Athena 16 Instruction Manual

SERIES
16
TEMPERATURE/PROCESS CONTROLLER
Instruction Manual
Safety Warning
In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When installing or using this instru­ment, follow all instructions carefully and use approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel.
Do not locate this instrument where it is subject to excessive shock, vibration, dirt, moisture, oil or other liquids. Safe ambient operating temperature range is 32° to 131° F (0° to 55° C).
NOTES ON CE EMC COMPLIANCE
This unit is compliant with the
following standards when properly
installed in a grounded metal panel:
EN55011 (CISPR 11), Class B
ENS0082-1
Introduction
Precautions
Congratulations on your purchase of an Athena®Series 16 Single-Loop Controller. It is designed for ease of use and reliability wherever accurate closed-loop control is required. Your Series 16 has been configured according to your order­ing specifications as either a universal process controller or a dedicated temperature controller. In addition, special func­tions such as a heater break alarm, digital communications, etc., do not require you to make any internal jumper or DIP switch settings.
After following the instructions for installation, simply step through and set your desired parameters using the Series 16’s easy menu system. The instrument may then be auto­matically or manually tuned to your process for optimum setpoint control. A Quick-Start Reference Card is attached to the back of the instruction manual for experienced users of PID controllers. If you still have questions or require any assistance in setting up or operating your controller, please contact your Athena representative or call 1-800-782-6776.
After unpacking, inspect the instrument for any physical damage that may have occurred in shipping. Save all packing materials and report any damage to the carrier immediately.
Table of Contents
Installation
Mounting 1 Wiring 2
Operation
Notes on Outputs 4 Parameter Menu Organization 6 Notes on Alarms 10 Tuning 17
Special Functions
Auto/Manual 22 Remote Setpoint Select 22 Process Variable Retransmission 24 Heater Break Alarm 25 Transducer Excitation 26
Digital Communications 27 Recalibration Procedure 34 Error Codes 34 Warranty/Repair Information 35 Technical Specifications 36 Ordering Codes 39
1
Installation
Figure 1. Recommended Panel Layout for Multiple Controllers
Measurements between centerlines of panel cutouts are minimum recommended.
C
L
C
L
C
L
C
L
2.850" (72.4 mm)
2.150" (54.6 mm)
1.171" (45 mm)
Figure 2. Case Dimensions
Prior to mounting the Series 16 in your panel, make sure that the cutout opening is of the right size, 1.771" x 1.771" (45 mm x 45 mm), and deburred to enable a smooth fit. A minimum of 4" (100 mm) of depth behind the panel is required.
Figure 3. Series 16 Mechanical Components
Bezel
Case Clip
Grips
Rubber Gasket
Customer Panel
2
Sensor Input Connections
Figure 5. Thermocouple Input Wiring
Make sure that you are using the appropriate thermocouple and extension wire. Connect the neg­ative lead (generally colored red in ISA-type thermocouples) to contact #9; connect the positive lead to contact #10. Extension wires must be the same polarity as the thermocouple.
Figure 6. RTD Wiring
The Series 16 accepts input from 2- or 3-wire, 100 ohm platinum resistance tempera­ture detectors (RTDs). Connect 2-wire RTDs to contacts #9 and #10, with a jumper across contacts #8 and #9. Keep leads short and use heavy gauge copper extension wire, if necessary, to minimize lead resistance. For long runs, 3-wire RTDs should be used.
Thermocouple circuit resistance should not exceed 100 ohms for rated accuracy; errors will occur at higher resistance values. If shielded thermocouple wire is used, terminate the shield only at panel ground.
Use wire with a resistance no greater than 10 ohms. An error of 0.2° F will result for each additional 10 ohms of resistance encountered. If shielded RTD wire is used, terminate the shield only at panel ground.
