Configure the control module according to your type of heating/cooling system using DIP switches on the back of the module.
Control Module (CT280-3H3C)
Heat pump
HVAC
The following devices can be connected to the controller:
air recirculation fan
humidifier
dehumidifier or air exchanger
dual-register meter (dual energy)
remote control device (for the unoccupied mode)
1.2
• CT280-3H3C control module
• TH146-P console with two wall anchors and mounting screws
• AC144-03 outdoor temperature sensor (3 m or 10 ft) with mount-
1.3
• RC845 relay (see section 2.4)
• AC146-410 plenum temperature sensor (see section 2.8)
• CT241 telephone controller (see section 2.10)
TH146-P-U 400-280-010-B 5/24/07 1/12
Supplied Parts
ing clip (see section 2.7)
Accessories
Install the control module near the heating/cooling system, away
from any heat source.
2.2
Install the console in a central location. Avoid locations with air
drafts (e.g., top of staircase or air outlet) or stagnant air (behind a
door). Do not install the console on a wall hiding air ducts nor
expose it to direct sunlight.
NOTE: If this controller replaces an old thermostat, any two of the
wires that were connected to the thermostat can be used to connect
the user console to the control module. The maximum wiring length
is 30 m (100 ft).
User Console (TH146-P)
n Choose a location about 1.5 m (5 ft) above the floor on an
inside wall.
o Loosen the captive screw under the console.
p Detach the console from its base by pulling the bottom section.
q Secure the base using th e w all an cho rs an d screw s.
r Connect the console to controller terminals TH and TH (no
polarity).
2.3
The terminals used to connect the heating/cooling system depend
on the type of system. See the appropriate wiring table on page 4.
Heating/Cooling System
needed if the heat pump is not connected to the controller
terminal WW.)
Install the sensor on the side of the plenum and
position it such that its aperture faces the air
flow.
Connect the sensor to controller terminals PS
and CS (no polarity). For more information,
refer to the instructions provided with the sensor.
NOTE: The maximum wiring length is 30 m
(100 ft).
2.9
Dual-energy Input
2.4
If you have an add-on installation, you might need an RC845 relay
to connect the furnace (auxiliary heating) and its fan to the controller. Install the relay near the control module and connect the wires
as follows:
•relay terminals W, G and C to controller terminals W1, G and C.
•relay terminals T and T to the appropriate furnace terminals: T
NOTE: Refer to the relay’s installation instructions for more details.
If you have a 3H1C or 4H2C heat pump, a second RC845 relay
might be required to connect the second auxiliary heat.
2.5
Connect the humidifier in series with the power supply between
controller terminals H and H (dry contact).
2.6
Connect the dehumidifier or air exchanger in series with the power
supply between controller terminals D and D (dry contact).
2.7
The outdoor sensor is required for the following:
When installing the sensor, observe the following guidelines:
Install the sensor using its mounting clip and connect it to controller
terminals OS and CS (no polarity).
NOTE: The maximum wiring length is 30 m (100 ft).
RC845 Relay
and T (oil); TH and TH (gas); R and W (electric).
Humidifier
Dehumidifier / Air Exchanger
Outdoor Sensor (AC144-03)
• outdoor temperature display
• balance points (heat pumps only, see section 4.2)
• defrost point (heat pumps only, see section 4.3)
• automatic humidity control (see section 7.2)
• use of an air exchanger (see section 4.10)
• Avoid locations where the sensor can be covered with snow
or exposed to direct sunlight.
• Avoid air outlets and concealed chimneys or stove pipes.
NOTE: The dual-energy input can be used only with a heat pump
equipped with auxiliary heat.
The dual-energy input can be connected to the dual-register meter
equipped with a normally open (NO) dry contact. Connect the controller terminals DE and CC to the meter terminals (yellow and red
wires).
The contact closes when the outdoor temperature drops below the
temperature setting on the meter. When the contact is closed, the
heat pump is disabled and only the auxiliary heat can be used.
2.10
To use the unoccu pied mode, the controller requires a remote control device such as Aube’s CT241 telephone controller equipped
with a normally open (NO) dry contact placed between terminals UN
and CC of the controller. The unoccupied mode is activated when
the contact closes. (See section 6.4.)
Unoccupied Mode Input
3. Configuration
3.1
To access the configuration switches, loosen the captive screw
under the console and separate the console from its base by pulling
the bottom section.
