Atlantic MULTI ELEC Technical Manual

Page 1
MULTI ELEC
Electric Boilers
TECHNICAL MANUAL
POBox11AshtonUnderLyneOL67TR
+44.(0) 1616215960 Fax+44.(0)1616215966
info@atlantic2000.co.uk
www.atlanticboilers.com
Page 2
2
Page 3
3
CONTENTS
DESCRIPTION………….………………………………...……………………………………1
PERFORMANCE………………………………………………………………………………
SCHEMATIC………………………………………………………………………………….
CONTROL PANEL DIAGRAM
COMMAND ELECTRIC DIAGRAM…………………..……………….……………………5
POWER ELECTRIC DIAGRAM…………………….……………………………….………
FUSES…………………………………………………………………………………………..
CONTROL PANEL + REGULATION………………………………………………………..
INSTALLATION……………………………………………………………………………….10
STARTING THE BOILER…………………………………………………..……………………….……. . SERVICING…………………………………………………………………………………….11
THE COMMISSIONING OF THE MULTI-ELEC…………………………………………27
THE GUARANTEE ON THE MULTI-ELEC……………………………………………….32
4
5
6
8
9
10
11
12
14
15
16
17
18
Page 4
BOI
LER
CONTROL PANEL
- 1 waterproof control panel mounted on the boiler including:
- 1 main switch
- 3 industrial cylinder cartridge fuse per stage
- 3 contactors ( 1 per stage )
- 1 protected transformator 415 / 240 V
- 1 light « operation »
- 1 light « lock out » ( circulation and safetythermostat )
- 1 digital régulation
- Terminals for external connections
- Output from 36 to 630 kW
- Boiler body in welded steel E 24
- Working pressure 4 bars
- Test pressure 6 bars
- Working temperature below 110°C
- 50mm thick mineral fibre insulation, polyester film aluminized glass cloth
- Safety thermostat with manual reset 110°C
- Internal expansion vessel
INCOLOY IMMERSION HEATERS
For boiler output between 36 and 288 kW
- Screwed elements diam.40
- Power of each unit: 12 kW
- 240/415Volts 3 phase + earth
- Removal of the immersion heaters: minimum height of 2 m.
.
For boiler output between 315 and 630 kW
- Screwed elements diam.80
- Power of each unit : 35 kW
- R=1M
- 415 Volts 3 phase + earth
- Removal of the immersion heaters: m
inimum height
of 2.5 m.
- Résistance d’isolement à froid à 1 mégohm
DESCRIPTION
The “Multi Elec” electric boilers have been designed for any heating system (maximum working pressure 4 Bars)
They are Class 1 boilers that required earth connections IP21 / IK 08
Page 5
PERFORMANCE, DIMENSIONS & CONNECTIONS
OUTPUT
No.of
elements
kW per element
Boiler
dimensions Volume Flow rate l/s
Pressure
drop max flow rate kPA
ØAD E F
Boiler
dry
weight
kg
Overall
dimensions
kW Foot
print
Height Litres Min Maxi H x L x P
90
3 30
520 1330 128
0.6 5.0 0.8
DN
80
235 920 180
117
1200x600x3
00
120
4 30 0.9 5.0 0.8
DN
80
121
150
5 30 0.9 9.7 2.8
DN
80
125
180
6 30 1.1 9.7 2.8
DN
80
129
210
6 35
670 1520 283
1.7 12.0 1.6
DN 100
255 1075 180
233
1400x800x3
00
245
7 35 1.7 12.0 1.6
DN 100
238
280
8 35 1.7 12.0 1.6
DN
100
243
315
9 35 1.7 12.0 1.6
DN 100
248
350
10 35 2.2 12.0 1.6
DN 100
253
1600x1000x
400
385
11 35 2.2 12.0 1.6
DN 100
258
420
12 35 2.2 12.0 1.6
DN 100
263
455
13 35
770 1520 395
2.8 26.0 1.6
DN 150
280 1020 180
340
1800x1000x
400
490
14 35 2.8 26.0 1.6
DN 150
345
525
15 35 2.8 26.0 1.6
DN
150
350
560
16 35 2.8 26.0 1.6
DN 150
355
595
17 35 3.6 26.0 1.6
DN 150
360
630
18 35 3.6 26.0 1.6
DN 150
365
Standard door opening ­A - to right Optional door opening -
B-to left
Return
Drain
Control panel housing
Drain
Page 6
OPTIONAL ACCESSORIES
SHUNT PUMP with contact relay and run/lock-out lamps
MOUNTING PACK with automatic air release, water flow switch, drain ball valve, safety relief valve and temperature & pressure relief valve
Automatic air release
Two relief valves
Water flow switches
Drain ball valve
Page 7
7
SCHEMATIC
1) Conventional Pipework
2) Weather compensated Pipework
3) Weather compensated pipework
Radiators or
under
-
floor heating
Page 8
8
