Athena 16C User Manual

SERIES
16C
TEMPERATURE/PROCESS CONTROLLER
Standard Options and
Digital Communications
User’s Guide
© Copyright 2004, Athena Controls, Inc.
Table of Contents
For information and instructions related to basic operations, refer to the Series C operator’s manual supplied with your controller.
Options Wiring Diagrams
Dual Alarm Outputs (Options #10 and #22) 1 Dual Open Collector Alarms (Option #20) 2 Dual 24 Volt DC Alarm Outputs (Option #21) 3 Relay, N.O. Alarm Output (Option #23) 4
RS-232 Communications (Option #30) 5 RS-485 Communications (Option #31) 6 Contact/Digital Input with Alarm
(Options #40, #41, #42) 7
Transducer Excitation (Options #50, #51,
#52, #53) 8 Auxiliary Output (Options #60, #61, #62, #63) 9 Remote Analog Setpoint (Options #80, #81,
#82, #83, #84) 10
Guide to Digital Communications
Remote Communications Options 12 Athena+ Protocol 14
- Message Format 15
- Sample Commands 19
- Request Messages 21
- Response Messages 24
- Communications Parameter List 27
- Auxiliary Commands 31
- Communications Error Codes 34
1
Dual Alarm Outputs
Option #10: Dual Alarm Output, N.O. Option #22: Dual Alarm Output, N.C.
This optional hardware module provides two alarm drive outputs. LED indicators A1 and A2 are used to indicate alarm conditions as configured in the Alarm Menu.
Option Description:
Option 10: Dual alarm, N.O. Option 22: Dual alarm, N.C. (Note: NC only when power
is applied to unit; otherwise NO)
Load Limits:
Max. Load Current 1 A rms Min. Load Current 0.5 mA rms Power Factor Range 0.2 to 1.0 (can drive small
motors, solenoids, valves, and contactors)
Max. Surge Current
Non-repeating for 1 second 7.5 A Max. I2T for fusing (0.01 sec) 4.5 amp-squared seconds (1 A -
ABC1 typical fuse)
2
Option #20: Dual Open Collectors, NPN, Isolated with Clamping Diode
Dual Open Collector Alarms
Option Description: Dual open collectors, NPN, isolated, with clamping
diode
Recommended operating conditions: Supply Voltage Pins 13 & 14; 200 working Vdc max. (Never exceed
300 Vdc) Collector Current 50 mA max. Specifications: Saturation Voltage 0.3 Vdc min.
1.2 V max.
Collector-Emitter
Breakdown 300 V min.
Isolation Isolation 300 volts ac/dc output-to-output or output-
to-controller
3
Dual 24 Vdc Alarm Outputs
Option #21: Dual 24 Vdc Alarm Outputs
Option Description: Dual 24 V outputs with clamping diodes
Pins 13 & 7 are connected internally
Source current is limited to 25 mA (1000 ohm
resistor)
Open circuit voltage is 25 volts Isolation: Isolation 300 volts ac/dc either output to
instrument
4
Tungsten Lamp, 360 W 120 Vac
Option Description: NO (Normally open) relay contact is closed when
either alarm is active. Jumpers on the board can be removed to activate the output for a single alarm only:
JP1 - Alarm A1 JP2 - Alarm A2
The relay life is greater than 100,000 operations at 5 operations per second switch­ing full load.
*
Connect load and supply voltage per the following table:
Relay, N.O. Alarm Output
Option #23: Relay, N.O. Alarm Output
Load Type 5 Amp Voltage Limit
Resistive DC 30 Vdc Inductive DC (L/R = 7 ms) 20 Vdc Resistive AC 250 Vac Inductive AC (pF = 0.4) 150 Vac
Motor, AC, 1/6 hp 250 Vac
*
*
5
RS-232 Communications
Option #30: RS-232 (one-to-one) Communications
Option Description: Provides a one-to-one connection between
the controller and an RS-232 port. Computers, PLCs, or dumb terminals may be used to set and access controller data.