3.1.1Access Mode (SW1-1)
INST: Installer mode. Gives access to all configuration parameters.
USER: User mode. Gives access to configuration parameters 1 to 4
only.
3.1.2Keypad Lock (SW1-2)
I: The keypad is locked. Settings cannot be changed.
O: The keypad is unlocked.
3.2
Configuration Switches
NOTE: In installer mode, the short-cycle protection is disabled
and the interstage delay is reduced to 1 minute.
Software Configuration
n Place the console in Installer mode (INST) using the SW1-1
2.8
The plenum sensor is required for the following:
Plenum Sensor (AC146-410)
• low temperature limit inside the plenum (HVAC only)
• high temperature limit inside the plenum (HVAC only)
• fan limit if gas heating is used (HVAC only)
• high pressure protection during defrost cycle (This protection
is generally needed for add-on installations only. It is not
switch on the back of the console.
o Press the Mode button for 3 seconds to access the configura-
tion menu (see page 8). The first menu item (parameter) is displayed.
p To view another menu item, briefly press the Mode button.
q To modify a parameter, press either button.
r To exit the configuration menu, press .
s Return the console to User mode (USER).
TH146-P-U 400-280-010-B 5/24/07 2/12
4. Principles of Operation
4.1
With automatic heating/cooling mode changeover, there’s no need to adjust
the controller at every change of season or weather condition. The controller
switches automatically between heating mode and cooling mode to maintain
the desired temperature.
Manual Mode
When the controller is in manual mode, the heating/cooling mode
changeover occurs as follows:
•The controller switches to cool ing mode when the indoor temperature
•The controller switches the heating mode when the indoor temperature
Automatic Mode
When the controller is in automatic mode, it follows the programmed schedule. Two temperature settings (heating setpoint and cooling setpoint) are
programmed for each period of the schedule. The heating/cooling mode
changeover occurs as follows:
•When the controller is in heating mode, the indoor temperature is main-
•When the controller is in cooling mode, the indoor temperature is main-
4.2
Balance Points are used to disable the heat pump or the auxiliary heating
when the outdoor temperature is below or above a set temperature.
•When the outdoor temperature is below the Balance Point Low
•When the outdoor temperature is above the Balance Point High (bP H),
NOTE: Balance Points cannot be used if the AC144-03 outdoor temperature
sensor is not connected to the controller.
4.3
The auxiliary heat is activated during defrost except under the following conditions:
•When the outdoor temperature is above the defrost point (see page 8,
•When the plenum temperature is above 40°C (104°F). The auxiliary
NOTE: The auxiliary heat’s short-cycle protection is disabled during defrost.
4.4
Automatic Heating/Cooling Changeover
is higher than the setpoint by more than 1.5°C (2.5°F) for 15 minutes.
is lower than the setpoint by more than 1.5°C (2.5°F) for 15 minutes.
tained at the heating setpoint. However, if the temperature rises and
remains above the cooling setpoint for 15 minutes, the controller will
switch to cooling mode.
tained at the cooling setpoint. However, if the temperature drops and
remains below the heating setpoint for 15 minutes, the controller will
switch to heating mode.
Balance Points (heat pumps only)
(bP L), the heat pump is disabled and only auxiliary heating can be
used (see page 8, item 5).
the auxiliary heat is disabled and only the heat pump can be used (see
page 8, item 6).
Heating During Defrost (heat pumps only)
item 7). Note: This condition will not apply if the AC144-03 outdoor sen-
sor is not connected to the controller.
heat is re-activated when the plenum temperature drops below 32°C
(90°F). Note: This condition will not apply if the AC146-410 plenum
sensor is not connected to the controller.
Types of Heat Pump Installations
•New Installation: In this type of installation, as there is not already a
furnace, the auxiliary heat source is installed at the same time as the
heat pump. In this type of installation, the indoor coils are located
upstream of the auxiliary heat. When the controller is configured for a
new installation, the heat pump and the auxiliary heat can operate
simultaneously.
4.5
Interstage Delay is the time allocated for the temperature to return to an
acceptable value when it deviates too far from the setpoint. If this time has
elapsed, the next heating or cooling stage is activated. The heating or cooling stage will be deactivated when the temperature returns to an acceptable
value. The Interstage Delay is fixed at 4 minutes if the controller is configured for an HVAC system and is user-adjustable if it is configured for a heat
pump (see page 8, item 9).
