TH144
Installation and User Guide
Electronic Thermostat for a Heat Pump
n
TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER
PANEL TO AVOID ELECTRICAL SHOCK
Installation should be carried out by an electrician or a qualified
technician.
Installation
.
1.
1.2 Prepare and Connect the Thermostat
1.1 Find a Location for the Thermostat
• For a new installation, choose a location about 5 ft. (1.5 m) above
the floor and on an inside wall.
• Avoid locations where there are air drafts (top of staircase, air outlet), dead air spots (behind a door), direct sunlight, concealed
chimneys or pipes, or air diffusers.
TABLE 1: Wiring Terminals
OUTPUT CONFIGURATIO N (MODEL)
Ter m i n a l s
R
C
W
Y
Y1
Y2
G
O/B
Fault
REM Unoccupied input (optional) - see 1.3 CT240/CT241/timer
Vcc (1)
Tx/Rx (2)
Gnd (3)
a. For 2H1C & 3H2C models, the AC144-02 is required to use the balance point option (compressor cut-off).
1H1C
Geothermal
2H1C
D D D D
DDDD
D D
DD
D D D D
DDDD
D D D D
AC144-02 Remote Indoor and Outdoor
Temperature Interface - see 1.4
2H2C
Geothermal
D D
DD
Loosen the captive screw
holding the base to the
module.
3H2C
Gently lift the lower part of
the module to remove it
from the base.
Connect to...
Supply 24 VAC
Auxiliary heat relay
Compressor relay
First compressor relay
Second compressor relay
Reversing valve
Heat pump fault output
AC144-02
Common
Fan relay
Secure the base using the
wall anchors & screws.
Wire the thermostat.
a
FIGURE 1: Typical Wiring Dia gram (model shown TH144-3H2C)
TH144 400-144-003-C 2008-02-08 1/6
1.3 Connecting the REM input (optional)
To remotely activate the Unoccupied mode, the REM input allows
connection to an optional CT240/CT241 telephone controller, a
central timer or an alarm system.
A closed contact remotely activates the Unoccupied mode (see 4.1).
24 VAC
24 VAC
TIMER
24 VAC
1.4 Connecting the AC144-02 RTI (optional)
The AC144-02 Remote Temperature Interface (RTI) connects to a
TH144 thermostat for remote indoor or outdoor temperature
readings.
NOTE: If you wish to use the balance point cut-off functi on to cut the
heat pump compressor when the outdoor temperature drops below
the defined cut-off setpoint (see section 4.4 to de fine this setpoint),
you must connect a remote temperature interface.
NOTE: Refer to the AC144-02 installation instructions for details on
how to connect the RTI to the thermostat.
1.4.1 Remote Indoor Sensing
The REM icon indicates that the
temperature is controlled from a remote
location using the RTI’s housing sensor or
the connected probe(s).
Temperature averaging can be obtained
using up to 4 probes.
To return to local control, disconnect the
RTI wires at the thermostat terminals and
turn off for at least 5 seconds.
1.4.2 Remote Outdoor Sensing
The OUT icon indicates the outdoor
temperature read from the outdoor probe
connected to the RTI.
On some models (2H1C & 3H2C), the
outdoor temperature is used for the compressor cut-off point.
1.5 First Power On
When you power TH144 for the first time, it
runs a sequence of tests and resets itself,
which lasts approximately 10 seconds. The
default setpoint is 20°C (68°F).
NOTE: The displayed ambient temperature
might be higher than the real ambient temperature if you are holding the thermostat.
Non-programmable models
Programmable
models
For the programmable models, open the thermostat’s door, and set
the time (
NOTE: To protect the compressor, TH144 has an On/Off delay of 2
Hour and Minute) and day (Day).
or 4 minutes (default is 2 minutes) before starting or stopping the
system (see the following section).
1.6 Configure the TH144
The TH144 offers many configuration options
using the DIP switches located on the back of
the thermostat. Default settings are inside the
shaded cells.
NOTE: After first power-up, wait at least 5 min-
utes while the internal battery is being charged
before configuring TH144.
Name DESCRIPTION UP DOWN
Select the display format. When you
Display
Cycle
Aux
Keys
Protect
Stages
Val v e
change the display format, the set-
°C/24h °F/12h
points revert to their default values.
20 minutes = heavy commercial
applications
15 minutes = residential & light
commercial applications
NOTE: On models not equipped with
20 min.
15 min.
the Protect switch, the On/Off delay is
set based on the cycle. That is, the
On/Off delay is 4 minutes for the 20
minute-cycle and is 2 minutes for the
15 minute-cycle.
W = the compressor turns Off during
auxiliary heating.
W + Y = the compressor remains On
W
W+Y
during auxiliary heating.
Lock the keypad. The icon is dis-
played when any button is pressed to
indicate that the setpoint or operating
mode cannot be modified. On the pro-
Lock
Unlock
grammable models, the schedule cannot be modified as well.
To protect the compressor against too
frequent On/Off, TH144 provides an
4 min.
2 min.
On/Off delay selectable via this switch.
Select between 2H2C and 1H1C. 1H1C 2H2C
Select the polarity of the reversing
valve. B= the valve is energized during
heating. O= the valve is energized dur-
B
O
ing cooling.
TH144 400-144-003-C 2008-02-08 2/6