Atlantic TA1800, TA3600 Product Manual

Product Manual | Manuel du Produit | Manual del Producto
1.330.274.8317
www.ATLANTICWATERGARDENS.com
M
TA1800 / TA3600
Introduction
This pump is designed to pump air. The oil-free, double damping air pump system produces a large volume of air with little noise. The aluminum casing and outer housing cover dissipate heat quickly and shield the compressor from the elements in an outdoor application.
Atlantic’s Typhoon Air Pump may be used in a variety of water-related applications including oxygenation of ponds and aquariums and de-icing of outdoor ponds.
To avoid an accident, do not use the pump in any way other than as described in this manual. Please note the manufacturer cannot be responsible for accidents arising because the product was not used as prescribed. After reading this manual keep it as a reference in case questions arise during use.
2
Prior to Operation and Installation
When the pump is delivered, first perform the following checks:
• Check for any damage to pump and power cable that may have occurred during shipping.
• Check the model number to make sure it is the product that was ordered and verify the voltage and frequency are correct.
Caution
• DO NOT operate this product under any condition other than those for which it is specified. Failure to observe this precaution can lead to electrical shock, electrical leakage, fire, water leakage or other problems.
• Please only use with a power supply voltage within 110-120 volt 60 Hz.
• Always turn o power or unplug the pump prior to performing any maintenance or placing your hands into the water.
CAUTION:
THIS AIR PUMP IS TO BE USED IN A CIRCUIT PROTECTED BY A GROUND FAULT CIRCUIT INTERRUPTER.
WARNING:
RISK OF ELECTRIC SHOCK - THIS PUMP IS SUPPLIED WITH A GROUNDING CONDUCTOR AND GROUNDING-TYPE ATTACHMENT PLUG. TO REDUCE THE RISK OF ELECTRIC SHOCK, BE CERTAIN THAT IT IS CONNECTED ONLY TO A PROPERLY GROUNDED, GROUNDING TYPE RECEPTACLE.
AIR PUMP OUTPUT
MODEL MAX @ 1' @ 2' @ 3' @ 4' @ 5' @6' @8' @10'
TA1800
LPM /
CFM
30 /
1.06
25 /
0.88
21 /
0.74
17 /
0.60
13 /
0.46
9 /
0.32
4 /
0.14
--- ---
TA3600
LPM /
CFM
60 /
2.12
54 /
1.91
47 /
1.66
40 /
1.41
34 /
1.2
28 /
0.99
23 /
0.81
12 /
0.42
2 /
0.07
MODEL OUTLET VOLTS WATTS
MAX
PRESSURE
MAX
DEPTH
CORD
LENGTH
TA1800
⅜" insert, ½" slip 115 25 3 psi 7’ 6'
TA3600
⅜" insert, ⅝" slip 115 35 5 psi 11’ 6'
3
Electrical Safety
• Electrical wiring should be installed by a qualified electrician in accordance with all applicable safety regulations. Incorrect wiring can lead to pump malfunction, electrical shock or fire.
• Air Pumps must be protected by a ground fault circuit interrupter (GFCI).
• Air Pumps must be plugged into a standard, properly grounded, three pronged outlet.
Safety Instructions
• If the pump falls into the water, do not reach for it. First unplug the air pump or disconnect the power supply and then retrieve the pump. Let a qualified technician inspect the pump if immersion occurs.
• Do not lift, lower or handle the pump by pulling on the electrical cord. Make sure the electrical cable does not become excessively bent or twisted and does not rub against a structure in a way that might damage it.
• The submersible pump should not be used if the electrical supply cable is damaged in any way. If a cable with damaged insulation is submerged in water, there is danger of
ATTENTION
Typhoon air pumps are NOT submersible, and must be placed in a secure area away from the water’s edge.
water seeping into the pump motor and causing a short. Altering the electrical cable in any way will void the warranty.
Installation
Pump Placement
The following factors must be considered when choosing a location for the air pump.