4.6
Low Temperature Limit (LLMT) and High Temperature Limit (HLMT) are
used to keep the plenum from becoming too cold or too hot. During cooling,
if the plenum temperature is lower than LLMT, a cooling stage is deactivated
starting with the one that was last activated. If, after a while, the temperature
is still too low, another cooling stage is deactivated and so on. Likewise, during heating, if the plenum temperature is higher than HLMT, a heating stage
is deactivated starting with the one that was last activated. If, after a while,
the temperature is still too high, another heating stage is deactivated and so
on. (see page 8, items 10 and 11.)
WARNING: LLMT and HLMT can be used in parallel with an UL353approved device but they do not replace such device.
NOTE: LLMT and HLMT cannot be used if the plenum temperature sensor is
not connected to the controller.
4.7
When Smart Fan is enabled (see page 8, item 15), the fan operates as follows:
•During periods 2 and 4 of automatic mode and during the unoccupied
•The fan operates continuously the rest of the time.
NOTE: For Smart Fan to work, set the fan to On (see section 5.3).
4.8
If a humidifier and a dehumidifier are both connected to the controller, the
controller will automatically switch between the two devices to maintain the
desired humidity level. The changeover occurs when the humidity deviates
from the setpoint by more than 3% for 30 minutes.
4.9
Dehumidification by droop is a method of dehumidification without using a
dehumidifier. This method is possible only if your system has a cooling
stage. When this feature is enabled (see page 8, item 18), if the humidity
level is too high, the temperature is temporarily lowered below the setpoint
to reduce the indoor humidity level.
NOTE: Dehumidification by droop can cause overcooling.
Interstage Delay
Low and High Temperature Limits
Smart Fan
mode (i.e., when you are away from home or sleeping), the fan operates only when heating or cooling is activated.
The controller can be configured for either of the following types of heat
pump installations (see page 8, item 8).
•Add-on Installation: This type of installation is performed when adding
a heat pump to an existing furnace. When the heat pump is installed,
the furnace becomes the auxiliary heat source. In this type of installation, the indoor coils are usually installed downstream of the auxiliary
heat source. When the controller is configured for an add-on installation, the heat pump is disabled during auxiliary heating to prevent overpressure.
TH146-P-U 400-280-010-B 5/24/07 3/12
4.10
Dehumidification using an air exchanger will not be efficient if the outdoor
temperature is too high. When an air exchanger is used, the controller will
disable dehumidification if the outdoor temperature is NOT lower than the
indoor temperature by more than 5°C (9°F). When this occurs, the message
HIGH TEMP is displayed.
Dehumidification by Air Exchanger
Wiring Tables
Heat Pump
TerminalDevice1H1C2H1C3H1C2H2C3H2C4H2C3H3C
TH
TH
PSPlenum sensorConnect the plenum sensor between the PS and CS terminals (no polarity)
CSCommon SCommon terminal for the plenum sensor and the outdoor sensor
OSOutdoor sensorConnect the outdoor sensor between the CS and OS terminals (no polarity)
DEDual EnergyConnect the dual-register meter between the DE and CC terminals (no polarity)
CCCommon CCommon terminal for the dual-energy meter and the unoccupied mode input
UNUnoccupied mode input Connect a dry contact between the UN and CC terminals (no polarity)
H
H
D
D
Dehumidifier (24 Vac / 1 A)Connect the dehumidifier between the D terminals (dry contact)
R
C
Y1Compressor 1 (24 Vac / 1 A)
Y2Compressor 2 (24 Vac / 1 A)
Y3Compressor 3 (24 Vac / 1 A)
W1Auxiliary heat 1 (24 Vac / 1 A)
W2Auxiliary heat 2 (24 Vac / 1 A)
W3/O/BReversing valve (24 Vac / 1 A)
GFan (24 Vac / 1A)
LFault (24 Vac / 5 mA)
WWDefrost (24 Vac / 5 mA)
NCNot used
ConsoleConnect the console between the TH terminals (no polarity)
Humidifier (24 Vac / 1 A)Connect the humidifier between the H terminals (dry contact)
ConsoleConnect the console sensor between the TH terminals (no polarity)
PSPlenum sensorConnect the plenum sensor betw een the PS and CS terminals (no polarity)
CSCommon SCommon terminal for both plenum sensor and outdoor sensor
OSOutdoor sensorConnect the outdoor sensor between the OS and CS terminals (no polarity)
DENot used
CCCommon CCommon terminal for the unoccupied mode input
UNUnoccupied mode inputConnect a dry contact between UN and R terminals (no polarity)
H
H
D
D
R
C√√√√√√√√√√√√√√
Humidifier (24 Vac / 1 A)Connect the humidifier between the H terminals (dry contact)
Dehumidifier (24 Vac / 1 A) Connect the dehumidifier between the D terminals (dry contact)
Power (24 Vac)
√√√√√√√√√√√√√√
Y1Cooling unit 1 (24 Vac / 1 A)√√√√√√√√√√√
Y2Cooling unit 2 (24 Vac / 1 A)√√√√√√√
Y3Cooling unit 3 (24 Vac / 1 A)√√√
W1Heating unit 1 (24 Vac / 1 A)√√√√√√√√√√√
W2Heating unit 2 (24 Vac / 1 A)√√√√√√√√
1√√Time format12 Hr / 24 Hr24 HrSelect the time display format.
