Conguration of the Ambient probe . . . . . . . . . 35
Conguration of the central ambient unit (radio) . . 35
- 2 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
" The following are required for the installation of this appliance:
- work must only be carried out by qualied personnel with a certicate of aptitude for handling
refrigerating uids (in compliance with article R543.106 of the Environmental code),
Values to be given to the user . . . . . . . . . . . . . . . . . . . . . . . . . 68
Installation and operating manual "1605 - EN"- 3 -
alfea hybrid duo heat pump oil low NOx CH
1 Presentation of the equipment
1.1 Packaging
• 1 box: Outdoor unit.
• 1 box: Hydraulic module with NOx low burner and
outdoor temperature probe.
Pairing table
Heat pumpOutdoor unitHybrid duo hydraulic module
Modelref. exportref.Coderef.Code
alféa hybrid duo 11 single phase522 694WOYG112LCT700117
alféa hybrid duo 14 + single phase 522 695WOYG140LCT700142
alféa hybrid duo 11 three phase522 696WOYK112LCT700118
alféa hybrid duo 14 three phase522 697WOYK140LCT700143
alféa hybrid duo 16 three phase522 698WOYK160LCT700163
MH-HD024208
1.2 Optional equipment
• 2nd circuit kit (ref. 073953).
- to connect 2 heating circuits.
• Ambient probe T55 (ref. 073951) or
Ambient probe radio T58 (ref. 075313).
- to correct the ambient temperature.
• Central ambient unit T75 (ref. 073954) or
Central radio ambient unit T78 (ref. 074061).
- to correct the ambient temperature
and programme the PAC.
• Anti-vibration pins (ref. 523574).
• Floor support in white PVC (ref. 809532).
• Duo pool kit (ref. 074064).
• High ow circulator kit (ref. 073959).
- for a 1 circuit heated oor installation
with a PAC model 13 and 16.
1.3 Scope
1.4 Denitions
- Split: the heat pump is composed of two parts (an
outdoor unit to be located outdoors and a Hydraulic
module to be installed inside the home).
- Air/water: the outdoor air is the energy source .
This energy is transmitted to the heating water by the
heat pump.
- Inverter: the fan and compressor speeds are modulated
to suit the heat requirements. This technology
economises energy and permits operation with single
phase power supply, regardless of the power rating
of the heat pump, by avoiding high current demands
when started.
- COP (coefcient of performance: this is the ratio
between the energy transferred to the heating circuit
and the electrical energy consumed.
- hybrid: the Hydraulic module operates with dual energy
(air/water heat pump and integrated oil boiler).
- low NOx: Burner designed to minimise the emission
of Nitrogen oxides NOx in the fumes. Generally low
This heat pump permits:
- heating in winter,
- the production of sanitary hot water,
- controlling two heating circuits *,
NOx burners are considered to be burners whose
emission rate is below the most severe regulations at
that time. This limit chnages regularly according to the
regulations and technical progress.
- heating the pool*.
*: These options require the use of additional kits
(see § "optional equipment").
1.5 General characteristics
Denomination : alféa hybrid duo oil low NOx ue model 1114 +11 3 ph.14 3 ph.16 3 ph.
Weight of the hydraulic module (empty/with water)kg215 / 482
Capacity in water of the heating bodylitre142
Expansion vessellitre18
Noise level at 1 m 1 ( hydr. mod. in thermodynamic oper.)dB35.535.5
Acoustic power as per EN 12102 2 (hyd. module)dB43.343.3
Noise level at 5 m 1 (outdoor unit)dB4243394142
Acoustic power as per EN 12102 2 (outdoor unit)dB6970666869
Heating system operating limits
Min./max. outdoor temperature °C-25 / +35
Max. water temperature thermodynamic mode°C60
Max. water temperature for start of heating°C80
Refrigerating circuit
Diameters of the gas pipesinches5/8
Diameters of the liquid pipesinches3/8
Factory volume added of refrigerating uid R410A
3
g2500
Max. operating pressurebar41.5
Min. length of pipesm5
Max. length of pipes
Max. length of pipes 5 / Max. height diff.
1
Sound pressure level at (x) m from the appliance, 1.5m from the ground,
4
5
free eld directivity 2.
2
the acoustic power is a laboratory measurement of the power of the
sound emitted but contrary to the sound level, it does not correspond
to the measurement of what is felt.
m15
m20 / 20
3
refrigerating uid R410A in compliance with standard NF EN 378.1.
4
factory volume of refrigerating uid R410A.
5
Taking into account the possible extra volume of refrigerating uid
R410A (see §2.8.3, page 22).
Installation and operating manual "1605 - EN"- 5 -
alfea hybrid duo heat pump oil low NOx CH
" outdoor unit,
model hybrid duo oil low NOx 11
model hybrid duo oil low NOx 14 +
Drain hole (Ø 20)4 holes (Ø 10)
317790033012
AIR
Air
AIR
Air
400
Vuedecôté
Side view
650
AIR
Air
370
Orificed’écoulement(Ø20)4trousØ10
3/8”
5/8”
196
99
147
170
Vu ede dessous
Bottom view
9
Vu edeface
Front view
1290
21
" outdoor unit,
model hybrid duo oil low NOx 11 3 phase,
model hybrid duo oil low NOx 14 3 phase,
model hybrid duo oil low NOx 16 3 phase
Drain hole (ø 20)
3112330
AIR
Air
AIR
Air
400
Side view
370
Top view
Vuededessus
650
Air
Bottom view
900
9
Front view
4 holes (ø 10)
1290
21
- 6 -
Top view
gure 1 - Dimensions in mm
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
" Hydraulic module
Flexible hoses
Ø 20x27 female
Start
DHW
Ø 26x34
male
Return
EFS
Ø int. ext. smoke
outlet 125 / 139
5386
1682
651
1075
130
91
Liquid 3/8”
670
1711
2
405
3
1
Fuel hose
passages
gure 2 - Dimensions in mm
4
6
Gas 5/8”
115
287
Front viewSide viewRear view
5
gure 3 - Remove the panel
Installation and operating manual "1605 - EN"- 7 -
gure 6 - Ohmic value of the sensors (outdoor unit)
- compressor
- Discharge
- Condensation
- Outdoor
- Evaporator outlet
- Evaporator medium
- Compressor housing
temperature °C
- 8 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
1.6 Description
" Model
hybrid duo oil low NOx 11 and 14 + single phase
3
1
2
13
8
11
5
4
7
15
14
9
" Model
hybrid duo oil low NOx 11, 14 and 16 3 phase
1
2
13
WO*K1**LCT
3
4
5
14
15
9
7
11
6
8
12
6
10
12
10
Legend:
1. High performance impeller and low noise level.
2. Electrical motor with variable "inverter" operation.
3. "Inverter" command module.
4. Control LEDs and buttons.
5. Connector terminals (power supply and interconnection).
6. Storage bottle for refrigerating uid.
7. Four way valve.
8. Panels treated against corrosion.
9. Electronic pressure regulator of the main circuit.
10. "Inverter" compressor acoustically and thermally insulated with liquid injection port.
11. Refrigerating connection taps (are connector) with protective cover.
12. Retention tank with drain hole of the condensates.
13. Evaporator with high performance exchange surfaces; aluminium ns with anti-corrosion and
hydrophilic treatments, grooved copper tubes.
14. Solenoid valve for injection of liquid.
15. Electronic pressure regulator for injection of liquid.
gure 8 - Parts of the outdoor unit
Installation and operating manual "1605 - EN"- 9 -
alfea hybrid duo heat pump oil low NOx CH
28
16
11
15
24
19
1213
22
26
27
17
30
31
18
25
29
20
10
23
6
8
5
14
Legend
1. Condenser
2. Liquid refrigeration connection
3. Gas refrigeration connection
4. Combustion chamber
5. Reversible chamber door
6. Chamber pressure socket
7. Flame viewer
8. Burner low NOx
9. Evacuation of smoke (ue)
10. Domestic hot water tank
11. Inspection trap of the domestic hot
water tank
1
9
7
4
2
21
3
12. Heating circulation pump
13. Domestic circulation pump
14. Drain valve
15. Safety valve
16. Manual drain tap
17. Non-return valve
18. Expansion vessel
19. Mixer valve CC1
20. Electrical housing
Sensors
21. Condensation sensor
22. heating circuit1 start sensor
23. Heater start sensor
24. Domestic sensor
Control panel
25. User interface
26. Reset button
(overheating safety device)
27. Start/Stop switch
28. "Sweeping" button
29. Pressure gauge
30. Burner on LED (green)
31. Burner safety LED (red)
- 10 -
gure 9 - Parts of the hydraulic module
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
1.7 Operating principle
The heat pump transmits the energy in the outdoor air
to the home to be heated.
The heat pump is formed of four main elements inside
which a refrigerating uid circulates (R410A).
- In the the evaporator (item. 13, gure 8, page 9):
The calories are taken from the outdoor air and
transmitted to the refrigerating uid. As its boiling point
is low, it changes from the liquid state to the vapour
state, even when the weather is cold.
- --In the compressor (item 10 or 16, gure 8, page 9):
The vaporised refrigerating uid is pressurised and
thus carries more calories.
- In the condensor (item 1, gure 9): The energy in the
refrigerant is transmitted to the heating circuit. The
refrigerating uid returns to its liquid state.
- In the pressure regulator (item 9 or 15, gure 8, page 9):
The liqueed refrigerating uid is taken to low pressure
and returns to its initial temperature and pressure.
The heat pump has a regulator that controls the indoor
temperature based on the measurement of the outdoor
temperature, regulation by water logic. The ambient
sensor (optional) provides a corrective action to the
water logic.
The Hydraulic module is tted with a burner that has an
AON operation, on demand from the regulator:
- to provide additional heating during the colder
periods,
- to provide support for the domestic (DHW) or
- to take over on "Peak Tariff" days (load shedding
function or EJP, see page 30).
Priority is given to the operation of the heat pump.
When the heat pump is not sufcient for the heating, the
burner automatically takes over.
• Regulation functions
- The initial temperature of the heating circuit is
controlled by water logic.
- In function of an initial heating temperature, the power
of the outdoor unit is modulated via the "inverter"
compressor.
- Management of the supplementary heating.
- The daily timer programme allows comfort or reduced
ambient temperature periods.
- Switching between summer/winter operation is
automatic.
- Domestic hot water: Timer heating programme,
management of operation of the DHW circulation
pump.
- Ambient sensor*: The ambient sensor provides a
corrective action to the water logic.
- Management of a 2nd heating circuit*.
- Management of the heating of the swimming pool*.
*When the PAC (heat pump) is tted with associated options and kits
• Protection functions
- Anti-legionella cycle for the domestic hot water.
- A pressure switch monitors the hydraulic pressure.
If the pressure is below 0.5 bar, an error message is
displayed (369) and the heat pump is stopped.
PAC
Dt
Cn
Air energy
gure 10 - Operating principle of a heat pump
Installation and operating manual "1605 - EN"- 11 -
• Operating principle of the domestic hot water
(DHW)
Two sanitary hot water temperatures (SHW)
can be programmed: comfort temperature
(line 1610 at 65 °C) and reduced temperature
(line 1612 àat40 °C).
The default DHW programme (line 560, 561, 562, 563
and 564) is set for a comfort temperature from 0h00
to 5h00 and from 15h00 to 18h00 and a reduced
temperature for the rest of the day.
The reduced temperature value may be useful to avoid
restarting the DHW too many times and for too long
through the day.
The production of domestic hot water (DHW) is started
when the temperature in the tank is 7°C below (setting
of line 5024) the reference value temperature.
The domestic hot water (DHW) is produced by the
heat pump then completed if required by the burner. To
ensure there is an DHW value higher than 45°C, the
burner must be operated.
Depending on the setting of the parameter (1620), the
comfort temperature may be reached either
- 24 h / day,
- in line with the timer programme of the heating
circuit,
- in line with the DHW timer programme,
- during the off peak periods,
- during off-peak periods and depending on the
SHW time programme.
The production of SHW has priority over heating, but the
production of SHW is managed by cycles that regulate
the time spent heating and the production of SHW when
simultaneous demands occur.
A function for switching from "reduced" to "comfort"
is available on the front panel of the user interface
(see item 1, gure 43, page 36).
Increase in temperature of the tank (without drawing)
°C
60
50
40
30
20
10
0
°C
60
50
0
Domestic hot water temperature (with open tab).
60
120180
10 l/min
12,5 l/min
15 l/min
40
30
20
min
Anti-legionella cycles may be programmed (lines 1640to
1647).
• Fan coil units with integrated regulation
Do not use an ambient sensor in the zone concerned.
