Athena OTC25, OTC25 N-L-P, OTC25 N User Manual

DIGITAL TEMPERATURE
CONTROLLERS
SERIES
OTC25 N/L/P
Instruction
Manual
Congratulations on your purchase of an Athena Series OTC25 Digital Temperature Controller. It is designed for ease of use and reliability wherever accurate temperature control is required.
After following the instructions for installation, simply step through and set each of the unit’s parameters using the OTC25’s easy menu system.
If you still have questions or require any assistance in setting up or operating your controller, please contact your Athena represen­tative or call 1-800-782-6776.
Features
Safety Warning
• Type J Input (OTC25 N, OTC25 L)
• Type J or K Input (OTC25 P)
• ±0.3% FS Accuracy
• Large, Easy-to-Read LED Display, Selectable for Either Setpoint or Process Temperature
• Adjustable Output Hysteresis to Prevent Rapid Cycling Around Setpoint Temperature (OTC25 N)
• Adjustable Deviation Alarm Flashes Display When Measured Temperature Exceeds or Falls Below Setpoint Temperature
• NEMA 4X Front Bezel, Splash-Proof and Resistant to Dust
• Discrete Status Indicators Illuminate When Temperature Display, Setpoint Display or Heat/Cool Output is Active
• Approvals: UR, cUR, CE
In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When installing or using this instrument, follow all instructions carefully and use approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel.
Do not locate this instrument where it is subject to excessive shock, vibration, dirt, moisture, oil, or other liquids. The safe operating temperature range for this unit is 32° F to 140° F (0° C to 60° C).
© Copyright 2004, Athena Controls, Inc.
Introduction
Table of Contents
Installation 1
Mounting 1 Wiring 2
Operation 2
OTC25 N On/Off Controller 4 OTC25 L Limit Controller 5 OTC25 P PID Controller 7
Calibration 10 Error Codes 11 IEC Requirements 11 Warranty/Repair Information 12 Technical Specifications 14
1
Installation
Pre-Installation Instructions
1. Inspect shipping carton for obvious signs of mishandling.
2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged unit.
3. Verify that the ordering code number indicated on the side of the controller matches what was ordered.
Figure 1. Case Dimensions
Prior to mounting the OTC25 in your panel, make sure that the cutout opening is of the right size, 3.622" x 3.622" (92 mm x 92 mm), and deburred to enable a smooth fit. A minimum of 5.0" (127.0 mm) of depth behind the panel is required.
0.25"
(6.35 mm)
3.5"
(88.9 mm)
3.780"
(96 mm)
3.780"
(96 mm)
°F
ACTUAL SETPOINT 02
01
Mounting
Figure 2. Mounting Diagram
Before installing OTC25, ensure gasket seats evenly around edges of unit and that there are no breaks or tears in the gasket.
Insert the OTC25 through the front panel cutout, slide mounting “U” bracket around unit and secure it with the screws provided.
Gasket should be evenly compressed around all sides to provide liquid-tight mounting.
0.25"
(6.35 mm)
3.5"
(88.9 mm)
3.780"
(96 mm)
3.780"
(96 mm)
ACTUAL SETPOINT HEAT
MOUNTING
SCREWS
GASKET
PANEL
BRACKET
3.780”
(96mm)
3.780”
(96mm)
0.25”
(6.35mm)
3.5”
(88.9mm)
3.780”
(96mm)
3.780”
(96mm)
0.25”
(6.35mm)
3.5”
(88.9mm)
2
Operation
Athena Series OTC25 Digital Temperature Controller
Just a few easy steps are required before your OTC25 can be placed into service. After completing the mounting and wiring procedures as previously instructed, set each controller parameter using the simple front-panel keys as instructed.
Power On
When power is first applied to the OTC25, all segments of the LED display, as well as the discrete indicators, will be momentarily illuminated while the instrument goes through a series of diagnostic checks to verify proper operation of the unit. A software version will then be displayed, e.g., . The last two digits of this code indicate the software revision supplied with your controller. Please provide this revision number when contacting us regarding your unit. This display is followed by a mnemonic code representing the OTC25 model type.
Wiring
IMPORTANT: All electrical wiring connections should be made only by trained personnel using Class 1 wiring, and in strict accordance with the National Electrical Code and local regula­tions. Both of the incoming power lines should be fused with 2AG, 0.5 A maximum rated fuses.
The OTC25 controller has built-in circuitry to reduce the effects of electrical noise (RFI) from various sources; however, power and signal wires should always be kept separate. We recommend separating wires into one bundle for power (from line power and output) and one bundle for signal (from thermocouple).
The OTC25 power supply accepts 100 through 250 Vac and 120 through 250 Vdc line power without any switch settings or polarity considerations.
Figure 3. Wiring Connections
OUTPUT #2
OUTPUT #1
COM.
N.O.
N.O.
L1
L2
COM.