• On: Heating or cooling starts in advance (as determined by the controller) so that the desired temperature is attained at the set times.
2√√Early StartOn / OFOF
3√√
4√√ Temperature format°C / °F°CSelect the temperature display format.
5√Balance point low
6√Balance point high
7√Defrost point
8√Installation typeAd / nrAd
9√
10√Low temperature limit
11√High temperature limit
12√√ Cycles per hour2 to 64
13√Heat typeGA / ELEL
14√Fan limit
15√√Smart FanOn / OFOF
16√√Temperature setback
17√√
18√√ Dehumidifier typeCo / AE / drCo
19√√
Note: Only items 1 to 4 are available when the controller is placed in user mode (SW1-1 switch).
Automatic daylight
savings adjustment
Auxiliary
interstage delay
Humidifier
operating mode
Minimum air
exchange time
OF / 1 / 2OF
-30 to 10°C
(-22 to 50°F)
-5 to 30°C
(23 to 86°F)
-10 to 15°C
(14 to 59°F)
5 to 90 min.30 min.Set the interstage delay for the auxiliary stage (see section 4.5).
-10 to 20°C
(14 to 68°F)
30 to 90°C
(86 to 194°F)
38 to 90°C
(100 to 194°F)
0 to 9°C
(0 to 16°F)
Co / HE / FnFn
0 - 60 min.0
-10°C
(14°F)
5°C
(41°F)
10°C
(50°F)
5°C
(41°F)
70°C
(158°F)
80°C
(176°F)
0°C
(0°F)
• OF (Off): Heating or cooling starts at the set times.
NOTE: Early Start applies for periods 1 and 3 (P1 and P3) only. When this
feature is enabled, heating or cooling will st art i n advance o f the set time for
P1 and P3 but will start at the set time for P2 and P4.
• OF (Off): The function is deactivated.
• 1 : The controller switches to daylight savings time on the f irst Sunday o f
April and to normal time on the last Sunday of October.
• 2 : The controller switches to daylight savings time on the second Sunday of March and to normal time on the first Sunday of November.
Set the bP L limit (see section 4.2).
NOTE: Lower bP L below its minimum (- -) if you do not wish to use this
function.
Set the bP H limit (see section 4.2).
NOTE: Raise bP H above its maximum (- -) if you do not wish to use this
function.
Set the defrost point temperature (see section 4.3).
NOTE: Raise the defrost point above its maximum (- -) if you do not wish to
use this function.
Set according to the type of heat pump installation (see section 4.4).
• Ad (add-on): Use this setting when the indoor coils are located downstream of the auxiliary heat source. This is generally the case for add-on
installations.
• nr (normal): Select this setting when the indoor coils are located
upstream of the auxiliary heat source. This is generally the case for new
installations.
Set the low temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you lower LLMT below its minimum
(- -) or if the plenum temperature sensor is not connected to the controller.
Set the high temperature limit of the plenum (see section 4.6).
NOTE: This function is not used if you raise HLMT above its maximum (- -)
or if the plenum temperature sensor is not connected to the controller.
Select the number of heating/cooling cycles per hour. For optimal heating
control, use the setting that matches your system as follows: 3=20 min (hot
water, 90%+ high-ef ficiency furnace), 4=15 min (gas or oil), 5=12 min (gas
or oil), 6=10 min (electric).
This setting determines the fan operation in automatic mode when the system is in heating mode (see section 5.3).