6
RS-485 Communications
Option #31: RS-485 (one-to-many) Communications
Option Description: Provides one-to-many communications.
If run exceeds 1000 ft., terminate the controller furthest from the computer by connect­ing a 120-ohm, 1/4-watt resistor between terminals 13 and 14.
*Converter is supplied with a wallplug-mount power transformer.
7
Contact/Digital Input with Alarm
Option Description: Dual function board (functions unrelated)
a. Output alarm is energized when either A1
or A2 is active.
b. Digital input controls Remote Standby, Ramp-Soak
Run/Hold, OR Second Setpoint Select.
Option 40: Active when switch closed. Option 41: Active when switch open.
Option 42: Active when 5 V input present Load Limits: Max. Load Current: 1 A rms Min. Load Current: 0.5 mA rms Power Factor Range: 0.2 to 1.0 (can drive small motors, solenoids, valves,
and contactors) Max. Surge Current, Non-Repeating for 1 second: 7.5 A Max. I2T for fusing (0.01 sec): 4.5 amp-squared secs (1A - ABC1
typical fuse)
Contact/Digital Input with Alarm
Options #40, #41, #42: Contact/Digital Input with Alarm
Input Option Menu
8
Transducer Excitation
Option #50, #51, #52, #53: Transducer Excitation
Option Description: The transducer excitation option provides power to
remote transducers. The transducer outputs, in turn, pro­vide a signal to the controller input which can be scaled in the appropriate engineering units. Option 50: 10 Vdc Option 51: 12 Vdc Option 52: 15 Vdc Option 53: 5 Vdc
All options will provide at least 20 mA. The transducer circuitry is thermally protected from short circuits.
9
Auxiliary Output
Option #60, #61, #62, #63: Auxiliary Output
Auxiliary Output
Input Option Menu
Option #60, #61, #62, #63: Auxiliary Output
Option Description: The Setpoint Variable or Process Variable is
transmitted to a remote device (chart recorders, indica­tors, data recorders, computers, process controllers, etc.) with 1 of 4 different interfaces: Option 60: 4-20 mA Option 61: 1-5 V Option 62: 0-20 mA Option 63: 0-5 V
The output signal is scalable in the Auxiliary Output Menu. Multiple remote indicators may be driven by the controller. However, current and voltage outputs cannot be used simultaneously.
For current (mA) options, the remote indicators are connected in series. The sum of the input resistance for all remote indicators must be less than 400 ohms. For voltage options, the remote indicators are connected in parallel. The sum of the currents for all remote indicators must be less than 10 mA.
10
Remote Analog Setpoint
Option #80, #81, #82, #83, #84: Remote Analog Setpoint
Option Description: Remote setpoints use either voltage or current inputs,
depending on the specified option: Option 80: 0-5 V Option 81: 1-5 V Option 82: 0-20 mA Option 83: 4-20 mA
Option 84: 0-10 V The input signal is scalable in the Remote Analog Setpoint Menu. Activation of the analog setpoint causes the F1 indicator to illuminate. For current (mA) options, the input resistance is 255 ohms. For voltage input options, the input resistance is greater than 10K ohms.
*Ground shield at one end, taking care not to run wires next to power circuitry.
Maximum length will be determined by noise performance.
11
Series
16C
with
Digital
Communications
Option
12
Digital Communications Option
Remote Communications Options
RS-232
This method allows bidirectional data transfer via a three­conductor cable consisting of signal ground, receive input and transmit output. It is recommended for communication distances less than 50 feet between the computer terminal and the instru­ment. Note: Multiple instruments cannot be connected to the same port.
The RS232 port is optically isolated to eliminate ground loop problems. Typically, “Data Out” of the computer/ terminal connects to the “RCV” terminal. “Data In” connects to the “XMT” terminal. If shielded cable is used, it should be connected to the frame ground at one end only. Signal ground is to be connected at appropriate ground terminals (refer to wiring diagram on next page).