• Typhoon Air Pumps feature weather-proof aluminum housings for outdoor use. However, installation in a dry, well-ventilated area will further prolong the service life of the air pump.
• Typhoon Air Pumps must be placed on a flat, stable surface above the water level of the pond.
• Proper ventilation is critical for heat dissipation and operation. Never cover the air pump unless adequate airflow to the pump is provided.
• Tubing must always be run on a downward slope away from the air pump to avoid condensation damage.
Air Pump Connections
Typhoon Air pumps will accept multiple sizes of tubing. Please refer to the chart on page 2 for acceptable tubing diameters for these Air Pumps. Using large diameter tubing and avoiding sharp bends will improve performance of this air pump after installation.
• Multiple air stones can be connected to the pump outlet by adding a 2-way air splitter.
Use new and suciently large air stones with enough discharge capacity. Air stones that are too small, old, worn out or placed too deep will reduce the output capacity. Place air stones no deeper than 7’ (TA1800) and 11’ (TA3600) below the surface of the water. Avoid kinks and tight turns in the tubing run and take care to never fully close o the pump outlet. Ensure that the pump can discharge sucient air at all times, otherwise the pump will overheat leading to diaphragm and compressor failure. Please note that an ambient temperature above 110° F can cause the diaphragm to overheat and crack.
4
To prevent any water from flowing back into the pump when powered o, it is advisable to install the pump above water level. Tubing must run at a downward slope away from the compressor. The use of an inline check valve is also recommended to further prevent moisture damage.
Service & Maintenance
Dust and debris blocking the air intake may cause abnormal noises or result in a failure of the pump. Periodic cleaning of the air intake and sponge is recommended:
• Unplug the air pump before cleaning or replacing the air intake sponge.
• Remove the air intake cover, intake filter and clean with mild detergent.
• Rinse the components thoroughly and allow to dry completely before reinstalling.
Diaphragm replacement
Rubber diaphragms are a wearable part that will need servicing over time. Moisture, heat and dust will all shorten the life of the diaphragms. Please follow the following steps when installing replacement diaphragms.
• Remove the top cover housing for the air pump. Loosen the air chamber screws (1) and remove the outer air chamber (2).
• Loosen the diaphragm nut (3) and remove the diaphragm depressor (4), electrostatic membrane (5) and the damaged diaphragm (6).
• Install the new diaphragm ensuring that the rubber tabs align properly with the notches on the inner air chamber.
• Once the diaphragm is seated properly, assemble the components by following the previous steps in reverse order.
Warranty
All Typhoon Air Pumps carry a three-year limited warranty. This limited warranty is extended solely to the original purchaser commencing from the date of original purchase receipt and is void if any of the following apply:
• The cord has been cut or altered.
• The pump has been misused or abused.
• The pump has been disassembled other than as described in this manual.
• Serial number tag has been removed.
Air Intake Cover
Air Intake Filter Sponge
Top Cover Housing
6
5
4
3
2
1
5
Problem Possible Cause Possible Solution
Air pump does not run
Power is o Turn power on
Power failure
Check power supply or contact local power company
Voltage drop/ Overload
Check/Replace the GFI (Ground Fault Interrupter)
Power cord is not connected Connect power cord
Air pump stops after starting
Air pump is overheating
Allow pump to cool
Power/Current overload
Check length/size of power cable. Check or replace GFI
Diminished air flow rate or no air flow
Kinked/damaged tubing Repair/replace tubing
Dirty filter media Clean filter media
Worn/damaged diaphragm
Consult your dealer. Replace diaphragm and flappers
Air line is submerged below operating depth
Raise air line to desired depth
Warranty Claims
In case of warranty claims, the air pump should be returned to place of purchase accompanied by original receipt.
Troubleshooting Guide
Always turn o power before inspecting the pump. Failure to observe this precaution can result in a serious accident.
Before ordering repairs, carefully read through this instruction booklet. If the problem persists, contact your dealer.
Loading...
+ 11 hidden pages