Atmor AT90008, AT90013, AT90010, AT90004, AT90006 User Manual

...
Hot Water on Demand
Installation and Operation Guide
900 Series InLine
3kW-13kW
www.atmor.net
Safety Instructions
OVERVIEW
This manual must be read carefully before attempting to install the water heater. If you do not follow the safety rules or the instructions outlined in this manual, the unit may not operate properly and it could cause property damage, serious bodily injury or death.
Atmor will not be liable for any damages because of failure to comply with the installation and operating instructions outlined in this manual or because of improper use. Improper use includes the use of this appliance
to heat any liquid other than water. Failure to comply with the installation and operating instructions or
improper use voids the warranty. Never remove the unit’s cover unless the electricity is turned off.
01
The water heater must be installed by a licensed electrician and in compliance with all local electrical and building regulations.
04
The heater must be installed according to the installation
instructions (see gures).
07
The plumbing installation requires metal or reinforced pipes that can withstand a minimum pressure of 8 bar. (Other types of pipes will
cause damage.)
02
Caution: The appliance must be grounded.
05
The plumbing installation must be completed before the electrical installation.
08
Do not install the heater where it may be subjected to direct sunlight, rain and/ or a constant spray of water.
03
A dedicated circuit breaker must be installed on the power distribution panel.
06
The heater operates at a
minimum water ow rate of
0.5 gallon/minute.
09
Always contact your local authorized licensed proffessional for service.
1
Technical Information
Model *Wattage Voltage Amperage Phase
AT900-03 3 kW 110 27 1 30 10 AWG
AT900-04 3.8 kW 240 16 1 20 12 AWG
AT900-06 6.5 kW 240 27 1 30 10 AWG
AT900-08 8.5 kW 240 36 1 40 6 AWG
AT900-10 10.5 kW 240 44 1 50 6 AWG
AT900-13 13 kW 240 55 1 60 4 AWG
Minimum water ow to activate unit: 0.5 GPM Nominal water volume: 2.7G/Min Working pressure: 0.5 -8 bar (7 -115 psi) Tested pressure: 16 bar (230 psi) Water connections: 1/2" NPT Dimensions (in) (H x W x D): 7.3 x 11.8 x 3.55 Weight (Ib): 3.4
* Wattage based on maximum voltage.
Circuit breaker
size
Model Guide - kW Output
Model 240V 208V 110V 120V
AT900-04 3.8 kW 2.8 kW - -
Required wire
size
AT900-06 6.5 kW 4.9 kW - -
AT900-08 8.5 kW 6.4 kW - -
AT900-10 10.5 kW 7.9 kW - -
AT900-13 13.0 kW 9.8 kW - -
AT900-03 - - 3.0 kW 3.5 kW
2
Assembly Instructions
01
Connect the Pressure Relief
Device (PRD) to the unit (Fig1)
Note: IMPORTANT – do not discard this step. A PRD must be installed.
Mount unit to wall with 4 screws at the
marked points (Figure 4)
04
05
The appliance must be mounted horizontally, with water inlets and outlets
at the bottom (Figure 5)
Connect the water inlet hose to the entry point of the heater (left side
inlet), and connect the outlet hose to the water outlet. Use a hose that can withstand a minimum pressure of 4 bars. Using any other type of hose will cause damage (Figure 5).
Residential plumbing systems with unstable pressure or pressure above 5 bar require the application of a pressure stabilizer valve, set to 4 – 5 bars.
Do not install the appliance with water inlets and outlets at the
top (Figure 6)
02
Remove the appliance
covers (Figure 2).
03
1. Mount ground plate to wall.
2. Pull wires through.
3. Cut out hole in back of unit (Right/Left
back) and pass wires
through
(Figure 3)
06
3
1
Rubber
PRD
Cold Hot
2
*
3 4
*3a) 3kW
L1 L2 N
L1
N
**
*3b)
3.5-8.5kW
L1GGN
G = Green or Yellow N = White L1/L2 = Black
L1G
L2
GNL1
*3c)
8.6-13kW
65
Note: Neutral (N) does not need to be connected.
L1
(L2)
L2
N
L1
4
07
Run the water ow for
one minute to check for leakage before connecting to power.
08
Connect the power cable to the terminal block. Caution: The heater must be grounded.
Reference gure *3 on page 4 and
Electrical diagram on page 6
1009
Reattach the front cover of the heater and secure it with 4 screws and then slide the bottom gray cover
12
Do not install the heater where it may be subject to direct sunlight.
Aerator provided with 3kW models only
Assembly instructions
Make sure that the
appliance is lled with
water before connecting
power. (Repeat step 7)
13
14
For optimal heating performance and proper operation, the provided 0.5GPM aerator must be installed to your sink faucet. This will ensure
a continuous ow and consistent, maximum
temperature rise. Output temperature will vary depending on seasonality and inlet cold water temperatures
11
When installed outdoors, the heater must be placed in sealed waterproof electrical box.
It is recommended that the appliance electrical connections be tested once
a year by a qualied technician.
Maximum of 0.5 GPM ow rate is needed for optimal heating performance
5
Electrical Diagram
1. 3-3.4kW (110V) - Install Line 1 (L1), E(G)-Ground, N (Neutral)
2. 3.5-8.5kW (240V) - Install Line 1 (L1), E(G)-Ground, Line 2 (L2)
1
L
E(G)
N
1
L1
E(G)
L2(*N)
8.6kW-10.5kW (240V)
L N
E(G)
L1
L2(*N)
E(G)
10.6kW-13kW (240V)
411 53 6
78
3
1. Terminal block
2. Thermal cut-out with reset
3. Thermal cut-out
4. Relay
5. Light
6. Switch 0- Off
(Option) 1- Low
7. Heating element
8. Read sensor
1. Terminal block
2. Thermal cut-out with reset
3. Thermal Cut out
4. Relay
5. Switch 0- Off 1- Low 2- Medium 3- High
6. Heating element
7. Read sensor
8. EARTH(G) Connection in
the heating canister
L
N
E (G)
L1
L2(*N)
E(G)
1
1
2 7
8
5 64
L1/L2 = Line1/Line2 (Black or Red) E(G) = Ground (Green/Yellow)
*N = Neutral (White or Silver)
*Neutral acts as Line 2 (L2) for 220V/240V *Neutral does not have to be connected for 3.5kW-13kW
1. Terminal block
2. Thermostat with reset
3. Thermostat
4. Switches with lights
5. Relay
6. Heating elements
7. Read sensor
8. EARTH(G) Connection in
the heating canister
6
Operation Guide
Low Medium High
MODEL kW kW kW
AT900-03 1 2 3
AT900-04 1.6 2.2 3.8
AT900-06 3 3.5 6.5
AT900-08 3.8 4.7 8.5
AT900-10 5.25 5.25 10.5
AT900-13 4.5 8.5 13
Troubleshooting
PROBLEM ISSUE POSSIBLE CAUSE SOLUTION
Water not hot enough.
Too much water owing
through the heater.
Reduction in the ambient temperature.
Water Pressure below of
0.5 bar (7 psi).
Electrical Malfunction.
Reduce the ow rate of the water via
the outlet tap.
Switch to higher temperature setting.
Check if the main water line stop valve is fully open and that there are no other restrictions in the water supply line.
Have the Heater unit check by a
qualied eIectrician or contact your
local authorized distributor.
7
Loading...
+ 16 hidden pages