10
0
0
gure 11 - Domestic Hot Water performance
15
30
min
- 12 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2 Installation
2.1 Statutory conditions
for installation and servicing
The appliance must be installed and the maintained
by an approved professional in accordance with the
prevailing regulations and code of practice, in particular:
- The legislation on the handling of refrigerants:
- Heating installation with oor heating system.
carrying out water oor heating systems.
- Low voltage electrical installations - Rules.
- Central heating installations for buildings.
- Sanitary plumbing for homes.
- Calculations for sanitary plumbing installations and
evacuation of rain water.
- Copper pipes. Distribution of cold water and sanitary
hot water, evacuation of dirty water, rain water, climatic
installations.
- Chimney and ue work.
- Rules and processes for calculating chimneys with
natural draft and appendices.
- Chimney for homes.
- Ventilation of homes.
2.3 Unpacking and reserves
2.3.1 Receipt
When the courier is present, carefully check the general
appearance of the appliances, check that the outdoor
unit has not been in horizontal position.
In the event of disagreement, write to the courier within
48 hours mentioning all reserves and send a copy of
this letter to the After Sales Department.
2.3.2 Handling
The outdoor unit must not be in horizontal position
during transport.
Transport in horizontal position creates a risk of damage
to the inner tubes and the compressor suspensions.
Damage caused by transport transport in horizontal
position is not covered by the warranty.
If required, the outdoor unit may be tilted only when
being moved by hand (to get it through a doorway, or
up stairs...).
This operation must be carried out carefully and the
appliance must be immediately returned to the vertical
position.
2.2 Use of new fuel oil types
This boiler and its burner are compatible with the new
domestic oil containing FAME (Fatty Acid Methyl Ester)
and with non-road diesel (NRD*) on the condition they
respect the rules for the use and storage of this fuel
(refer to document n°1474 supplied with the appliance
and the user instructions, § Rules for using and storing
domestic fuel containing FAME).
only FranceNe pas traduire:only France
2.3.3 Accessories supplied
2
1
1
1Elbow
Plugs (x2)
2
(depending on
model)
3Allen keyto open the valves
gure 12 - Accessories supplied with the external unit
2
for the evacuation of the
condensates
3
5
6
3
4
5Outdoor sensor
gure 13 - Accessories supplied with
the hydraulic module
Installation and operating manual "1605 - EN"- 13 -
To monitor the outdoor
temp
alfea hybrid duo heat pump oil low NOx CH
2.3.4 Containment of refrigerant circuits
All refrigerant circuits fear contamination from dust and
moisture. If such pollutants introduced into refrigeration
circuit, they can contribute to degrade the reliability of
the heat pump.
" It’s necessary to ensure correct containment
connections and refrigerant circuits (hydraulic
unit, outdoor unit).
" In case of subsequent failure and expertise, the
nding of the presence of moisture or foreign
objects into the compressor oil would lead to
systematic exclusion of warranty.
- Check upon receipt that the ttings and the refrigeration
circuit caps mounted on hydraulic unit and outdoor unit
are properly seated and locked (impossible to loosen
bare hands). If this’s not the case, tighten them using
an against wrench.
- Check also that the refrigerant connections are
sealed (plastic caps or tubes crushed at the ends
and soldered). If the caps must be removed during
installation (tubes cut by example), put back them as
soon as possible.
2.4 Positioning
The choice of the position is particularly important
as having to move it later is a delicate operation that
requires a qualied person.
Choose the position of the outdoor unit and the hydraulic
module after discussion with the client.
Respect the max. and min. distances between the
Hydraulic module and the outdoor unit (gure 21, page
20), the performances and life of the system depend
on this.
2.5 Installation the outdoor unit
2.5.1 Installation precautions
" The outdoor unit must only be installed
outdoors. If a shelter is requried, it must have
large openings on all 4 sides and respect the
installation clearances (gure 14).
• Prefer a sunny position sheltered from strong and
cold dominant winds (mistral, tramontane, etc...).
• the appliance must be fully accessible for the
installation and later maintenance work (gure 14).
• Ensure that the connections can be made easily with
the hydraulic module.
• The outdoor unit can be exposed to the weather,
however avoid installing it in places where it will
become dirty or have excessive water dripping onto it
(under a leaky drainpipe for example).
• When operating water may escape from the outdoor
unit. Do not install the appliance on a terrace,
prefer a drained spot (bed of gravel or sand).
If the installation is in an area where the temperature
can be lower than 0°C for a long period, check that the
presence of ice does not present any danger. It is also
possible to connect a drain pipe to the outdoor unit
(see gure 15, page 16).
• No obstacles must block the air circulation through the
evaporator and from the fan.
• Keep the outdoor unit away from sources of heat or
inammable products.
• Ensure that the appliance does not disturb neighbours
or users (sound levels, draughts caused, low
temperature of the air blown out with the risk of freezing
plants in its path).
• The surface on which the outdoor unit is tted must:
- be permeable (earth, gravel bed...),
- be easily capable of supporting its weight,
- allow solid attachment,
- not transmit any vibrations to the home (anti-vibration
pins are available among the accessories).
• The wall bracket can not be used in conditions likely to
transmit vibrations, ground position is preferred.
- 14 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
250
250
or more
150
200
300
200
1000
300
Max. 500
250
250
or more
300
250
1500
or more
250
1000
or more
Max. 500
500
1500
250
250
or more
1000
or more
1500
or more
150
500
250
250
or more
1500
150
1500
250
250
or more
500
Max.300
1000
600
2000
or more
250
250
or more
gure 14 - Minimum clearances for the installation around the outdoor unit (all models)
1500
600
3000
or more
600
Installation and operating manual "1605 - EN"- 15 -
alfea hybrid duo heat pump oil low NOx CH
2.5.2 Fitting the outdoor unit
The outdoor unit must be raised by at least 50 mm
from the ground. In snowy regions, this height must be
increased but must not exceed 1.5 m.
- Attach the outdoor unit using screw and spring or split
washers to ensure they do not come loose.
2.5.3 Connecting the condensates drain
If an evacuation pipe must be used:
- Use the elbow provided (C) and connect a exible
hose diameter 16 mm to drain off the condensates.
- Use the Plug(s) provided (B) to block the condensate
tray orice.
Fit so that gravity ow of the condensates is ensured
(waste water, rainwater, gravel bed).
" If it is installed in a region where the temperature
can drop below 0 °C for long periods, t a
tracing resistor to the drain pipe to avoid it
freezing up. The resistance trace must heat not
just the evacuation pipe but also the bottom of
the condensate drip tray of the appliance.
* In regions where there is often snow,
(H) must be higher than the average thickness of snow.
2.6 Installation of the Hydraulic module
2.6.1 Requirements to installation space
The room where the appliance operates must respect
the regulations in force.
The appliance must be installed in a suitable and well
ventilated room. The room must have a new air inlet (A)
300 mm
B
- 16 -
B
gure 15 - Fit the outdoor unit,
evacuation of the condensates
C
B
minimum
150 mm*
A
1000mm
*If the refrigerating connections need to be passed
behind the appliance.
gure 16 - Minimum clearances for the installation
around the Hydraulic module
Installation and operating manual "1605 - EN"
500mm
alfea hybrid duo heat pump oil low NOx CH
with a free cross section that cannot be obstructed of at
least 50 cm2 that opens onto the lower part and a used
air outlet (B) with a free cross section that cannot be
obstructed of at least 100 cm2 positioned on the upper
part and opening directly outdoors (see gure 16).
Refer to Departmental sanitary Regulations Type
(RSD), article 53.4 .
The atmospheric conditions in the room must not be
humid; humidity is damaging for electrical appliances.
If the ground is humid or soft, use a base of sufcient
height.
To facilitate the servicing operations and permit access
to the various parts, it is recommended that sufcient
space be left all around the hydraulic module.
" The warranty on the heater will not cover any
installation of the appliance in a chlorine rich
atmosphere (hairdressers, launderette, etc.) or
any other corrosive vapours.
This equipment may not be installed in a bathroom or a
shower room.
Be careful of the presence of inammable gas close
to the heat pump when it is installed, especially when
brazing is required. The appliances are not antiexplosion
and must therefore not be installed in an explosive
atmosphere.
- To avoid any condensation inside the condensor only
remove the refrigerating circuit plugs when making
refrigerating connections.
- If the refrigerant connection only occurs at the end of
the installation, be sure that the refrigerant circuit caps*
remain in place and tight throughout the installation
duration.
* (Hydraulic module side and outdoor unit side)
- After the work is carried out each time on the
refrigerating circuit, and before nal connection, ret
the Plugs to avoid any pollution of the refrigerating
circuit (sealing with adhesive is not allowed).
2.6.2 Reversible chamber door
The chamber door is tted with the hinges on the left
as standard. For it to open in the opposite direction,
change over the side on which the hinges and pins are
tted.
- Remove the burner.
- Remove the chamber door.
Remove the 4 door attachment screws.
Remove the upper pin.
- Raise and tilt the door.
" Do not hold the door by its thermal protection.
-- Remove the hinges and x them on the other
side.
- Remove the lower pin and position it on the RH side
of the door.
- Ret the chamber door and attach the upper pin.
" Lightly tighten the screws of the closing door.
gure 17 - Reversible chamber door
2.6.3 Evacuation pipe
(see gure 18, page 18)
The evacuation pipe must comply with the regulations
in force.
The evacuation pipe must have suitable dimensions.
Minimum cross section required = 2.5 dm2 for a chimney
of between 5 and 20 m in height, or a ball valve of 16
cm or Ø 18 cm.
The pipe must only be connected to a single appliance.
The pipe must be waterproof.
The pipe must be correctly thermally insulated in order
to avoid any problems of condensation; otherwise the
pipe must have a tube tted with a system for collecting
the condensates.
Use a good quality watertight tube that is compatible
with the fuel used, possibly with a system for collecting
the condensates.
Installation and operating manual "1605 - EN"- 17 -
alfea hybrid duo heat pump oil low NOx CH
40 cm
1,2 m
40 cm
8m
gure 18 - Height of the base
of the evacuation ue (B23)
8m
2.7 Refrigerating connections
40 cm
< 15°
2.6.4 Connection pipe
The evacuation pipe must comply with the regulations
in force.
The cross section of the connection pipe must not be
smaller than the outlet nozzle of the appliance.
The connection pipe must be removable.
It is strongly recommended to t a ue regulator to the
pipe when the low pressure of the chimney is greater
than 30 Pa. The ue gas case is reversible (2 screws)
and the smoke outlet axis may be offset with respect to
the axis of the boiler to the right or to the left.
The evacuation nozzle is to be connected to the pipe so
that there are no leaks.
" This appliance uses the refrigerating uid
R410A.
Respect the legislation for handling refrigerating uids.
2.7.1 Rules and precautions
• After each operation on the refrigerating circuit, and
before the nal connection, ensure that the plugs are
tted so as to avoid any pollution of the refrigerating
circuit.
• Minimum tooling required
- Set of pressure gauges (Manifold) with exible hoses
for HFC (Hydrouorocarbons).
- Vacuum gauge with isolation valves.
- Special vacuum pump for HFC (use of a classic
vacuum pump only allowed if tted with a non return
valve for the suction).
- Only lubricate with polyolester refrigerating oil (POE).
If POE oil is not available, t without oil.
• Brazing on the refrigerating circuit
(if required)
- Silver brazing (40% minimum recommended).
- Brazing with a dry Nitrogen stream only.
• To eliminate the swarf from the pipes, use dryNitrogen to
avoid introducing humidity that can harm the operation
of the appliance. In general, take every precaution to
avoid humidity penetrating into the appliance.
• Thermally insulate the gas and liquid pipe to avoid
all condensation. Use insulating sleeves that resist
temperatures of over 90°C. In addition, if the level
of humidity where the refrigerating pipes risks
exceeding 70%, protect them with insulating sleeves.
Use a 15 mm thicker sleeve if the humidity reaches
80%, and a 20 mm thicker sleeve if the humidity
exceeds 80%. If the recommended thicknesses are
not respected in the conditions described above,
condensation will form on the surface of the insulation.
Finally, ensure that insulating sleeves are used that
have a thermal conductivity equal to 0.045 W/mK or
lower when the temperature is equal to 20°C. The
insulation must be impermeable to resist the steam
passing during the defrosting cycles (glass wool is
prohibited).
- 18 -
Cover the ared surface
with POE refrigerating oil.
Do not use mineral oil.
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.7.2 Refrigerating connections
The connection between the outdoor unit and the
Hydraulic module must only be made with new copper
connectors (refrigerating quality) and individually
insulated.
Respect the diameters of the pipes and the authorised
lengths(gure 21, page 20).
If the refrigeration connections are exposed to
weathering or UV- and the insulation is not strong, it is
necessary to provide protection.
Handle the pipes and pass them through the walls with
the protection plugs in place.