• EL (electric heating): The fan starts and stops at the same time as heating.
• GA (gas or oil heating): The fan starts when the temperature inside the
plenum rises above the Fan Limit (see item 14) and stop s when th e temperature drops 12°C below the Fan Limit. NOTE: The fan will not start if
the plenum temperature sensor is not connected to the controller.
This parameter is available only when gas heating is selected (see it em 13).
WARNING: FLMT can be used in parallel with an UL353-approved device
but they do not replace such device.
NOTE: The fan will not start if you raise FLMT above its maximum (--).
• On: Smart Fan is On (see section 4.7).
• OF: Smart Fan is Off.
Set the amount of temperature setback when the controller is placed in
Unoccupied mode (see section 6.4).
• Co (conventional): The humidifier wi ll operate if the humi dity is too low. If
the fan is not already On, it will turn On at the same time as the humidifier.
• HE (heat): The humidifier can operate only when heating is activated.
• Fn (fan): The humidifier can operate as long as the fan is running,
whether heating is activated or not.
NOTE: The humidifier is disabled when cooling is activated.
Set according to the type of dehumidifier used.
• Co (conventional): Select this setting when using a dehumidifier (except
an air exchanger) or when you do not wish to dehumidify.
• AE (air exchanger): Select this setting when using an air exchanger (see
section 4.10).
• dr (droop): Select this setting to dehumidify by droop (see section 4.9).
This parameter is available only if the controller is configured for using an
air exchanger (see item 18). Use it to set the minimum air exchange time
(see section 8.3).
TH146-P-U 400-280-010-B 5/24/07 8/12
TH146-P-U
User’s Guide
Programmable H/C Controller
Time and day setting
Programming
Program day selection
Program clear
Humidity setting
Return
5. General Setting
5.1
n Press Clk. The hour display flashes.
o Set the hour using .
p Press Clk. The minute display flashes.
q Set the minutes using .
r Press Clk. The day display flashes.
s Set the day using .
t Press to return to the normal display.
5.2
n Press Clk for 3 seconds to display the year.
o Set the year using .
p Press Clk to display the mont h.
q Set the month using .
r Press Clk to display the date.
s Set the date using .
t Press to return to the normal display.
Clock and Day Setting
Date Setting
Indicator LEDs
Temperature
adjustment
mode selection
Fan operating
mode selection
System operating
mode selection
Up/Down buttons
Indicator LEDs
FAULT: System fault
EH: Emergency heat mode
DE: Dual energy
Backlight
The screen is lit for 12 seconds
when any button is pressed.
However, the screen remains li t
while you are configuring the
controller.
Day
Clock
Indoor temperature
Indoor humidity
Outdoor temperature
6. Temperature Setting
6.1
The controller normally displays the measured indoor temperature.
To view the setpoint, press one of the buttons. The setpoint and
the symbol will be displayed for the next 5 seconds.
6.2
Press Mode to place the system in one of the following modes:
Display
Appears when the
temperature setpoint
is displayed
Heating is On
Auxiliary heating is On
Temperature adjustment
mode (appears when the
system is in automatic
mode, disappears when it
is in manual mode)
System Operating Mode
Indoor temperature
Cooling is On
System operating mode
Fan operating mode (appears when the fan is in
continuous mode, disappears when it is in automatic mode)
5.3
Press the Fan button to select the fan operating mode.
•In automatic mode, the fan runs only when heating or cooling is
•In continuous mode, the fan runs continuously and the sym-
TH146-P-U 400-280-010-B 5/24/07 9/12
Fan Operating Mode
activated. NOTE: For gas-operated HV AC systems, there might
be a delay before the fan starts or stops when heating is activated or deactivated.
bol is displayed. NOTE: if Smart Fan is enabled, when the controller is in periods 2 and 4 of automatic mode and in
unoccupied mode, the fan will run only when heati ng or cooling
is activated. The fan will run continuously the rest of the time
HEAT
COOL
AUTO
OFF
EHEAT
The system is in heating mode.
The system is in cooling mode.
The system is in automatic changeover mode. (The system
switches between heating mode and cooling mode to maintain the desired temperature.)
The system is off.
The system is in emergency heat mode. Only auxiliary heat-
ing is used when there is a call for heat. (This mode applies
only when the controller is connected to a heat pump
equipped with auxiliary heating).
