Athena 6075 Instruction Manual

Page 1
SERIES 6075
TEMPERATURE CONTROLLERS
WITH AUTO-TUNING
PID AND
PLUG-IN COMPUTER INTERFACE
Page 2
Page 3
SERIES 6075
AUTO-TUNING
PID
TEMPERATURE CONTROLLER
CONTENTS
PAGE
SECTION 1 GENERAL INTRODUCTION . . . . . . . . . 1
1.1
General Description and Cautions . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . 4
SECTION 2 INSTALLATION INSTRUCTIONS . . . . . 5
2.1 Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Locating. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Removing Unit. . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Case Dimensions. . . . . . . . . . . . . . . . . . . . . . . . 6
SECTION 3 OUTPUT MODULES. . . . . . . . . . . . . . . . 7
3.1 Module Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SECTION 4 BASIC WIRING. . . . . . . . . . . . . . . . 8
4.1 Typical Wiring Examples. . . . . . . . . . . . . . . . . . . . 8
4.2 Wiring Thermocouple and RTD Circuits. . . . . . . . . . . . . . 9
SECTION 5 OPERATION. . . . . . . . . . . . . . . . . . . 12
5.1 Front Panel Features. . . . . . . . . . . . . . . . . . . . . . . . . 13
5.2 Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Tuning The Controller. . . . . . . . . . . . . . . . . . . . . 20
5.3.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . 20
5.3.2 Automatic
PlD
Tuning Procedure. . . . . . . . . . . . . . . 20
5.3.2.1 Damping
Settings. . . . . . . . . . . . . . . . . . . 20
5.3.2.2 Operating Instructions. . . . . . . . . . . . . . . . . . . . . 21
5.3.3 Manual Tuning procedure. . . . . . . . . . . . . . . . . . . . . . 22
Page 4
SECTION 6 COMMUNICATIONS . . . . . . . . . . . 26
6.1 Communications Modules . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.1 RS485. . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.2
RS232C. . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.3 20
mA
Current Loop. . . . . . . . . . . . . . . . . . . 27
6.2
Installing the Communications Modules. . . . . . . . . . . . . 28
6.3 Interface Examples. . . . . . . . . . . . . . . . . . . . . . 30
6.3.1 Read Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.3.2 Modify (Temporary). . . . . . . . . . . . . . . . . . . . . . . . . 31
6.3.3 Modify and Store. . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SECTION 7 CALIBRATION. . . . . . . . . . . . 33
7.1 Zero and Span Adjustments. . . . . . . . . . . . . . . . . . . . . . . 33
(Factory Set)
SECTION 8 TROUBLESHOOTING. . . . . . . . . . . . 34
8.1 Troubleshooting - General. . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.2
Troubleshooting - Communications. . . . . . . . . . . . . . . . 35
FIGURES
1.1
Ordering Code
-
Model Number. . . . . . . . . . . . . . . . 4
2.1
Series
6075 Dimensions. . . . . . . . . . . . . . . . . . . 6
4.1 Wiring Examples. . . . . . . . . . . . . . . . . . . . . . 8
5.1 6075 Front Panel Features. . . . . . . . . . . . . . . . . . 13
5.2
Configuration
Code Chart. . . . . . . . . . . . . . . . . . . 17
5.3 Ziegler
- Nichols Graph. . . . . . . . . . . . . . . . . . . . 23
6.1 Connector Pin Identification. . . . . . . . . . . . . . . . . . . . . 28
6.2 Wiring for
Communications. . . . . . . . . . . . . . . . . . 29
z
Page 5
GENERAL INTRODUCTION SECTION
1
1.1
General Description and Cautions Athena Controls, Inc. is proud of the Series 6075 which you will now use It
has been manufactured to our
exacting
production standards, and packed
for
maximum
protection in shipment You will get years of reliable
service from the unit if the information in the manual is followed regarding location, adjustments, and general operation.
CAUTlON
High Voltage and High Temperature can cause injury and are a Fire Hazard. Please read all instructions, have only skilled profes­sionals
wire the unit, and use an approved temperature
and/or pressure safety control. Even the best components can be damaged or may not failsafe.
Warning Notes:
1. "B"
Output for resistance load only.
2.
An open thermocouple will disable the INDEX function.
3.
Note also that in units utilizing only heating output the cooling
gain
should be set by user to the equivalent heating gain. The inverse IS
also true.