If the distance between the outdoor unit and the
hydraulic unit exceeds the length of the maximum
conduits indicated in the table, an additional charge of
R410A must be loaded.
The quantity of R410A added must be suited to the
length of the refrigerating circuit so as to maintain the
performances of the heat pump and not damage the
compressor (gure 21, page 20).
2.7.3 Flaring
- Cut the tube with a tube cutter to the required length
without deforming it.
- Carefully deburr while holding the tube downwards to
avoid introducing swarf into the tube.
- Remove the are nut from the connector on the valve
to be connected and t the tube into the nut.
- Flare it leaving the tube protruding fro the expandable
aring tool.
- After aring, check the condition of the journal (L).
It must not be scratched or signs of splitting. Also
check the side (B).
B
Expander
tube
pipe
Dimensions in mm
ø pipeLB 0/
9.52 (3/8")2.5 to 2.713.222
15.88 (5/8")2.9 to 3.119.729
gure 19 - Flared section for are connectors
L
C
-0,4
Spanner
Torque wrench
Flare
nut
C
2.7.4 Forming the refrigerant tubes
The refrigerating tubes must only be formed using a
bending machine or a bending spring in order to avoid
any risks of crushing or splitting.
" Warning!
• Remove the insulation locally to bend the tubes.
• Do not bend the copper to an angle of more than 90°.
• Do not bend the tubes more than 3 times at the same
position otherwise this can cause the pipe to split
(hardening of the metal).
DesignationTightening torque
Flare nut 9,52 mm (3/8")33 to 42 Nm
Flare nut 15,88 mm (5/8")63 to 77 Nm
Plug (A) 5/8"30 to 35 Nm
Plug (B) 3/8", 5/8"10 to 12 Nm
gure 20 - Tightening torques
Installation and operating manual "1605 - EN"- 19 -
alfea hybrid duo heat pump oil low NOx CH
2.7.5 Connecting the are connections
" The connections must be made the day the gas
is connected to the installation (see § 2.8, page
21).
" Pay special attention to the position of the tube
aligned with its connector to avoid damaging
the thread. A correctly aligned connector can be
tted easily by hand without much force being
- Remove the plugs from the pipes and refrigerating
connections
- Place the tube in front of the are connector and
screw on the nut by hand, holding the connector with a
spanner, until contact is made.
- Respect the tightening torques stated (see gure 20,
page 19).
required.
" The refrigerating circuit is very sensitive to dust
and humidity, check that the zone around the
connection is dry and clean before removing the
plugs that protect the refrigerating connectors.
PAC Modelalféa hybrid duo oil single phase and three phase
GasLiquid
Outdoor unit connectors5/8"3/8"
Diameter(D1) 5/8"(D2) 3/8"
Minimum length (L)5
Refrigerating
connections
Maximum * length (L)15
Maximum * length (L)20
Maximum ** height difference (D)20
Hydraulic module connectors5/8"3/8"
*: without additional volume of R410A
**: take into account any additional volume (see §2.8.3, page 22)
Outdoor
unit
Liquid
valve
Flare
nut
“Liquid” refrigeration connection
diameter D2
Gas
valve
Flare
nut
Hydraulic
unit
Flare
nut
Flare
nut
- 20 -
DL
“Gas” refrigeration connection
diameter D1
gure 21 - connection of thre refrigerating connectors (authorised diameters and lengths - in metres)
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.8 Commissioning
the refrigerating gas installation
" This operation is only to be carried out by
qualied tters in compliance with the legislation
for the handling of refrigerating uids.
" Evacuation with a calibrated vacuum pump is
essential (see appendix 1).
" Do not use equipment that has previously been
used with a refrigerating uid other than a HFC.
" Remove the refrigerant circuit caps only when
building the refrigerant connections.
" Unfavourable conditions:
- If the temperature outdoors is between +5 and
+10°C, a vacuum gauge must be used to check
the evacuation and use the 3 vacuum method.
(see appendix 2).
- If the temperature outdoors is below +5°C, it is
strongly recommended to connect the gas.
APPENDIX 1
Method for calibration and control of a vacuum
pump
- Check the oil level of the vacuum pump.
- Connect the vacuum pump with the vacuum gauge
according to the scheme.
Vacuum
Vacuomètre
Flexible
Outlet
bouché
hose
- Empty for 3 minutes
- After 3 minutes, the pump
reaches its threshold value and the vacuum gauge
needle does not move.
- Compare the obtained pressure with the value
of the table. Depending on the temperature, this
pressure must be less than the value indicated in
the table.
=> If this is not the case, change the seal, the
exible hose or the pump.
T °C5°C<T<10°C10°C<T<15°C15°C < T
Pmax
- bar . .
- mbar
. . . 0.009 . . .
. . . . . 9 . . . . .
. . . 0.015 . . .
. . . . 15 . . . .
2.8.1 Start procedure
gauge
Vacuum
Pompe
pump
à vide
. . . 0.020 . . .
. . . .20 . . . . .
APPENDIX 2
Method 3 empty
- Connect the high pressure exible of the manifold
on the load orice (gas connection). A valve must
be mounted on the exible hose from the vacuum
pump in order to isolate it.
a) Empty up to the desired value (see table appendix
1),
Jeu de manomètres
Set of pressure gauges
pressure
Low
Basse
pression
(manifold)
(manifold)
Lo
Hi
High
Haute
pressure
pression
Connection...
UE
liquid
Gas
Liaison...
liquide
gaz
MH
Vacuum gauge
Vacuomètre
Vacuum pump
Pompe à vide
b) Switch off the vacuum pump, close the valve at
the end of the service hose (yellow), Connect this
hose to the pressure regulator of the Nitrogen bottle,
inject 2 bars, close the hose valve,
Nitrogen
Lo
High
Hi
Haute
pressure
pression
UE
Connection...
Liaison...
liquid
liquide
gaz
Gas
MH
Azote
c) Connect the exible hose again to the vacuum
pump, switch it on and progressively open the
exible valve hose.
Lo
High
Hi
Haute
pressure
pression
Connection...
UE
liquid
Liaison...
liquide
gaz
Gas
MH
d) Repeat this operation at least three times.
" Reminder: it is strictly prohibited to carry out
these operations with refrigerating uid.
• Checks before connection:
Checking the gas connection (large diameter).
- Connect the "Gas" connection to the outdoor unit.
- Blow dry nitrogen into the "Gas" connection and
observe this end:
If water or impurities come out, use a new refrigerating
connection.
Otherwise expand and immediately connect to the
Hydraulic module.
Installation and operating manual "1605 - EN"- 21 -
Checking the liquid connection (small diameter).
- Connect the "Liquid" connection to the hydraulic unit.
- Blast with Nitrogen the entire gas-condensor-liquid
connection and observe the end (outdoor unit side).
If water or impurities come out, use a new refrigerating
connection.
Otherwise expand and immediately connect to the
outdoor unit.
alfea hybrid duo heat pump oil low NOx CH
• First leak test
- Remove the protection plug (B) from the lling orice
(Schrader) on the gas valve (large diameter).
- Connect the high pressure exible hose of the Manifold
to the lling orice (gure 22).
- Connect the Nitrogen bottle to the Manifold (only use
dehydrated Nitrogen type U).
- Pressurise the Nitrogen (10 bar maximum) in
the refrigerating circuit (gas-condensor-liquid connection assembly).
- Let the circuit under pressure for 30 minutes.
Nitrogen
Lo
High
Hi
Haute
pressure
pression
UE
Connection...
Liaison...
liquid
liquide
Gas
gaz
MH
Azote
10 bars max.
30 mn mini
- Search for leaks with a leak detector product, repair
and repeat the test.
Lo
High
Hi
Haute
pressure
pression
UE
Leak test
Liaison...
liquide
gaz
Vanne fermée,
Pressure check
Contrôle pression
Contrôle d’étanchéité
MH
Valve closed
- When the pressure is stable and any leakage is
excluded, leaving empty nitrogen to a pressure greater
than atmospheric pressure (0,2 to 0,4 bar).
• Evacuation and connection of gas to refrigerating connections
- If required, calibrate the pressure gauge(s) of the
Manifold at 0 bar. Adjust the vacuum gauge to the
atmospheric pressure (≈ 1013 mbar).
- Connect the vacuum pump to the Manifold. Connect
a vacuum gauge if the vacuum pump is not equipped.
Lo
High
Hi
Haute
pressure
pression
UE
Connection...
Liaison...
liquid
liquide
Gas
gaz
MH
Vacuum gauge
Vacuomètre
Vacuum pump
Pompe à vide
- Create a vacuum until the residual pressure* in the
circuit falls below the value given in the following
table. (* measured with the vacuum gauge).
T °C5°C<T<10°C10°C<T<15°C15°C < T
Pmax
- bar . .
- mbar
. . . 0.009 . . .
. . . . . 9 . . . . .
. . . 0.015 . . .
. . . . 15 . . . .
. . . 0.020 . . .
. . . .20 . . . . .
Refrigerating connector (gas)
Liaisonfrigorifique
Plug (A)
Bouchon(A)
3 way valve
Vanne3voies
4 mm Allen key
Cléhexagonalede4mm
Filling orice
Orificedecharge
Plug (B)
Flexibledeservice(bleu)
High pressure
munid’unpoussoirdevalve
exible hose (red)
gure 22 - connection of the exible hose to the gas valve
Bouchon(B)
- Let the pump continue to operate for another (30)
minutes after reaching the vacuum.
- Close the Manifold tap then switch off the vacuum
pump without disconnecting any exible hoses.
" If the outdoor temperature is between
+5 and +10 °C, use method 3 empty
(cf. APPENDIX 2).
- Remove the access plugs (A) from the valve controls.
" If an additional charge is requires, add the additional
charge before lling the hydraulic unit with gas.
Refer to paragraph Page22.
- First open the liquid valve (small) then the gas valve
(large) to maximum with an Allen key (anticlockwise
direction) without forcing it too far.
- Quickly disconnect the Manifold hose.
- Ret the 2 original plugs (ensure they are clean) and
tighten to the recommended torque from the table
gure 20, page 19. The sealing is performed in the
caps only metal to metal.
The outdoor unit does not contain any additional
refrigerating uid to allow the installation to be drained.
Drain by ushing is strictly forbidden.
2.8.2 Final leak test
The sealing test must be performed with a certied gas
detector (sensitivity 5g/year).
Once the refrigerating circuit has been lled with gas
as described previously, check all of the refrigerating
connectors of the installation for leaks (4 connectors).
If the tube expanders have been correctly used, there
should be no leaks. If required check the refrigerating
tap plugs for leaks.
" In case of leaks:
- Feed gas into the outdoor unit (pump down). The
pressure must not drop below atmospheric pressure
(0 bar relative read on Manifold) to avoid polluting the
gas collected with air or humidity.
- Make the connection again,
- Re-start the commissioning procedure.
2.8.3 Additional volume added
- 22 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
50 g of R410A
per additional metre
Length of the
connections
Additional volume
added
15 m20 m max.
none250 g
The volumes on the outdoor units correspond to
maximum distances between the outdoor unit and
Hydraulic module dened in gure 21, page 20. If the
distances are greater, an additional volume of R410A
is required. The additional volume added depends, for
each type of appliance, on the distance between the
outdoor unit and the hydraulic module. The additional
volume added of R410A must only be added by a
qualied specialist.
• Example of additional volume added:
An outdoor unit at a distance of 17 m from the hydraulic
requires an additional charge of:
Additional volume = (17 – 15) x 50 = 100 g
The volume must be added after evacuation and
before connecting the gas to the Hydraulic module,
as follows:
- Disconnect the vacuum pump (yellow hose) and
connect in place a bottle place of R410A in the
position of liquid drawing.
- Open the tap of the bottle.
- Drain the yellow exible hose by loosening it slightly
on the manifold side.
- Place the bottle on precision scales with a minimum of
10g. Note the weight.
- Carefully open the blue tap slightly and monitor the
value displayed on the scales.
- As soon as the value displayed has dropped by the
value of the calculated additional charge, close the
bottle and disconnect it.
- Sharply disconnect the exible hose from the appliance.
- Add the gas to the hydraulic module.
" Warning!
• Only use R410A!
• Only use tools adapted to R410A (set of pressure
gauges).
• Always add charge in liquid phase.
• Do not exceed the maximum length or difference in height.
2.8.4 Collecting the refrigerating uid
in the outdoor unit
" Only for the 3 phase models
Carry out the following procedures to collect the
refrigerating uid.
1. Place the ON/OFF switch in the position 0 (item 27,
gure 9, page 10).
2. Remove the front panel of the hydraulic module.
Place the DIP SW1 of the interface board to ON.
3. Turn the ON/OFF switch to position 1.
(the green and red LED sstart to ash;
1s lit / 1s extinguished).
