l’EMX4i en connexion 6 fils, toujours installer un contacteur principal ou un disjoncteur magnéto-thermique à bobine de déclenchement.
Si l'entrée de démarrage est fermée lorsque la tension de commande est appliquée, le démarreur tentera d'effectuer un démarrage.
Vérifier que l'entrée de démarrage/arrêt est ouverte avant d'appliquer la tension de commande.
710-14888-00C EMX4i User Manual 7
Page 9
SYSTEM DESIGN
Streamlined setup process
Easy to understand interface
Supports energy efficiency
Extensive range of models
Extensive input and output options
Versatile starting and stopping options
Customisable protection
Optional features for advanced applications

3. System Design

3.1 Feature List

• Configuration profiles for common
applications
• Built-in metering and inputs/outputs
• Multi-language menus and displays
• Descriptive option names and feedback
messages
• Real-time performance graphs
• IE3 compatible
• 99% energy efficient when running
• Internal bypass
• Soft start technology avoids harmonic
• Scheduled start/stop
• Adaptive Control
• Constant Current
• Current Ramp
• Kickstart
• Pump Clean
• Timed voltage ramp start/stop
• Coast To Stop
• DC Brake
• Soft Brake
• Reverse Direction
• Motor overload
distortion
• 24 A~580 A (nominal)
• 200~525 VAC
• 380~690 VAC
• Inside delta installation
• Remote control inputs
(2 x fixed, 2 x programmable)
• Relay outputs
(1 x fixed, 2 x programmable)
• Analog output
• Excess Start Time
• Undercurrent/Overcurrent
• Underpower/Overpower
• Undervoltage/Overvoltage
• Current imbalance
• Input Trip
• Motor thermistor
• Smart cards
• Communication options:
DeviceNet, Ethernet/IP, Modbus RTU, Modbus TCP, Profibus, Profinet
8 EMX4i User Manual 710-14888-00C
Page 10

3.2 Model Code

–
Control voltage
C1 = 110~120 VAC or 220~240 VAC
SYSTEM DESIGN
EMX4i- 0 0 6 9 –

3.3 Model Selection

Starter sizing

C2 = 24 VAC/VDC
Mains voltage V5 = 200~525 VAC
V7 = 380~690 VAC
Bypass B = internally bypassed
Nominal current rating
The soft starter must be the correct size for the motor and the application. Select a soft starter that has a current rating at least equal to the motor's full load
current (nameplate) rating, at the start duty. The soft starter's current rating determines the maximum motor size it can be used
with. The soft starter's rating depends on the number of starts per hour, the length and current level of the start, and the amount of time the soft starter will be off (not passing current) between starts.
The soft starter's current rating is only valid when used in the conditions specified in the AC53b code - the soft starter may have a higher or lower current rating in different operating conditions.
710-14888-00C EMX4i User Manual 9
Page 11
SYSTEM DESIGN
Start time (seconds)
Starter current rating (amperes)
3.0-10:350
3.5-15:345
4.0-10:350
4.0-20:340
5.0-5:355
3.0-10:590
3.5-15:585
4.0-10:590
4.0-20:580
5.0-5:595
EMX4i-0064B
64
63
60
51
54
EMX4i-0200B
200
171
165
138
150
EMX4i-0229B
229
194
187
157
170
EMX4i-0580B
580
579
555
470
508

3.4 Current Ratings

For operating conditions not covered by these ratings charts, download AuCom's free WinStart selection application, or contact your local supplier.

IEC ratings

• AC53b format
80 A : AC-53b
3.5 - 15 : 345 Off time (seconds)
Start current (multiple of motor full load current)
• Ratings
All ratings are calculated at altitude of 1000 metres and ambient temperature of 40 ºC.
In-line installation
EMX4i-0024B 24 20 19 16 17 EMX4i-0042B 42 34 34 27 32 EMX4i-0052B 52 42 39 35 34
EMX4i-0069B 69 69 69 62 65 EMX4i-0105B 105 86 84 69 77 EMX4i-0115B 115 108 105 86 95 EMX4i-0135B 135 129 126 103 115 EMX4i-0184B 184 144 139 116 127
EMX4i-0250B 250 244 230 200 202 EMX4i-0352B 352 287 277 234 258 EMX4i-0397B 397 323 311 263 289 EMX4i-0410B 410 410 410 380 400 EMX4i-0550B 550 527 506 427 464
10 EMX4i User Manual 710-14888-00C
Page 12
SYSTEM DESIGN
3.0-10:350
3.5-15:345
4.0-10:350
4.0-20:340
5.0-5:355
3.0-10:590
3.5-15:585
4.0-10:590
4.0-20:580
5.0-5:595
EMX4i-0064B
96
94
90
76
81
EMX4i-0069B
103
103
103
93
97
EMX4i-0200B
300
256
247
207
225
EMX4i-0229B
343
291
280
235
255
EMX4i-0580B
870
868
832
705
762
Inside delta installation
EMX4i-0024B 36 30 28 24 25 EMX4i-0042B 63 51 51 40 48 EMX4i-0052B 78 63 58 52 51
EMX4i-0105B 157 129 126 103 115 EMX4i-0115B 172 162 157 129 142 EMX4i-0135B 202 193 189 154 172 EMX4i-0184B 276 216 208 174 190
EMX4i-0250B 375 366 345 300 303 EMX4i-0352B 528 430 415 351 387 EMX4i-0397B 595 484 466 394 433 EMX4i-0410B 615 615 615 570 600 EMX4i-0550B 825 790 759 640 696
710-14888-00C EMX4i User Manual 11
Page 13
SYSTEM DESIGN
Light
300%, 10 s,
6 starts per hour
Normal
350%, 30 s,
4 starts per hour
Heavy
450%, 30 s,
4 starts per hour
A
HP
HP
HP
A
HP
HP
HP
A
HP
HP
HP
EMX4i-0064B
64
20
50
60
52
15
30
40
40
10
25
30
EMX4i-0069B
69
25
50
60
59
20
40
50
46
15
30
40
EMX4i-0229B
229
75
150
200
156
60
125
150
124
40
100
100
EMX4i-0250B
250
100
200
250
195
75
150
200
156
60
125
150

NEMA motor ratings

All ratings are calculated at altitude of 1000 metres and ambient temperature of 50 ºC.
@230
VAC
@460
VAC
@575
VAC
@230
VAC
@460
VAC
@575
VAC
@230
VAC
@460
VAC
@575
VAC
EMX4i-0024B 24 7.5 15 20 17 5 10 15 14 3 10 10 EMX4i-0042B 42 15 30 40 28 10 20 25 22 7.5 15 20 EMX4i-0052B 52 15 30 50 35 10 25 30 28 10 20 25
EMX4i-0105B 100 30 75 100 77 25 50 60 52 15 40 50 EMX4i-0115B 115 40 75 100 81 30 60 75 65 20 50 60 EMX4i-0135B 135 50 100 125 99 30 75 100 77 25 60 75 EMX4i-0184B 164 60 125 150 124 40 75 100 96 30 60 75 EMX4i-0200B 200 75 150 200 131 50 100 125 104 40 75 100
EMX4i-0352B 341 125 250 350 240 75 150 200 180 60 150 150 EMX4i-0397B 389 150 300 400 261 100 200 250 203 75 150 200 EMX4i-0410B 410 150 300 450 377 150 300 350 302 100 250 300 EMX4i-0550B 550 200 450 500 414 150 350 450 321 125 250 300 EMX4i-0580B 580 200 500 500 477 200 400 500 361 150 300 350
12 EMX4i User Manual 710-14888-00C
Page 14

3.5 Dimensions and Weights

A B
C
D
E
A B
C
D
E
17043.B
Width
mm (inch)
Height
mm (inch)
Depth
mm (inch)
Weight
kg (lb)
A B C D E
EMX4i-0069B
(6.0)
(3.6)
(13.2)
(12.1)
(9.1)
EMX4i-0105B
5.5
EMX4i-0250B
(8.5)
(7.1)
(17.7)
(9.6)
EMX4i-0352B
15.5
SYSTEM DESIGN
EMX4i-0024B EMX4i-0042B EMX4i-0052B
4.8
(10.7)
4.9
EMX4i-0064B 152 92 336 307 231 (10.9)
EMX4i-0115B EMX4i-0135B EMX4i-0184B EMX4i-0200B
495
(12.1)
12.7
EMX4i-0229B 216 180 (19.5) 450 243 (28.0)
EMX4i-0397B
523
(34.2) EMX4i-0410B EMX4i-0550B EMX4i-0580B
710-14888-00C EMX4i User Manual 13
(20.6)
19.0
(41.9)
Page 15
SYSTEM DESIGN
DD
17044.B
C
C
B
A
Between starters
Solid surfaces
A B C
D

3.6 Physical Installation

> 100 mm (3.9 inch) > 10 mm (0.4 inch) > 100 mm (3.9 inch) > 10 mm (0.4 inch)

3.7 Accessories

Expansion Cards

The EMX4i offers expansion cards for users requiring additional inputs and outputs or advanced functionality. Each EMX4i can support a maximum of one expansion card.
• Smart Card
The smart card has been designed to support integration with pumping applications and provides the following additional inputs and outputs:
• 3 x digital inputs
• 3 x 4-20 mA transducer inputs
• 1 x RTD input
• 1 x USB-B port
• Communication Expansion Cards
The EMX4i supports network communication via easy-to-install communications
• Remote keypad connector
expansion cards. Each communications card includes a remote keypad connector port.
Available protocols: DeviceNet, Ethernet/IP, Modbus RTU, Modbus TCP, Profibus, Profinet.
14 EMX4i User Manual 710-14888-00C
Page 16
SYSTEM DESIGN
WARNING

Remote Keypad

EMX4 starters can be used with a remote keypad, mounted up to 3 metres away from the starter. Each expansion card includes a keypad connection port, or a dedicated keypad connector card is available.

Finger Guard Kit

Finger guards may be specified for personnel safety. Finger guards fit over the soft starter terminals to prevent accidental contact with live terminals. Finger guards provide IP20 protection when used with cable of diameter 22 mm or greater.
Finger guards are compatible with models EMX4i-0184B ~ EMX4i-0580B.

Soft Starter Management Software

PC software can provide real-time or offline management of soft starters.
• For real-time management in a network of up to 254 starters, the
software must connect to the soft starter via a Modbus TCP or Modbus RTU card. The software can monitor, control and program the starter across the network.
• The software can be used to program the starter via the USB port on the
pumping smart card.
• For offline management, a configuration file generated in the software
can be loaded into the starter via the USB port.

3.8 Main Contactor

A main contactor is recommended to protect the soft starter from voltage disturbances on the network, while stopped. Select a contactor with an AC3 rating greater than or equal to the full load current rating of the connected motor.
Use the main contactor output (33, 34) to control the contactor.
When connecting the EMX4i in inside delta configuration, always install a main contactor or shunt trip circuit breaker.

3.9 Circuit Breaker

A shunt trip circuit breaker may be used instead of a main contactor to isolate the motor circuit in the event of a soft starter trip. The shunt trip mechanism must be powered from the supply side of the circuit breaker or from a separate control supply.
710-14888-00C EMX4i User Manual 15
Page 17
SYSTEM DESIGN
K1
K1
1
2
4
3
20234.A
1
Soft starter
CAUTION

3.10 Power Factor Correction

If power factor correction is used, a dedicated contactor should be used to switch in the capacitors.
To use the EMX4i to control power factor correction, connect the PFC contactor to a programmable relay set to Run. When the motor reaches full speed, the relay will close and power factor correction will be switched in. Do not use the soft starter relay output to directly switch in power factor correction.
2 Programmable output (set = Run) 3 Power factor correction contactor 4 Power factor correction
Power factor correction capacitors must be connected to the input side of the soft starter. Connecting power factor correction capacitors to the output side will damage the soft starter.

3.11 Short Circuit Protection Devices (SCPD)

Fuses may be installed to protect the soft starter or the installation.

Type 1 Coordination

Type 1 coordination requires that, in the event of a short circuit on the output side of a soft starter, the fault must be cleared without risk of injury to personnel. There is no requirement that the soft starter must remain operational after the fault.
HRC fuses (such as Ferraz/Mersen AJT fuses) can be used for Type 1 coordination according to IEC 60947-4-2 standard.

Type 2 Coordination

Type 2 coordination requires that in the event of a short circuit on the output side of a soft starter, the fault must be cleared without risk of injury to personnel or damage to the soft starter.
Semiconductor fuses for Type 2 circuit protection are additional to HRC fuses or MCCBs that form part of the motor branch circuit protection.
16 EMX4i User Manual 710-14888-00C
Page 18
SYSTEM DESIGN
CAUTION
CAUTION
Nominal Rating
(A)
SCR I2t (A2s)
Type 1
coordination 480 VAC, 65 kA Bussmann NH
fuse links
Type 2
coordination 690 VAC, 65 kA
Bussmann DIN 43 653
EMX4i-0042B
42
7200
63NHG000B
170M3013
EMX4i-0052B
52
80NHG000B
EMX4i-0184B
184
250NHG2B
EMX4i-0200B
200
320000
170M3020
EMX4i-0550B
550
781000
630NHG3B
170M6012
EMX4i-0580B
580
DC Brake: A high brake torque setting can result in peak currents up to motor DOL being drawn while the motor is stopping. Ensure protection fuses installed in the motor branch circuit are selected appropriately.
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.

3.12 IEC Coordination with Short Circuit Protection Devices

These fuses were selected based on start current of 300% FLC for 10 seconds.
EMX4i-0024B 24 1150 40NHG000B 170M3010
EMX4i-0064B 64 15000 100NHG000B 170M3014 EMX4i-0069B 69 EMX4i-0105B 105 80000 EMX4i-0115B 115 EMX4i-0135B 135 125000
EMX4i-0229B 229 EMX4i-0250B 250
160NHG00B
315NHG2B
170M3015
170M3016
170M3021 EMX4i-0352B 352 202000 355NHG2B 170M6009 EMX4i-0397B 397
400NHG2B
EMX4i-0410B 410 320000 425NHG2B 170M6010
710-14888-00C EMX4i User Manual 17
Page 19
SYSTEM DESIGN
Model
Nominal Rating (A)
3 cycle short cct rating
@600 VAC ##1 †
EMX4i-0069B
69
10 kA
EMX4i-0105B
105
EMX4i-0250B
250
EMX4i-0352B
352

3.13 UL Coordination with Short Circuit Protection Devices

Standard Fault Short Circuit Current Ratings

Suitable for use on a circuit capable of delivering not more than the stated level of amperes (symmetrical rms, refer ##1 in table), 600 VAC maximum.
• Maximum fuse rating (A) – Standard fault short circuit current
EMX4i-0024B 24 5 kA EMX4i-0042B 42 EMX4i-0052B 52 EMX4i-0064B 64
EMX4i-0115B 120 EMX4i-0135B 135 EMX4i-0184B 184 EMX4i-0200B 225 EMX4i-0229B 229 18 kA
EMX4i-0397B 397 EMX4i-0410B 410 EMX4i-0550B 550 30 kA EMX4i-0580B 580
† Suitable for use in a circuit with the prospective current noted, when protected by any Listed fuses or Listed circuit breakers sized according to the NEC.
18 EMX4i User Manual 710-14888-00C
Page 20
SYSTEM DESIGN
Model
Nominal
Rating (A)
Short Circuit
Rating @ 480 VAC
max.
Listed fuse rating
(A)
##3
Fuse class
##2
EMX4i-0042B
42 50
EMX4i-0052B
52 60
EMX4i-0135B
135 150
EMX4i-0184B
184 200
EMX4i-0200B
225 225
J, T
EMX4i-0410B
410 450
EMX4i-0550B
550 600
EMX4i-0580B
580 600