4.
A unique algorithm in the Model 6075 prevents continual buildup of
oscillation due to grossly misadjusted rate/reset
(-rt-)
or gain. When
this occurs the unit
will
control at some point higher or lower than set
point
outside the proportional band. If this occurs -rt- was probably set
too low and/or gain set too high.
5.
-rt-
sets Rate
(Derivative)
and Reset (Integral) action. The number dis­played is the Rate time in seconds. This is tracked by the Reset time in seconds (1:6 ratio).
Page 6
Page 7
Page 8
Page 9
SECTION 2 INSTALLATION INSTRUCTIONS
2.1
Unpacking Unpack the instrument and inspect for shipping damage. Report any
damage to the carrier immediitely.
2.2 Locating Select a
location
for the controller where it will not be subject to excessive shock vibration, dirt moisture or oil. The ambient temperature of the area should be between
32º
and 131 ºF (A model
DC-15
dust, oil and water
resis-
tant cover is available to protect from harsh environments.)
2.3
Mounting Mount the controller into a 92 mm (3
5/8”)
square cutout See figure for the cutout and case dimensions. The plug-in controller does not have to be removed from its housing for mounting. Remove two screws that hold the mounting slides and then remove the slides. Insert case from front panel
and
re-install
the two slides and two screws. Do not over-tighten screws. The
length of the slides must be reduced if the controller is to be mounted in an
extra thick
panel.
If the controller has been unplugged from its housing, the
top of the housing can be determined because it features the serial tag.
2.4
Removing
Unit
The 6075 can be removed
from
its housing by pulling firmly on the black
front bezel. If a communication port is connected, it should be removed first
Page 10
Page 11
SECTION 3 OUTPUT MODULES
3.1
Module
Description
The Athena 6075 offers field interchangeable output modules. This unique feature makes it possible to fill output requirements for a variety of applications with a single controller model.
Module Type B: This
7A/5A
relay (at
120/240 Vac)
is used for driving
resis-
tive
heaters.
NOTE:
Do not use this output module with mechanical
contactors
because they generate an excessive
EMI
field which can interfere
with the
6075’s
microprocessor, Instead, we recommend
“T’
output modules for this application
Module Type
F: This 4-20mA
output module can deliver full output to loads having an input impedance of 500 Ohms or less. The cycle time setting must be ZERO for smooth current output.
Module Type S: Similar to
F.
but pulsed 20 Vdc output
for
driving solid state
relays.
Up
to 6 (input series connected) solid state relays can be used.
Cycle
time can be set to optimize the load response time
requirements.
“F’ & “S”
MODULE
NOTE:
A
push-on
terminal is
utilized
as a return for ground
currents
of
the
milliamp
source. It is connected internally by the mating lug
on the circuit board. To avoid ground loops, drive floating
(ungrounded) loads.
Module Type T:
This solid state relay is capable of 1
amp at 120/240 Vac.
It is
zero voltage switched and
optically
isolated from the drive signal. With it
resistive loads up to
I20
watts at
I20 Vac
and 240 watts at 240
Vac
may
be
Page 12
Page 13
Page 14
Standard Thermocouples
I.SA.
Type
Materials
Color Code
J
Iron-Constantant (I/C)
White( +
)
Red(
-
)
K
Chromel-Alumel
Yellow( +
)
Red(
-
)
T
Copper-Constanan
Blue( +
)
Red( -
)
Platinum-Platinum
13%Rhodium
-
Platinum-Platinum 10%
Rhodium
-
Wiring RTD Circuits 6275 units are designed for 100 Ohm Platinum
RTD’s 2-wire RTD’s
are
connected to terminals 1 and 2 with a jumper connecting 2 to 3. Keep leads
short and use heavy gauge
copper
extension wires if necessary, to minimize
lead resistance. For long runs
3-wire
RTD should be used and wire gauge
should be sufficient that resistance does not exceed 10 Ohms. An error of
0.2ºF
will result for each additional 10 Ohms Per lead
DO NOT RUN RTD LEADS IN IN THE SAME CONDUIT AS POWER LINES.
If shielded RTD wire is used, terminate the shield only at the controller end, using the comer screw provided for that purpose.