6.3
6.3.1Manual Adjustment
Use this mode to set the temperature manually. To place the controller in this mode, press Auto/Man so that disappears from the
screen. Set the temperature using the buttons.
NOTE: If the controller is in automatic heat/cool changeover (see
section 6.2), the setpoint is automatically redu ced or raised by 1°C
(1.8°F) when the controller switches to heating mode or to cooling
mode respectively. For example, if the setpoint is 24°C (75°F) in
heating mode, it will become 25°C (77°F) in co oling mode and will
return to 24°C (75°F) when the controller switches back to heating
mode.
6.3.2Automatic Adjustment
Use this mode if you want the controller to adjust the temperature
according to the programmed schedule. To place the controller in
this mode, press Auto/Man so that appears on the screen.
Pre-programmed Schedule
The following schedule has been programmed at the factory. Two
temperature settings are programmed for each period of the schedule: a heating setpoint and a cooling setpoint.
point is 22°C (72°F) and you set the heating setpoint to 23°C (73°F),
the cooling setpoint will automatically become 24°C (75°F). However, if you raise the heating setpoint to 21°C (70°F), the cooling
setpoint will remain at 22°C (72°F). The same principle applies
when you set the cooling temperature.
•Press to exit.
The following diagram shows how to navigate the programming
menu.
MOTU
6:006:00
P1
Heat
2125.52125.5
P2
Heat
16.529.516.529.5
Temporary Bypass
When you modify the temperature setpoint while the control ler is in
automatic mode, the new temperature is used for the next 2 hours.
The icon flashes during the bypass. After the bypass, the temperature set for the current period is used.
Pgm
Mode
8:008:00
Mode
CoolHeat
Pgm
Pgm
Cool
Day
Day
Heat
Mode
Mode
Pgm
Cool
Pgm
Pgm
Cool
Modifying the Schedule
You can program up to 4 periods per day. To program a period, you
need to set the start time, the heating setpoint and the cooling setpoint. The program can be different for each day of the week.
•Press Pgm to enter the programming mode. The setti ngs for
Monday, Period 1 (P1) appear.
•To select a day to program, press Day until the day is displayed. Press for 3 seconds to select all 7 days.
NOTE: If you select all 7 days, the settings of the displayed
period will be copied to all 7 days. For example, if you select all
7 days while period 1 is displayed, they will all now have the
same settings for period 1. If you display period 2 while all 7
days are selected, they will all now have the same settings for
period 2.
•To set the start time of a period, press Pgm until the period
number (P1 to P4) is displayed and the time display flashes.
Then press the buttons. The time changes in increments of
15 minutes.
NOTE: To skip a period, display the period and press Clr. For
example, in the pre-programmed schedule, periods 2 and 3
have been skipped for Saturday and Sunday.
•To set the temperatures for a period, press Pgm until the period
number (P1 to P4) is displayed and the temperature display
flashes. If necessary, press Mode to display the heating set-
point or the cooling setpoint. Press the buttons to set the
temperature.
NOTE: The cooling setpoint is always higher than the heating setpoint by a minimum of 1°C (1.8°F). For example, if the cooling set-
6.4
Y ou can place the controller in the unoccupied mode using a remote
control device such as Aube’s CT241 telephone controller. In this
mode, the temperature is lowered in heating mode or raised in cooling mode (see page 8, item 16). The message UNOC appears during
the unoccupied mode.
NOTE: Automatic changeover is disabled during the unoccupied
mode.
Temporary Bypass
In the unoccupied mode, only the buttons work. When you
adjust the temperature during this mode, the new temperature will
be used for the next 2 hours, after which the controller will return to
the previous setpoint. The message UNOC flashes during the bypass.
Unoccupied Mode
TH146-P-U 400-280-010-B 5/24/07 10/12
7. Humidity Setting
7.1
Display
Appears when
dehumidification is
disabled because the
outdoor temperature
is too high
Appears when the
humidity setpoint
is displayed
Humidity level
8.2
To deactivate the air exchange mode:
Manual Deactivation
n Press the Hum button until one of the following appears on the
screen.
AUTO: The air exchanger is in humidity control mode (automatic adjustment).
MAN: The air exchanger is in humidity control mode (manual
adjustment).
OFF: The air exchanger is Off.
o Press the button to return to normal display.
Humidifier is On
Dehumidifier is On
7.2
Manual Adjustment
The humidity level is set by the user (5 to 60%).