High Fault Short Circuit Current Ratings

• Maximum fuse rating (A) – High fault short circuit current
Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes, 480 VAC maximum, when protected by fuses of the stated class and rating (refer ##2 and ##3 in table).
EMX4i-0024B 24
30
Any
(J, T, K-1, RK1, EMX4i-0064B 64 EMX4i-0069B 69 EMX4i-0105B 105
80 80
125
RK5)
EMX4i-0115B 120 65 kA 125 J, T, K-1, RK1
EMX4i-0229B 229 EMX4i-0250B 250 EMX4i-0352B 352 EMX4i-0397B 397
250 300 400 450
Any
710-14888-00C EMX4i User Manual 19
(J, T, K-1, RK1,
RK5)
Page 21
SYSTEM DESIGN
Model
Nominal
Rating (A)
Breaker 1: Eaton
(rating, A)
##4
Breaker 2: GE
(rating, A)
##5
Breaker 3: LS
(rating, A) 1
##6
UTS150H-xxU-040
UTS150H-xxU-050
UTS150H-xxU-060
EMX4i-0064B
64
EMX4i-0229B
229
SELA36AT0400
UTS150H-xxU-300
EMX4i-0352B
352
• Circuit breakers – High fault short circuit current
Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes, 480 VAC maximum, when protected by circuit breaker models noted in ##4, ##5 or ##6.
EMX4i-0024B 24 HFD3030 (30 A)
EMX4i-0042B 42 HFD3050 (50 A)
EMX4i-0052B 52 HFD3060 (60 A)
HFD3100 (100 A)
EMX4i-0069B 69 EMX4i-0105B 105
HFD3125 (125 A)
EMX4i-0115B 120
EMX4i-0135B 135 HFD3150 (150 A)
EMX4i-0184B 184 EMX4i-0200B 225 HFD3250 (250 A)
SELA36AT0060
(60 A)
SELA36AT0150
(150 A)
SELA36AT0250
(250 A)
(40 A)
(50 A)
(60 A)
UTS150H-xxU-100
(100 A)
UTS150H-xxU-125
(125 A)
UTS150H-xxU-150
(150 A)
UTS150H-xxU-250
(250 A)
EMX4i-0250B 250 HFD3300 (300 A)
EMX4i-0397B 397
EMX4i-0410B 410
EMX4i-0550B 550
EMX4i-0580B 580 UTS150H-NG0-800
1
For LS breakers, xx represents FM, FT or AT.
20 EMX4i User Manual 710-14888-00C
HFD3400 (400 A)
HFD3600 (600 A)
(400 A)
SELA36AT0600
(600 A)
(300 A)
UTS150H-xxU-400
(400 A)
UTS150H-xxU-600
(600 A)
UTS150H-xxU-800
(800 A)
Page 22
SYSTEM DESIGN
Model
SCR I2t (A2s)
EMX4i-0042B
EMX4i-0052B
EMX4i-0064B
EMX4i-0184B
EMX4i-0200B
EMX4i-0229B
EMX4i-0550B
EMX4i-0580B

3.14 Fuse Selection for Type 2 Coordination

Type 2 coordination is achieved by using semiconductor fuses. These fuses must be able to carry motor start current and have a total clearing I soft starter SCRs.
When selecting semiconductor fuses for EMX4i, use the I2t values in the table. For further information on selecting semiconductor fuses, contact your local
distributor. I2t values for Type 2 coordination
EMX4i-0024B 1150
2
t less than the I2t of the
7200
15000
EMX4i-0069B EMX4i-0105B
80000
EMX4i-0115B EMX4i-0135B 125000
320000
EMX4i-0250B EMX4i-0352B
202000
EMX4i-0397B EMX4i-0410B 320000
781000
710-14888-00C EMX4i User Manual 21
Page 23
SYSTEM DESIGN

3.15 Specifications

Supply

Mains voltage (L1, L2, L3)
EMX4i-xxxxB-V5 ....................................................... 200~525 VAC (± 10%)
EMX4i-xxxxB-V7 ....................................................... 380~690 VAC (± 10%)
Control voltage (A1, A2, A3)
EMX4i-xxxxB-xx-C1 (A1, A2) ........... 110~120 VAC (+10%/-15%), 600 mA
EMX4i-xxxxB-xx-C1 (A2, A3) ........... 220~240 VAC (+10%/-15%), 600 mA
EMX4i-xxxxB-xx-C2 (A1, A2) ........................... 24 VAC/VDC (± 20%), 2.8 A
Mains frequency .............................................................. 50 Hz~60 Hz (±5 Hz)
Rated insulation voltage to earth ....................................................... 600 VAC
Rated impulse withstand voltage ............................................................. 6 kV
Form designation ..................................................................................................
................. Bypassed or continuous, semiconductor motor starter form 1

Short circuit capability

Coordination with semiconductor fuses .............................................. Type 2
Coordination with HRC fuses ................................................................ Type 1

Electromagnetic capability (compliant with EU Directive 2014/35/EU)

EMC Immunity .......................................................................... IEC 60947-4-2
EMC Emissions ........................................................... IEC 60947-4-2 Class B

Inputs

Input rating ......................................................... Active 24 VDC, 8 mA approx
Motor thermistor (B4, B5) .................................. Trip >3.6 kΩ, reset <1.6 kΩ

Outputs

Relay outputs .............. 10 A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Main contactor (33, 34) ...................................................... Normally Open
Relay output A (41, 42, 44) ...................................................... Changeover
Relay output B (53, 54) ....................................................... Normally Open
Analog output (21, 22)
Maximum load ................................................... 600 Ω (12 VDC @ 20 mA)
Accuracy .............................................................................................. ± 5%
22 EMX4i User Manual 710-14888-00C
Page 24

Environmental

Operating temperature ................ -10 ˚C~60 ˚C, above 40 ˚C with derating
Storage temperature .............................................................. -25 °C~+ 60 °C
Operating Altitude ........................... 0~1000 m, above 1000 m with derating
Humidity ............................................................... 5%~95% Relative Humidity
Pollution degree ................................................................ Pollution Degree 3
Vibration .................................................................................... IEC 60068-2-6
Protection
EMX4i-0024B~EMX4i-0135B .............................................................. IP20
EMX4i-0184B~EMX4i-0580B .............................................................. IP00

Heat dissipation

During Start .................................................................. 4.5 watts per ampere
During Run
EMX4i-0024B~EMX4i-0052B ........................................ ≤ 35 watts approx
SYSTEM DESIGN
EMX4i-0064B~EMX4i-0135B ........................................ ≤ 50 watts approx
EMX4i-0184B~EMX4i-0250B ...................................... ≤ 120 watts approx
EMX4i-0352B~EMX4i-0580B ...................................... ≤ 140 watts approx

Motor Overload Protection

Default: The default settings of parameters 1D, 1E and 1F provide Motor Overload Protection: Class 10, Trip Current 105% of FLA (full load amperage) or equivalent.

Certification

CCC ................................................................................................... GB 14048.6
CE .................................................................................................... EN 60947-4-2
C-UL ...................................................................................... C22.2 Nº 60947-4-2
UL ..................................................................................................... UL 60947-4-2
Marine
Lloyds ................................................... Lloyds Marine No 1 Specification
ABS .................................................................... Steel Vessels Rules 2010
RCM ......................................................................................... IEC 60947-4-2

Operational life (internal bypass contacts)

.......................................................................................... 100 000 operations

3.16 Disposal Instructions

Equipment containing electrical components may not be disposed of together with domestic waste.
It must be collected separately as electrical and electronic waste
710-14888-00C EMX4i User Manual 23
according to local and currently valid legislation.
Page 25
INSTALLATION
WARNING
WARNING
MENU

4. Installation

4.1 Command Source

The EMX4i can be started and stopped via the digital inputs, remote keypad, communication network, smart card or scheduled auto-start/stop. The command
Do not apply mains voltage to the starter until all wiring is complete.
Always apply control voltage before (or with) mains voltage.
source can be set via the Setup Tools, or using parameter 1A

4.2 Setup Procedure Overview

1. Mount the soft starter (refer to
2. Connect control wiring (refer to
3. Apply control voltage to the starter.
4. Configure your application:
1. Press
2. Press
to open the Menu.
to open the Quick Setup menu.
3. Scroll through the list to find your application, then press
configuration process (refer to
5. If your application is not listed in Quick Setup:
1. Press
2. Use
to return to the Menu.
to scroll to Main Menu and press .
3. Scroll to Motor Details and press
Physical Installation
Input Terminals
Quick Setup
, then press again to edit
on page 25 for details).
on page 33 for details).
on page 14 for details).
Command Source
to begin the
.
parameter 1B
Motor Full Load Current
.
4. Set parameter 1B to match the motor's full load current (FLC).
5. Press
6. Close the Menu by pressing
to save the setting.
repeatedly.
7. (Optional) Use the built-in simulation tools to check that the control wiring is
connected correctly (refer to
Run simulation
on page 35).
8. Power off the soft starter.
9. Connect the motor cables to starter output terminals 2/T1, 4/T2, 6/T3.
10. Connect mains supply cables to starter input terminals 1/L1, 3/L2, 5/L3 (refer
Power Terminations
to
The soft starter is now ready to control the motor.
24 EMX4i User Manual 710-14888-00C
on page 28).
Page 26

4.3 Inputs

CAUTION
NOTE
B4 B5 10 11 12 13 14 15 21 22
B4, B5
Motor thermistor input
The control inputs are powered by the soft starter. Do not apply external
INSTALLATION
voltage to the control input terminals.
Cables to the control inputs must be segregated from mains voltage and motor cabling.

Input Terminals

10, 11 Reset input 11, 12 Start/stop input 13, 14 Programmable input A
(default = Input Trip (N/O))
13, 15 Programmable input B
(default = Input Trip (N/O))
USB port

Motor Thermistor

Motor thermistors can be connected directly to the EMX4i. The soft starter will trip when the resistance of the thermistor circuit exceeds approximately 3.6 kΩ or falls below 20 Ω.
710-14888-00C EMX4i User Manual 25
Page 27
INSTALLATION
NOTE
NOTE
A
B
17622.A
A
B
WARNING NOTE
The thermistors must be wired in series. The thermistor circuit should be run in screened cable and must be electrically isolated from earth and all other power and control circuits.
The thermistor input is disabled by default, but activates automatically when a thermistor is detected. If thermistors have previously been connected to the EMX4i but are no longer required, use the Thermistor Reset function to disable the thermistor. Thermistor Reset is accessed via the Setup Tools.

Reset/Starter Disable

The reset input (10, 11) is normally closed by default. The EMX4i will not perform a start if the reset input is open. The display will show "Not Ready".
If the reset input opens while the EMX4i is running, the starter will remove power and allow the motor to coast to stop.
The reset input can be configured for normally open or normally closed operation. Use parameter 7I
Reset/Enable Logic
.

Start/Stop

The EMX4 requires two-wire control.
Reset Start/Stop
If the start input is closed when control voltage is applied, the starter will attempt to start.
Check that the start/stop input is open before applying control voltage.
The EMX4i will only accept commands from the control inputs if parameter
Command Source
1A
is set to Digital Input.

Programmable Inputs

The programmable inputs (13, 14 and 13, 15) allow external equipment to control the starter.
The operation of the programmable inputs is controlled by parameters 7A~7H.
26 EMX4i User Manual 710-14888-00C
Page 28
INSTALLATION
33 34 41 42 44 53 54
B4 B5 10 11 12 13 14 15 21 22
33, 34

Main contactor output

41, 42, 44
Relay output A (default = Run)
CAUTION

USB Port

The USB port can be used to upload a configuration file, or download parameter settings and event log information from the starter. Refer to page 36 for details.

4.4 Outputs

Output Terminals

USB Save & Load
on
21, 22 Analog output
53, 54 Relay output B (default = Run)

Analog Output

The EMX4i has an analog output, which can be connected to associated equipment to monitor motor performance.
The operation of the analog output is controlled by parameters 9A~9D.
Main Contactor Output
The main contactor output (33, 34) closes as soon as the soft starter receives a start command and remains closed while the soft starter is controlling the motor (until the motor starts a coast to stop, or until the end of a soft stop). The main contactor output will also open if the soft starter trips.
Some electronic contactor coils are not suitable for direct switching with PCB mount relays. Consult the contactor manufacturer/supplier to
710-14888-00C EMX4i User Manual 27
confirm suitability.
Page 29
INSTALLATION
A3 A1 A2
C1 C1 C2
NOTE

Programmable Outputs

The programmable outputs (41, 42, 44 and 53, 54) can report the status of the starter, or can be used to control associated equipment.
The operation of the programmable outputs is controlled by parameters 8A~8F.

4.5 Control Voltage

Control Voltage Terminals

Connect the control supply according to the supply voltage being used.
• EMX4i-xxxxB-xx-
• EMX4i-xxxxB-xx-
• EMX4i-xxxxB-xx-
(110~120 VAC): A1, A2 (220~240 VAC): A2, A3 (24 VAC/VDC): A1, A2

UL Compliant Installation

For models EMX4i-0184B to EMX4i-0580B to be UL compliant, supplementary or branch overcurrent protection must be used on the control circuit supply (A1, A2, A3), in accordance with the electrical code applicable at the installation location.

4.6 Power Terminations

Some units use aluminium busbars. When connecting power terminations, we recommend cleaning the surface contact area thoroughly (using an emery or stainless steel brush) and using an appropriate jointing compound to prevent corrosion.
28 EMX4i User Manual 710-14888-00C
Page 30
INSTALLATION
EMX4i-0024B~EMX4i-0135B
05966.E
112
90.A
EMX4i-0184B~EMX4i-0250B
EMX4i-0352B~EMX4i-0580B
19 Nm (14.0 ft-lb)
66 Nm (49.0 ft-lb)
6 mm
20 mm
9 mm
(M8)
17045.A
6 mm
34 mm
13 mm
(M12)
17047.A
NOTE
Model
Recommended lugs part No.
EMX4i-0229B
EMX4i-0550B
OPHD 240-12
The power input and output terminals for EMX4 are at the bottom of the unit.
• Models EMX4i-0024B~EMX4i-0135B use cage clamps. Use only copper
stranded or solid conductors, rated for 75 ºC or higher.
• Models EMX4i-0184B~EMX4i-0580B use busbars. Use copper or
aluminium conductors, stranded or solid, rated for 60 ºC/75 ºC.
Cable size: 6-70 mm
2
(AWG 10-2/0) Torque: 4 Nm (2.9 ft-lb) 14 mm (0.55 inch)
Torx T20 x 150
Flat 7 mm x 150
If the installation requires large diameter cables, it is possible to complete each termination with two smaller cables, one on each side of the busbar.