NOTE
RTDs
tend to be shock sensitive and require extra care in handling
and installation. THERMOCOUPLE PLACEMENT
(or RTD)
Proper thermocouple placement can eliminate many problems in the sys­tem. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed close to the heater. In processes where heat demand is variable, the probe should be close to the work area. Some experimenting with probe location is often needed to find its optimum Position.
A WORD ON ELECTRICAL NOISE Microprocessor are essentially small computers. As such they can
randomly be interferred with by large electrical spikes, even with elaborate
10
R S
Page 15
watchdog circuits and filtering built into the unit Contacts and coils must be suppressed! One very effective filter is a
.1 ufd/600V
capacitor in series with a
100 Ohm,
1/2
watt (min.) resistor. This network must be put on all contacts, especially across hard contacts that are switching coils and across the coils themselves. The filter should be placed as close to the noise source as Possible
i.e.
right on a
contactors
coil etc.
Other recommended practices include: * Run sensor wires separately, shield if possible and ground only one end
of the shield.
* Install
.01 ufd/100V
or greater capacitors from each sensor terminal to
case ground (the green screw).
* Connect each unit’s ground (the green case screw) directly to the machine
(ground). Do not connect it to the panel Paint and corrosion can cause
poor
signal transmission Do not connect ground wires in series from
unit to unit Ground wires must be connected from each unit directly
to ground
* Make sure the machine is connected to earth ground Do not assume
it is.
11
Page 16
SECTION 5 OPERATION
5.1
Front Panel Features
Touch Key and Indication Operation Layout
1.
2.
3.
4.
5.
6.
7.
Process Temperature or Parameter code is viewed on the upper display.
Set Point or Parameter setting is viewed on the lower display. Degrees F and C is also displayed.
Set Point
Key:
Allows user to return to set point
ENTER/TUNE
Key:
Enters a selected value into nonvolatile memory.
Also initiates Auto-Tuning when used in the correct sequence. Up and Down Keys: Raises and lowers setting respectively. 2 Step scan
rate: Slow and Faster (after 5 seconds).
Index
Key:
Selects Parameters to be addressed
STAND-BY/CANCEL
Key:
Disables outputs. Unit is put in idle mode.
LED above
switch
lights in STAND-BY mode. STAND-BY is also used as the position from which AUTO-TUNE is accessed. If the key is pressed during Auto-Tuning the unit will cancel the
Auto-Tuning
pro-
cedure and return to the STAND-BY
mode.
8.
Receive (RX) and
transmit
(TX) lights: Indicate a signal is present at the
communication
port
tights only
momentarily
9.
Heat (HT) a
nd
CooI
(CT) Output
Lighk
Lights when output drive signal
is present
10.
Alarm Lights (A1 and A2): Lights when unit is in alarm. (programmable
Hi, Low, process or deviation.)
12
Page 17
Page 18
5.2
Basic Series 6075 Setup
1.
The 6075 has dual-input ranges which allow selection of one of two ranges and T/C types, by simply moving the position of the internal
jumper.
To set unit to proper range, remove unit from case and position jumper on top board. Front position is range A, rear position is range B, grouped
s
offered.
A = 01F No Jumper = 26F A = 33F A = 22F No Jumper = 22C B = 02F
B = 32F B = 26C
Consult Serial Tag for actual range and sensor type ordered. Ranges are defined in Section
1.3,
Model Number Identification.
The Series 6075 is shipped from the factory with the following settings: SP = 100 CG = 30 Id = 01
A1 = 105 CC = 05 (F=00) bd = 02
A2 = 95 cd = 08 cL = Range dependent
rt = 00 AT = 00 cH = Range dependent HG = 30 cF = 08 (05 for ºC ranges) HC = 05 (F=00) ct ct = 00
14
Page 19
2. .
Range of Adjustments (Parameters)
All
parameters are accessed by pressing the INDEX key. They
are
listed
in
the order they are displayed when the
lNDEX
key is pressed.
The front panel of the Model 6075 contains a lower display of 5 digits
which displays the set point temperature, the other parameter values and degrees F or C. The upper display consists of 4 digits which display the
process
value or the
parameter
abbreviations;
e.g. -A1-
identifies
Alarm
1.
As the INDEX key is pressed the second column
abbreviations
appear in the upper display. To the right of the ENTER Key is an
EXIT
Key
labelled
‘SET POINT’ which allows the user to EXIT parameters 2
thru 16 back to parameter # 1 (set point).