4) Heating and hot water pipework
NB: Boiler pump flow should be 5% superior to the sum of heating and DHW primary pump
expansion
vessel
pressure &
temperature relief
3 port valve
auto air
vent
pump
non return
valve
Fill loop
pressure relief
valve
isolating ball valve
Radiators
Page 9
MAINS POWER 400V, THREE PHASES + EARTH (NO NEUTRAL
)
EARTH
MAIN SWITCH
TS
Fuses
COPPER PLATE
TERMINAL
TRANSFO
415/240V
Ka1
Terminal
FLEXIBLE ISOLATED
COPPER LINKS
FAN
(from 216 kW)
Km3
Km2 Km1
CONTROL PANEL DIAGRAM
Page 10
VIEW OF THE CONTROL PANEL
Page 11
11
COMMAND ELECTRIC DIAGRAM
Lockout
Power
Lockout
415 Volts
3Phases supply
415/240
Fan
Sensor
Digital
Regulation
Fan V from 216 kW
F1-F2-F3 and Transfowill vary according to boiler output
Limit Stat
Flow switch
Pump lockout
Other lockouts
Enable
Lockout signal
Green
Red
S1: Power Switch
I 1: Controller Switch T1: 30s delay T2: 1min delay T3: 2min delay
Earth
: Green/Yellow 4mm²
Wires 0 to 6 : Red 1mm² Wire 9 : Black1mm² Other wires : Brown 1mm²
Page 12
BOILER ELECTRICAL OUTPUT
Output per step control
Output Step 1 Step 2 Step 3
90 kW 30 30 30 120 kW 60 30 30 150 kW 60 60 30 180 kW 60 60 60 210 kW 70 70 70 245 kW 105 70 70 280 kW 105 105 70 315 kW 105 105 105 350 kW 140 105 105 385 kW 140 140 105 420 kW 140 140 140 455 kW 175 140 140 490 kW 175 175 140 525 kW 175 175 175 560 kW 210 175 175 595 kW 210 210 175 630 kW 210 210 210
Page 13
13
BOILER ELECTRICAL PROTECTION
Selection of fuses
Fuses F1, F2 & F3 - cartridge size 8.5 x 31.5
90kW to 280kW F1 - 1A type aM F2 - 1A type gG F3 - 0.5A type gG 315kW to 630kW F1 - 1A type aM F2 - 2A type gG F3 - 0.5A type gG
Fuses F4, F5 & F6 Cartridge size 22 x 58 - 63A type gG
Miniature circuit breakers output - 0 - 125A type gG output - 1 - 160A type gG output - 2 - 250, 315 & 400A type gG
Selection of FUSES or CIRCUIT BREAKERS
Boiler output
F4 F5 F6
Boiler
output
F4 F5 F6
90 kW 63 A 63 A 63 A 385 kW 250 A 250 A 160 A 120 kW 125 A 63 A 63 A 420 kW 250 A 250 A 250 A 150 kW 125 A 125 A 63 A 455 kW 315 A 250 A 250 A 180 kW 125 A 125 A 125 A 490 kW 315 A 315 A 250 A 210 kW 125 A 125 A 125 A 525 kW 315 A 315 A 315 A 245 kW 160 A 125 A 125 A 560 kW 400 A 315 A 315 A 280 kW 160 A 160 A 125 A 595 kW 400 A 400 A 315 A 315 kW 160 A 160 A 160 A 630 kW 400 A 400 A 400 A 350 kW 250 A 160 A 160 A
Page 14
14
CONTROL PANEL + REGULATION
CONTROL PANEL
REGULATION
FRONT
BACK
Factory Settings
(Heating Circuit)
Set Point Temperature
:
80°C
77°C 74°C
Stage 1
Stage 2 Stage 3
Maximum Temperature :
95°C
Minimum Temperature : 20°C Delay T1 : 30 secondes Delay T2 : 1 minute Delay T3 : 2 minutes Safety Thermostat : 110°C
Power On
Off
Lockout
Boiler
temperature
Set
Point
Stages
1 = Stage1
2 =Stage2 5 =Stage3
Stage3
Stage1
Stage2
240V
Sensor
Page 15
Change the set point
Increase the set point temperature: Press the key
Decrease the set point temperature: Press the key 
Never press the
PGM
and
EXIT
keys
For other settings, please contact Atlantic.
Information on the control panel
1.
2.
3.
Identification number plate on the control panel
The maximum acceptable current is Icw = 23 kA.
Only authorised person should have acccess to the contrl panel
4.5.Connection to earth is compulsory. (Class 1)
After commissioning (8 days) :
A/ Check the immersions heaters tightness B/ Check the power circuit connections tightness For information, advised tightness of the bolts:
M6
M8 M10
1,3m.daN
2,8 m.daN
5 m.daN
Check the tightness annually.
6.
Factory test
Regulation Isolation of the power circuit
7. The boiler and the control panel should not been installe din a corrosive atmosphere or outside.
8. Ventilation (Natural convection or fan) Leave enough space to allow air circulation. . Do not obstruct the fan and the grid.