UL Compliant Installation

For models EMX4i-0184B to EMX4i-0580B to be UL compliant, you must use the recommended pressure terminal/connector.
EMX4i-0184B EMX4i-0200B OPHD 185-10
EMX4i-0250B EMX4i-0352B EMX4i-0397B OPHD 150-12 EMX4i-0410B
EMX4i-0580B
710-14888-00C EMX4i User Manual 29
Page 31
INSTALLATION
NOTE
34
33
K1
K1F1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
M
3
K1
Main contactor (strongly recommended)
F1
Fuses or circuit breaker (optional)
M
3
U1(1) U2(4)
V1(2)
V2(5)
W1(3) W2(6)
K1
F1
34
33
K1
6/T3
2/T1
5/L3
3/L2
1/L1
4/T2
33, 34
Main contactor output

Motor Connection

The EMX4i can be connected to the motor in-line or inside delta (also called three-wire and six-wire connection). When connecting in inside delta, enter the motor full load current (FLC) for parameter 1B. The EMX4i will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
If the starter is not correctly detecting the motor connection, use parameter
Motor Connection
20F
• In-line installation
33, 34 Main contactor output
• Inside delta installation
.
K1 Main contactor
30 EMX4i User Manual 710-14888-00C
F1 Fuses or circuit breaker (optional)
Page 32
INSTALLATION
A
+
M
42
41
6/T3
2/T1
33
34
4/T2
54
53
44
21
22
B5
B4
12
13
14
15
11
A2
A1
A3
5/L3
3/L2
10
1/L1
F1
S1
S2 K1
K1
7
6
5
3
2
1
10
4
9
8
17674.B
(L/+)

4.7 Typical Installation

The EMX4i is installed with a main contactor (AC3 rated). Control voltage must be supplied from the input side of the contactor.
The main contactor is controlled by the main contactor output (33, 34).
710-14888-00C EMX4i User Manual 31
Page 33
INSTALLATION
1
Three-phase supply
K1
Main contactor
2
Motor F1
Semiconductor fuses
3
Control voltage (soft starter)
10, 11 (S1)
Reset
4
5
6
Relay outputs
13, 15
Programmable input B
7
8 9
10
Communications / Smart
21, 22
Analog output
Digital inputs 11, 12 (S2) Start/Stop Motor thermistor input 13, 14 Programmable input A
Analog output B4, B5 Motor thermistor input
(optional)
(default = Input Trip (N/O))
(default = Input Trip (N/O))
Control voltage (external
33, 34 Main contactor output
equipment) Pilot lamps 41, 42, 44 Relay output A (default = Run)
53, 54 Relay output B (default = Run)
card expansion port
32 EMX4i User Manual 710-14888-00C
Page 34
INSTALLATION
Application
Start Mode Start Ramp Time
(seconds)
Initial Current
(%)
Current Limit
(%)
Adaptive Start
Profile
Stop Mode Stop Time
(seconds)
Adaptive Stop
Profile
Pump Centrifugal
Adaptive
10
200
500
Early
Adaptive
15
Late
Pump Hydraulic
Constant
2
200
350
n/a
Coast To
n/a
n/a
Fan Undamped
Constant
2
200
450
n/a
Coast To
n/a
n/a
Compressor
Constant
2
200
450
n/a
Coast To
n/a
n/a
Bow thruster
Constant
5
100
400
n/a
Coast To
n/a
n/a
NOTE

4.8 Quick Setup

The Quick Setup Menu makes it easy to configure the EMX4i for common applications. The EMX4i guides you through the most common installation parameters, and suggests a typical setting for the application. You can adjust each parameter to suit your exact requirements.
All other parameters remain at default values. To change other parameter values or review the default settings, use the menu (refer to
Always set parameter 1B full load current.
Motor Full Load Current
Control
Pump bore Adaptive
Control
3 200 500 Early
to match the motor's nameplate
accel.
accel.
Current
Fan Damped Constant
2 200 350 n/a Coast To
Parameter List
Control Adaptive
Control
Stop
for details).
decel.
3 Late
decel.
n/a n/a
Compressor Screw
Recip Conveyor Constant
Bandsaw Constant
710-14888-00C EMX4i User Manual 33
Current
Current Constant
Current
Current
Current
Current
Current
2 200 400 n/a Coast To
5 200 450 n/a Coast To
2 200 450 n/a Coast To
Stop
Stop
n/a n/a
Stop
Stop
n/a n/a
Stop
Stop
n/a n/a
Stop
The Adaptive Start and Stop Profile settings only apply when using Adaptive Control. The settings are ignored for all other start and stop modes.
Page 35
SETUP TOOLS
MENU
MENU
LOCAL/REMOTE

5. Setup Tools

Setup Tools includes options to load or save parameters to a backup file, set the starter's network address, check the status of the inputs and outputs, reset the thermal models or test operation using the Run Simulation.
To access the Setup Tools, press
to open the Menu then select Setup Tools.

5.1 Set Date and Time

To set the date and time:
1. Press
to open the menu then select Setup Tools.
2. Scroll to Set Date & Time.
3. Press the
4. Press the
5. Use the
6. Press
button to enter edit mode. and buttons to select which part of the date or time to edit.
and buttons to change the value.
after the last digit to save the setting. When the action has been completed, the screen will briefly display a confirmation message, then return to the previous menu level.

5.2 Command Source

The EMX4i can be started and stopped via the digital inputs, remote keypad, communication network, smart card or scheduled auto-start/stop. The command source can be set via the Setup Tools, or using parameter 1A
If the remote keypad is installed, the access to the Command Source function in Setup Tools.
button provides shortcut
Command Source
.

5.3 Commissioning

Commissioning lets the starter be started and stopped via the local keypad. Use the
and buttons to select a function, then press to send the selected
command to the starter. The available functions are:
• Quick stop (coast to stop)/Reset
• Start
• Stop
34 EMX4i User Manual 710-14888-00C
Page 36
SETUP TOOLS
NOTE
MENU
Apply Start Signal
3. Apply a start command from the selected NOTE
MENU to Continue
4. Press . The EMX4i simulates starting. The Run
MENU to Continue
Apply Stop Signal
6. Apply a stop command from the selected
MENU to Continue
8. Press . The EMX4i activates then deactivates
MENU to Continue

5.4 Run simulation

The run simulation simulates a motor starting, running and stopping to confirm that the soft starter and associated equipment have been installed correctly.
The soft starter must be disconnected from mains voltage. The simulation is only available when the soft starter is in Ready state.
To use the run simulation:
1. Press
to open the menu then select Setup
Tools.
2. Scroll to Run Simulation and press .
command source. The EMX4i simulates its pre-start checks and closes the main contactor relay. The Run LED flashes.
If mains voltage is connected, an error message is shown.
Run Simulation Ready
Run Simulation Pre-Start Checks MENU to Continue
Run Simulation ATTENTION! Remove Mains Volts
LED flashes.
5. Press . The EMX4i simulates running.
command source. The EMX4i simulates stopping. The Run LED flashes.
7. Press . The Ready LED flashes and the main
contactor relay opens.
each programmable output.
Run Simulation Starting X:XXs
Run Simulation Running
Run Simulation Stopping X:XXs MENU to Continue
Run Simulation Stopped
Run Simulation Prog Relay A On
9. Press to return to the Setup Tools.
710-14888-00C EMX4i User Manual 35
Page 37
SETUP TOOLS
1. Press MENU to open the menu then select Setup
2. Scroll to Load/Save Settings and press the
Yes
NOTE

5.5 Load/Save Settings

Load/Save Settings allows users to:
• Reset the EMX4i's parameters to default values
• Load parameter settings from an internal file
• Save the current parameter settings to an internal file
The internal file contains default values until a user file is saved. To load or save parameter settings:
Tools.
Load/Save Settings
button.
3. Scroll to the required function and press the
button.
4. At the confirmation prompt, select YES to confirm
or NO to cancel, then press
to proceed.
When the action has been completed, the screen will briefly display a confirmation message, then return to the previous menu level.

5.6 USB Save & Load

The USB Save & Load menu lets you:
• Save parameter settings and all event log entries to an external file (CSV
format)
• Save parameter settings to an external file (proprietary format)
Load Defaults Load User Set Save User Set
Load Defaults No
• Load parameter settings from a previously saved external file
• Load custom messages to display on the keypad when a programmable
input is active
The EMX4 supports FAT32 file systems. The EMX4's USB functions are not compatible with NTFS file systems.
36 EMX4i User Manual 710-14888-00C
Page 38

Save & Load Procedure

MENU
Load Master Params
Yes
SETUP TOOLS
1. Connect the external drive to the USB port.
2. Press
to open the menu then select Setup
Tools.
3. Scroll to USB Save & Load and press the button.
4. Scroll to the required function and press the
button.
5. At the confirmation prompt, select YES to confirm
or NO to cancel, then press
to proceed.
When the action has been completed, the screen
USB Save & Load Save Params and Logs Save Master Params
Save Params and Logs No
will briefly display a confirmation message, then return to the previous menu level.

File Locations and Formats

Save Parameters and Logs: The EMX4i will create a directory at the top level of the USB drive, named with the soft starter's serial number. The event log and parameter settings are saved as individual CSV files, and the soft starter's software and system information are saved to a text file.
Save Master Parameters: The EMX4i will create a file called Master_Parameters.par, in the top level of the USB drive.
Load Master Parameters: The EMX4i will load the file Master_Parameters.par from the top level of the USB drive. This file can be created or edited using WinMaster management software.
Load Custom Message: The EMX4i will load the files Custom_Message_A.txt and Custom_Message_B.txt from the top level of the USB drive.
710-14888-00C EMX4i User Manual 37
Page 39
SETUP TOOLS
MENU
2. Scroll to Auto-Start/Stop and press the button.
Start/Stop Monday
5. To save changes, press the button. The EMX4i will confirm the changes. MENU
4. The first digit of the address will be highlighted.

5.7 Auto-Start/Stop

The EMX4i can be configured to automatically start and/or stop the motor at a particular time, or run it in cycles of a specified duration.
The Auto-Start/Stop option in Setup Tools gives quick access to the auto-start/stop parameters.
1. Press
to open the menu then select Setup
Tools.
Auto-Start/Stop
3. Scroll to the required function and press the
button.
4. Adjust the settings as required:
Press the
and buttons to select which information to edit. Use the
To cancel changes, press the button.
and buttons to change the value.
Start/Stop Mode Start/Stop Sunday
Start/Stop Sunday Start/Stop Disable Start Time: 00:00 Stop Time: 00:00

5.8 Network Address

To use the EMX4i on an Ethernet network, separate addresses must be configured for:
• IP Address
• Gateway Address
• Subnet Mask
To set the network addresses:
1. Press
to open the menu then select Setup Tools.
2. Scroll to Network Address and press the
3. Scroll to the required function and press the
5. Use and to select which digit to alter.
Use the
6. Press
and buttons to change the value.
after the last digit to save the setting.
When the action has been completed, the screen will briefly display a confirmation message, then return to the previous menu level.
button.
button.
Set IP Address
192.168.000.002
38 EMX4i User Manual 710-14888-00C
Page 40
SETUP TOOLS
NOTE
NOTE
The top line of the screen shows the start/stop, reset
33 34 41 42 44 53 54
10 11 12 13 14 15 21 22
7654321
1
5
2
6
3
7
4
The top line of the screen shows the state of the The top line of the screen shows the product name.
0410-V5-S1-C1
The network address can also be set using parameters 12H~12S.
To configure the EMX4i for use with other communication protocols, use parameters 12A~12G.

5.9 Digital I/O State

and programmable inputs. The bottom line of the screen shows the fixed Main Contactor output, then programmable outputs A and B.
10, 11: Reset input 11, 12: Start/stop input
33, 34: Main contactor output 41, 42, 44: Relay output A
Digital I/O State Inputs: 00000000 Outputs: 00000000
13, 14: Programmable input A 13, 15: Programmable input B
53, 54: Relay output B

5.10 Analog I/O State

motor thermistor input. The bottom line of the screen shows the value of the analog output.
Thermistor input:
S = Short H = Hot C = Cold O = Open

5.11 Serial Number & Rating

Analog I/O State Thermistor: 0 4-20mA Output: 04.0
mA
Serial Number & Rating
The middle line shows the unit's serial number. The bottom line of the screen shows the model number.
710-14888-00C EMX4i User Manual 39
EMX4i 123456-123
Page 41
SETUP TOOLS
NOTE
CAUTION

5.12 Software Versions

The software versions screen reports the version of each software component in the starter:
• user interface
• motor control
• remote keypad (if connected)
• parameter list
• bootloader
• expansion card (if fitted)
Updated software, including alternative languages, can be loaded into the starter via the USB port if required. Contact your local supplier for further information.

5.13 Thermistor Reset

The thermistor input is disabled by default, but activates automatically when a thermistor is detected. If thermistors have previously been connected to the EMX4i but are no longer required, use the Thermistor Reset function to disable the thermistor.

5.14 Reset Thermal Model

The soft starter's thermal modelling software constantly monitors the motor's performance. This allows the starter to calculate the motor's temperature and ability to start successfully at any time.
The thermal model can be reset if required.
Resetting the motor thermal model will compromise thermal model protection and may compromise motor life. Only reset the thermal model in
40 EMX4i User Manual 710-14888-00C
an emergency.
Page 42

6. Logs

MENU
LOGS
NOTE
STORE
NOTE
The Logs Menu provides information on events, trips and starter performance.
LOGS
To access the Logs Menu on the local keypad, press select Logs. On the remote keypad, press
.
to open the Menu then

6.1 Event Log

The Event Log stores details of the starter's most recent trips, warnings, and operations (including starts, stops and configuration changes).
Event 1 is the most recent and event 384 is the oldest stored event.
The event log can be exported to an external file for analysis away from the starter. Refer to
USB Save & Load
on page 36 for details.

6.2 Counters

The counters store statistics on the starter's operation:
• Hours run (lifetime and since counter last reset)
• Number of starts (lifetime and since counter last reset)
To view the counters:
• Number of times the thermal model has been reset
1. Open the Logs.
2. Scroll to counters and press
3. Use the
and buttons to scroll through the counters. Press to view
.
details.
4. To reset a counter, press
Reset/Do Not Reset. Press
To close the counter and return to the Logs, press
then use the and buttons to select
to confirm the action.
.

6.3 QR Code

The EMX4i can generate a QR code which allows a smartphone to display key information about the starter, including serial number, firmware versions and installed options, plus details of the starter’s three most recent trips. This information can be useful when requesting assistance from your local supplier.
You must install AuCom's free Pocket Technician app in order to read the
710-14888-00C EMX4i User Manual 41
QR code.
Page 43
KEYPAD AND FEEDBACK
Local keypad
Remote keypad (if installed)
Ready Run Trip Local
Menu Store
Exit
Reset
1
2
3
17691.C
Start Stop Reset
LC
L
RMT
Menu Store
Exit
Alt
Logs T
ools
17692.B
1
2
3
4
5
6
1
2
3
4
5
Soft starter local control buttons
6
Shortcut buttons for quick access to common tasks. LOGS ALT
TOOLS

7. Keypad and Feedback

7.1 The Keypad

Four-line display for status and programming details. Status LEDs Menu navigation buttons:
: Exit the menu or parameter, or cancel a parameter change. On the local
keypad, this button also resets a trip.
: Enter a menu or parameter, or save a parameter change.
: Scroll to the next or previous menu or parameter, change the setting of
the current parameter or scroll through the status screens. Shortcut to the command source menu in Setup Tools.
: Open the Logs Menu.
: Select which graph to view, or pause/restart the graph (hold longer than
0.5 seconds) : Open the Setup Tools.
42 EMX4i User Manual 710-14888-00C
Page 44
KEYPAD AND FEEDBACK
START
STOP
RESET
NOTE
NOTE NOTE

7.2 Remote Keypad

The remote keypad can be used to control the soft starter if parameter 1A
Command Source
is set to 'Remote Keypad'.
• If the remote keypad is not selected as the command source, the
and
buttons will have no effect.
• The menu navigation buttons and display on the remote keypad are
always active.
• If a button is pressed on the starter's local keypad, the display on the
remote keypad will update to match.
The remote keypad can be safely connected or removed while the starter is running. It is not necessary to remove mains or control voltage.
If parameter 1A remote keypad will cause a trip.
Command Source
is set to Remote Keypad, removing the

7.3 Lighten/Darken the Display

,
The backlight on the display can be adjusted:
• to lighten the display, hold down the
• to darken the display, hold down the
The local and remote keypads can be adjusted independently.
button and press the key
button and press the key
710-14888-00C EMX4i User Manual 43
Page 45
KEYPAD AND FEEDBACK
Ready Run
Trip
Local
17694.
A
LED name
On
Flashing
Ready
The motor is stopped and the
The motor is stopped and the
Run
The motor is in run state (receiving
The motor is starting or stopping. Trip
The starter has tripped.
The starter is in warning state.
Local
The starter is being controlled via
–
(remote keypad software version is only displayed when a remote
69.0 A
Running
69.0 A 415 V
Parameters 10H
User Parameter 1
and 10I
User Parameter 2

7.4 Starter status LEDs

starter is ready to start.
starter is not ready to start:
• waiting for the
(parameter 5P)
• the thermal models indicate the
starter and/or motor are too hot to start safely
• the reset input (10, 11) is open
full voltage).
a remote keypad.
If all LEDs are off, the starter is not receiving control voltage.