RS-422
This method allows bidirectional data transfer via a four­wire conductor cable for distances over 50 feet between the computer terminal and the instrument. A signal ground wire is not required.
RS-485
The RS485 multipoint capability allows up to 32 controllers to be connected together in a half-duplex network or up to 100 con­trollers with an appropriate communications repeater.
Three remote commu­nications options are available for the 16C which allow interfacing to remote devices utilizing the most common industry standards: RS232, RS422, and RS485.
13
Digital Communications Option
This method allows bidirectional data transfer over a twisted pair cable. The twisted pair cable is a transmission line; therefore, terminating resistors are required at the most distant ends of the line to minimize reflections (typically 120 ohms at each end). The RS485 circuit is fully optically isolated, eliminating ground loop problems. Parallel drops from the transmission lines should be kept as short as possible; however, the line may be daisy-chained at each controller. The polarity of the line is important and each device will specify an “A” (+) and “B” (-) connection.
Figure 1a. Wiring diagram for RS-232 digital communications.
Figure 1b. Wiring diagram for RS-485 digital communications.
Note: Call factory for a recommended RS485 converter.
14
Athena+ Protocol (Standard)
Communications Option Menu
Athena+ Protocol
The Athena+ Protocol provides an easy way to query and modify controller parameters using a personal computer and the optional digital communications option of the 16C. In this manual, the word “host” refers to the personal computer
that’s communicating with the controllers in the serial link, and the word “slave” refers to the controllers themselves.
All transactions between the host and the slaves are done with messages consisting of only printable ASCII characters. There are only two primary types of messages: Requests and Responses. Messages coming from the host are called requests and messages coming from the slaves are called responses.
With the exception of a broadcast request, for every request sent from the host, the slave will send back a response. If a slave does not respond within 100 milliseconds, then the request can be con­sidered lost.
A broadcast request is a request having an ID of ‘00’ (see Message Formats on next page). It is used to address all slaves on the net­work. All slaves on the network will perform the actions requested in a broadcast message. However, a response message will not be returned. Therefore, the host can only broadcast Write or Auxiliary Command Requests. All slaves will ignore all Read Broadcast Requests.
Digital Communications Option
15
Message Formats
All Athena+ messages adhere to the general format of: [START CHAR][ID][ZONE][TYPE][PARAM][ERROR]
[DATA][CHKSUM][END CHAR]
START CHAR
This is a single character which designates the start of the mes­sage. For a Request message, this character is the ASCII ‘$’ and for a Response message, this character is the ASCII ‘%’.
ID
This is a two-character ID identifying the receiving controller. Controller IDs go from 1-255 inclusively and all slaves in the net­work must have unique IDs. The ID number of ‘00’, when used in a request, designates a broadcast message that is used to address all controllers in the network. See the section Request Message for an explanation of the broadcast message.
In order to represent 255 with just two ASCII characters, a number system known as the Message Code Numbering System is used. In this system, the most significant digit is represented with the numbers 0-9 and the letters A-Z and the least significant digit is represented with the numbers 0-9. The numbers 0-9 have the
Digital Communications Option
16
same values as their decimal counterparts and the letters A-Z have the values of 100 - 350 inclu­sively in increments of 10.
Example:
Message Code Value = Decimal Value
00 0 + 0 = 00
99 90 + 9 = 99 A0 100 + 0 = 100 A2 100 + 2 = 102 B8 110 + 8 = 118 P5 250 + 5 = 255
Zone
This is a two character ID identifying the Zone number in multi­zone capable controllers. For the 16C, this number must be 01.
Digital Communications Option
17
Type
This is a single character identifying the type of message. The fol­lowing table lists the type characters for all messages.