Page 16
INSTALLATION
The “multi-elec” electric boiler should be installed in a louvered plantroom in order to ensure an ambient temperature below 30ºC and relative humidity between 30 and 80%.
The boiler should not be used in a corrosive atmosphere or in an external position.
Adequate access should be left around the boiler in order to carry out maintenance.
The following safety devices are obligatory:
Safety valve (4 Bars maximum)An automatic air vent on the boiler flowA blow down valve
Electrical wiring
The“multi-elec” electric boiler should be connected to 415V without neutral
The circuit breaker and the cables section should be chosen according to British standards.
Class 1 material IP21 / IK08
If the boiler is powered without any water, it will generate the thermocouple failure (no warrantee)
Transport and storage
The unit should be transported and stored in the original package until it reached the installation point.
Ambiant temperature below 80ºC
Relative humidity between 30 and 80%
Page 17
STARTING THE BOILER
Remove the power fusesCheck that the boiler is filled with waterCheck that the immersion heaters are sound. If isolation is below 2MΏ, please
find the reason and remdy it.
Turn the power on using the main switch and the key switchCheck that the circulation pump is running.Check that there is a lockout if the circulations pump stopsAdjust the temperature settingsStop the boiler using the main switchPut the power fuse inSwitch the boiler back onCheck the immersion heaters electrically for faults. Tight all the connections up
after one week of operation
If the boiler is powered without any water, it will cause the immersion heaters or
sensors to fail (no warranty)
Page 18
SERVICING
Loss of water velocity through the boiler can lead to temperature rise
Consider a sediment vessel on the return to capture sediment depositBlocking immersion heaters irrigation can destroy them
NOTE : The immersion heaters can be destroyed by blockage of the water flow
It is essential that a periodical cleaning is carried out on the main heat exchanger and the sensors. The water also needs to be clean without any antifreeze or scale remover product
Removal of sludge and sediment reduce corrosion risks
On first start:
Check the electrical operation Check each terminal to avoid any contact resistance or temperature rise Activate the safety valve manually
Monthly servicing
Check
The automatic air ventThe safety valve
Biannual servicing
Check each terminal to avoid any contact resistance or temperature rise
Page 19
19
THE COMMISSIONING OF THE ATLANTIC MULTI ELEC
All Atlantic boilers and water heaters are thoroughly tested for mechanical, electrical and combustion performance at the factory The prime object of the site commissioning of the boiler(s) is, subject to installed conditions, to match the optimum combustion performance results reached at the factory and to ensure the boiler(s) is/are installed according to the conditions of guarantee. The following check list should be satisfied before the commissioning takes place. To arrange the commissioning Atlantic should be given a minimum of ten days notice of the date and time required.
Commissioning sheet
Page 20
THE GUARANTEE ON THE ATLANTIC MULTI ELEC
This guarantee is to the purchaser of the boiler(s) who is deemed to be the installer. If the boiler(s) is (are) purchased by the eventual user who then arranges to install the boiler(s), the eventual user is deemed to be the installer. The details of the guarantee are given to assist the installer in obtaining effective action within the guarantee and they are in addition to the installer’s legal rights under the relevant statutory enactments for the time being in force in England, Wales, and Scotland. Electrical equipment: The replacement or repair of the item, including the cost of its delivery to the site of the installation or its equal within England, Wales and Scotland, provided that the defect or flaw occurs within 1 calendar year of the commissioning date. Removable component of the boiler assembly (other than the electrical equipment) The replacement or repair of the item, including the cost of its delivery to the site of the installation or its equal within England Wales and Scotland if the defect or flaw occurs within 1 calendar year of the commissioning date. The main body of the boiler. The repair of any welding defects in the main body of the water heater including any necessary removal or replacement of that part of the water heater on site if the defect occurs within 3 calendar years of the commissioning date. Definitions: The effective actions stipulated in this guarantee are subject to the purchaser complying completely with the following:
1) The boilers are installed according to the recommendations of this technical booklet, the recommended codes of practice of the C.I.B.S.E and the B.S.I., and the checklist on page 13 is satisfied.
2) The commissioning of the boilers by ACM Atlantic and their regular annual servicing and maintenance.
3) The payment in full, by the purchaser unless otherwise agreed, of the invoice for the supply and delivery of the boiler(s) to site, any other relevant invoices connected with the boiler positioning and fixing, and the invoices for commissioning and any correction of installation error, all to be made within one calendar month of the date of the invoice.
4) The presentation, at the time of a claim under the guarantee, of the boiler registration number, the commissioning record with date, and the necessary information for defining any replacement part.
5) When a replacement item is supplied for a defective item, the defective item must be returned to ACM Atlantic at their registered office within 6 weeks of the date of notification of the defect carefully labeled with registration number of the boiler and the name and the order reference of the purchaser of the boiler. If this is not complied with, the purchaser will be charged with the cost of the item and its delivery.
Loading...