7.5 Displays

Restart Delay
The keypad displays a wide range of performance information about the soft starter. To scroll through the feedback screens, press the

Starter information

At power-up, the starter information screen shows details of the starter's rating, software versions and serial number.
Welcome
01.01/01.00/01.00
EMX4i-0069B-V5-S1-C1

Starter status screen

and buttons.
Software versions: user interface, motor control, remote keypad Model code: current rating, mains voltage, frame size, control voltage
keypad is connected)
motor running current Starter status
44 EMX4i User Manual 710-14888-00C
Page 46
KEYPAD AND FEEDBACK
000.0A 000.0A 000.0A
350 % FLC ∆ Temp 5%
Mains Frequency 59.7 Hz
Motor pf 1.01
Motor Temp 85%
05050.C
0
00.0 A 0-
400%
ALT

Current

The current screen shows real-time line current on each phase.
Phase Currents

Last Start Information

The last start information screen shows details of the most recent successful start:
• start duration (seconds)
• maximum start current drawn (as a percentage of motor full load
current)
• calculated rise in motor temperature
Last start 010 s

User configurable screen

The programmable screen can be configured to show the most important information for the particular application. Use parameters 10J ~ 10M to select which information to display.
Motor Power 37.0 kW

Date and Time

The date/time screen shows the current system date and time (24 hour format). For details on setting the date and time, refer to
Set Date and Time
on page 34.

Performance Graph

The performance graph provides a real-time display of operating performance. Use parameters 10B~10E to format the graph.
The display on the main keypad shows information for motor current.
If a remote keypad is connected, press show:
• motor current
to change the graph data. The graph can
• motor temperature
• motor pf
710-14888-00C EMX4i User Manual 45
• analog input data from the smart card (if installed)
Page 47
OPERATION
NOTE

8. Operation

8.1 Start, Stop and Reset Commands

The EMX4i can be started and stopped via the digital inputs, remote keypad, communication network, smart card or scheduled auto-start/stop. The command source can be set via the Setup Tools, or using parameter 1A
Command Source
.
• The EMX4i will only accept Start and Reset commands from the
designated command source.
• The EMX4i will accept Stop commands from the designated command
source, but can be forced to stop by opening the reset input, or by opening the start/stop input during an auto-start/stop cycle.
• The programmable input can be used to override the selected command
source (refer to parameter 7A
Input A Function
).

8.2 Command Override

The programmable input (13, 14) can be used to override the command source, for situations where the normal control mechanism has been lost. Set parameter 7A
Input A Function
Keypad'). While the input is active, the starter will only accept commands from the selected
override source. To restore control to the command source selected in parameter
to the alternative command source (eg 'Command Override:
1A
Command Source
, reopen the input.

8.3 Auto-Start/Stop

The EMX4i can be configured to automatically start and/or stop the motor at a particular time, or run it in cycles of a specified duration.
Start delay, restart delay and auto-reset delay all apply to auto-start operation.

Clock mode

The starter can start and/or stop the motor once per day. For clock mode to operate:
• parameter 4A
• parameter 1A
Auto-Start/Stop Mode Command Source
• the reset input must be closed
• the start input (11, 12) must be active. This allows the EMX4i to be stopped
via the digital inputs in an emergency.
must be set to 'Enable'
must be set to 'Clock'
Clock mode operation is controlled by parameters 4D ~ 4X.
46 EMX4i User Manual 710-14888-00C
Page 48
OPERATION
NOTE
CAUTION
phase soft start technology and additional care is

Timer mode

The starter can automatically stop the motor after a specified run time, then restart it after a specified off (stopped) time. The starter will repeat the cycle while the start signal remains active.
For timer mode to operate:
• parameter 4A
• parameter 1A
Auto-Start/Stop Mode Command Source
must be set to 'Enable'
must be set to 'Timer'
• the reset input must be closed
• the first start must be commanded by a start signal
Timer mode operation is controlled by parameters 4B ~ 4C.

8.4 PowerThrough

PowerThrough allows the soft starter to control the motor even if the soft starter is damaged on one phase. The EMX4i will use two-phase control techniques to soft start and soft stop the motor.
The starter will trip on Lx-Tx Shorted on the first start attempt after control power is applied. PowerThrough will not operate if control power is cycled between starts.
• PowerThrough is only available with in-line installations. If the starter is
installed inside delta, PowerThrough will not operate.
• PowerThrough remains active until '3-Phase Control Only' is reselected.
While operating in PowerThrough, the trip LED will flash and the display will indicate ‘2 Phase - Damaged SCR'.
PowerThrough operation does not support Adaptive Control soft starting or
soft stopping. In PowerThrough, the EMX4i will automatically select constant current soft starting and timed voltage ramp soft stopping. If PowerThrough is enabled, parameters 2C and 2D must be set appropriately.
PowerThrough uses a two­required when sizing circuit breakers and protection. Contact your local supplier for assistance.
710-14888-00C EMX4i User Manual 47
Page 49
OPERATION
NOTE
CAUTION

8.5 Emergency Mode

Emergency mode allows the EMX4i to run the motor and ignore trip conditions. Emergency mode is controlled via a programmable input (input A 13, 14 or input B
13, 15) and parameter 7A
Input A Function
/7E
Input B Function
must be set to 'Emergency Mode'. A closed circuit across 13, 14 activates emergency mode. When the EMX4i receives a start command, it will continue to run until a stop command is received, ignoring all trips and warnings.
Emergency mode can be used in conjunction with any command source.
Although emergency mode operation satisfies the functionality requirements of Fire Mode, AuCom does not recommend its use in situations that require testing and/or compliance with specific standards as it is not certified.
Continued use of emergency mode is not recommended. Emergency mode may compromise the starter and/or motor life as all protections and trips are disabled.
Using the starter in emergency mode will void the product warranty.

8.6 Auxiliary Trip

An external trip circuit (such as a low pressure alarm switch for a pumping system) can be used to trip the soft starter and stop the motor. The external circuit is connected to a programmable input (input A 13, 14 or input B 13, 15). To control the behaviour of the trip, set the following parameters:
• Parameter 7A
• Parameter 7B
the input trip to when the soft starter is running only.
• Parameter 7C
activating and the soft starter tripping.
• Parameter 7D
monitors the state of the input, after the start signal. For example, a delay may be required to allow time for pipeline pressure to build up.
• Parameter 7J
Input A Function
Input A Trip
: select 'Input Trip (N/O)'.
: set as required. For example, 'Run Only' limits
Input A Trip Delay
Input A Initial Delay
Input A Name
: select a name, eg 'Input A Trip' (optional).
: sets a delay between the input
: sets a delay before the soft starter
48 EMX4i User Manual 710-14888-00C
Page 50
OPERATION
Application
Start Mode
Start Ramp
Time
(seconds)
Initial Current
(%FLC)
Current Limit
(%FLC)
Stop Mode
Stop Time
(seconds)
Bow thruster
Constant Current
5
100
400
Coast To Stop
n/a
Centrifuge (Separator)
Constant Current
1
200
450
Coast To Stop
n/a
Chipper
Constant Current
1
200
450
Coast To Stop
n/a
Compressor - reciprocating
Compressor - reciprocating
Compressor - screw -
Compressor - screw ­Conveyor - inclined
Constant Current
2
200
450
Coast To Stop
n/a
Conveyor - vertical (bucket)
Constant Current
2
200
450
Coast To Stop
n/a
Crusher - cone
Constant Current
1
200
350
Coast To Stop
n/a

8.7 Typical Control Methods

The requirements of an application differ between each installation, but the methods listed below are often a good starting point for common applications.
- loaded
Constant Current
Constant Current
- unloaded
Constant Current
loaded
Constant Current
unloaded Conveyor - horizontal Constant Current 5 200 400 TVR Soft Stop 10
Crusher - jaw Constant Current 1 200 450 Coast To Stop n/a Crusher - rotary Constant Current 1 200 400 Coast To Stop n/a Debarker Constant Current 1 200 350 Coast To Stop n/a Fan - axial (damped) Constant Current 1 200 350 Coast To Stop n/a Fan - axial (undamped) Constant Current 1 200 450 Coast To Stop n/a Fan - centrifugal (damped) Constant Current 1 200 350 Coast To Stop n/a
1 200 450 Coast To Stop n/a
1 200 400 Coast To Stop n/a
1 200 400 Coast To Stop n/a
1 200 350 Coast To Stop n/a
Fan - centrifugal (undamped)
Fan - high pressure Constant Current 1 200 450 Coast To Stop n/a Mill - ball Constant Current 1 200 450 Coast To Stop n/a Mill - hammer Constant Current 1 200 450 Coast To Stop n/a
Pump - bore
Pump - centrifugal
Pump - Hydraulic Constant Current 2 200 350 Coast To Stop n/a Pump - positive
displacement
710-14888-00C EMX4i User Manual 49
Constant Current
Adaptive Control
(Early accel.)
Adaptive Control
(Early accel.)
Adaptive Control
(Const. accel.)
1 200 450 Coast To Stop n/a
3 n/a 500
10 n/a 500
10 n/a 400
Adaptive Control
(Late decel.)
Adaptive Control
15
(Late decel.)
Adaptive Control
10
(Const. decel.)
3
Page 51
OPERATION
Application
Start Mode
Start Ramp
Time
(seconds)
Initial Current
(%FLC)
Current Limit
(%FLC)
Stop Mode
Stop Time
(seconds)
(%motor full load current)
700%
600%
500%
300%
100%
400%
200%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
1
3
2
Pump - submersible
Adaptive Control
5 n/a 500
(Early accel.)
Adaptive Control
5
(Late decel.) Saw - bandsaw Constant Current 1 200 450 Coast To Stop n/a Saw - circular Constant Current 1 200 350 Coast To Stop n/a Shredder Constant Current 1 200 450 Coast To Stop n/a

8.8 Soft Start Methods

Constant Current

Constant current is the traditional form of soft starting, which raises the current from zero to a specified level and keeps the current stable at that level until the motor has accelerated.
Constant current starting is ideal for applications where the start current must be kept below a particular level.
1:
Initial Current
(parameter 2C)
Current
Rotor speed (% full speed)

Constant Current with Current Ramp

Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3), over an extended period of time (2).
Current ramp starting can be useful for applications where:
• the load can vary between starts (for example a conveyor which may start
loaded or unloaded). Set the initial current (parameter 2C) to a level that will start the motor with a light load, and the current limit (parameter 2D) to a level that will start the motor with a heavy load.
• the load breaks away easily, but starting time needs to be extended (for
50 EMX4i User Manual 710-14888-00C
example a centrifugal pump where pipeline pressure needs to build up slowly).
• the electricity supply is limited (for example a generator set), and a slower
application of load will allow greater time for the supply to respond.
2:
Current Limit
(parameter 2D)
3: Full voltage current
Page 52
(%motor full load current)
700%
600%
500%
300%
100%
400%
200%
1
4
3
2
1:
Time
(%motor full load current)
1
2
6
4
5
3
Rotor speed (% full speed)
NOTE
NOTE
Initial Current
OPERATION
(parameter 2C)
Start Ramp Time
2:
Current Limit
3:
Current
(parameter 2B)
(parameter 2D)
4: Full voltage current

Constant Current with Kickstart

Kickstart provides a short boost of extra torque at the beginning of a start, and can be used in conjunction with current ramp or constant current starting.
Kickstart can be useful to help start loads that require high breakaway torque but then accelerate easily (for example helical rotor pumps).
1:
Kickstart Level Kickstart Time
2:
Initial Current
3:
Current
4:
Start Ramp Time
(parameter 2G)
(parameter 2F)
(parameter 2C)
(parameter 2B)

Timed Voltage Ramp

Timed voltage ramp (TVR) soft starting ramps the application of voltage to the motor over a defined time period. The voltage ramp reduces the initial starting torque and slows the motor's rate of acceleration.
TVR starting can be useful for applications where multiple motors of different sizes are connected in parallel, and/or the loads are not mechanically linked.
TVR soft starting is not suitable for high inertia loads (such as fans), which require a high level of voltage to accelerate the load.
For multiple motors of the same sizes, and/or mechanically coupled loads,
For a timed voltage ramp start, the following are typical values and can be adjusted to suit your specific application:
710-14888-00C EMX4i User Manual 51
use constant current starting.
• Add the FLC value of all the connected motors. Use this combined value
to set parameter 1B value must not exceed the starter rating.)
Current Limit
5: 6: Full voltage current
(parameter 2D)
Motor Full Load Current
. (Note that the combined
Page 53
OPERATION
3
1
2
6
5
4
09294.B
1:
Initial Current
(parameter 2C)
NOTE
0
1
0%
20%
30%
4
0
%
50%
60
%
70%
80
%
90%
10
0%
0
482
7.C
1
2
3
4
Time
NOTE
Motor Full
• Set parameter 2C
500% and set the ramp time as required (parameter 2B
).
Time
Initial Current
to 100%, parameter 2D
2:
Current Limit
3:
Start Ramp Time
(parameter 2D)
Current Limit
Start Ramp
(parameter 2B)
to
4: Full voltage 5: Motor 1 current 6: Motor 2 current
Time

Adaptive Control for Starting

In an adaptive control soft start, the EMX4i adjusts the current in order to start the motor within a specified time and using a selected acceleration profile.
The EMX4i will apply the current limit on all soft starts, including adaptive control. If the current limit is too low or the start ramp time (parameter 2B) is too short, the motor may not start successfully.
Adaptive Start Profile
(parameter 2E):
1. Early Acceleration
Speed
2. Constant Acceleration
3. Late Acceleration
4.
Start Ramp Time
(parameter 2B)
• Fine-tuning Adaptive Control
If the motor does not start or stop smoothly, adjust the adaptive control gain (parameter 2L). The gain setting determines how much the EMX4i will adjust future adaptive control starts and stops, based on information from the previous start. The gain setting affects both starting and stopping performance.
• If the motor accelerates or decelerates too quickly at the end of a start or
stop, increase the gain setting by 5%~10%.
• If the motor speed fluctuates during starting or stopping, decrease the
gain setting slightly.
The EMX4i tunes Adaptive Control to match the motor. Changing the following parameters will reset Adaptive Control and the first start/stop cycle will use constant current start/timed voltage ramp stop: 1B
52 EMX4i User Manual 710-14888-00C
Load Current
, 2D
Current Limit
, 2L
Adaptive Control Gain
.
Page 54
OPERATION
NOTE
1
NOTE
CAUTION

8.9 Stop Methods

Coast to Stop

Coast to stop lets the motor slow at its natural rate, with no control from the soft starter. The time required to stop will depend on the type of load.

Timed Voltage Ramp Soft Stop

Timed voltage ramp reduces the voltage to the motor gradually over a defined time. This can extend the stopping time of the motor and may avoid transients on generator set supplies.
The load may continue to run after the stop ramp is complete.
1:
Stop Time
Voltage (% full voltage)
Time
(parameter 2J)

Adaptive Control for Stopping

In an adaptive control soft stop, the EMX4i controls the current in order to stop the motor within a specified time and using a selected deceleration profile. Adaptive Control can be useful in extending the stopping time of low inertia loads.
If adaptive control is selected, the first soft stop will use timed voltage ramp. This allows the EMX4i to learn the characteristics of the connected motor. This motor data is used by the EMX4i during subsequent adaptive control stops.
Adaptive control does not actively slow the motor down and will not stop the motor faster than a coast to stop. To shorten the stopping time of high inertia loads, use brake.
Adaptive Control controls the motor's speed profile, within the programmed time limit. This may result in a higher level of current than traditional control methods.
If replacing a motor connected to an EMX4i programmed for Adaptive Control starting or stopping, the starter will need to learn the characteristics of the new motor. Change the value of parameter 1B
710-14888-00C EMX4i User Manual 53
Motor Full Load Current
or parameter 2L
Page 55
OPERATION
100%
90% 80% 70% 60% 50% 40% 30% 20% 10%
0
04835.C
1 2 3
4
Adaptive Stop Profile
Application
Constant Deceleration
Low to medium head, high flow applications where the fluid
Early Deceleration
Open pump systems where fluid must drain back through
CAUTION
CAUTION
Adaptive Control Gain
to initiate the re-learning process. The next start will use
constant current and the next stop will use timed voltage ramp.
Adaptive Stop Profile
(parameter 2K):
1. Early Deceleration
Speed
2. Constant Deceleration
3. Late Deceleration
4.
Stop Time
(parameter 2J)
Time
Adaptive Control is ideal for pumping applications, where it can minimise the damaging effects of fluid hammer. We recommend testing the three profiles to identify the best profile for the application.
Late Deceleration
High head systems where even a small decrease in motor/pump speed results in a rapid transition between forward flow and reverse flow.
has high momentum.
the pump without driving the pump in reverse.