Note: For 2 Wire RTD
Jumper 8 & 9
3
Power Wiring
Figure 7. Process and Linear Input Wiring
Voltage Inputs: Connect the positive voltage input to contact #10; the negative input to contact #8. mV/Current Inputs: Connect the positive current input to contact #10; the negative input to #9.
The Series 16 power supply accepts 100 to 250 Vac and 100 to 330 Vdc line power without any switch settings or polarity considerations. All connections should be made in accor­dance with the National Electrical Code and local regulations, using only NEC Class 1 wiring for all power terminals.
It is advisable, but not necessary, to fuse one leg of the incoming power line, contact #11, with a 2AG, 0.5 amp rated fuse. Be sure that only instrument power input is fused
— not power to the load.
Figure 8. Power Wiring Connection
100 - 250 Vac 50/60 HZ 100 - 330 Vdc (Auto Polarity)
VOLTAGE
CURRENT OR 50 mV
+
4
Output Type Description
B 5A/3A (120/240 Vac) relay, normally
open, used for switching resistive loads. If relays or solenoids are to be driven, select the “T” output. If a “B” output is selected, order snubber network 235Z005U01.
E 0-20 mA
F4-20 mA, full output to load with 500 ohm
impedance max. (suppressed).
S 20 Vdc pulsed output for solid-state relays.
T1 A @ 120/240 Vac , solid-state relay, zero
voltage-switched and optically isolated from drive signal. Only resistive loads to may be controlled directly. Larger loads may be controlled using an external contactor.
Y 5A/3A (120/240 Vac) relay, but normally
closed (output 2 only).
Operation
Athena Series 16 Universal Controller
The Series 16 is a full-function, autotuning PID controller, calibrated and pre-configured for your application require­ments, according to the ordering code specified, either as a temperature or linear process controller. (See page 39 for specifications and ordering code).
Just a few easy steps are required before the instrument can be placed into service. After completing the mounting and wiring procedures as previously instructed, set your individ­ual process parameter values by stepping through the Series 16’s setup menus, using the simple front-panel keys as instructed. Then, initiate the autotuning sequence as shown (or tune manually).
Notes on Outputs
When you ordered your Series 16 controller, a specific output type was specified, designated as either “B”, “E”, “F”, “S”, “T” or “Y”. You also had the option of configuring your controller with either one or two output actions. Generally, output 1 is a heat (reverse-acting) function and output 2 is a cool (direct-acting) function. For best results, follow the recommendations for setting cycle times for the output type supplied with your controller. A brief description of output types follows:
Throughout this manual, instructions that pertain solely to the Series 16 process controller are shown in blue.
5
Operation
Mode Key Used to access Standby, Tune, Run or Manual modes.
Lower Key Used to scroll down through available parameter settings, decrease values or change menu levels (Hold for fast-step progression)
Raise Key Used to scroll up through available parameter settings, increase values or change menu levels (Hold for fast-step progression)
Parameter/Access Key Used to index through parameters or to access Menu Levels
After mounting and wiring your Series 16 controller, you are ready to set the parameter values required of your application. Take a moment to familiarize yourself with the unit’s front panel con­trols and indicators.
Process Value
Displays measured process temperature in °F or °C or process
value in engineering units
Setpoint Value
Displays programmed setpoint temperature in °F or °C or setpoint
value in engineering units
Output 1
LED indication of Heat cycle
(Output 1 action)
Output 2
LED indication of Cool cycle
(Output 2 action)
Alarm 1
LED indication of Alarm1 condition
Alarm 2
LED indication of Alarm 2 condition
Function 1
LED indication of Special Function 1
Function 2
LED indication of Special Function 2
Figure 10. Front Panel Controls and Indicators
6
Operation
Power On
When power is first applied to the Series 16, both displays and all LED indicators are momentarily illuminated. The Process Value (PV) window then displays [ -At- ] or [ -Ap- ] and the Setpoint Value (SV) window displays an initialization code, e.g., [ tf06 ]. The last two digits of this code indicate the software revision supplied with your controller. Please pro­vide this revision number when contacting us regarding your controller. Depending upon whether Setpoint Target Time [ SP.tt ] is enabled, you may also see this symbol: or . This means that the controller is ramping up or down to set­point according to its previously programmed parameters. The default setpoint on initial power up is equal to the process temperature (process value). Before proceeding further, wait until the display has stabilized and then use the Raise or Lower keys to enter or adjust your desired Setpoint Value.