TYPE character Message Type
R Read Request or Read
Response Returning a Positive Result
r Read Response Returning a
Negative Result
W Write Positive Value Request
and Response
w Write Negative Value Request
and Response
A Auxiliary Command
For further information, see following sections on the different message types.
Digital Communications Option
18
PARAM
This is a two character, message specific, parameter ID. For a Read/Write Request or Response message, this ID identifies the controller parameter. For an Auxiliary Command Request or Response message, this ID specifies the command.
STATUS
This is a single-character field used in all response messages, con­taining a status code specifying the status of the request message received.
DATA
This field contains the ASCII representation of the value of the parameter. For the Auxiliary Request or Response messages, this field either contains the ASCII representation of a numeric value or just ASCII data. The length of this field depends on the message type. The discussion on the specific message types gives the exact requirements for this field.
All ASCII representations of numeric values must be done using the characters ‘0’-‘9’, and ‘.’. Any use of other ASCII characters, including‘ ‘ and ‘-’ will result in a bad message. Negative numbers CANNOT be represented by preceding the number with ‘-’ charac­ter. Instead, a special message type is used. See subsequent sec­tions for more information.
Digital Communications Option
19
Digital Communications Option
IMPORTANT:The data field in the Read and Write Request and
Response messages must and will only contain the characters ‘0’-’9’, and the decimal point ‘.’. All other characters are considered illegal. When the data field is listed as Unused or Ignored in an auxiliary command, it does not mean that the field can be skipped when sending in the request message. Instead, this field must be padded with any 10 alphanumeric (only letters and numbers are allowed) ASCII characters.
Figure 2. Sample Communications Commands
Figure 3. Requesting a Parameter from a Controller
20
Examples of valid numeric representations for a 6 character data field:
Numeric Value ASCII Representation
3 3.0000
000003
003.00
100 100.00
0100.0 000100
3.2 003.20
0003.2
Examples of invalid numeric representations for 6 character data field: (B represents a blank, or a space, character)
Numeric Value Bad ASCII Representation Why?
3 BBBBB3 Leading blanks
are not allowed.
3.0BBBB Trailing blanks are not allowed.
-3.2 -3.20000 ‘-’ is not allowed.
Digital Communications Option
21
CHKSUM
This is a two character Message Code Numbering System, repre­senting the sum of all the ASCII values of all the characters (excluding the START, CHAR, the END CHAR, and the CHKSM themselves) in the message. The sum is computed using the fol­lowing formula:
CHKSM = SUM(All Message Characters)%256 % represents the modulus operator.
END CHAR
This is a single character designating the end of the message. For all messages, the character used is <CR>, the carriage return.
Request Messages:
Request Messages are sent from the host to the slaves. Each request will have an ID identifying the intended recipient of the request. If the ID is ‘00’ (zero), then the request is a broadcast message. All slaves will perform the action requested in the broad­cast request. However, a response message will not be returned. Therefore, it only makes sense to send Write or Auxiliary Command Requests as broadcast requests. There are three types of Request Messages: Read, Write, and Auxiliary Commands.
Digital Communications Option
22
The Read Request:
The Read Request is used to query parameter values and it has the following message format:
[START CHAR][ID][ZONE][TYPE][PARAM][CHKSUM][END CHAR] Field Description: TYPE Must contain the uppercase letter ‘R’.
Request Message Description
$Ø1Ø1RØ5C1<CR> Queries the value of the Process Variable
of Controller #1.
$Ø1Ø1RØ9C5<CR> Queries the value of the EEPROM
Setpoint 1 of Controller #1
$Ø2Ø1RØ9C6<CR> Queries the value of the EEPROM
Setpoint 1 of Controller #2.
END CHAR CHKSUM PARAM TYPE ZONE ID START CHAR
Digital Communications Option
Examples of the responses to these requests are given in later sections on Response Messages.