DC Brake

Brake reduces the time required to stop the motor. During braking an increased noise level from the motor may be audible. This is a
normal part of motor braking.
When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3) in positive phase sequence.
If the brake torque is set too high, the motor will stop before the end of the brake time and the motor will suffer unnecessary heating which could result in damage. Careful configuration is required to ensure safe operation of the starter and motor.
54 EMX4i User Manual 710-14888-00C
A high brake torque setting can result in peak currents up to motor DOL being drawn while the motor is stopping. Ensure protection fuses installed in the motor branch circuit are selected appropriately.
Page 56
OPERATION
CAUTION
10
0%
7
5%
0%
5
0%
25
%
1
2
3
Brake operation causes the motor to heat faster than the rate calculated by the motor thermal model. If you are using brake, install a motor thermistor or allow sufficient restart delay (parameter 5P).
Stop Time
1:
Brake Time
Speed
2:
(parameter 2J)
(parameter 2P)
3: Coast to stop time
Time
Parameter settings:
• Parameter 2I
• Parameter 2J
Stop Mode
Stop Time
: set to 'DC Brake'.
: This is the total braking time (1) and must be set sufficiently longer than the brake time (parameter 2P) to allow the pre-braking stage to reduce motor speed to approximately 70%. If the stop time is too short, braking will not be successful and the motor will coast to stop.
• Parameter 2O
DC Brake Torque
: set as required to slow the load. If set too low, the motor will not stop completely and will coast to stop after the end of the braking period.
• Parameter 2P
DC Brake Time
: Set Brake Time (parameter 2P) to approximately one quarter of the programmed Stop Time. This sets the time for the Full Brake stage (2).

DC Brake with External Zero Speed Sensor

For loads which may vary between braking cycles, install an external zero-speed sensor to ensure the soft starter ends DC braking when the motor has reached a standstill. This avoids unnecessary motor heating.
Configure DC brake for the longest braking time required, and also set parameter 7A
Input A Function
the zero speed sensor opens the circuit across 13, 14 and the soft starter terminates the stop.
to 'Zero Speed Sensor'. When the motor reaches a standstill,
710-14888-00C EMX4i User Manual 55
Page 57
OPERATION
44
1
2
3
5
4
1
Three-phase supply
K1
Line contactor (Run)
2
Motor terminals
K2
Line contactor (Brake)
3
Relay output A
A2
Zero speed sensor
4
5

Soft Brake

For applications with high inertia and/or a variable load requiring the maximum possible braking torque, the EMX4i can be configured for soft braking.
The EMX4i uses a changeover relay to control forward run and braking contactors. While braking, the EMX4i reverses the phase sequence to the motor and supplies reduced current, gently slowing the load.
When motor speed approaches zero, the zero speed sensor (A2) stops the soft starter and opens the braking contactor (K2).
Soft braking can be used with both the primary and secondary motor sets, and must be configured separately for each.
Parameter settings:
• Parameter 2I
• Parameter 2Q
• Parameter 2R
Stop Mode
: set to 'Soft Brake'
Brake Current Limit Soft Brake Delay
: controls the time the soft starter will wait
: set as required to slow the load
after a stop signal is received, before it begins to supply braking current to the motor. Set to allow time for K1 and K2 to switch.
• Parameter 7A
• Parameter 8A
Input A Function Relay A Function
: set to 'Zero Speed Sensor'
: set to 'Soft Brake Relay'
K1/K2 coil supply
56 EMX4i User Manual 710-14888-00C
Programmable input A
Page 58
OPERATION
Forward current (%FLC)
300%
200%
100%
400%
50%
25%
0%
20124.A
2
4
8
6
1
7
5
3
Time
NOTE
NOTE

8.10 Pump Clean

The starter can perform a pump clean function before soft starting the motor. This can help dislodge debris from the impeller.
Pump clean starts the motor in reverse then forward direction, then stops the motor. Pump clean can be configured to repeat the process up to 5 times. After the specified number of cleaning cycles, the starter performs the programmed soft start.
Pump clean operation is controlled by the start/stop input (11, 12). A programmable input must be set to pump clean (refer to parameter 7A
Input A Function
for details)
and the input must be closed when the start signal is applied.
1:
Reverse Torque Reverse Time
2: 3:
Forward Current Limit
(parameter 11A)
(parameter 11B)
(parameter 11C) 4:
Forward Time
5:
Pump Stop Time
Reverse torque/
6: Cleaning cycle
Pump Clean Cycles
7:
(parameter 11D)
(parameter 11F)
(parameter 11G) 8: Programmed soft start

8.11 Reverse Direction Operation

The starter can control a reversing contactor, to operate the motor in reverse direction. When reverse operation is selected, the starter will perform a soft start using the opposite phase sequence from normal operation.
Reverse operation is controlled by the start/stop input (11, 12). A programmable input must be set to reverse direction (parameter 7A output must be set to reversing contactor (parameter 8A
Input A Function
Relay A Function
) and an
).
The input must be closed when the start signal is applied. The starter will keep the reverse relay in the same state until the end of the starting/stopping cycle.
This example shows a simple installation, but many different configurations are possible depending on your application requirements. Contact your local supplier for an application note showing more installation options.
710-14888-00C EMX4i User Manual 57
The first start after the direction is changed will be constant current.
If phase sequence protection is required, install the reversing contactor on the output (motor) side of the soft starter.
Page 59
OPERATION
44
1
2
4
3
5
1
2
Motor terminals
K2
Reversing contactor
3
Programmable input A
4
Relay output A
5
K1/K2 coil supply
CAUTION
Three-phase supply K1 Forward run contactor
(set = Reverse Direction)
(set = Reversing Contactor)

8.12 Jog Operation

Jog runs the motor at reduced speed, to allow alignment of the load or to assist servicing. The motor can be jogged in either forward or reverse direction.
Jog is only available when the starter is controlled via the digital inputs (parameter 1A
Command Source
= 'Digital Input'). To operate in jog, a programmable input must be set to jog (refer to parameter 7A for details) and the input must be closed when the start signal is applied.
Slow speed running is not intended for continuous operation due to reduced motor cooling.
Jog operation causes the motor to heat faster than the rate calculated by
58 EMX4i User Manual 710-14888-00C
the motor thermal model. If you are using jog, install a motor thermistor or allow sufficient restart delay (parameter 5P).
Page 60
OPERATION
NOTE
0
%
1
00
%
90
%
80
%
20
%
4
0%
1
0%
3
0
%
5
0
%
6
0%
70
%
05
7
23
.D
Adaptive Control Start
The starter performs a constant current start.
Adaptive Control Stop
The starter performs a TVR soft stop if parameter 2J
Stop
If parameter 2J is set to 0 secs the starter performs a coast
NOTE
NOTE
The maximum available torque for jog forward is approximately 50%~75% of motor full load torque (FLT) depending on the motor. The torque when the motor is jogged in reverse is approximately 25% to 50% of FLT.
Parameters 2H and 3J torque the soft starter will apply to the motor.
Jog Torque
control how much of the maximum available jog
Torque settings above 50% may cause increased shaft vibration.
1. Motor FLT
2. Jog forward maximum torque
Available torque
3. Jog reverse maximum torque

8.13 Inside Delta Operation

When connecting in inside delta, enter the motor full load current (FLC) for parameter 1B. The EMX4i will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
Adaptive Control, Jog, Brake and PowerThrough functions are not supported with inside delta (six-wire) operation. If these functions are programmed when the starter is connected inside delta the behaviour is as given below:
Time
is >0 secs.
to stop.
Jog
The starter issues a warning with the error message
Unsupported option. DC Brake The starter performs a coast to stop. Soft Brake The starter performs a coast to stop. PowerThrough The starter trips with the error message Lx-Tx Shorted.
When connected in inside delta, the EMX4i will not detect phase loss on T2
710-14888-00C EMX4i User Manual 59
during run.
If the starter is not correctly detecting the motor connection, use parameter
Motor Connection
20F
.
Page 61
OPERATION
NOTE

8.14 Secondary Motor Set

The EMX4i can be programmed with two separate starting and stopping profiles. This allows the soft starter to control the motor in two different starting and stopping configurations.
The secondary motor set is ideal for dual winding (Dahlander) motors, multi-motor applications, or situations where the motor may start in two different conditions (such as loaded and unloaded conveyors).
The secondary motor set can also be used for duty/standby applications.
For duty/standby applications, set parameter 6Q Log Only and install temperature protection for each motor.
To use the secondary motor set, a programmable input must be set to 'Motor Set Select' and the input must be closed when a start command is given (refer to 7A
Motor Overtemperature
to
Input A Function
use at a start, and will use that motor set for the entire start/stop cycle.
and 7E
Input B Function
). The EMX4i checks which motor set to
60 EMX4i User Manual 710-14888-00C
Page 62
PROGRAMMABLE PARAMETERS
MENU
MENU
NOTE
STORE
EXIT

9. Programmable Parameters

9.1 Main Menu

The main menu lets you view and change programmable parameters that control how the EMX4i operates.
To open the main menu, press the
button then scroll to Main Menu and
press
again.
Parameters for smart card functions are only visible in the parameter list if the smart card is installed.

9.2 Altering Parameter Values

To change a parameter value:
• scroll to the appropriate parameter in the main menu and press
enter edit mode.
• to alter the parameter setting, use the
or
once will increase or decrease the value by one unit. If the button is held for longer than five seconds, the value will increase or decrease at a faster rate.
• to save changes, press
saved and the keypad will return to the parameter list.
. The setting shown on the display will be
to
and buttons. Pressing
• to cancel changes, press
return to the parameter list without saving changes.
. The keypad will ask for confirmation, then

9.3 Adjustment Lock

You can prevent users from altering parameter settings by turning on the adjustment lock (parameter 10G
If a user attempts to change a parameter value when the adjustment lock is active, an error message is displayed:
Access Denied Adj Lock is On
Adjustment Lock
).
710-14888-00C EMX4i User Manual 61
Page 63
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
1
Motor Details
1B
Motor Full Load Current
Model dependent
1C
Motor kW
0 kW
1D
Locked Rotor Time
00:10 (mm:ss)
2
Motor Start/Stop
2E
Adaptive Start Profile
Constant Acceleration
2F
Kickstart Time
000 ms
2G
Kickstart Level
500%
2M
Multi Pump
Single Pump
2N
Start Delay
00:00 (mm:ss)
3 Motor Start/Stop 2