After
changing a value the ENTER Key must be pressed. This enters the new value in memory. If it is
not
pressed
and power is removed, the last value entered for that
parameter
will
be set up for that parameter.
DlSPLAYED
NUMBER
CODE
PARAMETER
RANGE
0
Process Temperature
Zero to span of unit
(ºF
or ºC)
1
Set Point
Zero to span of
unit
(ºF
or
ºC)
2
-A1-
Alarm One
Zero to span of unit (ºF or ºC)
3
-A2-
Alarm Two
Zero to span of unit
(ºF
or
ºC)
4
-rt-
Rate/Reset
(1:6
ratio)
0 to 255 Seconds
5
-HG-
6
-HC-
7
-CG-
8
-CC-
9 cd-
Heat Gain Heat Cycle Time Cool Gain Cool Cycle Time Access Code
(See Note
6)
(See Note 2) 0 to 120 Seconds (See Note 7) 0 to 400 (See Note 2) 0 to 120 Seconds (See Note 7) 0 to 255 (See Note 3)
15
-
-
1 to 400
Page 20
Locally Adjustable only (Not by Remote Keyboard) 10
-At-
Auto-Tune Damping
0=Low,
1
=normal,
2=High
11
-cF-
Configuration
0 to15
(See Note 4)
12xx
-ct-
Cooling Type
0-Oil or none,
1
-Air, 2-Water
13
-Id-
Unit ID CODE 0 to 99
(See Note 5)
14
-bd-
Baud Rates
300(0),600(
1)
1200(2), 2400(3)
15
-cL-
Calibration, Low
±3% Span
(ZERO)
(°F/ºC)
16
-cH-
Calibration, High
±3% Span
(SPAN)
(ºF/ºC)
xx
Not on RTD units
When setting up the unit for the first time, push the “STAND BY" key
(LED above button is on), and the unit will be placed into an idle condi­tion. Outputs and alarms will be off. On completion of
inital
setup, push
the key again (LED
off)
for normal operation.
press the INDEX key until parameter #9 (-cd-) appears in the process display area. a.
Set
14 in lower display to gain access to configuration code, by
pressing the up or down arrow and then pressing the
ENTER
key.
press the INDEX key until parameter
#11 (-cF-)
appears in the process display area. a. Refer to the configuration code chart and select a number that
represents the desired configuration of thealarms and display
units e.g., #06 = ºF, Deviation Alarms Alarm 1=Low Acting, Alarm 2=High
Acting. b. Set this number into the lower display, using the keys c.
press the ENTER key.
16
Note: Changing temperature scale requires
re-setting
of all points.
3.
4.
5.
Page 21
Page 22
pressed the INDEX key, the unit
will
advance to the High and Low
Calibration
positions.
but index no further until the SETPOINT
key is
depressed.
CAUTION: DO NOT CHANGE THE
CALIBRATION
LOW
[cL(Zero)]
OR
CALlBRATlON
HIGH
[cH(Span)]
ADJUSTMENT UNLESS YOU INTEND TO, ARE QUALIFIED AND HAVE A
CALIBRATION
TEST SETUP CONNECTED.
9.
Press Index and Alarm One (Al) appears in the upper display area. If
this option is installed. set in the desired temperature value, then
press ENTER.
10.
Repeat
for
(-A2-)
Alarm two, if installed
11.
Refer to the
section
on tuning the 6075 for the remainder of the
settings.
NOTE: When finished entering all parameters return to
-cd-
using the INDEX key. Select the level of security desired and enter the appropriate value into memory.
#1 -
Allows changes to set point
only.
#8 -
Allows changes to first nine parameters
only.
#14 -
Allows changes to 9 parameters and calibration constants.
NOTE: Any other value only allows changes to
-cd-
Reference Notes NOTE 1: Parameters
#
10 thru # 16 are accessed from the front panel only,
and can not be set from a remote terminal
NOTE 2: The gain value
(-HG-&-CG-)
is multiplier used to increase the
sen-
sitivity of the controller according
to the
formula: Output = Gain (E + I + D)
where E
=
Error. I = Integral. D= Derivative, Its relationship to proportional
band is as follows:
Unit
Span
PROP BAND =
=
Heat Gain (HG) or Cool
Gain (CG)
Note that proportional band is an inverse function of gain, The range of
18
adjustment is 0 to 400 for Heat. 0 to
400
for Cool.