4. The outdoor unit starts in the cold mode for
approximately 3 minutes after it is switched on.
Close the liquid valve on the outdoor unit 1 minute
after the outdoor unit is started.
5. Close the gas valve on the outdoor unit 1 to 2
minutes after closing the liquid valve, while the
outdoor unit continues to turn.
6. Disconnect the electrical power supply.
Remarks:
- Check that the ON/OFF switch is in the position 0
before pressing DIP SW1.
- When the heat pump is operating, the collection cannot
be activated even if the DIP SW 1 is at ON.
- Do not forget to place the DIP SW 1 to OFF once
collection is complete.
- If the collection operation fails, try the
procedure again by turning off the machine and
opening the "gas" and "liquid" valves. Then
2 to 3 minutes repeat the collection.
DIP SW
OFF
ON
LED1
(red)
LED2
(green)
1 2 3 4
Gas
Interface board
R410A
Liquid
gure 23 - Gaz bottle R410A
Installation and operating manual "1605 - EN"- 23 -
gure 24 - Position of the DIP switches and the LEDs on
hydraulic module interface board
alfea hybrid duo heat pump oil low NOx CH
2.9 Hydraulic connection
2.9.1 General
The connection must comply with trade practices
according to the regulations in force.
The heating circulation pump is integrated into the
hydraulic module.
Connect the pipe of the central heating to the hydraulic
module respecting the direction of the circulation.
The diameter of the pipes, between the Hydraulic
module and the heating manifold must be at least equal
to 1 inch (26x34 mm).
Calculate the diameter of the pipes in function of the
ow rates and lengths of the hydraulic systems.
Tightening torque: 15 to 35 Nm.
Use union connectors to facilitate the removal of the
hydraulic module.
Prefer the use of exible connector hoses to avoid
transmitting noise and vibrations to the building.
Connect the evacuations of the drain tap and the safety
valve to the drain.
Verify the correct functioning of the expansion system.
Control the vessel pressure (precharge 1 bar) and the
safety valve setting.
Reminder: Make the assembly impervious respecting
trade practices in force for the plumbing work:
- Use suitable seals (bre seals, O rings).
- Use Teon or hemp tape.
- Use sealant (synthetic as required).
There is no need for glycol. If water containing glycol
is used, carry out an annual check of the quality of the
glycol. The use of glycol monoethylene is prohibited.
" In certain installations, the presence of different
metals may cause corrosion problems; in which
case the formation of metal particles and sludge
may be observed in the hydraulic circuit.
" In this case, it is preferable to use a corrosion
inhibitor in the proportions recommended by its
manufacturer.
" It is also necessary to ensure that the water
treated does not become aggressive.
Ø 26x34
male
Sanitary exible hoses
Ø 20x27 female
Legend
CAR: Non-return valve
D: Disconnector
GS: Safety device
D
MT
CAR
MT: Thermostatic mixing
valve
R1: Heating circuit
R1
- 24 -
GS
gure 25 - Overall view of the electrical connections
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.9.2 Connection to the domestic circuit
Place a safety group with a valve calibrated to 7 bar
on the cold water inlet, and connect an evacuation pipe
leading to the drain. Operate the safety unit according
to manufacturer's specications. Connect the safety
valve evacuation to the drain
To allow the tank to be emptied by siphoning, the safety
unit must be placed at a lower level than the cold water
inlet.
It is recommended that the hot water outlet is tted
witha thermostatic mixing valve.
2.9.3 Rinsing the installation
Before connecting the hydraulic module to the
installation, rinse the heating system correctly to
eliminate the particles that could compromise the
correct operation of the appliance.
Do not use solvents or aromatic hydrocarbons (petrol,
oil, etc.).
For older installations, t a decanting pot of adequate
capacity on the boiler return circuit and at the lowest
point equipped with a drain, in order to collect and
evacuate the impurities.
Add to the water an alkaline product and a dispersant.
Rinse the installation several times before nal lling.
2.9.4 Filling and draining the installation
Valve closed
(normal operating
position)
Valve closed
(lling or drain
position )
gure 26 - Non return valve
P
CAR
CAR
P
" Imperative! Fill and pressurise the domestic
tank before lling the heater with water.
The warranty of the appliance will not apply if
this procedure is not respected.
- Check the attachment of the pipes, that the connectors
are tight and that the hydraulic module is stable.
- Check the direction of circulation of the water and that
all of the valves are open.
- Disconnect the non return valves (gure 26).
- Fill the installation.
- During lling, do not operate the circulator, open all
drains on the installation and the Hydraulic module
(gure 27) to evacuate the air in the pipes.
- Close the drains and add water until the pressure of
the hydraulic circuit reaches 1 bar.
- Check that the hydraulic circuit is drained correctly.
Close the non-return valves.
- Check that there are no leaks and that the circulating
pumps are not seized (if need be, release them).
After step § 2.15, page 34, once the machine
is running, drain the Hydraulic module again
(2 litres of water). If the pressure is below 0,5 bar,
the PAC stops and displays error 369.
" Precise lling pressure is determined by the
manometric height of the installation.
gure 27 - Drains (P) and non return valves (CAR)
gure 28 - Freeing the circulation pump
III
hybrid duo 11
hybrid duo
14+
hybrid duo 16
II
hybrid duo 11
hybrid duo
14+
hybrid duo 16
gure 29 - recommended speed
for the radiator circuit
Installation and operating manual "1605 - EN"- 25 -
alfea hybrid duo heat pump oil low NOx CH
2.10 Connection of the fuel supply
Refer to the instructions supplied with the burner.
In order for the burner to operate correctly, a lter
(60 μm) must be installed on the fuel supply pipe.
" Recommendation: The use of a deaerator air
lter is recommended.
Pass the fuel hoses in the passage (either on the right
or left) at the rear of the appliance.
Choice of passage
on right or left
2.11 Electrical connections
Before carrying out any work, ensure that the general
electrical power supply is switched off.
2.11.1 Characteristics of the electrical power supply
the electrical installation must comply with the
regulations in force.
The electrical connections will only be made when
all of the other assembly operations (attachment,
assembly,...) have been carried out.
" Warning!
The contract taken out with the energy supplier must
be sufcient to cover the power of the heat pump as
well as the sum of the power requirements of all of the
appliances likely to be operated at the same time. If
the power supply is insufcient, check with your energy
supplier the value of the power supply dened in your
contract.
Never use electrical sockets for the power supply.
The PAC must be powered by special lines protected
from the electrical panel by bipolar circuit breakers
dedicated to the PAC, surve D for the outdoor unit
The electrical installation must be equipped with a
differential protection of 30 mA.
This appliance is designed to operate at a nominal
voltage of 230V, +/- 10%, 50 Hz for the single phase
model and at a nominal voltage of 400V, +/- 10%, 50 Hz
for the 3 phase model.
2.11.2 General remarks on the electrical connections
It is essential that the phase-neutral polarity is respected
for the electrical connection.
Clamp the cables with stufng glands to avoid any
accidental disconnection of the conductive wires.
• Connection on the connectors:
- Remove the corresponding connector and make the
connection.
- Tighten the screws of the terminal blocks correctly.
Failure to tighten sufciently may cause overheating,
faults or even res.
gure 30 - Passages of the oil exible hoses
• Connection on the spring terminals:
The earth connection and its continuity must be ensured.
Rigid wire:
- Bare the end of the wire over a length of around
10 mm.
- Slide the wire into the orice provided.
- Push the spring with a screwdriver so that the wire
enters the cage.
- Remove the screwdriver and check that the wire
remains blocked in the cage, and pull it to check.
3
- 26 -
1
2
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.11.3 Overall view of the electrical connections
The electrical wiring diagram of the hydraulic module is detailed on gure 51, page 56.
Central ambient radio unit T78 (option)
Outdoor probe
Sonde extérieure
cable 2 x 0,75 mm
câble 2 x 0,75 mm²
Connexion unité extérieure/module hydraulique
Outdoor unit/hydraulic module connection
(see below)
(voir ci-dessous)
2
Centrale ambiance radio T78 (option)
Ambient radio probe T58 (option)
Sonde d’ambiance radio T58 (option)
Central ambient unit T75 (option)
Centrale ambiance T75 (option)
Ambient probe T55 (option)
Sonde d’ambiance T55 (option)
câble3x0,5 mm²
cable 3 x 0,5 mm
cable 2 x 0,5 mm
câble2x0,5 mm²
or
ou
2
or
ou
2
Electrical
Tableau
panel
électrique
Electrical power supply
Alimentation électrique
(voir tableau ci-dessous)
(see table below)
gure 31 - General diagram of the electrical connections for a simple installation (1 heating circuit)
2.11.4 Cross section of the cable and protection rating
The cross sections of the cables are provided for information only and do not dispense the electrician from checking
that these cross sections correspond to the requirements and satisfy the standards in force.
• Power supply of the outdoor unit:
Single phase heat pump Electrical power supply 230 V - 50 Hz
Model
Max. absorbed
power
hybrid duo oil low NOx 115060 W
hybrid duo oil low NOx 14 +5750 W
Connector cable
(phase, neutral, earth)
3 x 6 mm²32 A
Circuit breaker rating
curve D
heat pump 3 phase Electrical power supply 400 V - 50 Hz
Connector cable
(3 phases, neutral,
earth)
Circuit breaker rating
curve D
Model
Max. absorbed
power
hybrid duo oil low NOx 115865 W
5 x 2.5 mm²20 Ahybrid duo oil low NOx 146555 W
hybrid duo oil low NOx 167245 W
• Inter-connection between the outdoor unit and the hydraulic module: The hydraulic module is powered by the
outdoor unit, via a cable 4 x 1.5 mm² (phase, neutral, earth, communication bus).
" Before carrying out any work, ensure that the general electrical power supply is switched off.
Installation and operating manual "1605 - EN"- 27 -
alfea hybrid duo heat pump oil low NOx CH
2.11.5 Electrical connections on the
outdoor unit side for single phase model
Access to the connector terminals
- Remove the front panel. Remove the screws and the
cover of the front panel.
Remove the screws
and push downwards
Terminal
block
Remove
the front
cover.
Refrigerating
connector
cover
- Make the connections as per diagram (gure 34 and
gure 40, page 31).
Terminal block
Inter-connection between
outdoor unit and hydraulic
module
Mains electrical
power supply
gure 33 - Access to the terminal block
of the single phase outdoor unit
1
Insulation (seal)
Isolant (joint)
Hook
(4 positions)
Attachment plate
Plaque de fixation
gure 34 - Terminal block connections
1
of the single phase outdoor unit
- Use the cable clamps to avoid any accidental disconnection of the conductor wires.
- Use the attachment plate to hold the cables against
the insulating plate (gure 32).
23
Cable clamp
Serre-câble
Cables
Câbles
(power supply
(alimentationet
and inter-connections)
interconnexion)
Attachment plate
Plaque de fixation
- 28 -
IMPORTANT
ATTENTION
Attach the cables so that they are not
Fixer les câbles afin qu'ils ne soient pas
in contact with the pipes and valves
en contact avec les tuyaux et les vannes.
gure 32 - Finalise the connection of the outdoor unit
Cables
Câbles
Clearance
Dégagement
"Gas" valve
Vanne“gaz”
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.11.6 Electrical connections on the
outdoor unit side for 3 phase model
Access to the connector terminals
- Remove the front panel. Remove the screws and the
cover of the front panel.
Remove the screws
and push downwards
Terminal
block
Remove the front
panel
- Use the cable clamps to avoid any accidental
disconnection of the conductive wires.
- Obstruct the space at the cable inlet in the outdoor unit
with the insulating plate.
Cable
clamp
gure 35 - Access to the terminal block
of the three phase outdoor unit
- Make the connections as per the diagram(s) (gure 36
and gure 40, page 31).
Terminal
block
L1 L2 L3 N
1
2 3
INDOOR UNITPOWER
Inter-connection
between outdoor unit
and hydraulic module
gure 36 - Terminal block connections
of the three phase outdoor unit
General electrical
power supply
(power supply and
cables
interconnection)
gure 37 - Finalise the connection
of the three phase outdoor unit
Siderear
front
gure 38 - Passages of the cables and refrigerating con-
nectors of the three phase outdoor unit
Installation and operating manual "1605 - EN"- 29 -
lower
alfea hybrid duo heat pump oil low NOx CH
2.11.7 Electrical connections
on Hydraulic module side
Grommets (power)
1
3
Terminal blocks
Heat pump
regulator
Stufng gland
(probes)
2
Interface board
gure 39 - Access to hydraulic unit electric box and description
Access to the connector terminals
Use the tip provided with the appliance (Torx T20).
- Remove the front panel.
- (1, 2) Remove the cover from the electrical housing
(2 screws).