Humidity Adjustment
Humidity control mode
(auto, manual, off or
air exchange)
n Press the Hum button until MAN appears on the screen.
8.3
If the controller is configured for a minimum air exchange time every
hour and that minimum has not already been attained by the end of
the hour, the air exchanger will be activated regardless of the indoor
humidity level (see page 8, item 19). Let’s say the minimum time is
set to 10 minutes. If the air exchanger has operated for 7 minutes
during a particular hour, it will automatically be activated for another
3 minutes by the end of that hour.
Minimum Air Exchange Time
9. Technical Specifications
o Press one of the buttons to adjust the humidity level.
p Press the button.
Automatic Adjustment
The humidity level is set by the controller based on the outdoor temperature to prevent ice formation or condensation on the windows
while providing enough humidity for your comfort. However, the user
can apply an offset (-9 to 9%). For example, the user can enter a
negative offset if there is ice formation or condensation on the windows.
n Press the Hum button until AUTO appears on the screen. The
humidity level set by the controller is also displayed.
o Press one of the buttons to enter or change the offset.
CT280-3H3C CONTROL MODULE
Power supply: 24 VAC
Current consumption: 150 mA
Maximum load per output: 1 A @ 24 VAC
Short cycle protection: 2 minutes
Control cycles: 2 to 6 per hour
Operating temperature: 0°C to 50°C (32°F to 122°F)
Storage temperatur e : -20°C to 50°C (-4°F to 122°F)
Humidity conditions: 0 to 95%, non-condensing
Dimensions: 95 x 137 x 30 (3.8 x 5.4 x 1.2 in.)
p Press the button.
Off
To turn off the humidity control:
n Press the Hum button until OFF appears on the screen.
o Press the button to save and exit the programming.
8. Air Exchange Duration Setting
8.1
If an air exchanger is connected to the controller, it can be used in
either of the following modes:
In air exchange mode, the air exchanger is activated to circulate air
between indoors and outdoors regardless of the indoor humidity
level). To activate the air exchange mode:
Manual Activation
• Humidity control mode (see section 7.2)
• Air exchange mode (see below).
TH146-P USER CONSOLE
Temperature setpoint range
Heating mode: 5°C to 30°C (40°F to 86°F)
Cooling mode: 15°C to 40°C (59°F to 104°F)
Humidity setpoint range: 5 to 60%
Indoor temperature display range: 0°C to 70°C (32°F to 158°F)
Outdoor temp. display range: -50°C to 70°C (-58°F to 158°F)
Temperature display resolution: 0.5°C (1°F)
Program protection: non-volatile memory
Operating temperature: 0°C to 50°C (32°F to 122°F)
Storage temperatur e : -20°C to 50°C (-4°F to 122°F)
Humidity conditions: 0 to 95%, non-condensing
Dimensions: 79 x 79 x 24 mm (3.1 x 3.1 x 1 in.)
n Press the Hum button until AIR appears on the screen.
o Set the duration you want the air exchanger to operate using
the buttons. Select 10 - 90 minutes for a specific duration
or On for an indefinite length of time.
p Press the button.
TH146-P-U 400-280-010-B 5/24/07 11/12
10.Warranty
Aube warrants this product, excluding battery, to be free from
defects in the workmanship or materials, under normal use and
service, for a period of three (3) years from the date of purchase by
the consumer. If at any time during the warranty period the product
is determined to be defective or malfunctions, Aube shall repair or
replace it (at Aube's option).
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to
the place from which you purchased it, or
(ii) contact Aube. Aube will make the determination whether the
product should be returned, or whether a replacement product
can be sent to you.
This warranty does not cover removal or reinstallation costs. This
warranty shall not apply if it is shown by Aube that the defect or
malfunction was caused by damage which occurred while the
product was in the possession of a consumer.
Aube's sole responsibility shall be to repair or replace the product
within the terms stated above. AUBE SHALL NOT BE LIABLE FOR
ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY
INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING,
DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY
WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE
OF THIS PRODUCT. Some provinces and states do not allow the
exclusion or limitation of incidental or consequential damages, so
this limitation may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY AUBE
MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED
WARRANTIES, INCLUDING THE WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, IS HEREBY LIMITED TO THE THREE-YEAR
DURATION OF THIS WARRANTY. Some provinces and states do
not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have
other rights which vary by province or state.
11.Support
If you have any questions about the product installation or
operation, or concerning the warranty, contact us at the address
shown below.