23
The Write Request:
The Write Request is used to modify parameter values and it has the following message format: [START CHAR][ID][ZONE]
[TYPE][PARAM][DATA][CHKSUM][END CHAR] Field Description: TYPE This field must contain one of the following
two characters. W– Value in DATA is a positive value.
w– Value in DATA is a negative value.
DATA A six-character ASCII representation of a
numeric value.
Request Message Description
$Ø1Ø1WØ91Ø.123G7<CR> Change both the RAM and EEPROM
copies of Setpoint #1 in controller #1 to the value of 10.123
$Ø1Ø1w1Ø1Ø.123J1<CR> Change only the RAM copy of
setpoint #1 in controller #1 to the value of -10.123 (notice the lowercase ‘w’).
END CHAR CHKSUM DATA PARAM TYPE ZONE ID START CHAR
Digital Communications Option
24
Response Messages:
Response Messages are replies to the requests sent from the host. For each request received, the slave will reply back with a response.
For all requests, the Athena+ Protocol specifies a maximum response time of 100 milliseconds. If a response is not received after 100 milliseconds, that request can be considered lost.
There are three types of Response Messages: Read, Write, and Auxiliary Commands.
The Auxiliary Command Request:
The Auxiliary Command Request is used to issue commands to the controllers and it has the following message format:
Field Description: TYPE This field must contain the uppercase
letter ‘A’
DATA A ten-character ASCII representation of a
numeric value or 10 alphanumeric ASCII char­acters.
Request Message Description
$Ø1Ø1AØ1XXXXXXXXXXL2<CR> Tell controller #1 to load
all parameters with their defaults. The 10 X’s are padding characters.
$Ш2Ш1AШ2ШШШ1.ШШШШШ69<CR> Tell controller #2 to
perform a low RTD calibration.
END CHAR CHKSUM DATA PARAM TYPE ZONE ID START CHAR
Digital Communications Option
25
The Read Response:
The Read Response will be sent in response to a Read Request. Some examples:
Request Message Description
%Ø1Ø1RØ5Ø21.123K8<CR> The value of the Process
Variable is 21.123 Degrees C.
%Ø2Ø1R1Ø1G7<CR> A serial transmission has
occurred: Framing Error
%Ø1Ø1rØ9Ø21.ØØØN8<CR> The value of the EEPROM
setpoint #1 is -21 Degrees C (notice the lowercase ‘r’).
END CHAR CHKSUM DATA STATUS PARAM TYPE ZONE ID START CHAR
Digital Communications Option
26
The Auxiliary Command Response:
The Auxiliary Command Response will be sent in response to an Auxiliary Command Request.
Some examples are:
Request Message Description
%Ø1Ø1AØ1ØXXXXXXXXXXØ4<CR> Default load all para-
meters has started.
%Ш2Ш1AШ2ШШ.ШШШШШШШШB6<CR> RTD low calibration
on controller #2 has started.
END CHAR CHKSUM DATA STATUS PARAM TYPE ZONE ID START CHAR
The Write Response:
The Write Response will be sent in response to a Write Request. Some examples:
Request Message Description
%Ø1Ø1WØ93I1<CR> A serial transmission error
has occurred: Parity error. Write failed.
%Ø1Ø1w1ØØK2<CR> RAM copy of setpoint #1
modified successfully.