9.4 Parameter List

1A
1E 1F 1G
2A 2B 2C 2D
Command Source
Digital Input
Locked Rotor Current Motor Service Factor Reserved
Start Mode Start Ramp Time Initial Current Current Limit
Constant Current
00:10 (mm:ss)
200%
350%
600%
105%
2H 2I 2J 2K 2L
2O 2P 2Q 2R
3A 3B
Jog Torque Stop Mode Stop Time Adaptive Stop Profile Adaptive Control Gain
DC Brake Torque DC Brake Time Brake Current Limit Soft Brake Delay
50%
TVR Soft Stop
00:00 (mm:ss)
Constant Deceleration
75%
20%
00:01 (mm:ss)
250%
400 ms
Motor Full Load Current-2 Motor kW-2
0 kW
Model dependent
3C 3D
62 EMX4i User Manual 710-14888-00C
Start Mode-2 Start Ramp Time-2
Constant Current
00:10 (mm:ss)
Page 64
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
3E
Initial Current-2
200%
3K
Stop Mode-2
TVR Soft Stop
3L
Stop Time-2
00:00 (mm:ss)
3R
DC Brake Time-2
00:01 (mm:ss)
3S
Brake Current Limit-2
250%
4
Auto-Start/Stop
4A
Auto-Start/Stop Mode
Disable
4B
Run Time
00:00 (hh:mm)
4H
Monday Start Time
00:00 (hh:mm)
4I
Monday Stop Time
00:00 (hh:mm)
4O
Wednesday Stop Time
00:00 (hh:mm)
4P
Thursday Mode
Start/Stop Disable
3F 3G 3H 3I 3J
3M 3N 3O 3P 3Q
Current Limit-2
350%
Adaptive Start Profile-2 Kickstart Time-2 Kickstart Level-2 Jog Torque-2
000 ms
500%
50%
Adaptive Stop Profile-2 Adaptive Control Gain-2 Multi Pump-2 Start Delay-2 DC Brake Torque-2
Single Pump
00:00 (mm:ss)
20%
Constant Acceleration
Constant Deceleration
75%
3T
4C 4D 4E 4F 4G
4J 4K 4L
Soft Brake Delay-2
Stopped Time Sunday Mode
00:00 (hh:mm)
Start/Stop Disable
Sunday Start Time Sunday Stop Time Monday Mode
Tuesday Mode
Start/Stop Disable
Start/Stop Disable
Tuesday Start Time Tuesday Stop Time
400 ms
00:00 (hh:mm)
00:00 (hh:mm)
00:00 (hh:mm)
00:00 (hh:mm) 4M 4N
4Q
710-14888-00C EMX4i User Manual 63
Wednesday Mode Wednesday Start Time
Thursday Start Time
Start/Stop Disable
00:00 (hh:mm)
00:00 (hh:mm)
Page 65
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
4R
Thursday Stop Time
00:00 (hh:mm)
4X
Saturday Stop Time
00:00 (hh:mm)
5
Protection Levels
5C
Undercurrent
20%
5D
Undercurrent Delay
00:05 (mm:ss)
5J
Overvoltage Delay
00:01 (mm:ss)
5K
Underpower
10%
5Q
Starts per Hour
0 5R
Phase Sequence
Any Sequence
6
Protection Actions
6D
Undercurrent
Soft Trip and Log
6E
Overcurrent
Soft Trip and Log
4S 4T 4U 4V 4W
5A 5B
5E 5F 5G
Friday Mode Friday Start Time Friday Stop Time Saturday Mode Saturday Start Time
Current Imbalance
Start/Stop Disable
00:00 (hh:mm)
00:00 (hh:mm)
Start/Stop Disable
00:00 (hh:mm)
30%
Current Imbalance Delay
Overcurrent Overcurrent Delay Undervoltage
400%
00:00 (mm:ss)
350 V
00:03 (mm:ss)
5H 5I
5L 5M 5N 5O 5P
6A 6B
Undervoltage Delay Overvoltage
500 V
Underpower Delay Overpower Overpower Delay Excess Start Time Restart Delay
Auto-Reset Count Auto-Reset Delay
150%
00:01 (mm:ss)
00:20 (mm:ss)
00:10 (mm:ss)
0
00:05 (mm:ss)
00:01 (mm:ss)
00:01 (mm:ss)
64 EMX4i User Manual 710-14888-00C
6C
6F 6G
Current Imbalance
Undervoltage Overvoltage
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Page 66
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
6H
Underpower
Log Only
6N
Remote Keypad Fault
Soft Trip and Log
6O
Frequency
Soft Trip and Log
7
Inputs
7F
Input B Trip
Operating Only
7G
Input B Trip Delay
00:00 (mm:ss)
8
Relay Outputs
8F
Relay B Off Delay
00:00 (mm:ss)
8G
Low Current Flag
50%
8H
High Current Flag
100%
6I 6J 6K 6L 6M
6P 6Q 6R 6S 6T
7A
Overpower Excess Start Time Input A Trip Input B Trip
Log Only
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Network Communications
Phase Sequence Motor Overtemperature
Soft Trip and Log
Soft Trip and Log
Motor Thermistor Circuit Shorted SCR Action Battery/Clock
Soft Trip and Log
Input A Function
3-Phase Control Only
Input Trip (N/O)
Soft Trip and Log
Soft Trip and Log
7B 7C 7D 7E
7H 7I 7J 7K
8A 8B 8C
Input A Trip Input A Trip Delay
Operating Only
00:00 (mm:ss)
Input A Initial Delay Input B Function
Input Trip (N/O)
Input B Initial Delay Reset/Enable Logic Input A Name Input B Name
Relay A Function Relay A On Delay Relay A Off Delay
Input A Trip
Input B Trip
Run
00:00 (mm:ss)
00:00 (mm:ss)
00:00 (mm:ss)
00:00 (mm:ss)
Normally Closed (N/C)
710-14888-00C EMX4i User Manual 65
8D 8E
Relay B Function Relay B On Delay
Run 00:00 (mm:ss)
Page 67
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
8I
Motor Temperature Flag
80%
9
Analog Output
9C
Analog A Maximum Adjustment
100%
9D
Analog A Minimum Adjustment
000%
10
Display
10D
Graph Maximum Adjustment
400%
10E
Graph Minimum Adjustment
0%
10J
User Parameter 3
Mains Frequency
10K
User Parameter 4
Motor pf
10L
User Parameter 5
Motor Power
11
Pump Clean
11B
Reverse Time
00:10 (mm:ss)
11C
Forward Current Limit
100%
12
Communications Card
12A
Modbus Address
1
8J
9A 9B
10A 10B 10C
10F 10G
Main Contactor Time
Analog Output A Analog A Scale
Language
English
Temperature Scale Graph Timebase
Current Calibration Adjustment Lock
Current (% FLC)
4-20 mA
Celsius
30 seconds
100%
Read & Write
400 ms
10H 10I
10M
11A
11D 11E 11F 11G
User Parameter 1 User Parameter 2
User Parameter 6
Reverse Torque
Forward Time Pump Stop Mode Pump Stop Time
20%
00:10 (mm:ss)
Coast To Stop
00:10 (mm:ss)
Pump Clean Cycles
Current Motor Voltage
Motor Temp (%)
1
12B 12C 12D
66 EMX4i User Manual 710-14888-00C
Modbus Baud Rate Modbus Parity Modbus Timeout
None
Off
9600
Page 68
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
12E
Devicenet Address
0
12K
Gateway Address
4
100
12L
IP Address
192
12R
Subnet Mask
3
255
12S
Subnet Mask
4
0
20
Advanced
20B
Pedestal Detect
80%
20C
Bypass Contactor Delay
150 ms
30
Pump Input Configuration
30A
Pressure Sensor Type
None
30G
Flow at 4 mA
0 30H
Flow at 20 mA
0 30I
Units per Minute at Max Flow
0
12F 12G 12H 12I 12J
12M 12N 12O 12P 12Q
Devicenet Baud Rate Profibus Address Gateway Address Gateway Address Gateway Address
IP Address IP Address IP Address
2 168 3 0 4 2
Subnet Mask Subnet Mask
1 192 2 168 3 0
255 2 255
125kB
12T 12U
20A
20D
20E
20F
30B 30C 30D
DHCP Location ID
Tracking Gain
Model Rating Screen Timeout
Disable
0
50%
Model dependent
1 minute
Motor Connection
Pressure Units
kPa
Pressure at 4 mA Pressure at 20 mA
Auto-detect
0
0 30E 30F
710-14888-00C EMX4i User Manual 67
Flow Sensor Type Flow Units
litres/second
None
Page 69
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
30J
Pulses per Minute at Max Flow
0
31
Flow Protection
32
Pressure Protection
32A
High Pressure Trip Level
10
32F
Low Pressure Response Delay
00:00:50 (mm:ss:ms)
33
Pressure Control
33E
Stop Response Delay
00:00:50 (mm:ss:ms)
34
Depth Protection
35
Thermal Protection
30K 30L 30M 30N 30O
31A 31B 31C 31D
32B 32C
Units per Pulse Depth Sensor Type Depth Units Depth at 4 mA Depth at 20 mA
High Flow Trip Level Low Flow Trip Level Flow Start Delay Flow Response Delay
High Pressure Start Delay
0
None
metres
0
0
10
5
00:00:50 (mm:ss:ms)
00:00:50 (mm:ss:ms)
00:00:50 (mm:ss:ms)
High Pressure Response Delay
00:00:50 (mm:ss:ms) 32D 32E
33A 33B 33C 33D
34A 34B 34C 34D
Low Pressure Trip Level Low Pressure Start Delay
Pressure Control Mode Start Pressure Level Start Response Delay Stop Pressure Level
Depth Trip Level
5
Depth Reset Level Depth Start Delay
00:00:50 (mm:ss:ms)
Depth Response Delay
Off
5
00:00:50 (mm:ss:ms)
10
10
00:00:50 (mm:ss:ms)
5
00:00:50 (mm:ss:ms)
35A 35B
68 EMX4i User Manual 710-14888-00C
Temperature Sensor Type Temperature Trip Level
None
40
Page 70
PROGRAMMABLE PARAMETERS
Parameter Group
Default Setting
36
Pump Trip Action
36F
High Flow
Soft Trip and Log
36G
Low Flow
Soft Trip and Log
36A 36B 36C 36D 36E
36H 36I 36J
Pressure Sensor Flow Sensor Depth Sensor High Pressure Low Pressure
Flow Switch Well Depth RTD/PT100 B
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
Soft Trip and Log
710-14888-00C EMX4i User Manual 69
Page 71
PROGRAMMABLE PARAMETERS
1A –
Command Source
Options:
Network
The EMX4i will accept start and stop The EMX4i will accept start and stop
Description: 1B –
Motor Full Load Current
Range: Description:
1C –
Motor kW
Range:
Default:
Description:
NOTE

9.5 1 Motor Details

Digital Input (default)
The EMX4i will accept start and stop commands from the digital inputs.
commands from the communication expansion card.
Remote Keypad
commands from the Remote Keypad.
Clock
The EMX4i will start and stop as scheduled in parameters 4D to 4X.
Smart Card
The EMX4i will accept start and stop
commands from the smart card. Smart Card + Clock
The EMX4i will accept start commands from
the smart card if they are within the operating
schedule set in parameters 4A to 4X. A stop
command from the smart card will be
accepted regardless of the schedule. Timer
After a start signal is received, the EMX4i will
start and stop the motor according to the
timers set in parameters 4B and 4C. Selects the command source for controlling the soft starter.
Model dependent Matches the starter to the connected motor's full load current.
Set to the full load current (FLC) rating shown on the motor nameplate.
0 - 9999 kW
0
Sets the running power of the connected motor, in kilowatts. This setting is the basis for power reporting and protection.
The motor nameplate may state different power ratings for different supply voltages or power connections. Ensure that the motor kW setting is accurate for the installation.
70 EMX4i User Manual 710-14888-00C
Page 72
1D –
Locked Rotor Time
Range:
Default:
Description:
1E –
Locked Rotor Current
Range:
Default:
Description:
1F –
Motor Service Factor
Range:
Default:
Description:
NOTE
1G –
Reserved
Description:
2A –
Start Mode
Options:
Description:
NOTE
2B –
Start Ramp Time
Range:
Default:
Description:
PROGRAMMABLE PARAMETERS
100% - 130%
0:01 - 2:00 (minutes:seconds)
10 seconds
Sets the maximum length of time the motor can sustain locked rotor current from cold before reaching its maximum temperature. Set according to the motor datasheet.
400% - 1200% FLC
600%
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the motor datasheet.
105%
Sets the motor service factor used by the thermal model. If the motor runs at full load current, it will reach 100%. Set according to the motor datasheet.
Parameters 1D, 1E and 1F determine the trip current for motor overload protection. The default settings of parameters 1D, 1E and 1F provide Motor Overload Protection: Class 10, Trip Current 105% of FLA (full load amperage) or equivalent.
This parameter is reserved for future use.

9.6 2 Motor Start/Stop

The EMX4i will apply the current limit on all soft starts, including adaptive control. If the current limit is too low or the start ramp time (parameter 2B)
Constant Current (default) Adaptive Control
Selects the soft start mode.
is too short, the motor may not start successfully.
0:01 - 3:00 (minutes:seconds)
Sets the total start time for an Adaptive Control start or the
10 seconds
ramp time for current ramp starting (from the initial current to
710-14888-00C EMX4i User Manual 71
the current limit).
Page 73
PROGRAMMABLE PARAMETERS
2C –
Initial Current
Range:
Default:
Description:
2D –
Current Limit
Range:
Default:
Description:
2E –
Adaptive Start Profile
Options:
Description:
NOTE
2F –
Kickstart Time
Range:
Default:
Description: 2G –
Kickstart Level
Range:
Default:
Description:
CAUTION
2H –
Jog Torque
Range:
Default:
Description:
100% - 600% FLC
200%
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so that the motor begins to accelerate immediately after a start is initiated. If current ramp starting is not required, set the initial current equal to the current limit.
100% - 600% FLC
350%
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load current.
Early Acceleration Constant Acceleration (default) Late Acceleration
Selects which profile the EMX4i will use for an Adaptive Control
The EMX4i will apply the current limit on all soft starts, including adaptive control. If the current limit is too low or the start ramp time (parameter 2B) is too short, the motor may not start successfully.
Kickstart subjects the mechanical equipment to increased torque levels. Ensure the motor, load and couplings can handle the additional torque
soft start.
0 – 2000 milliseconds
0000 milliseconds
Sets the kickstart duration. A setting of 0 disables kickstart.
100% - 700% FLC
500%
Sets the level of the kickstart current.
before using this feature.
The EMX4i can jog the motor at a reduced speed, which allows precise positioning of belts and flywheels. Jog can be used for either forward or reverse operation.
72 EMX4i User Manual 710-14888-00C
20% - 100% Sets the current limit for jog operation.
50%
Page 74
2I –
Stop Mode
Options:
Description: 2J –
Stop Time
Range:
Default:
Description:
2K –
Adaptive Stop Profile
Options:
Description:
2L –
Adaptive Control Gain
Range:
Default:
Description:
2M –
Multi Pump
Options:
Description:
2N –
Start Delay
Range:
Default:
Description:
PROGRAMMABLE PARAMETERS
Coast To Stop TVR Soft Stop (default) Adaptive Control DC Brake Soft Brake
Selects the stop mode.
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage ramp or Adaptive Control. If a main contactor is installed, the contactor must remain closed until the end of the stop time. Use the main contactor output (33, 34) to control the main contactor.
Early Deceleration Constant Deceleration (default) Late Deceleration
Selects which profile the EMX4i will use for an Adaptive Control soft stop.
1% - 200%
75%
Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control.
Single Pump (default) Manifold Pump
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a common outlet manifold.
710-14888-00C EMX4i User Manual 73
0:00 - 60:00 (minutes:seconds)
0 second
Sets a delay after the starter receives a start command, before it starts the motor.
Page 75
PROGRAMMABLE PARAMETERS
2O –
DC Brake Torque
Range:
Default:
Description:
2P –
DC Brake Time
Range:
Default: Description: 2Q –
Brake Current Limit
Range:
Default: Description: 2R –
Soft Brake Delay
Range:
Default: Description:
3A –
Motor Full Load Current-2
Range: Description: 3B –
Motor kW-2
Range:
Default: Description: 3C –
Start Mode-2
Options:
Description: 3D –
Start Ramp Time-2
Range:
Default: Description:
20% - 100%
20%
Sets the amount of brake torque the EMX4i will use to slow the motor.
0:01 - 0:30 (minutes:seconds)
1 second
Sets the duration for DC injection during a braking stop.
100% - 600% FLC
250%
Sets the current limit for soft brake.
400 - 2000 milliseconds
400 milliseconds
Sets the time the soft starter will wait after a stop signal is received, before it begins to supply braking current to the motor. Set to allow time for K1 and K2 to switch.

9.7 3 Motor Start/Stop-2

The parameters in this group control the operation of the secondary configuration of the motor. Use the programmable input to select the active motor set.
Refer to
Secondary Motor Set
Model dependent Sets the secondary motor's full load current.
0 - 9999 kW Sets the running power of the secondary motor, in kilowatts.
Constant Current (default) Adaptive Control
Selects the soft start mode.
on page 60 for details.
0
0:01 - 3:00 (minutes:seconds)
10 seconds
Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial current to
74 EMX4i User Manual 710-14888-00C
the current limit).
Page 76
3E –
Initial Current-2
Range:
Default: Description:
3F –
Current Limit-2
Range:
Default: Description:
NOTE
3G –
Adaptive Start Profile-2
Options:
Description:
3H –
Kickstart Time-2
Range:
Default: Description: 3I –
Kickstart Level-2
Range:
Default: Description: 3J –
Jog Torque-2
Range:
Default: Description: 3K –
Stop Mode-2
Options:
Description:
PROGRAMMABLE PARAMETERS
The EMX4i will apply the current limit on all soft starts, including adaptive control. lf the current limit is too low or the start ramp time (parameter 2B) is too short, the motor may not start successfully.
100% - 600% FLC
200%
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so that the motor begins to accelerate immediately after a start is initiated. If current ramp starting is not required, set the initial current equal to the current limit.
100% - 600% FLC
350%
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load current.
Early Acceleration Constant Acceleration (default) Late Acceleration
Selects which profile the EMX4i will use for an Adaptive Control soft start.
0 – 2000 milliseconds
0000 milliseconds
Sets the kickstart duration. A setting of 0 disables kickstart.
100% - 700% FLC
500%
Sets the level of the kickstart current.
20% - 100%
50%
Sets the current limit for jog operation.
Coast To Stop DC Brake TVR Soft Stop (default) Soft Brake Adaptive Control
710-14888-00C EMX4i User Manual 75
Selects the stop mode.
Page 77
PROGRAMMABLE PARAMETERS
3L –
Stop Time-2
Range:
Default: Description:
3M –
Adaptive Stop Profile-2
Options:
Description:
3N –
Adaptive Control Gain-2
Range:
Default: Description:
3O –
Multi Pump-2
Options:
Description:
3P –
Start Delay-2
Range:
Default: Description:
3Q –
DC Brake Torque-2
Range:
Default: Description:
3R –
DC Brake Time-2
Range:
Default: Description:
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage ramp or Adaptive Control. If a main contactor is installed, the contactor must remain closed until the end of the stop time. Use the main contactor output (33, 34) to control the main contactor.
Early Deceleration Constant Deceleration (default) Late Deceleration
Selects which profile the EMX4i will use for an Adaptive Control soft stop.
1%~200%
75%
Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control.
Single Pump (default) Manifold Pump
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a common outlet manifold.
0:00 - 60:00 (minutes:seconds)
0 second
Sets a delay after the starter receives a start command, before it starts the motor.
20% - 100%
20%
Sets the amount of brake torque the EMX4i will use to slow the motor.
76 EMX4i User Manual 710-14888-00C
0:01 - 0:30 (minutes:seconds)
1 second
Sets the duration for DC injection during a braking stop.
Page 78
3S –
Brake Current Limit-2
Range:
Default: Description:
3T –
Soft Brake Delay-2
Range:
Default: Description:
4A –
Auto-Start/Stop Mode
Options:
Description: 4B –
Run Time
Range:
Default: Description:
4C –
Stopped Time
Range:
Default: Description:
4D –
Sunday Mode
Options:
Start/Stop
Disables auto-start/stop control. Any times
Stop Only
Enables auto-stop control. Any auto-start
Description:
PROGRAMMABLE PARAMETERS
100% - 600% FLC
250%
Sets the current limit for soft brake.
400 - 2000 milliseconds
400 milliseconds Sets the time the soft starter will wait after a stop signal is received, before it begins to supply braking current to the motor.
Set to allow time for K1 and K2 to switch.