___________________
Page 23
SPECIAL
NOTE:
For Units utilizing only heating output, the cooling gain should be set by the user to the equivalent heat
gain.
The inverse is also true. Setting CG to 0 initiates an on-off (narrow deadband) output for cooling, which is recommended for cooling-only applications. Setting
HG
to 0 disables the Heat output.
NOTE 3: The access code is a number stored in ROM that upon entering in location
-cd-
allows user access to change parameters. Depending on the
code entered the user may then alter calibration and configuration of the
controller. When this is accomplished the code may be changed to prevent tampering with critical
values. When
the number
is"
1" only the set point can be changed. When the number is ”8”, changes are allowed to the first nine parameters. When the number is
“14”
all
settings
can be altered. When
neither
1, 8
or 14 are entered only the access code can be altered.
NOTE 4: The configuration code allows the user to configure the alarms for
process/deviation, high or low energizing. The code also selects ºF or
ºC
operation of the unit. SEE THE
CONFIGURATlON
CODE CHART.
NOTE 5:
-Id-
is the unit identification code. It is variable from 00 thru 99 and
is used with the communications interface to allow a remote
device
to iden-
tify which controller it is communicating with.
NOTE 6: Setting RT to 0 disables rate and reset
action
for
proportional
only control. This will cause an offset between set point and process termperature.
NOTE 7: Set the heat cycle
(-HC-)
and cool cycle
(-CC-)
according to power
handler being used. 0
for "F" (4-20mAdc)
outputs,
5-20
for
contactors
and
solenoids. Setting HC or CC to 0 initiates 200 millisecond
timebase
for fast
cycling of the
respective
output. Use with external solid state relays
(“S"
Modules) or
SCR
Power Controllers
("F"
Modules).
19
Page 24
5.3
Tuning the Controller
5.3.1
Introduction
5.3.2
The Series 6075 is a state-of-the-art automatic tuning PlD temperature con­troller. The user has the option of automatically selecting the controller’s PlD
settings or manually setting the unit as desired.
Tuning a
3-Mode
controller involves three (3) major adjustments;
propor­tional Band (Gain), Rate (Derivative) and Reset (lntegral) action. Athena has simplified the adjustment procedure with the incorporation of the Rate and Reset settings into one adjustment
"RT"
which is displayed in seconds of
Rate time. The Reset time is automatically set at six (6) times the displayed Rate values.
Automatic
PlD
Tuning procedure
NOTE FOR OPTlMUM RESULTS
Set point must be a minimum of 100°F above the starting or
ambient
temperature when tuning is initiated for accurate tuning. Less than
100ºF may not yield effective tuning settings.
Multi-zone applications require Auto-Tune units on each zone and
simultaneous warmup.
Loss of power or a turn-off during the
Auto-Tune
cycle requires a restart
from ambient (or at least
I00ºF
rise to set point) for reliable
PlD values. Change of state processes, i.e. solid to liquid or liquid to gas, may introduce erroneous tuning parameters during process warmup.
Tuning should be done after the change has
occured
5.3.2.1
Damping Settings Heat Damping Choices (“-At-“: position # 10)
To allow the controller to provide automatic tuning for a wide variety of pro­cesses that may exhibit varying heating characteristics and/or varying heat-
ing capabilities, the controller offers three damping choices:
00 Low Damping - For processes that (any combination of the following)
-
are adequately powered with excellent coupling between heater and probe.
20
-
require quick response and the tightest possible temperature control is desired
1.
2.
3.
4.
Page 25
Page 26
STEP 6:
When
ready to
start Auto-Tuning
calculation
of
PlD settings
press the “Enter/Tune” button. The displays will return to process and set point displayed. The F/C digit will blink while tuning is in pro­cess.
Upon completion of tuning, the digit will stop blinking. TO
stop the Auto-Tuning press
standby/cancel.
NOTE:
Series 6275, RTD input will not
Auto-Tune
when the decimal point
range is used. If tenth degree range is desired either auto tune on the other range and then move the range jumper or use manual tuning methods.