END CHAR CHKSUM STATUS PARAM TYPE ZONE ID START CHAR
Digital Communications Option
27
Digital Communications Option
Parameter Parameter Number Description Number Description 1 Controller Type 19 Manual Control 2 Software Version 2 Percentage 3 Communications Output 1 Deadband
Version 21 Output 1 Hysteresis 4 Status Byte 22 Output 1 Proportional 5 Process Value Band 6 Operating Mode 23 Output 2 Proportional 7 Access Level Band 8 Contact/Digital Rate/Derivative Action
Input State 32 Reset/Integral Action 9 Setpoint - RAM, 34 Manual Reset/
EEPROM Internal Action 1Ø Setpoint - RAM 37 Output 2 Deadband
Only 38 Output 2 Hysteresis 11 Second Setpoint - 39 Autotune Damping
RAM, EEPROM Recipe Option 12 Second Setpoint - 41 Single Setpoint Ramp
RAM Only Time 13 Remote Analog 42 Ramp Time 1
Setpoint 43 Ramp Time 2 14 Recipe Setpoint 44 Ramp Time 3 16 Output 1 Percentage 45 Ramp Time 4 17 Output 2 Percentage 46 Ramp Time 5 18 Manual Control 47 Ramp Time 6
1 Percentage 48 Ramp Time 7
Table 1. Communications Parameter List (Athena+ Protocol)
28
Digital Communications Option
Table 1. Continued
Parameter Parameter Number Description Number Description 49 Ramp Time 8 73 Soak Time 8 5Ø Ramp Event 1 74 Soak Event 1 51 Ramp Event 2 75 Soak Event 2 52 Ramp Event 3 76 Soak Event 3 53 Ramp Event 4 77 Soak Event 4 54 Ramp Event 5 78 Soak Event 5 55 Ramp Event 6 79 Soak Event 6 56 Ramp Event 7 Soak Event 7 57 Ramp Event 8 81 Soak Event 8 58 Soak Level 1 82 Recycle Number 59 Soak Level 2 83 Holdback Band 6Ø Soak Level 3 84 Termination State 61 Soak Level 4 85 Power Resume 62 Soak Level 5 86 Input Bias 63 Soak Level 6 87 Input Low Scale 64 Soak Level 7 88 Input High Scale 65 Soak Level 8 89 Lower Setpoint Limit 66 Soak Time 1 Upper Setpoint Limit 67 Soak Time 2 91 Input Filter 68 Soak Time 3 92 Input Type 69 Soak Time 4 94 Output 1 Type 7Ø Soak Time 5 95 Output 1 Action 71 Soak Time 6 96 Output 1 Alarm 72 Soak Time 7 Action
29
Digital Communications Option
Table 1. Continued
Parameter Number Description B6 TC/RTD Decimal Position B7 Linear Decimal Position B8 Display Filter B9 Display Units C1 Display Blanking C2 Alarm 1 Action C3 Alarm 1 Operation C4 Alarm 1 Delay C5 Alarm 1 Inhibit C6 Alarm 1 Process Setpoint C7 Alarm 1 Deviation Setpoint C8 Alarm 2 Action C9 Alarm 2 Operation DØ Alarm 2 Delay D1 Alarm 2 Inhibit D2 Alarm 2 Process Setpoint D3 Alarm 2 Deviation Setpoint D4 Communication Protocol D5 Communication ID D6 Communication Baud Rate D7 Communication Data Format D8 Communication
Transmit Delay E1 Output 1 Failsafe % E2 Output 2 Failsafe %
Parameter Number Description 97 Output 1 Alarm Operation 98 Output 1 Alarm Delay 99 Output 1 Alarm Inhibit AØ Output 1 Process
Alarm Setpoint
A1 Output 1 Deviation
Alarm Setpoint A2 Output 1 Cycle Time A3 Output 1 Low Limit A4 Output 1 High Limit A5 Output 2 Type A6 Output 2 Action A7 Output 2 Alarm
Action N/A A8 Output 2 Alarm Operation A9 Output 2 Alarm
Delay N/A BØ Output 2 Alarm Inhibit B1 Output 2 Process
Alarm Setpoint B2 Output 2 Deviation
Alarm Setpoint B3 Output 2 Cycle Time B4 Output 2 Low Limit B5 Output 2 High Limit
30
Parameter Number Description E3 Loop Break Time E4 Highest Reading E5 Lowest Reading E8 Option Selection N/A E9 TC Zero Calibration FØ TC Span Calibration F1 RTD Zero Calibration F2 RTD Span Calibration F3 Low-Voltage Zero
Calibration
F4 Low-Voltage Span
Calibration
F5 High-Voltage Zero
Calibration
F6 High-Voltage Span
Calibration F7 Current Zero Calibration F8 Current Span Calibration G1 Auxiliary Output Variable G2 Auxiliary Output
Scale Low G3 Auxiliary Output
Scale High G5 RAS Scale Low G6 RAS Scale High
Digital Communications Option
Table 1. Continued
Parameter Number Description G7 Contact/Digital
Switch Function H2 Autotune State H3 Recipe State H5 Current Recipe
Segment H6 Active Setpoint H7 Resume Exhaustion
Flag F4 Low-Voltage Span H8 LED Status Indicator H9 RTD (with decimal
support) Zero Calibration
I
Ø RTD (with decimal
support) Span Calibration
31
Auxiliary Commands:
Command: Load Parameter Defaults Parameter #: 01 Description Restore all menu parameters to their
default values.