9.8 4 Auto-Start/Stop

The EMX4i can be configured to automatically start and/or stop the motor at a particular time, or run it in cycles of a specified duration.
Disable (default) Enable Timer Mode Enable Clock Mode
Enable or disable auto-start/stop operation.
00:00 - 23:59 hh:mm
00:00 Sets the duration for the starter to run, after a timer mode
auto-start.
00:00 - 23:59 hh:mm
00:00 Sets the duration for the starter to remain stopped, when
operating in timer mode.
Disable (default)
scheduled in parameters 4E or 4F will be
ignored. Start Only Enable
Enables auto-start control. Any auto-stop
times scheduled in parameter 4F will be
ignored.
Enable
Start/Stop Enable
710-14888-00C EMX4i User Manual 77
Enables or disables auto-start/stop for Sunday.
times scheduled in parameter 4E will be
ignored.
Enables auto-start and auto-stop control.
Page 79
PROGRAMMABLE PARAMETERS
4E –
Sunday Start Time
Range:
Default: Description: 4F –
Sunday Stop Time
Range:
Default: Description: 4G –
Monday Mode
Options:
Description: 4H –
Monday Start Time
Range:
Default: Description: 4I –
Monday Stop Time
Range:
Default: Description: 4J –
Tuesday Mode
Options:
Description: 4K –
Tuesday Start Time
Range:
Default: Description: 4L –
Tuesday Stop Time
Range:
Default: Description: 4M –
Wednesday Mode
Options:
Description: 4N –
Wednesday Start Time
Range:
Default: Description:
Start/Stop Disable (default) Stop Only Enable
00:00 - 23:59
00:00
Sets the auto-start time for Sunday (24 hour format).
00:00 - 23:59
00:00
Sets the auto-stop time for Sunday (24 hour format).
Start Only Enable Start/Stop Enable Enables or disables auto-start/stop for Monday.
00:00 - 23:59
00:00
Sets the auto-start time for Monday (24 hour format).
00:00 - 23:59
00:00
Start/Stop Disable (default) Stop Only Enable
Start/Stop Disable (default) Stop Only Enable
Sets the auto-stop time for Monday (24 hour format).
Start Only Enable Start/Stop Enable Enables or disables auto-start/stop for Tuesday.
00:00 - 23:59
00:00
Sets the auto-start time for Tuesday (24 hour format).
00:00 - 23:59
00:00
Sets the auto-stop time for Tuesday (24 hour format).
Start Only Enable Start/Stop Enable
78 EMX4i User Manual 710-14888-00C
Enables or disables auto-start/stop for Wednesday.
00:00 - 23:59
00:00
Sets the auto-start time for Wednesday (24 hour format).
Page 80
4O –
Wednesday Stop Time
Range:
Default: Description: 4P –
Thursday Mode
Options:
Description: 4Q –
Thursday Start Time
Range:
Default: Description: 4R –
Thursday Stop Time
Range:
Default: Description: 4S –
Friday Mode
Options:
Description: 4T –
Friday Start Time
Range:
Default: Description: 4U –
Friday Stop Time
Range:
Default: Description: 4V –
Saturday Mode
Options:
Description: 4W –
Saturday Start Time
Range:
Default: Description: 4X –
Saturday Stop Time
Range:
Default: Description:
PROGRAMMABLE PARAMETERS
Start/Stop Disable (default) Stop Only Enable
Start/Stop Disable (default) Stop Only Enable
00:00 - 23:59
00:00
Sets the auto-stop time for Wednesday (24 hour format).
Start Only Enable Start/Stop Enable Enables or disables auto-start/stop for Thursday.
00:00 - 23:59
00:00
Sets the auto-start time for Thursday (24 hour format).
00:00 - 23:59
00:00
Sets the auto-stop time for Thursday (24 hour format).
Start/Stop Disable (default) Stop Only Enable
Start Only Enable Start/Stop Enable Enables or disables auto-start/stop for Friday.
00:00 - 23:59
00:00
Sets the auto-start time for Friday (24 hour format).
00:00 - 23:59
00:00
Sets the auto-stop time for Friday (24 hour format).
Start Only Enable Start/Stop Enable Enables or disables auto-start/stop for Saturday.
00:00 - 23:59
00:00
710-14888-00C EMX4i User Manual 79
Sets the auto-start time for Saturday (24 hour format).
00:00 - 23:59
00:00
Sets the auto-stop time for Saturday (24 hour format).
Page 81
PROGRAMMABLE PARAMETERS
5A –
Current Imbalance
Range:
Default: Description: 5B –
Current Imbalance Delay
Range:
Default: Description:
5C –
Undercurrent
Range:
Default: Description:
5D –
Undercurrent Delay
Range:
Default: Description:
5E –
Overcurrent
Range:
Default: Description:
5F –
Overcurrent Delay
Range:
Default: Description:
5G –
Undervoltage
Range:
Default: Description:
NOTE

9.9 5 Protection Levels

10% - 50%
30%
Sets the trip point for current imbalance protection.
0:00 - 4:00 (minutes:seconds)
3 seconds
Slows the EMX4i's response to current imbalance, avoiding trips due to momentary fluctuations.
0% - 100%
20%
Sets the trip point for undercurrent protection, as a percentage of motor full load current. Set to a level between the motor's normal working range and the motor's magnetising (no load) current (typically 25% to 35% of full load current). A setting of 0% disables undercurrent protection.
100 - 1000 V
0:00 - 4:00 (minutes:seconds)
5 seconds
Slows the EMX4i's response to undercurrent, avoiding trips due to momentary fluctuations.
80% - 600%
400%
Sets the trip point for overcurrent protection, as a percentage of motor full load current.
0:00 - 1:00 (minutes:seconds)
0 second
Slows the EMX4i's response to overcurrent, avoiding trips due to momentary overcurrent events.
350
Sets the trip point for undervoltage protection. Set as required.
80 EMX4i User Manual 710-14888-00C
Voltage protections will not operate correctly until the starter is in Run mode.
Page 82
5H –
Undervoltage Delay
Range:
Default: Description:
5I –
Overvoltage
Range:
Default: Description: 5J –
Overvoltage Delay
Range:
Default: Description:
5K –
Underpower
Range:
Default: Description: 5L –
Underpower Delay
Range:
Default: Description:
5M –
Overpower
Range:
Default: Description: 5N –
Overpower Delay
Range:
Default: Description:
5O –
Excess Start Time
Range:
Default: Description:
PROGRAMMABLE PARAMETERS
100 - 1000 V
0:00 - 1:00 (minutes:seconds)
1 second
Slows the EMX4i's response to undervoltage, avoiding trips due to momentary fluctuations.
500
Sets the trip point for overvoltage protection. Set as required.
0:00 - 1:00 (minutes:seconds)
1 second
Slows the EMX4i's response to overvoltage, avoiding trips due to momentary fluctuations.
10% -120%
10%
Sets the trip point for underpower protection. Set as required.
0:01 - 1:00 (minutes:seconds)
1 second
Slows the EMX4i's response to underpower, avoiding trips due to momentary fluctuations.
80% -200%
150%
Sets the trip point for overpower protection. Set as required.
0:01 - 1:00 (minutes:seconds)
1 second
Slows the EMX4i's response to overpower, avoiding trips due to momentary fluctuations.
0:00 - 4:00 (minutes:seconds)
20 seconds
Excess start time is the maximum time the EMX4i will attempt to start the motor. If the motor does not transition to Run mode within the programmed limit, the starter will trip. Set for a period slightly longer than required for a normal healthy start. A
710-14888-00C EMX4i User Manual 81
setting of 0 disables excess start time protection.
Page 83
PROGRAMMABLE PARAMETERS
5P –
Restart Delay
Range:
Default: Description:
5Q –
Starts per Hour
Range:
Default: Description:
5R –
Phase Sequence
Options:
Description:
CAUTION
6A –
Auto-Reset Count
Range:
Default: Description:
6B –
Auto-Reset Delay
Range:
Default: Description:
0 - 10
00:01 - 60:00 (minutes:seconds)
10 seconds
The EMX4i can be configured to force a delay between the end of a stop and the beginning of the next start. During the restart delay period, the display shows the time remaining before another start can be attempted.
0
Sets the maximum number of starts the EMX4i will attempt in a 60 minute period. A setting of 0 disables this protection.
Any Sequence (default) Positive Only Negative Only
Selects which phase sequences the soft starter will allow at a start. During its pre-start checks, the starter examines the sequence of the phases at its input terminals and trips if the actual sequence does not match the selected option.
When using DC brake, the mains supply must be connected to the soft starter (input terminals L1, L2, L3) in positive phase sequence and parameter 5R
Phase Sequence
must be set to Positive Only.

9.10 6 Protection Action

The reset counter increases by one each time the soft starter
Setting 6A to zero disables auto-reset.
0 – 5
0
Sets how many times the soft starter will auto-reset, if it continues to trip.
auto-resets, and resets after a successful start.
82 EMX4i User Manual 710-14888-00C
0:05 - 15:00 (minutes:seconds)
5 seconds
Sets a delay before the soft starter will auto-reset a trip.
Page 84
6C –
Current Imbalance
Options:
Soft Trip and
The soft starter will stop the motor as Trip Starter
The soft starter will remove power and the Log Only
The protection will be written to the event log
Description:
6D –
Undercurrent
Options:
Description: 6E –
Overcurrent
Options:
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description: 6F –
Undervoltage
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Description:
PROGRAMMABLE PARAMETERS
Log (default)
Soft Trip and Reset
Trip and Reset
Warn and Log
selected in parameter 2I or 3K
Stop Mode
, then enter trip state. The trip must be reset before the EMX4i can restart. The soft starter will stop the motor as selected in parameter 2I or 3K
Stop Mode
, then enter trip state. The trip will reset after the auto-reset delay
motor will coast to stop. The trip must be reset before the EMX4i can restart. The soft starter will remove power and the motor will coast to stop. The trip will reset after the auto-reset delay The protection will be written to the event log and the display will show a warning message,
Soft Trip and Log (default) Trip and Reset
Soft Trip and Log (default) Trip and Reset
but the soft starter will continue to operate.
but the soft starter will continue to operate.
Selects the soft starter's response to each protection. All protection events are written to the event log.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Selects the soft starter's response to the protection event.
Trip Starter Log Only
710-14888-00C EMX4i User Manual 83
Selects the soft starter's response to the protection event.
Page 85
PROGRAMMABLE PARAMETERS
6G –
Overvoltage
Options:
Description: 6H –
Underpower
Options:
Description: 6I –
Overpower
Options:
Soft Trip and Reset
Warn and Log
Description: 6J –
Excess Start Time
Options:
Soft Trip and Log (default)
Trip and Reset
Soft Trip and Reset
Warn and Log
Trip Starter
Log Only
Description: 6K –
Input A Trip
Options:
Soft Trip and Log (default)
Trip and Reset
Description: 6L –
Input B Trip
Options:
Description: 6M –
Network Communications
Options:
Trip and Reset
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log Trip Starter Log Only
Log Only (default) Trip Starter
Log Only (default) Trip Starter
Selects the soft starter's response to the protection event.
Soft Trip and Log Trip and Reset Soft Trip and Reset Warn and Log
Selects the soft starter's response to the protection event.
Soft Trip and Log Trip and Reset
Selects the soft starter's response to the protection event.
Selects the soft starter's response to the protection event.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Warn and Log
Soft Trip and Reset Log Only
84 EMX4i User Manual 710-14888-00C
Trip Starter Stop
Page 86
PROGRAMMABLE PARAMETERS
Description:
6N –
Remote Keypad Fault
Options:
Description: 6O –
Frequency
Options:
Description: 6P –
Phase Sequence
Options:
Trip Starter
Log Only
Description: 6Q –
Motor Overtemperature
Options:
Description: 6R –
Motor Thermistor Circuit
Options:
Description: 6S –
Shorted SCR Action
Options:
Description:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Log (default) Trip and Reset
Selects the soft starter's response to the protection event. If set to Stop, the EMX4i will perform a soft stop, then can be restarted without a reset.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Trip and Reset
Soft Trip and Log (default) Trip and Reset
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log
Selects the soft starter's response to the protection event.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Reset Warn and Log Trip Starter Log Only
Selects the soft starter's response to the protection event.
3-Phase Control Only (default) PowerThrough
Selects whether the soft starter will allow PowerThrough operation, if the soft starter is damaged on one phase. The soft starter will use two-phase control, allowing the motor to continue operating in critical applications. Refer to
710-14888-00C EMX4i User Manual 85
PowerThrough
on page 47 for further information.
Page 87
PROGRAMMABLE PARAMETERS
6T –
Battery/Clock
Options:
Description:
7A –
Input A Function
Options:
Command
Overrides the setting of 1A and sets the Input Trip (N/O)
A closed circuit across 13, 14 trips the soft Jog Reverse
Activates jog operation in reverse direction.
Zero Speed
An open circuit across 13, 14 indicates to the Reverse
A closed circuit across 13, 14 instructs the
Pump Clean
Activates the pump clean function.
Description:
Soft Trip and Log (default) Trip and Reset
Soft Trip and Reset Warn and Log Trip Starter Log Only

9.11 7 Inputs

Selects the soft starter's response to the protection event.
Override: Network Command Override: Digital Command Override:
command source to the communications network. Overrides the setting of 1A and sets the command source to the digital inputs. Overrides the setting of 1A and sets the command source to the remote keypad.
Keypad
(default) Input Trip (N/C)
starter. An open circuit across 13, 14 trips the soft starter.
Emergency Mode
A closed circuit across 13, 14 activates emergency mode. When the EMX4i receives a start command, it will continue to run until a stop command is received, ignoring all trips and warnings.
Jog Forward Activates jog operation in a forward direction.
Sensor
soft starter that the motor has reached a standstill. The soft starter requires a normally open zero speed sensor.
Motor Set Select
A closed circuit across 13, 14 instructs the starter to use the secondary motor configuration for the next start/stop cycle.
Direction
starter to reverse the phase sequence for the
86 EMX4i User Manual 710-14888-00C
Selects the function of Input A.
next start.
Page 88
7B –
Input A Trip
Options:
A trip can occur at any time when the soft
Description: 7C –
Input A Trip Delay
Range:
Default:
Description:
7D –
Input A Initial Delay
Range:
Default:
Description:
7E –
Input B Function
Options:
Description:
7F –
Input B Trip
Options:
Description: 7G –
Input B Trip Delay
Range:
Default:
Description:
PROGRAMMABLE PARAMETERS
Always Active
starter is receiving power.
Operating Only (default)
Run Only
A trip can occur while the soft starter is running, stopping or starting. A trip can only occur while the soft starter is running.
Selects when an input trip can occur.
0:00 - 4:00 (minutes:seconds)
0 second
Sets a delay between the input activating and the soft starter tripping.
00:00 - 30:00 (minutes:seconds)
0 second
Sets a delay before an input trip can occur. The initial delay is counted from the time a start signal is received. The state of the input is ignored until the initial delay has elapsed.
Input Trip (N/O) (default) Zero Speed Sensor Input Trip (N/C) Motor Set Select
Emergency Mode Reverse Direction Jog Forward Pump Clean Jog Reverse
Selects the function of Input B. Refer to parameter 7A
Function
for details.
Input A
Always Active Operating Only (default) Run Only
Selects when an input trip can occur.
0:00 - 4:00 (minutes:seconds)
0 second
Sets a delay between the input activating and the soft starter
710-14888-00C EMX4i User Manual 87
tripping.
Page 89
PROGRAMMABLE PARAMETERS
7H –
Input B Initial Delay
Range:
Default:
Description:
7I –
Reset/Enable Logic
Options:
Description:
NOTE
7J –
Input A Name
Options:
Low Level
Interlock Trip
High Level
Motor Temperature
No Flow
Motor Protection
Description:
7K –
Input B Name
Options:
Input B Trip (default)
Controller
Low Pressure
PLC
High Pressure
Vibration Alarm
Description:
If the reset input is active, the starter will not operate.
Input A Trip (default) Controller
00:00 - 30:00 (minutes:seconds)
0 second
Sets a delay before an input trip can occur. The initial delay is counted from the time a start signal is received. The state of the input is ignored until the initial delay has elapsed.
Normally Closed (default) Normally Open
Selects whether the reset input (10, 11) is normally open or normally closed.
Low Pressure PLC High Pressure Vibration Alarm Pump Fault Field Trip
Starter Disable Feeder Protection
Custom Message
Selects a message for the keypad to display when Input A is active.
The custom message can be loaded via the USB port. Refer to
USB Save & Load
on page 36 for details.
Pump Fault Field Trip
88 EMX4i User Manual 710-14888-00C
Low Level Interlock Trip High Level Motor Temperature No Flow Motor Protection Starter Disable Feeder Protection
Custom Message
Selects a message for the keypad to display when Input B is active.
Page 90