- (3) Tilt the control panel (2 screws).
Make the connections as per diagram
(gure 40 andgure 41).
Do not place in the same stufng gland the probe
lines and the mains lines to avoid interferences due toi
voltage peaks of the mains supply.
Ensure that all of the electrical cables are housed in the
spaces provided.
• Inter-connection between the outdoor unit and the
hydraulic module:
Respect the correspondence between the terminal
blocks references of the hydraulic module and those of
the outdoor unit when connecting the inter-connection
cables.
An incorrect connection can cause the destruction of
one of the units.
• Second heating circuit
- Refer to the instructions provided with the hydraulic kit
of the 2nd circuit.
• Contract subscribed with the energy supplier
It is possible to control the DHW operation of the heat
- Connect the "energy supplier" contact to input EX5.
- Set the parameter (1620) to "Off peak Tariff".
• 230 V on input EX5 = "peak rate" information activated
(basic setting / modication possible line 5989,
Conguration menu).
During peak hours, the SHW rate is reduced, during
off peak hours the SHW rate depends on the setting of
parameter 1620.
• Load shedding or EJP (Delete peak rate day)
The purpose of load shedding is to reduce the electrical
consumption when it is too high compared to the
contract with the energy supplier.
- Connect the contact of the electricity meter to terminals
7 and 8.
- Check that parameter 2920 is set to "locked".
- Check that parameter 5987 is set to "Work Contact".
• Closed contact = HP stopped, Boiler authorized
During "Peak rate" days the PAC will stop and the
burner alone will provide the heating.
• In the case of a heated oor
- Connect the heated oor thermal safety device to
the heated oor circulator connector (QX3: circuit 1,
QX23: circuit 2).
- 30 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
" Single phase model
Electrical
power supply
230 V
single phase
outdoor unit
Interconnection between outdoor unit
and hydraulic module
green/yellow
red
blue
brown
Burner
Hydraulic module
" Three phase model
three phase outdoor unit
1 2 3 L1
L1
L2 L3 N
L3
L2
Electrical
power supply
400 V
Burner
green/yellow
red
blue
brown
N
Interconnection between outdoor unit
Hydraulic module
and hydraulic module
gure 40 - connection to terminal blocks and power relays
Installation and operating manual "1605 - EN"- 31 -
alfea hybrid duo heat pump oil low NOx CH
Contact d'information
du compteur HP/HC *
If the controlling part does not provide
* Si l'organe de commande ne délivre
pas de contact libre de potentiel il
a contact that has free potential, the
faudra relayer le contact pour obtenir
contact needs to be relayed to obtain
Dans tous les cas, se reporter
In all cases, refer to the instructions
aux notices des organes externes
of the external parts (load shedder,
(délesteur, compteurs d'énergie …)
energy meters, ...) for the wiring
** Option
** Option
T75 : Le raccordement de la borne 3 de la centrale ambiance T75
T75: terminal 3 of the central ambient unit T675 does not have to
n'est pas obligatoire (éclairage de la centrale ambiance).
be connected (lighting of the central ambient unit)
pour réaliser le câblage.
Outdoor
Sonde
probe
extérieure
HP/HC meter
information contact*
un câblage équivalent.
equivalent wiring.
3
Ambient
Centrale
central unit
ambiance
T75**
T75 **
7 85
7 8
EX5
M B9
CL- CL+
X60
CL- CL+
G+
1
1
2
2
Ambient probe
Sonde
T55** (circuit 1 or 2)
d’ambiance
(circuit 1 ou 2)
T55**
CL- CL+
X60
Ambient radio central
Centrale ou sonde
unit or probe
ambiance
T78** or T58**
radio T78** ou T58**
Load shedding or EJP
Délestage ou EJP
(deletion of peak day)
(Effacement Jour de Pointe)
2
1
Ambient probe
Sonde
T55** (circuit 1 or 2)
d’ambianceT55**
(circuit 2 ou 1)
gure 41 - connections to the PAC regulator (accessories and options)
- 32 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.12 Outdoor sensor
The Outdoor sensor is required for the correct operation
of the heat pump.
Consult the assembly instructions on the packaging of
the sensor.
Place the sensor on the front panel that is the worst
exposed, in general the North or North west front panel.
Under no circumstances must it be exposed to the sun
in the morning.
It is to be installed so that it is easily accessible but at
least 2.5 m from the ground.
Avoid sources of heat such as chimneys, the tops of
doors or windows, nearby extraction ducts, underneath
balconies and porches, that would insulate the sensor
from the variations in the temperature of the air outdoors.
- Connect the outdoor probe to terminals M
and B9 on the regulation board of the PAC
(gure 41).
2.13 Ambient sensor
and/or central ambient unit (radio)
The ambient sensor (or the central ambient unit) is
optional.
Consult the assembly instructions on the packaging of
the sensor.
The sensor must be installed in the living room area on
a very uncluttered wall. It must be installed so as to be
easily accessible.
Avoid sources of direct heat (chimney, television,
cooker, sunlight) and areas exposed to draughts
(ventilation, doors). Draughts due to the building usually
cause cold air to enter via the electrical ducts. Seal the
electrical ducts if there is a cold draught at the back of
the ambient sensor.
• Installation tted with two ambient sensors (T55)
- Connect each of the sensors to one of the terminals
CL+ and CL- on the PAC regulation board
(gure 41) using the connector supplied.
• Installation tted with one ambient sensor (T55)
and a central ambient unit (T75)
- Connect the probe to one of the terminals
CL+ and CL- of the PAC regulation board
(gure 41).
- Connect the central ambient unit to the other terminals
CL+, CL- and the terminal G+.
• Installation tted with a radio central ambient unit
(T78)
Refer to the instructions supplied with the radio central
ambient unit.
• Installation tted with a radio ambient sensor (T58)
Refer to the instructions supplied with the radio ambient
sensor.
Installation and operating manual "1605 - EN"- 33 -
alfea hybrid duo heat pump oil low NOx CH
2.14 Verications and commissioning
• Carry out the usual verications on the burner and its
power supply circuit.
• Check the turbulators are tted correctly.
• Check correct assembly of electrical connections on
the terminals.Check draught.
• Connect the appliance to the mains supply and start
up:
- Engage the main isolator switch of the installation.
When rst commissioning (or in winter), to
preheat the compressor, engage the main circuit
breaker of the installation (outdoor unit power
supply) a few hours before carrying out the tests.
- Switch on the Start/Stop button of the heat pump.
To ensure the appliance operates correctly:
Check that the phase-neutral polarity of the
electrical power supply is respected.
When put into service and every time that the Start/Stop
switch is switched off and then back on, the outdoor
unit requires approximately 4 min. to start up even if the
regulation has demanded heating.
The display may show error 370 when starting.
This error code will disappear when the
communication between the refrigerating unit
and the hydraulic module is established (again).
During the initialisation phase of the regulator, all of
the symbols are displayed, then the "Data, update",
then"Heat pump status" is displayed.
- Make all of the specic settings for the regulation
(conguration of the installation in particular):
Start/Stop
ESC
"Sweeping" button
gure 42 - Control panel
OK
Burner on LED (green)
2.15 Setting the burner
Refer to the instructions supplied with the burner.
Low NOx burner (ATL F10E2)
JetPump pressure
GPH & anglebarkg/h
0.55 gph - 80°S 152.30
2.15.1 Setting the electrodes
Refer to the instructions supplied with the burner.
Oil ow,
burner hot
- Press the OK OK button.
- Press in the button for 3s and select
the "Commissioning" access level using
the knob .
- Validate with the OK OK button.
- Set the PAC regulation parameters (consult the list of
settingspage 40).
" If the installation is tted with a heated oor: It is
essential that parameters 741 and/or 1041 be set
(page 42 and/or page 44).
When commissioning (or in the event of an error 10)
the burner may start even if the instantaneous outdoor
temperature is higher than the trip temperature of the
burner (parameter 3700 by default).
The regulating system uses an average initial outdoor
temperature of 0°C and requires some time to update
this temperature.
To resolve this situation, with the outdoor probe
connected correctly, re-initialiser parameter 8703
(Commissioning level, consumer diagnosis menu).
Once the machine is running, drain the hydraulic module
again (2 litres of water).
2.15.2 Setting the combustion air
The "sweeping" push buttongure 42
- authorises the operation of the burner for an hour.
- Create a heating demand to start the burner.
To get optimum operation from the boiler, the aiur burner
should be adapted to the conditions of the installation
Refer to the instructions supplied with the burner.
- 34 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
2.16 Congurationof the Ambient probe
T55 or T58 - To set the ambient probe and link it to
the correct heating zone:
- Press for more than 3s the presence button
(item11, gure 43, page 36). The ambient sensor
displays RU and a gure ashes.
- Turn the knob to select the zone (1, 2).
If the installation is tted with 2 ambient probes,
rst connect one probe and parameter it to zone 2
then connect the other probe which is set by default
to zone 1.
- Press the presence button, the ambient probe will
display P1 and a ashing number. 1: Automatic
storage; correction of the reference value with the
button is adopted without any special validation
(timeout) or by pressing the operating level button.
2: Save with conrmation; a correction of the value with
the knob is only adopted after pressing the operation
button.
- Press the presence button, the ambient probe will
display P2 and a ashing number.
0: OFF; all operating parts are triggered.
1: ON; the operating parts are locked:
- Switching the operation mode of the heating
circuit
- Adjusting the comfort value
- Changing the operating level
The ambient probe displays OFF for 3s when a locked
button is pressed.
2.17 Conguration
of the central ambient unit (radio)
T75 - During commissioning, after initialising for around
3 minutes, the user language must be set:
- Press the OK OK button.
- Select the "user Interface" menu.
- Select the language. Selection the language (English,
The operation of the heat pump is controlled by the
water logic.
The reference temperature of the heating circuit water
is adjusted in function of the outdoor temperature.
If there are thermostatic valves tted to the installation,
they must be opened fully or set higher than the normal
value of the ambient temperature.
3.3.1 Manual setting
During the installation, the water logic must be set in
function of the heating transmitters and the insulation
of the building.
The water law curves (gure 45) refer to an ambient
reference value equal to 20 °C.
The slope of the water law (parameter 720) determines
the impact of the outdoor temperature variations on the
initial heating temperature variations.
Specic case: When the slope is equal to or greater than
2 and the outdoor temperature is greater than 2 °C, it is
possible there is a little discomfort in the home. In this
case, it is possible to increase the value of parameter
3700.
The water law offset (parameter 721) modies the initial
temperature of all the curves, without modifying the
slope (gure 46) .
The corrective actions in case of discomfort are listed in
the table (gure 47).
INFO
PROG
ECO
temperature ambiante
- Holiday mode activated.
- Process in progress.
- Compressor operation.
- operation of burner.
- Default message.
- Maintenance, special operation.
- Information level activated.
- Program activated.
- ECO function activated
(heating temporarily stopped).
- Time /
parameter number /
reference value.
- 38 -
temperature ambiante
temperature ambiante
- ambient temperature /
reference value.
- Reference value Information /
parameter information .
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
° C
100
90
80
Burner operation
70
60
Heat pump/burner operation
50
40
Heat pump operation alone
30
20
10
70
-100
gure 45 - heating curve slope (line 720)
water law slopes
2,753
2,5
2,25
2
1,75
1,5
1,25
1
0,75
0,5
0,25
-20
radiator
High and medium
temperature
radiator
low temperature
Floor heating
system
° C
heating °C
initial temperature
30
+4,5
Translation
...in mild weather
GoodGood
Cold
Cold
60
50
40
30
20
-4,5
10
10
0
outdoor temperature °C
0
gure 46 - Translation of the heating curve (line 721)
gure 47 - Corrective actions in case of discomfort
Installation and operating manual "1605 - EN"- 39 -
OK
alfea hybrid duo heat pump oil low NOx CH
3.4 Regulation parameters
3.4.1 General
Only the parameters accessible at the levels:
U - Final user.
I - Commissioning.
S - Specialist.
are described in this document.
The access levels are listed in the 2nd column of the
table by the lettres U, I and S.
The OEM parameters are not described and require a
manufacturer access code.
Basic
display
OK
Short press
End user
Time and dateHours / Minutes1Time1...24 h
User interfaceDay / Month2Minutes0...60 min
CC1 time programYear3
...
3.4.2 Setting the parameters
- Selecting the desired level.
- Scroll the list of menus.
- Selecting the desired menu.
- Scroll the function lines.
- Selecting the desired line.
- Adjusting the parameter.
- Validate the setting by pressing OK.
- To return to the menu, press ESC.
If no settings have been made for 8 minutes, the screen
automatically returns to the basic display.
OKOK
Press for
3 seconds
End userCommissioningSpecialist (Engineer)OEM
Time and date
User interface
CC1 time programYear3
...