How to override automatic tuning
parameters
(Also refer to Ziegler-
Nichols Tuning Method) It is possible to set or fine tune the three mode parameters manually. To manually enter parameters
1)
Press Index button until
"Rt"
(Rate),
"HG"
(Heat Gain) or
CG
(Cool
Gain)
are displayed.
2) Enter new parameter
setting
desired using the up/down buttons.
3) Press the “Enter” key.
The new parameters will now take control of the process.
5.3.3 Manual Tuning procedure
The following procedure can be used for fine tuning after or instead of Auto-
Tuning.
Ziegler-Nichols
PID
Tuning Method
This has long been an accepted method of tuning
PID (3 Mode)
controllers using a minimum of time and set up to reach effective tuning parameters. Before
proceeding make sure the basic unit setup is done as discussed in
section 5.2.
22
Page 27
Page 28
4. Press STAND-BY again and temperature will begin to rise. When the pro­cess rises to the desired set point it will probably oscillate. Periodically
decrease the Gain (lower the HG number) until a small constant oscilla­tion is obtained. Reducing the Gain by steps of one half (1/2) the previous
-HG- setting
is an acceptable method to obtain the desired small
oscilla-
tion. Note time between oscillations in seconds (“T” on Figure 5.3).
5.
Decrease the Heat Gain to 60% of the value obtained in the previous step.
The Gain is now tuned. Enter the same number in the Cool Gain.
6.
The best rate time (-RT-) setting is one-eighth (1/8) the time in seconds of
one cycle (see cycle time "T" in Figure 5.3). This will give a conservatively tuned system. If faster response and/or faster rise to set point is desired one-twelth (1 /12) of "T" may be used. Note that faster settings may yield instability and temperature overshoots on startup. Remember that the reset automatically tracks the rate (-rt-) adjustment
7.
Connect cooling apparatus Observe control stability.
8. If oscillation occurs lower the cool gain number. If cooling is sluggish raise the cooling gain number.
NOTE: In order to observe changes in process temperature, especially as they relate to time, it is helpful to use a temperature recorder in conjunction with all tuning and parameter setting procedures.
TUNING HINTS
1.
Once the optimum -rt- and -HG- have been set into the unit, cold start tests
of the process should be tried. Remember that start-up and running parameters will usually be different and it is desirable to adjust both gain (HG) and rate/reset (RT) ±25% to strike a balance between good startup and running settings.
Generally higher settings of -rt- will give more controlled start-ups with
less overshoot lower values will give faster recovery from process upsets Higher gain settings will give tighter control of the running process. but
may give more overshoot on start-up.
24
Page 29
Page 30
SECTION 6 COMMUNICATIONS
6.1 Communications Modules
Optional plug-in modules are available for the Series 6075 to allow interfac-
ing to the most common industry standards. A brief description of each type
follows.
6.1.1
RS485
RS485 is a specification standard for balanced voltage digitial interface cir-
cuits published by the EIA.
It was published in 1983 as an upgrade of RS422A electrical specifications, with emphasis given to the application of multipoint systems. The interface circuits used in
the Athena Model 6075 meet the electrical characteristics of
the RS485 standard.
The RS485 multipoint capability allows up to thirty-two (32) units to be con-
nected together in a half duplex network More can be added with the use of “repeaters” such as the Athena Model CC.1 interface box
This module allows
bi-directional
data transfer over a shielded twisted pair.
The
twisted
pair
is a
transmission line
with
drops to communicating devices. Since it is a transmission line, terminating resistors are required at the most distant ends of the line to minimize reflections. (Typically 60 ohms from each line to signal ground).
The Model 6075 RS485 module is fully optically
isolated, eliminating ground loop problems, Parallel drops from the transmission line should be kept as short as possible. Alternately the line
could be daisy chained at each DB-9 connector. Note that the polarity of the
line is important and each device will
specify an
“A” and ”B”
connection. On
the 6075 RS485 module, “A" is pin 8 and 4; “B” is pin 7 and 3 and com-
munications ground is available on pins
1,2,
and 6. Frame ground is pin 5
and 9.
6.1.2 RS232C
The RS232C is a standard that was published in 1968 by the “Electronic Industries Association” (ElA). The RS is an acronym for Recommended
26
Page 31
Standard and the 232 is the identification number for that particular Stan­dard. The C designates the last revision made to the RS232 standard. The
purpose of this standard is to define the electrical characteristics for the interfacing of ”data terminal equipment” and “data communications equip
ment”. The standard providesvoltage ranges for data and control signals to
provide proper transmission.