Request Data Field: Ignored. Response Data Field: Ignored.
Command: Perform Process Low Calibration Parameter #: 02 Description: Performs a Low Calibration. The
data field in the request message specifies the process. Make sure the prerequisite for the calibration is satisfied before issuing a calibration command. For instance, the RTD calibration command must only be used when the input sensor type is chosen as RTD or RTD w/ Decimal.
Digital Communications Option
32
Request Data Fields: A 10 character ASCII representation
of a numeric value specifying what to calibrate.
0 - Thermocouple 1 - RTD, Resistive Thermal Device 2 - Linear 3 - RAS, Remote Analog Setpoint
Response Data Field: Ignored. Command: Perform Process High Calibration
Parameter #: 03 Description: Performs a High Calibration. The data
field in the request message specifies the process. Make sure the prerequi­site for the calibration is satisfied before issuing a calibration command For instance, the RTD calibration command must only be used when the input sensor type is chosen as RTD or RTD w/ Decimal.
Request Data Field: A 10 character ASCII representation
of a numeric value specifying what to calibrate.
Digital Communications Option
33
0 - Thermocouple 1 - RTD, Resistive Thermal Device 2 - Linear 3 - RAS, Remote Analog Setpoint
Command: Retrieve Display Parameter #: 05 Description: Retrieves the string currently dis-
played on the slave’s display. The data field in the request message specifies which display and the data field in the response message contains the string.
Request Data Field: A 10 character ASCII representation
of a numeric value specifying which display to retrieve data from.
0 - Lower Display 1 - Upper Display
Response Data Field: The ASCII string. Command: Clear Latched Alarms
Parameter #: 10 Description: Clear all latched alarms. Request Data Field: Ignored. Response Data Field: Ignored.
Digital Communications Option
34
Table 2. Communications Error Codes Returned.
Code Description
0 No error. 1 Framing error. 2 Hardware error. 3 Parity error. 4 Bad character in the TYPE field. 5 Bad message. Message cannot be understood. 6 Bad checksum. The checksum received did not
match the checksum of the message. 7 Bad zone ID. 8 Bad auxiliary command ID. The auxiliary command
is not supported in this controller. 9 Bad parameter ID. The parameter is not supported
in this controller. A Bad data. Bad representation in the data field or
data is out of range. B Attempt to write to a read only parameter. C Cannot write to a parameter because it’s in use.
Digital Communications Option
35
Communications Option Menu
Option “ED” – SPI Protocol
NOTES
For technical assistance, call toll free
1-800-782-6776 (in the U.S.)
or
610-828-2490
(from anywhere in the world),
or
e-mail: techsupport@athenacontrols.com.
Athena Controls, Inc.
5145 Campus Drive
Plymouth Meeting, PA 19462 USA
Toll-free: 800.782.6776
Tel: 610.828.2490
Fax: 610.828.7084
techsupport@athenacontrols.com
athenacontrols.com
900M012U00 REV “C” - 05022005
Loading...