Hours / Minutes1
Day / Month2
Date for start of summer
time
End date of summer time5
401.01...31.12
3.4.3 List of function lines (settings, diagnosis, state)
LineFunctionSetting range or displaySetting increment Basic setting
Time and date
1UHours / minutes00:00... 23:591
2UDay / month01:01... 31.121
3UYear1900... 20991
5SSummer start time (day/ month)01:01... 31.12125.03
6SSummer end time (day/ month)01:01... 31.12125.10
The time change appears at 03h00 on the rst Sunday after the date set.
User interface
20U LanguageEnglish, Français, Italiano,
22SInfoTemporary | PermanentTemporary
26SOperation lockingStop| StartStop
27SProgramming lockingStop| StartStop
28SDirect setting Storing......automatic |...with
- 40 -
Nederlands...
conrmation
Installation and operating manual "1605 - EN"
French
conrmation
...with
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
44IOperation HC2 (command HC2)Common to CC1, independentCommon
Common to CC1 or independent This function permits the choice to be made if the ambient sensor (in option) has an
action on the two zones or on a single zone.
46ICCP operation (command of sanitary circuit circulator, output QX2)
501U1st phase (in service)00:00... --:--10 min06:00
502U1st phase (not in service)00:00... --:--10 min22:00
503U2nd phase (in service)00:00... --:--10 min--:--
504U2nd phase (not in service)00:00... --:--10 min--:--
505U3rd phase (in service)00:00... --:--10 min--:--
506U3rd phase (not in service)00:00... --:--10 min--:--
516URetrieval of the standard settingsNo, YesNo
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
with heating
circuit 1
Common
with heating
circuit 1
Mon-Sun
Timer programme for heating, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
521U1st phase (in service)00:00... --:--10 min06:00
522U1st phase (not in service)00:00... --:--10 min22:00
523U2nd phase (in service)00:00... --:--10 min--:--
524U2nd phase (not in service)00:00... --:--10 min--:--
525U3rd phase (in service)00:00... --:--10 min--:--
526U3rd phase (not in service)00:00... --:--10 min--:--
536URetrieval of the standard settingsNo, YesNo
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
561U1st phase (in service)00:00... --:--10 min00:00
562U1st phase (not in service)00:00... --:--10 min05:00
Mon-Sun
Mon-Sun
563U2nd phase (in service)00:00... --:--10 min15:00
564U2nd phase (not in service)00:00... --:--10 min18:00
565U3rd phase (in service)00:00... --:--10 min--:--
566U3rd phase (not in service)00:00... --:--10 min--:--
576URetrieval of the standard settingsNo, YesNo
Yes + OK: The standard values, saved in the regulator, replace and cancel the personalised heating programmes.
Your personal settings are therefore lost.
Installation and operating manual "1605 - EN"- 41 -
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
Time program 5 / Cooling
(Not available with DHW model).
Holidays, circuit 1
641UPre-selection of the holiday periodPeriod 1 to 8Period 1
642UDate of start of holidays (day/month).01:01... 31.121
643UDate of end of holidays (day/month).01:01... 31.121
648UOperating level (during the holidays)Frost protection, reducedFrost
Holidays, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
651UPre-selection of the holiday periodPeriod 1 to 8Period 1
652UDate of start of holidays (day/month).01:01... 31.121
653UDate of end of holidays (day/month).01:01... 31.121
658UOperating level (during the holidays)Frost protection, reducedFrost
Setting the heating, circuit 1
710UAmbient comfort temperature valueReduced temperature …
max. comfort reference value .
712UReduced setpointfrost protection temperature …
comfort temperature
714UAmbient "antifreeze" temperature value4 °C… reduced temperature 0.5 °C8 °C
716SMaximum comfort value20 °C... 35 °C1 °C28 °C
720Islope of the heating curve (see gure 45)0.1... 40.020.5
721ITranslation of the heating curve-4.5 °C... 4.5 °C0.5 °C0
726ITranslation of the heating curve Stop| StartStop
0.5 °C20 °C
0.5 °C18 °C
protection
protection
Warning! Do not modify, leave on Stop.
730ISummer/winter heating limit8 °C... 30 °C0.5 °C18 °C
When the mean of the external temperatures over the last 24 hours reaches 18°C the regulator stops the heating (economy).
In summer operation, the display shows "Eco". This function is only active in automatic operation.
732SDaily heating limit-10 °C... 10 °C1 °C-3 °C
This function permits, between seasons, to deviate partially from the automatic switching between summer/winter.
If the value is increased, the switch to summer operation is delayed.
If the value is reduced, the switch to summer operation is brought forward.
This function is only active in automatic operation.
740Smin. initial reference value . (for fan-
741SMax. start value8... 95 °C1 °C80 °C
750SInuence of the ambient temperature1%... 100%1%20%
790SMaximum optimisation when started 0... 360 min10 min120 min
convector)
Heated oor= 50 °C
.
Important remark:
The maximum limit is not a safety function as that required for under-oor heating.
If the installation is equipped with an ambient sensor:
This function allows the inuence of the ambient temperature on the regulation to be chosen.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
(anticipation of start to reach the comfort reference value).
8... 95 °C1 °C8 °C
- 42 -
Installation and operating manual "1605 - EN"
50
45
40
35
30
20
50
25
55
1157
X
10
18
25
15
1
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
791SMax. optimisation when switching off0... 360 min10 min120 min
(anticipation of stoppage to switch from comfort to reduced)
800SStart increasing the reduced operation-30... 10 °C1 °C--
801SEnd of increase in reduced operation-30... 10 °C1 °C-5 °C
830SRaising of mixing valve0... 50 °C1 °C0
834SServomotor travel time30... 873 s1 s240 s
850IFloor slab drying check (gure 48)Stop
- Stop= early interruption of the current programme, programme inactive
- Functional heating
- Curing heating
- Functional heating + Curing heating
- Curing heating + functional heating
- Manual
The manual mode ca be used to programme the slab drying .
The function ends automatically after 25 days.
851Imanual slab drying reference value
(if line 850 = manual)
This function allows the customised oor drying temperature to be set. This temperature remains xed.
The oor drying programme stops automatically after 25 days of operation.
gure 48 - Diagram of the oor slab drying programmes
" Respect the standards and reference values of the builder! Correct
operation of this function is only possible with a correct installation
(hydraulic, electricity and settings)! The function may be interrupted
earlier by setting to "Stop".
Installation and operating manual "1605 - EN"- 43 -
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
Setting the heating, circuit 2
If the installation is composed of 2 heating circuits (only displayed with 2nd circuit kit option)
1010U Ambient comfort temperature valueReduced temperature …
1012U Reduced setpointfrost protection temperature …
1014U Frost protection setpoint4 °C… reduced temperature0.5 °C8 °C
1016SMaximum comfort value20... 35 °C1 °C28 °C
1020Islope of the heating curve (see gure 45)0.1... 40.020.5
1021ITranslation of the heating curve-4.5... 4.5 °C0.5 °C0
1026STranslation of the heating curve Stop, StartStop
Warning! Do not modify, leave on Stop.
1030ISummer/winter heating limit8... 30 °C0.5 °C18 °C
When the mean of the external temperatures over the last 24 hours reaches 18°C the regulator stops the heating (economy).
In summer operation, the display shows "Eco". This function is only active in automatic operation.
1032SDaily heating limit-10... 10 °C1 °C-3 °C
This function permits, between seasons, to deviate partially from the automatic switching between summer/winter.
If the value is increased, the switch to summer operation is delayed.
If the value is reduced, the switch to summer operation is brought forward.
This function is only active in automatic operation.
1040Smin. initial reference value . (for fan-
convector)
max. comfort reference value .
comfort temperature
8... 95 °C1 °C8 °C
0.5 °C20 °C
0.5 °C18 °C
1041SMax. start value8... 95 °C1 °C80 °C
Heated oor= 50 °C
.
Important remark:
The maximum limit is not a safety function as that required for under-oor heating.
1050SAmbient inuence 1 %... 100 %1 %20 %
If the installation is equipped with an ambient sensor:
This function allows the inuence of the ambient temperature on the regulation to be chosen.
If no value is entered, the regulation is via the water logic.
If the parameter is set to 100%, the regulation is only made using the ambient temperature.
1090SMaximum optimisation when started0... 360 min10 min0
1091SMaximum optimisation when stopped0... 360 min10 min0
1100S Start increasing the reduced operation-30... 10 °C, --°C1 °C--
1101S End of increase in reduced operation-30... 10 °C, --°C1 °C-5 °C
1130S Raising of mixing valve0... 50 °C1 °C0
1134S Servomotor travel time30... 873 s1 s240 s
1150IFloor slab drying check (gure 48)Stop
- Stop= early interruption of the current programme, programme inactive
- Heating working.
- Heating ready for occupation.
- Heating working + heating ready.
- Heating ready for occupation + heating working
- Manual - The manual mode ca be used to programme the slab drying .
The function ends automatically after 25 days.
1151IFloor slab drying reference value (if line1150 =
Manual)
This function allows the customised oor drying temperature to be set. This temperature remains xed.
The oor drying programme stops automatically after 25 days of operation.
1156ICurrent drying day0... 32
1157IDrying days completed0... 32
- 44 -
0... 95 °C1 °C25 °C
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
1610U DHW nominal set pointreduced reference value (dened
in line 1612) 65 °C
To reach this value, the boiler is used.
1612U Lower DHW temperature setting8 °C...
comfort ref. value (defined in line 1610)
1620ILiberation of the DHW load24h/day
Heat. circ. timer prog.
Timer programme 4/SHW
Off peak tariff (THC)
4/SHW and THC timer prog.
24h/day: The DHW temperature is maintained permanently at the DHW comfort value.
Heat. circuits timer prog. .: The production of SHW follows the timer programme of the ambient temperature
(with 1 hour's anticipation of the start).
4/SHW timer programme : The DHW programme is independent from the heating circuit programme.
Off peak tariff (THC*): The SHW reference value follows the electricity tariff signal (HP = reduced ; HC = comfort).
4/SHW and THC*timer prog.: The SHW reference value follows the SHW timer programme and the electricity tariff
signal (programme SHW reduced + HP = reduced ; the rest of the time = comfort).
Protection
mode
165 °C
140 °C
Timer
programme 4/
DHW
* - Connect the "energy supplier" contact to input EX5. (see § gure 41, page 32). In the case of a HP/HC contract
(day/night), the DHW value is controlled by the energy supplier tariff.
1640IAnti-legionnella functionStop
Periodic (as per line 1641)
Fixed week day (as per line 1642)
1641IFrequency of anti-legionella cycle1 to 71 day7
1642IDay of Anti-legionnella cycle operation Mon, Tues,.. SunSaturday
1644ITime of anti-legionella cycle operation--:--, 00:00... 23:50--:--
If no value has been entered, no anti-legionella cycle will be run.
1645IAnti-legionella cycle temperature value55 °C... 95 °C65 °C
1646IDuration of anti-legionella cycle--:--, 10 min... 360 min30 min
1647Ioperation of Anti-legionnella circulatorStart... StopStart
1660ILiberation of sanitary circulator **Timer programme 3/ CCP
Liberation of SHW
Timer programme 4/SHW
** Not available with hybrid duo models .
Swimming pool (only displayed with the swimming pool kit option)
2056U Generator ref. heating value8... 35 °C22 °C
Heat pump
Stop
Liberation of
DHW
2843SDuration of compr min. stop.0... 60 min1 min20 min
2844SMax. temp. of thermodynamic operation8... 100 °C1 °C80 °C
2862SLocking time stage2/mod0... 40 min1 min5 min
2873SCompress. modul. operation time10... 240 s1 s240 s
2882SComplete liberation of electrical top ups
No electrical top up so not used with hybrid
model
2884SElectrical liberation - start under outdoor temperature
No electrical top up so not used with hybrid model
2886SHeat decit compensation Stop, Start,
Installation and operating manual "1605 - EN"- 45 -
0... 500 °Cmin1 °Cmin100 °Cmin
-30... 30 °C2 °C
Stop
Only for drying function
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
2910SLiberation dependent on outdoor T°-30... 30 °C1 °C--
2920SIn case of EJP blocking signal (EX4)Locked (locked waiting)...
3720SComplete liberation to relieve boiler0... 120 °C . min1 °C . min50 °C . min
3723SGenerator blockage time1... 120 min1 min10 min
DHW tank
5020SRaising of initial ref. value0... 30 °C1 °C18 °C
5024SSwitching differential0... 20 °C1 °C7 °C
5030SLimiting load duration10... 600 min10 min90 min
5060SElectrical resistance modeReplacement,
Replacement
Summer, Always,
Cooling level
5061SElectric immersion heater release24h/day,
Liberation SHW,
liberation
SHW
Timer programme 4/SHW
Conguration of installation
5700IPre-settings1,2,3,... 14113
This command permits one of the 2 pre-selected installation congurations to be chosen
(the hydraulic diagrams of the various congurations are detailed in the paragraph “’installation congurations”).