9.12 8 Relay Outputs

8A –
Relay A Function
Options:
Run (default)
The Run output closes when the soft start is
Trip
The relay closes when the starter trips (refer
Low Current
The relay closes when the low current flag
Soft Brake Relay
The relay closes when the soft starter
Description: 8B –
Relay A On Delay
Range:
Default:
Description:
Off Relay A is not used.
PROGRAMMABLE PARAMETERS
Ready
Warning
Flag
The relay is closed when the starter is in Ready state.
complete (when the starting current falls below 120% of the programmed motor full load current) and remains closed until the beginning of a stop (either soft stop or coast to stop). The relay closes when the starter issues a warning (refer to
6 Protection Action
on page
82).
to
6 Protection Action
on page 82).
activates while the motor is running (refer to
High Current Flag
Motor Temperature Flag
parameter 8G The relay closes when the high current flag activates while the motor is running (refer to parameter 8H The relay closes when the motor temperature flag activates (refer to parameter 8I
Temperature Flag
Low Current Flag
High Current Flag
).
).
).
Motor
receives a stop signal, and remains closed until the end of soft brake.
Reversing Contactor
The relay will control an external contactor, for reverse operation. Refer to
Direction Operation
on page 53 for details.
Reverse
Selects the function of Relay A. Relay A is a changeover relay.
710-14888-00C EMX4i User Manual 89
0:00 - 5:00 (minutes:seconds) Sets the delay for changing the state of Relay A.
0 second
Page 91
PROGRAMMABLE PARAMETERS
8C –
Relay A Off Delay
Range:
Default: Description: 8D –
Relay B Function
Options:
Description:
8E –
Relay B On Delay
Range:
Default: Description: 8F –
Relay B Off Delay
Range:
Default: Description: 8G –
Low Current Flag
Range:
Default: Description:
8H –
High Current Flag
Range:
Default: Description:
0:00 - 5:00 (minutes:seconds)
0 second
Sets the delay for changing the state of Relay A.
Off Low Current Flag
Ready High Current Flag Run (default) Motor Temperature Flag Warning Soft Brake Relay Trip Reversing Contactor
Selects the function of Relay B (normally open). Refer to parameter 8A
Relay A Function
for details.
0:00 - 5:00 (minutes:seconds)
0 second
Sets the delay for closing Relay B.
0:00 - 5:00 (minutes:seconds) Sets the delay for re-opening Relay B.
0 second
The EMX4i has low and high current flags to give early warning of abnormal operation. The current flags can be configured to indicate an abnormal current level during operation, between the normal operating level and the undercurrent or instantaneous overcurrent trip levels. The flags can signal the situation to external equipment via one of the programmable outputs.
The flags clear when the current returns within the normal operating range by 10% of the programmed flag value.
1% - 100% FLC
50%
Sets the level at which the low current flag operates, as a percentage of motor full load current.
90 EMX4i User Manual 710-14888-00C
50% - 600% FLC
100%
Sets the level at which the high current flag operates, as a percentage of motor full load current.
Page 92
PROGRAMMABLE PARAMETERS
8I –
Motor Temperature Flag
Range:
Default: Description:
8J –
Main Contactor Time
Range:
Default: Description:
9A –
Analog Output A
Options:
Motor
The motor's temperature, calculated by the
Motor pf
Motor power factor, measured by the soft
Description: 9B –
Analog A Scale
Range:
Description:
The EMX4i has a motor temperature flag to give early warning of abnormal operation. The flag can indicate that the motor is operating above its normal operating temperature but lower than the overload limit. The flag can signal the situation to external equipment via one of the programmable outputs.
100 – 2000 milliseconds
0% - 160% Sets the level at which the motor temperature flag operates, as
a percentage of the motor's thermal capacity.
Sets the delay period between the starter switching the main contactor output (terminals 33, 34) and beginning the pre-start checks (before a start) or entering the not ready state (after a stop). Set according to the specifications of the main contactor
used.

9.13 9 Analog Output

Current (% FLC) (default)
80%
400 milliseconds
Current as a percentage of motor full load current.
0-20 mA
Temperature (%)
thermal model.
starter. Motor Power (%kW) Heatsink
Temperature
Motor power, as a percentage of the
programmed power.
The soft starter's temperature, measured at
the heatsink. (°C)
Selects which information will be reported via the analog output.
4-20 mA (default) Selects the range of the analog output.
710-14888-00C EMX4i User Manual 91
Page 93
PROGRAMMABLE PARAMETERS
9C –
Analog A Maximum Adjustment
Range:
Default:
Description:
9D –
Analog A Minimum Adjustment
Range:
Default:
Description:
10A –
Language
Options:
Description:
10B –
Temperature Scale
Options:
Description:
10C –
Graph Timebase
Options:
Description:
10D –
Graph Maximum Adjustment
Range:
Default: Description: 10E –
Graph Minimum Adjustment
Range:
Default: Description:
0% - 600% Calibrates the upper limit of the analog output to match the
signal measured on an external current measuring device.
0% - 600% Calibrates the lower limit of the analog output to match the
signal measured on an external current measuring device.

9.14 10 Display

English (default) Português Chinese Français Español Italiano Deutsch Russian
Selects which language the keypad will use to display messages
100%
0%
and feedback.
Celsius (default) Fahrenheit
Selects whether the EMX4i will display temperatures in degrees Celsius or Fahrenheit.
30 seconds (default) 1 minute 30 minutes 1 hour
Sets the graph time scale. The graph will progressively replace the old data with new data.
92 EMX4i User Manual 710-14888-00C
0% – 600%
400%
Adjusts the upper limit of the performance graph.
0% – 600%
0%
Adjusts the lower limit of the performance graph.
Page 94
PROGRAMMABLE PARAMETERS
10F –
Current Calibration
Range:
Default: Description:
10G –
Adjustment Lock
Options:
Read & Write
Allows users to alter parameter values in the
Description:
10H –
User Parameter 1
Options: Motor Voltage
Average rms voltage across all three P3 Voltage
Phase 3 voltage.
The average frequency measured on three
Hours Run
The number of hours the motor has run via
85% - 115%
100%
Calibrates the soft starter's current monitoring circuits to match an external current metering device. Use the following formula to determine the necessary adjustment:
Calibration (%) = Current shown on EMX4i display Current measured by external device
(default) Read Only
main menu. Prevents users altering parameter values in the main menu. Parameter values can still be
viewed.
Selects whether the keypad will allow parameters to be changed via the main menu.
Blank
Current (default) Average rms current across all three phases
P1 Voltage Phase 1 voltage. P2 Voltage Phase 2 voltage.
Mains Frequency
Motor pf
Motor Power The motor's running power in kilowatts.
Displays no data in the selected area, allowing long messages to be shown without overlapping.
phases.
phases. The motor's power factor, measured by the soft starter.
Motor Temperature (%)
Number of Starts
710-14888-00C EMX4i User Manual 93
The motor's temperature, calculated by the thermal model.
the soft starter. The number of starts the EMX4i has completed since the start counter was last
reset.
Page 95
PROGRAMMABLE PARAMETERS
Pump Pressure
The pressure at the pump, as configured in
Pump Flow
The flow at the pump, as configured in Heatsink
The soft starter's temperature, measured at
SCR
The temperature of the SCRs, calculated by
Description:
10I –
User Parameter 2
Options:
Default:
Description:
10J –
User Parameter 3
Options:
Default:
Description:
parameters 30B~30D. This information is only available if the smart card is installed.
parameters 30F~30K. This information is only available if the smart card is installed.
Well Depth
Pump Temperature
Analog Output Value
Temperature Bypass Model (%)
Temperature Rating Capacity (%)
The depth of the well, as configured in parameters 30M~30O. This information is only available if the smart card is installed. The pump temperature, as measured by the PT100. This information is only available if the smart card is installed. The value of the analog output (refer to parameters 9A~9D).
the heatsink. The percentage of thermal capacity remaining in the bypass contactor.
the thermal model. The thermal capacity available in the soft starter for its next start.
Selects which information will be displayed on the main monitoring screen.
Refer to parameter 10H
User Parameter 1
Motor Voltage
for details.
Selects which information will be displayed on the main monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
Refer to parameter 10H
User Parameter 1
Mains Frequency
for details.
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
94 EMX4i User Manual 710-14888-00C
Page 96
PROGRAMMABLE PARAMETERS
10K –
User Parameter 4
Options:
Default:
Description:
10L –
User Parameter 5
Options:
Default:
Description:
10M –
User Parameter 6
Options:
Default:
Description:
11A –
Reverse Torque
Range:
Default: Description:
11B –
Reverse Time
Range:
Default: Description:
11C –
Forward Current Limit
Range:
Default: Description:
11D –
Forward Time
Range:
Default: Description:
Refer to parameter 10H
User Parameter 1
Motor pf
for details.
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
Refer to parameter 10H
User Parameter 1
Motor Power
for details.
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1
for details.
Refer to parameter 10H
User Parameter 1
Motor Temp (%)
for details.
Selects which information will be displayed on the programmable monitoring screen. Refer to parameter 10H
User Parameter 1

9.15 11 Pump Clean

20% - 100% Sets the torque level for reverse jog operation during pump
clean.
0:00 - 1:00 (minutes:seconds)
Sets the time for the starter to operate in reverse jog during a pump clean cycle.
100% - 600% FLC
for details.
20%
10 seconds
100%
0:00 - 1:00 (minutes:seconds)
710-14888-00C EMX4i User Manual 95
Sets the current limit for forward start operation during pump clean.
10 seconds
Sets the time for the starter to run the motor after a forward start, during a pump clean cycle.
Page 97
PROGRAMMABLE PARAMETERS
11E –
Pump Stop Mode
Options:
Description: 11F –
Pump Stop Time
Range:
Default: Description: 11G –
Pump Clean Cycles
Range:
Default: Description:
12A –
Modbus Address
Range:
Default: Description: 12B –
Modbus Baud Rate
Options:
Description: 12C –
Modbus Parity
Options:
Description: 12D –
Modbus Timeout
Options:
Description:
Coast To Stop (default) TVR Soft Stop
0:00 - 1:00 (minutes:seconds)
Selects the stop mode for pump clean.
Sets the stopping time for the starter during a pump clean cycle.
1 – 5 Sets how many times the soft starter will repeat the pump clean
cycle.

9.16 12 Communications Card

10 seconds
1
1 - 254
1
Sets the Modbus RTU network address for the soft starter.
4800 9600 (default) 19200 38400
Selects the baud rate for Modbus RTU communications.
None (default) Odd Even 10-bit
Selects the parity for Modbus RTU communications.
Off (default) 10 seconds 60 seconds 100 seconds
96 EMX4i User Manual 710-14888-00C
Selects the timeout for Modbus RTU communications.
Page 98
PROGRAMMABLE PARAMETERS
12E –
Devicenet Address
Range:
Default: Description: 12F –
Devicenet Baud Rate
Options:
Description: 12G –
Profibus Address
Range:
Default: Description: 12H –
Gateway Address
Range:
Default: Description:
12I –
Gateway Address
2
Range:
Default: Description: 12J –
Gateway Address
3
Range:
Default: Description: 12K –
Gateway Address
4
Range:
Default: Description:
NOTE
12L –
IP Address
Range:
Default: Description:
0 - 63
0
Sets the DeviceNet network address for the soft starter.
125 kB (default) 250 kB 500 kB
Selects the baud rate for DeviceNet communications.
1 - 125
1
Sets the Profibus network address for the soft starter.
0 - 255
192
Sets the first component of the network gateway address. The
The network address can also be set via the Network Address options in the Setup Tools. Refer to
gateway address is set using parameters 12H~12K and the default address is 192.168.0.100.
0 - 255
168
Sets the second component of the network gateway address.
0 - 255
0
Sets the third component of the network gateway address.
0 - 255
100
Sets the fourth component of the network gateway address.
Network Address
on page 38 for details.
0 - 255
192
Sets the first component of the soft starter's IP address, for Ethernet communications. The IP address is set using
710-14888-00C EMX4i User Manual 97
parameters 12L~12O and the default address is 192.168.0.2.
Page 99
PROGRAMMABLE PARAMETERS
12M –
IP Address
2
Range:
Default: Description:
12N –
IP Address
3
Range:
Default: Description:
12O –
IP Address
4
Range:
Default: Description:
NOTE
12P –
Subnet Mask
Range:
Default: Description:
12Q –
Subnet Mask
2
Range:
Default: Description:
12R –
Subnet Mask
3
Range:
Default: Description:
12S –
Subnet Mask
4
Range:
Default: Description:
NOTE
The network address can also be set via the Network Address options in the
0 - 255
168
Sets the second component of the soft starter's IP address, for Ethernet communications.
0 - 255
0
Sets the third component of the soft starter's IP address, for Ethernet communications.
0 - 255
2
Sets the fourth component of the soft starter's IP address, for Ethernet communications.
Setup Tools. Refer to
0 - 255
0 - 255
0 - 255
Network Address
on page 38 for details.
255
Sets the first component of the network subnet mask, for Ethernet communications. The subnet mask is set using parameters 12P~12S and the default mask is 255.255.255.0.
255
Sets the second component of the network subnet mask, for Ethernet communications.
255
Sets the third component of the network subnet mask, for Ethernet communications.
0 - 255
Sets the fourth component of the network subnet mask, for Ethernet communications.
0
The network address can also be set via the Network Address options in the
98 EMX4i User Manual 710-14888-00C
Setup Tools. Refer to
Network Address
on page 38 for details.
Page 100
PROGRAMMABLE PARAMETERS
12T –
DHCP
Options:
Description:
NOTE
12U –
Location ID
Range:
Default: Description:
20A –
Tracking Gain
Range:
Default: Description: 20B –
Pedestal Detect
Range:
Default: Description:
20C –
Bypass Contactor Delay
Range:
Default: Description:
20D –
Model Rating
Range:
Default: Description:
M/R: 0085 Made in New Zealand
RoHS
18595.B
1
NOTE
Disable (default) Enable
Selects whether the communications card will accept an IP address assigned by DHCP.
DHCP addressing is available with Modbus TCP and Ethernet/IP. DHCP addressing is not supported with Profinet.
0 - 65535
Sets the soft starter's unique location ID.

9.17 20 Advanced

1% - 200%
0
50%
100 – 2000 milliseconds
Fine-tunes the behaviour of the adaptive control algorithm.
0% - 200%
80%
Adjusts the behaviour of the adaptive control algorithm for soft stop.
150 milliseconds
Sets the starter to match the bypass contactor closing/opening time. Set according to the specifications of the bypass contactor used. If this time is too short, the starter will trip.
0020~0580
Model dependent
The soft starter’s internal model reference, as shown on the silver label on the side of the unit (
).
This parameter can only be adjusted by authorised servicing agents.
710-14888-00C EMX4i User Manual 99