T/C
(-)
(+)
OTC25 N Operation
Figure 5a. Series OTC25 N Parameters and Default Settings
Parameter Descriptions
Default Display
This parameter determines whether the OTC25 N’s display shows the Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Parameter Key. This will cause the alternate value to be displayed for five seconds.
Control Hysteresis
Control Hysteresis is adjustable between 2 and 252° F (1 to 140° C ). This parameter is used by the control algorithm to prevent rapid cycling of the output around Setpoint. The default value is 4° F (2° C). This means the heat will turn OFF when the Actual Temperature exceeds the Setpoint by 2° F (1° C). Conversely, the heater will not turn ON until the Actual Temperature drops 2° F (1° C) below the Setpoint.
Display Offset
Display Offset is adjustable from -126 to 126° F (-70 to 70° C). It can be used to provide limited adjustment of the displayed temperature as a com­pensation for offsets between the true temperature and the temperature seen by the thermocouple.
To enter the configuration menu, press and hold the Parameter key for 10 seconds until the display changes to the parameter mode. Press the Parameter key again to index through the avail­able parameters. Pressing the Parameter Key for 3 seconds or allowing 60 seconds of inactivity will cause the OTC25 N to exit the menu system and return to normal operating mode.
3
Parameter Range Range Display Options Default Default
Default Display
Control 2 to 1 to Hysteresis 252 140
Display -126 to -70 to Offset 126 70
Deviation OFF, 1 OFF, 1 Band Alarm to 252 to 140
Display Units
Low Calibration
High Calibration
°F °C °F °C
Fixed Fixed
Fixed Fixed
OTC25 N Operation
The Calibration High and Calibration Low selections are accessi­ble only when the calibration jumper is installed as instructed on page 10 (Figure 6).
OTC25 N On/Off Temperature Controller
Normal Operation
The factory default display setting of the OTC25 N is for Actual Temperature . The default display may be changed to setpoint temperature by selecting Setpoint at the Default Display parameter selection. When the Default Display is changed to Setpoint, the setpoint temperature may be adjusted by using the Raise or Lower keys. The setpoint is adjustable from 32 to 905° F (0 to 485° C).
When the Default Display setting is “Actual” , adjustment of the Setpoint may only be accomplished by pressing the Parameter Key momentarily to switch the display to Setpoint, and then using the Raise or Lower Keys to change the Setpoint Value. The display will automatically revert back to “Actual” five seconds after the last keypress.
Parameter Configuration
Your OTC25 N controller’s parameter selections are explained on the next page, with default settings shown in Figure 5a.
Parameter Key
Used to access available parameters to set or change values.
Raise Key
Used to scroll up through available parameter settings or to increase values. (Hold for fast-step progression)
Lower Key
Used to scroll down through available parameter settings or to decrease values. (Hold for fast-step progression)
Discrete LED Indicators
OTC25 N OTC25 L OTC25 P
Actual: amber Actual: amber Actual: amber Setpoint: amber Setpoint: amber Setpoint: amber Heat: orange Limit: orange Output 1: orange
Output 2: orange
Operation
Three-Digit LED Display
Displays measured temperature, setpoint, or parameter labels and settings.
Figure 4. Front Panel Controls and Indicators
4
°
ACTUAL
SETPOINT
HEAT
5
OTC25 L Operation
OTC25 L Limit Controller
Normal Operation
The factory default display setting of the OTC25 L is for Actual Temperature . The default display may be changed to setpoint temperature by selecting Limit Setpoint at the Default Display parameter selection. When the Default Display is changed to Limit Setpoint, the limit setpoint temperature may be adjusted by using the Raise or Lower keys. The limit setpoint is adjustable from 32 to 905° F (0 to 485° C).
When the Default Display setting is “Actual” , adjustment of the Limit Setpoint may only be accomplished by pressing the Parameter Key momentarily to switch the display to Limit Setpoint, and then using the Raise or Lower Keys to change the Limit Setpoint Value. The display will automatically revert back to “Actual” five seconds after the last keypress.
Parameter Configuration
Your OTC25 L controller’s parameter selections are explained on the next page, with default settings shown in Figure 5b. To enter the configuration menu, press and hold the Parameter key for 10 seconds until the display changes to the parame­ter mode. Press the Parameter key again to index through the available parameters. Pressing the Parameter Key for 3 seconds or allowing 60 seconds of inactivity will cause the OTC25 L to exit the menu system and return to normal operating mode.
OTC25 N Operation
Deviation Band Alarm
A Deviation Band is a pre-set number of degrees, plus and minus, around the Setpoint Value, ex.
+
10° F. A Deviation Band Alarm provides an indication to the operator that the Actual Temperature has either exceeded or dropped below the chosen deviation. This parameter can be turned off or adjusted from 1 to 252° F (1 to 140° C). When the process variable is out­side the deviation band, the alarm is indicated by flashing the display (regardless of whether setpoint or actual temperature is displayed) and the optional alarm output is activated.
Display Units
This allows the operator to have the display indicate either degrees Fahrenheit or degrees Celsius.
Loading...
+ 16 hidden pages