- Pre-setting 1 to 12: Do not use with alféa hybrid duo heat pump. Reserved for alféa S or alféa duo heat pumps.
- Pre-setting 13: 1 heating circuit.
- Pre-setting 14: 2 heating circuits.
5711S Cooling circuit 1
(not available with model SHW).
Stop, 4 tubes system,
2 tubes system
5870SCombi storage tankNo, YesNo
5987SAction direction input EX4Rest contact
Work contact
Operation
contact
" it is essential that this parameter be set to "Work contact".
5989SAction direction input EX5Rest contact
Rest contact
Work contact
6046IH2 input function
1... 1619
1: Switching of heating circuit + DHW
operation.
2: Switching of heating circuit operation.
3: Switching of heating circuit1 operation.
4: Switching of heating circuit2 operation.
6: Error/alarm message.
9: Monitoring of dew point.
16: Liberation of swimming pool.
Stop
6047IAction direction contact H2Rest contact
Work Contact
Work contact
6048Sfunction value contact H20... 130 °C45 °C
6100SCorrection of outdoor temperature sensor-3... 3 °C0.1 °C0 °C
6120SFrost protection of the installationStart, StopStart
6205SReset to default parametersNo, YesNo
6220SSoftware version (RVS)0... 99
- 46 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
7070STime interval for the maintenance of the heat pump --, 1... 2401 month--
7071SOperating time of the heat pump since last
maintenance.
Reset? no, yes
7072SMax. number of start up operations of the
compressor authorised per hour of operation.
7073SMean number of starts of the compressor
per hour of operation, over the last 6
weeks.
Reset? no, yes
7076SDiff condens max/week--, 1... 2501--
7077SCurrent maximum difference condens / week.
Reset? no, yes
7078SDiff condens min/week--, 1... 2501---
7079SCurrent minimum difference condens / week.
Reset? no, yes
7090SDHW tank period--, 1... 2401 month---
0... 2401 month0
--, 0.1... 120.1--
0... 120
0... 2500
0... 2500
7091SDHW tank since maintenance.
Reset? no, yes
7141U Emergency operationStop, StartStop
Stop: The heat pump does not use the boiler when there is a fault (error 370).
Start: The heat pump uses the boiler when there is a fault (error 370).
In the "Start" position the energy bill may be high if the error is not resolved.
7142SEmergency operating function typeManual, AutomaticManual
Manual: The emergency operation is not activated when there is a fault (emergency operation = Stop).
Start: The emergency operation is activated automatically when there is a fault (emergency operation = start).
In the "Automatic" position, the energy bill may be high if the error is not detected and resolved.
7150ISimulation of outdoor temperature---, -50... 50 °C0.5--
7181IManager's telephone 10... 255
7183IManager's telephone 20... 255
Installation and operating manual "1605 - EN"- 47 -
0... 2400
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
Test of inputs/outputs
7700IRelay testNo test
This test consists of commanding the regulator relays one by one and checking the outputs. This permits a check that
the relays are operating and that the wiring is correct (for this, check that each appliance is operating on the installation).
(0) No test, (1) Everything is STOPPED , (2) Relay output QX23 module 1: Pool circulator , (3) Relay output QX21 module 1: not used, (4) Relay output QX22 module 1: not used, (5) Relay output QX1: opening valve for circuit 1
mixer, (6) Relay output QX2: Closure of circuit 1 mixing valve, (7) Relay output QX3: Circuit 1 heating Circulator ,
(8) Relay output QX4: SHW Circulator , (9) Relay output QX5: not used, (10) Relay output QX6: Starting of burner,
(11) Relay output QX23 module 2: Circuit 2 heating Circulator or pool Circulator , (12) Relay output QX21 module
2: Opening valve for circuit 2 mixer, (13) Relay output QX22 module 2: Closure of circuit 2 mixing valve, (14) Relay
output QX7: Not used.
The display shows the "key" symbol. By pressing the Info button, "error 368" is displayed.
Warning! During the test, the component tested is electrically powered.
0 = No test
1 = Everything is stopped
2 = Digital output DO1
3 = Digital output DO2
Heating level
No test
Heating
operation
7915IInput Ex50, 230 V0
7916IInput Ex60, 230 V0
State
8000IState of heating circuit 10
8001IState of heating circuit 20
8003IState of circuit SHW0
8004IState of cooling circuit 10
8006IState of heat pump0
8011IState of pool circuit 0
8022IState of additional generator0
8050IHistory 1Date, time, state code
8052IHistory 2Date, time, state code
8054IHistory 3Date, time, state code
- 48 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
8056IHistory 4Date, time, state code
8058IHistory 5Date, time, state code
8060IHistory 6Date, time, state code
8062IHistory 7Date, time, state code
8064IHistory 8Date, time, state code
8066IHistory 9Date, time, state code
8068IHistory 10Date, time, state code
Diagnosis of generator
8402Ielectrical resistor 1 startStop, StartStop
8403Ielectrical resistor 2 startStop, StartStop
8406ICondenser pumpStop, StartStop
8410U Heat pump return temperature0... 140 °C
Heat pump ref. value (return)
8412U Heat pump start temperature0... 140 °C
Heat pump ref. value (start)
8413U Compressor modulation0... 100%
8425I140°C-50... 140 °C
8454SDuration of heat pump locking
Reset? no, yes
8455SHeat pump counter locking
Reset? no, yes
8456SHours of operation of electrical start
Reset? no, yes
8457SCounter for n° of electrical starts
Reset? no, yes
Consumer diagnostis
8700U Outdoor temperature-50... 50 °C
8701U Minimum outdoor temperature
Reset? no, yes
8702U Maximum outdoor temperature
Reset? no, yes
8703IAttenuated outdoor temperature
Reset? no, yes
0... 2730 h
0... 65535
0... 2730 h
0... 65535
-50... 50 °C
-50... 50 °C
-50... 50 °C
This is the mean outdoor temperature over a period of 24 h.
This value can be used for the automatic switching between summer/winter (line 730).
8704IOutside temp composite-50... 50 °C
The mixed outdoor temperature is a combination of the "current outdoor temperature" and the "mean outdoor
temperature" calculated by the regulator. This value is used to calculate the start temperature.
8730IHeating circuit pump HC1Stop, StartStop
8731IMixer valve CC1 openStop, StartStop
8732IMixer valve CC1 closedStop, StartStop
8740U Room temperature 10... 50 °C20 °C
Ambient temperature reference value 120 °C
8743U Start temperature 10... 140 °C50 °C
Installation and operating manual "1605 - EN"- 49 -
alfea hybrid duo heat pump oil low NOx CH
LineFunctionSetting range or displaySetting increment Basic setting
Start temperature ref. value 150 °C
8756U Cooling start temperature 10... 140 °C0
Initial cooling temperature reference value
1
8760IPump CC2Stop, StartStop
8761IMixer valve CC2 openStop, StartStop
8762IMixer valve CC2 openStop, StartStop
8770U Room temperature 20... 50 °C20 °C
Ambient temperature reference value 220 °C
8773U Start temperature 20... 140 °C50 °C
Start temperature ref. value 250 °C
8820IDHW pumpStop, StartStop
8821IElectrical resistor SHW K6Stop, StartStop
8830U DHW temperature0... 140 °C
DHW temperature value50 °C
8840SHours of operation of DHW pump0... 2730 h
8841SCounter for DHW pump starts0... 2730 h
8842SHours of operation of DHW electrical
system
0... 2730 h
0
8843SCounter for DHW electrical system starts0... 65535
8900U Swimming pool temperature0... 140 °C
Swimming pool temperature value22 °C
8950ICommon start temperature0... 140 °C
Common start temperature value0
8957ICommon start value, Refrigeration0... 140 °C
9031IRelay output QX1Stop, StartStop
9032IRelay output QX2Stop, StartStop
9033IRelay output QX3Stop, StartStop
9034IRelay output QX4Stop, StartStop
9035IRelay output QX5Stop, StartStop
9036IRelay output QX6Stop, StartStop
9037IRelay output QX7Stop, StartStop
9050IRelay output QX21 module 1Stop, StartStop
9051IRelay output QX22 module 1Stop, StartStop
9052IRelay output QX23 module 1Stop, StartStop
9053IRelay output QX21 module 2Stop, StartStop
9054IRelay output QX22 module 2Stop, StartStop
9055IRelay output QX23 module 2Stop, StartStop
- 50 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
Installation and operating manual "1605 - EN"- 51 -
alfea hybrid duo heat pump oil low NOx CH
4 Overall view of the electrical connections
• Conguration 13: 1 heating circuit.
SA1
R
Circuit 1
SP
SE
VE
SE - outdoor probe
SP - Heated oor safety device
VE - Expansion tank
M
Br
- 52 -
Legend
Br - Burner
R - radiator or fan-convector
SA - Ambient probe (option)
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
• Conguration 14: 2 heating circuits.
SA1
SA2
R
R
Circuit 2
K2c
M
SDp2
CC2
VM2
Circuit 1
VE
SP
CAR
SP - Heated oor safety device
VE - Expansion tank
VM2 - mixer valve circuit 2
R - radiators (or fan-convectors)
SA1 - Ambient probe circuit 1 (option)
SA2 - Ambient probe circuit 2 (option)
SE - outdoor probe
M
SDp2 - start probe circuit 2
Br
SE
Legend
AVS - Regulator, 2nd circuit
CAR - non return valve
CC2 - Heating circulator circuit 2
Br - Burner
K2c - 2nd circuit kit
Installation and operating manual "1605 - EN"- 53 -
alfea hybrid duo heat pump oil low NOx CH
5 Electrical wiring diagrams
Pressure
switch
Temp. sensor.
Compressor
Temp. sensor.
Outdoor
Temp. sensor.
Evaporator
Temp. sensor.
Back-ow
Temp. sensor.
radiator
Temp. sensor.
Evaporator medium
Temp. sensor.
Pressure
regulator.
Compressor
Inverter board
Fuse
F4 T 5A - 250 V
Main regulation board
Option (connector)
see the technical
instructions
Re-injection
coil
4 way valve
Pressure
regulator coil
Re-injection
pressure
regulator coil
Coil
Relay
Colour codes
BK blackBN brownBU BlueGN green
GY Grey
OG Orange
RD red
VT Violet
WH whiteYE yellow
Terminal
block
Terminal
block
WOYG112LBT / WOYG112LCT
WOYG140LBT / WOYG140LCT
Active
lter
board
Diode bridge
Posistor
Fuse
F2 T 3,15A - 250 V
Filter board
fuse
10A
Interconnection
between outdoor unit
and hydraulic module.
Terminal
block
Electrical
power supply
230 V.
Fan 1 motor (upper)
Fan 2 motor (lower)
- 54 -
gure 49 - Electrical wiring of outdoor unit (single phase model)
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
Re-injection
Inverter board
coil
BN
OG
Re-injection
BU
BU
RD
RD
BU
OG
YE
BK
BK
WH
pressure
regulator coil
Temp. sensor.
Pressure
regulator.
WH
BK
Compressor
GN
RD
Filter
board
RD
WH
BK
BK
BK
WH
RD
WH
BK
Temp. sensor.
Inverter
radiator
RD
WH
BK
BK
YE
GN
YE
BU
WH
WH
OG
Condenser
board
RD
RD
BN
RD
OG
YE
GN
BU
GN
GN
BK
OG
VT
P.F.C. board
BK
BK
Reactors
Fuses
BK
BK
BK
BN
BN
BK
BK
BU
BU
BN
WH
BK
BK
BK
BK
BK
RD
BU
OG
YE
WH
RD
BK
WH
YE
BK
WH
YE
BN
BN
RD
BN
RD
Temp. sensor.
Evaporator medium
Temp. sensor.
radiator
P.F.C.
Temp. sensor.
Back-ow
Temp. sensor.
Evaporator outlet
Temp. sensor.
Outdoor
Temp. sensor.
Compressor
Pressure
switch
Fan reactor
4 way
valve
Pressure
regulator coil
Fan 1 motor (upper)
Fan 2 motor (lower)
3 L1L2L3 N
12
Electrical power supply
3 phases 400 V.
Interconnection
between outdoor unit
and hydraulic module.