This module allows bi-directional data transfer via a three conductor cable consisting of signal ground (pin 7). receive (input, pin 2) and transmit (out-
put, pin 3). It is recommended for less than fifty feet between computer/ terminal and instrument Note that multiple instruments cannot be tied to the same port The module is optically isolated to eliminate ground Ioop problems. Note that in a typical installation, “data out” of the computer/ terminal connects to "receive data" of the 6075 and "receive data" of the computer/terminal connects to *‘data out” of the 6075. If shielded cable is
used it should be connected to frame ground at one end only. Signal ground
is connected at both ends. The RS232 module is configured for active operation.
6.1.3 20 mA
Current
Loop
This module allows bi-directional data transfer via a current loop with each
instrument series connected within the loop (10 Units Maximum). The mod-
ule is “passive” i.e. an external current source is required. This is usually available at the computer/terminal. Typically the receive and transmit sec­tion of each instrument is series connected and inserted into the loop: however a separate loop for receive and transmit may be used in the event there is insufficient headroom in the energizing supply. For series transmit and receive approximately two volts of headroom is taken for each instru-
ment on line. For operation with separate loops, approximately 1.5 volts is taken for receive and 0.5 volts for transmit Care must be observed to insure the polarity of connections is correct because current will still flow in the loop
if polarity is reversed making troubleshooting difficult Wiring connections are: pin 3 = Transmitting Position (+), pin 4 = Transmit (-), pin 7 =
Receive (+), pin 8 = Receive
(-),
pins 5 and 9 are Frame Ground.
27
Page 32
Page 33
Page 34
Page 35
Page 36
Page 37
SECTION 7 CALIBRATION
WARNING: These adjustments are factory set and should only be changed by a
qualified
person
using
calibrated equipment. Adjustment is not necessary during
the life of these
controllers.
7.1
Zero
(-cL-)
and Span
(cH)
Calibration
1.
2.
3.
4.
5.
Unlock access to the calibration constants by entering the unlock number (14) into location 9 (-cd-).
Use a tempemture calibmtor with a range appropriate for the unit to be calibrated. Set in the value for low scale calibration, e.g. (1 % of range).
Step to -cL- (calibmte low [ZERO]) using tie index key on the 6075. press the up/down keys on the 6075 until both instruments agree
press the ‘ENTER’ key. Set in a value on the calibrator equivalent to the high-end capability of
the unit under test e.g. (95% of range). Step to -cH- (calibrate high [SPAN]) using the INDEX key. Press the up/down keys on the 6075 until both instruments agree.
Press the "ENTER" key. Repeat steps2 thru 7 until readings agree. Some interaction between
Zero(-cL-) and Span (-cH-) calibration usually occurs Lock out configumtion access, if desired, and return to set point by
pressing "SET POINT" key.
NOTE: Pressing index continuously selects -cH- or -cL- (Span and Zero) in
the calibrate mode to faciliite testing. Exit this mode by pressing the ‘SET
POINT" key.
33
6.
7.
8.
9.
Page 38
SECTION 8 TROUBLESHOOTING
8.1
Troubleshooting -
General
Symptom
Display does not
light
up.
Process display shows
(- - -)
or
‘HHHH’
Probable Cause &
Corrective Action
No power, blown fuse.
Process display shows LLLL or counts down scale when temperature is rising.
About 30% error.
No heat
Display
blinks;
entered values
change.
Open thermocouple circuit Shorting terminals 1 and 2 should indicate temperature at back of case.
Repair or replace thermocouple.
Check for reversed thermocouple.
Wrong thermocouple type connected or internal range jumper in wrong position. Check serial tag for sensor type and then check probe. Consult manual for jumper location for desired range and then check unit and sensor.
Incorrect heater wiring, wrong output module. Check for cause and correct the components
Electromagnetic interference
(EMI).
To
eliminate
high voltage spikes, separate sensor and controller wiring from “dirty” power lines. Ground heated devices. Suppress all coils and con­tacts.
See section on Electrical Noise.
34
Page 39
ATHENL
Athena Controls, Inc.
5145
Campus Drive Plymouth
Meeting,
PA
19462
Tel:
(610) 828-2490
Fax:
(610)
828-7084
Loading...