BK
BU
WH
Terminal
block
F3
10A - 250 V
F2
3,15A - 250 V
Main regulation board
F1
5A - 250 V
(connector)
WOYK 112 LAT / WOYK 112 LCT
WOYK 140 LAT / WOYK 140 LCT
WOYK 160 LAT / WOYK 160 LCT
Option
Colour codes
BK blackBN brownBU BlueGN green
GY Grey
OG Orange
RD red
VT Violet
WH whiteYE yellow
gure 50 - Electrical wiring of outdoor unit (3 phase model )
Installation and operating manual "1605 - EN"- 55 -
alfea hybrid duo heat pump oil low NOx CH
Domestic circulation pump
Heating circulation pump
Mixing valve
Colour codes
BK Black
BN brownBU Blue
ON/OFF switch
Burner
connections on terminals
(see gure 39, page 31)
burner ON LED
Safety thermostat
connections on the PAC regulator, accessories and
options (see gure 40, page 31)
21 FlashesConnection error with the hydraulic module.
22 FlashesHydraulic unit abnormality condition.
(3)
SW3SW4SW5
(4)
Installation and operating manual "1605 - EN"- 59 -
alfea hybrid duo heat pump oil low NOx CH
6.4 Display information
The Info button calls up various information.
Depending on the appliance type, the conguration and
the state of operation, certain information lines may not
be available.
- Possible error messages from the list of error codes.
(see table, page 57).
- Maintenance messages possible in the maintenance
code list.
- Special operation messages.
- Miscellaneous information (see below).
DesignationLine
Current drying value.-
Current drying day.-
Drying days completed.-
State of heat pump8006
State of additional generator8022
DHW state.8003
State of swimming pool.8011
State of heating circuit 1.8000
State of heating circuit 2.8001
State of cooling circuit 1.8004
Outdoor temperature.8700
Ambient temperature 1.
Ambient value 1.
Start temperature 1.
Initial ref. value 1.
Ambient temperature 2.
Ambient value 2.
Start temperature 2.
Initial ref. value 2.
DHW temperature.8830
Heat pump return temperature.
PAC ref. value (initial).
Heat pump start temperature.
Heat pump ref. value (start)
Heat pump ref. value (start)
Swimming pool temperature
8740
8743
8770
8773
8410
8412
8900
- 60 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
Installation and operating manual "1605 - EN"- 61 -
alfea hybrid duo heat pump oil low NOx CH
7 Servicing of the installation
Before carrying out any work, ensure that the general
electrical power supply and the fuel supply valve are
switched off.
7.1 Checking the hydraulic circuit
" Warning:If frequent rells are required it is
essential that you look for any leaks.
If lling and re-pressurization are required,
check what type of uid has been used initially.
Recommended lling pressure: between 1 and 2 bar
(the precise lling pressure is determined according to
the manometric height of the installation).
Every year,
- Check the pressure of the expansion tank (pre-inate
to 1 bar) and the correct operation of the safety valve.
- Check the safety unit on the sanitary cold water inlet.
Make it work as prescribed by the manufacturer.
- Check the circuit breaker.
7.2 Servicing the tank
The tank must be serviced once a year (the frequency
may vary depending on the hardness of the water)
- Reduce the pressure in the primary circuit (P < 0.5
bar).
- Drain the tank by turning the security group valve
- Remove the inspection hatch.
- Remove any scale deposits that may have accumulated
in the tank. It is preferable to leave any limescale xed
to the walls of the tank: it forms a protective layer.
- Gently remove any limescale deposit on the
thermowell. Do not use any metal objects or chemical
or abrasive products.
- Replace the hatch gasket at each disassembly of the
hatch.
- Reinstall the inspection hatch and tighten the bolts
"crossover".
" Don’t forget to put the sensor into the sanitary
thermowell.
7.4 Checking the electrical circuit
- Check connections and possible tightening.
- Checking the condition of the cables and plates.
7.5 Servicing of the heat exchanger
The boiler must be serviced regularly to maintain high
its output.
Depending on the operating conditions, the servicing
operation is to be carried out once or twice a year.
- Switch off the electrical power supply to the appliance.
- Open the rebox door.
- Remove the turbulators and clean them.
- Clean the exchanger using a scraper and a nylon
swab Ø 50 mm.
- Remove residues of cleaning by the soot hatch.
- Don’t use abrasive material or metal brush on the
ceramic door protection
- Ret all of the parts correctly.
- Close the soot hatch and the rebox door, check for
leaks
" Lightly tighten the screws of the closing door
7.6 Servicing the burner
The burner must be serviced regularly (cell, jet,
combustion head, electrode, pump lter) by a specialist
once or twice a year depending on the conditions of use.
These servicing operations are detailed in the technical
instructions of the burner.
Before carrying out any work, ensure that the general
electrical power supply and the fuel supply valve are
switched off.
After retting, check the operation of the burner to
ensure that the setting has not been modied and that
they suit the desired power level if the boiler.
- The "sweeping" (gure 56) push button authorises the
burner operation for one hour.
- Create a heating demand to start the burner.
7.3 Checking the outdoor unit
- Dust off the heat exchanger if necessary, being careful
not to damage the ns.
- Straighten the vanes using a comb.
- Check that there is nothing obstructing the passage
of air.
- Check the fan.
- Verify that condensate drain is not obstructed.
• Checking the refrigerating circuit:
- When the volume of refrigerating uid is over 2 kg, the
refrigerating circuit must be checked every year by a
company that complies with the legal requirements in
force (cf. § 2.1, page 13)
- Check that there are no leaks (connectors, valves...).
- 62 -
7.6.1 Servicing the chimney
The chimney must be checked and cleaned and by a
specialist at least once a year.
7.6.2 Servicing the safety appliances
Every year, check that the expansion system is operating
correctly. Check the pressure of the expansion tank and
the calibration of the safety valve.
Check the safety unit on the domestic cold water inlet.
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
gure 55 - Access to the ue exchanger
"sweeping"
button
ESC
gure 56 - Sweeping function
OK
Installation and operating manual "1605 - EN"- 63 -
alfea hybrid duo heat pump oil low NOx CH
8 Start-up procedure
Before switching on the hydraulic unit:
• Check the electrical wiring.
• Ensure that all of the DIP SW on the interface board
are in the OFF position before starting.
• Check the gas supply to the refrigerating circuit.
• Check the pressure in the hydraulic circuit (1 to 2
bars), check that the PAC is drained, as well as the
rest of the installation.
8.1 Start-up check-list
8.1.1 Before starting-up
• Sight checks
outdoor unit (see chapter "Installation de the outdoor unit" §2.5, page 14).
Location and ttings, condensate evacuation.
Compliance with distances from obstacles.
• Hydraulic checks
Hydraulic module (see chapter "Installation of Hydraulic module" §2.6, page 16).
connections of the pipes, valves and pumps (heating circuit, SHW).
Installation water volume (expansion vessel of adequate capacity ?).
No leaks.
Primary system and degassing pressure.
OKNon conforming
OKNon conformingValue
• Refrigeration connections and checks
(see chapters "refrigerating connections" and "Connecting gas supply to the installation" §2.7, page
18 and § 2.8).
Checking the refrigerating circuits (sealing respected, no dust or humidity)
Connections between units (pipe length, are tightening torque...).
Installation of HP pressure gauges on gas line (large tube).
Pump down required.
Nitrogen leak test (~ 10 bar).
Opening of refrigeration valves to outdoor unit.
Refrigerant lling of hydraulic unit and pipes.
OKNon conforming
• Electrical checks
outdoor unit (see chapter "electrical connections" § 2.11, page 26).OKNon conformingValue
Mains power supply (230v ou 400v).
Protection by rated circuit breaker.
Cross section of cable.
Earth connection .
Hydraulic module (see chapter "electrical connections on Hydraulic module side" § 2.11.7, page 30).
connection with the outdoor unit (L, N, Eartch or 3 L + Earth).
Sensors connection (positioning and connections).
connection of directional valves (measure and SHW) and circulator.
Supply and protection of the electrical power option).
OKNon conforming
- 64 -
Installation and operating manual "1605 - EN"
alfea hybrid duo heat pump oil low NOx CH
8.1.2 Starting-up
• Switching On
(see "Commissioning" chapter § 2.14, page 34
and § Page40).
Engage the main circuit breaker of the installation (outdoor unit power supply)
2 hours before carrying out the tests => Pre-heat the compressor.
Engage the ON/OFF switch => Initialisation within a few seconds.
Operation of the heating circulation pump
The outdoor unit starts after 4 min.
Set the hour, Date and timer Programmes CC, SHW, if different from the default values.
Congure the hydraulic circuit (parameter 5700).
Set the heating curve (720 and 1020).
Adjust the max. initial ref. value (741 and 1041).
• Outdoor unit checks
Operation of fan(s), compressor
Current measurement.
After a few minutes, measurement of air temp. delta.
Check the pressure / temperature of condensation and evaporation.
• Hydraulic unit checks
OKNon conforming
OKNon conformingValue
After 15 mins of operation.
Primary water temp. delta.
Priority to SHW (switch of directional valve).
Heating in operation, boiler measurement...
• Room control
(see chapter "Conguration de the Ambient probe" §2.16, page 35).
Set parameters, handling, checks.
Set the timer programme of the heating periods (500 to 516 / 520 to 536)
Set the reference values of the heating circuits if different from the default values (710 - 714 ; 1010-
1014).
Set the reference values SHW (1610-1612), if different from the default values .
Setpoint display.
Explanations on use.
The heat pump is ready for operation !
OKNon conformingValue
OKNon conforming
Installation and operating manual "1605 - EN"- 65 -
alfea hybrid duo heat pump oil low NOx CH
8.2 Settings sheet
ParameterDesignationSetMenus
Preliminary settings
20languageinter. user
1hours / minutestime and
date
2day / monthtime and
date
3yeartime and
date
5700installation cong.conguration
Heating circuit N° 1
if 2 circuits = the colder one (ex: oor)
Absence of GAS leaks (appliance identication
n°: )
Correct installation of refrigerating connection (length
m)
Reading in HEATING operating modeL3/TV
Compressor discharge temperature °CN/TV
Liquid line temperature°C
Condensation
temperature
Tank water output temperature°CΔT° condensation°C
Tank water input temperature°CΔ secondary T°°C
Evaporation temperatureLP = bar°C
Suction temperature°COverheating°C
Battery air input temperature°CΔevaporation T°°C
Battery air output temperature°CΔT° battery°C
Hydraulic system of hydraulic unit
Secondary system
Domestic hot water ; tank type
Estimated water volume of secondary systemL
Options & accessoires:
Location of room sensor correctAmbient sensor T55
2 circuits kitambient probe T58
Swimming pool kitCentral ambient unit T75
Serial N°
modelmodel
HP = bar°Csub-cooling°C
Floor heating system
LV radiators
Fan-convectors
}
Hydraulic module
L/T or L1/TV
L2/TV
IcompA
}
}
}
}
}
}
Circulator brandType
Central ambient unit T78
Details
Serial N°
Control settings
Conguration type
Essential parameters
Installation and operating manual "1605 - EN"- 67 -
9 Values to be given to the user
- Advise the user in the choice of the most suitable
electricity contract to benet fully from the advantages
offered by the hybrid heat pump: thermodynamics, the
"Off peak rate tariff" days and the boiler on "Peak rate"
days.
- Explain to the user how his installation operates, in
particular the functions of the room thermostat and the
programs accessible to him from the user interface.
- Emphasize that under-oor heating has considerable
inertia and that consequently the settings need to be
progressive.
- Also explain to the user how to check the heating circuit
is lled.
Complies with:
- Low voltage directive 2006/95/EC, under standard EN 60335-1.
- Regulation 842/2006 of the european parliament on certain uorinated greenhouse gases.
- The standards relating to the product and the testing methods used: Air-conditioners, refrigeration unit s and heat pumps with
compressor driven by electric motor for heating and refrigeration in 14511-1, 14511-2, 14511-3, and 14511-4.
- To standard XP ENV 12102: Air-conditioners, heat pumps and dehumidiers with compressor driven by electric motor. Measurement
of airborne noise. Determination of acoustic power level.
This appliance is marked with this symbol. This means that electrical and electronic products shall not be mixed with general household waste.
European Community countries (*), Norway, Iceland Liechtenstein should have a dedicated collection system for these products.
Do not try to dismantle the system yourself as this could have harmful effects on your health and on the environment.
The dismantling and treatment of refrigerant, oil and other parts must be done by a qualied installer in accordance with relevant local and national regulations.
This appliance must be treated at a specialized treatment facility for re-use, recycling and other forms of recovery and shall not be disposed of in the municipal waste stream.
Please contact the installer or local authority for more information.
* subject to the national law of each member state
Date of installation :
Contact your heating technician or your after-sales service.
www. atlantic-comfort.com
www.atlantic.fr
Société Industrielle de Chauffage
SATC - BP 64 - 59660 MERVILLE - FRANCE
RC Dunkirk - Siren 440 555 886
The specications of this equipment may be modied without prior instructions - Non contractual document
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.