Parameter Menu Organization
Your Series 16 controller has five distinct menu levels. This enables quick access to relevant parameters without the need for scrolling through long menus. Menu “05” is used for initial controller configuration and menus “02” and “03” are used for setting or changing parameters. Menus “00” and “01” are used when the controller is in regular unattended operation and are not used for setting parameters. For safety
and security purposes, we recommend placing the con­troller in menu level “00” or “01” when in regular opera­tion; however, it is not required.
If you wish to “escape” from parameter selection within these menus at any time, simply press the Mode key once. A description of the menu hierarchy and a detailed list­ing of menus and parameters begins on page 15.
7
Operation
Standby Mode
When the controller is placed in Standby Mode, outputs are disabled; however, access is permitted to all menu levels and, unless the controller is at Run menu levels “00” or “01”, operating parameters may still be changed. Use this mode for tuning the controller. To enter Standby Mode, press and hold the Mode key for four seconds until the lower window display flashes [ StbY ]. To exit Standby Mode from Menu Levels “01” to “05”, press and hold the Mode key for four seconds until the lower window display flashes [ tUnE ]. (If the Damping setting in menu “02” is [ OFF ], then [HEAt ] or [ Cool ] will be displayed instead of [ tUnE ]. Press and hold the Mode key for four more seconds until the lower window returns to a steady display of Setpoint Value. (This procedure will not affect tuning). Removing power to the controller will also take the instrument out of Standby Mode.
Accessing Menu Levels
To access menu levels from Standby Mode from menu levels “02” to “05”, press the Parameter/Access key once. From menu levels “00” and “01”, press and hold the Parameter/Access key for approximately 11 seconds until the lower window display alternates between [ Ac.Cd ] and the menu level number last activated.
You cannot enter Standby Mode from menu level “00”. Follow the instructions for changing menu levels to select another level.
8
Operation
Changing or Displaying Menu Levels
To change menu levels, access the menu level display as instructed in the previous paragraph, then use the Raise or Lower key to set the desired menu level number. To display the current menu level setting in menu levels “02” to “05”, from Standby or while adjusting/viewing parameters, press the Parameter/Access key once. For menu levels “00” and “01”, press and hold the Parameter/Access key for approximately 11 seconds.
Because the Series 16’s initial configuration affects other menu levels, it is important to set all required parameters in this menu first before accessing other menu levels.
Operation
Menu Level Descriptions
Menu “05” (Configuration Setup)
This is the menu level used for specifying initial configuration parameters before the controller is placed in Run mode.
After changing the access code to “05” as instructed in the previous paragraph, press the Parameter/Access key to step through the various control parameters. Available para­meters will flash in the lower window display, alternating with the current value for that parameter. To increase or decrease the value, simply press the appropriate Raise or Lower
key, then press the key to step to the next parame-
ter. To exit the menu at any time, press the Mode key.
Note: When programming in menu level “05”, all outputs are disabled; however, any active alarms will remain active until the alarm condition is removed. New alarm conditions will not be recognized.
Menu “04” (Communications and Calibration Setup)
This menu is used to set up the controller for digital communications and for recalibrating the controller. If your Series 16 controller was ordered with the digital communica­tions option, set these parameters next. To access this menu level, follow the instructions previously given.
Menu “03” (Alarm, Timing and Limit Setup)
In this menu, alarms, cycle times, setpoint target time and lim­its are established. After changing the access code to “03”, press the Parameter/Access key to step through the vari­ous parameters. To set or change parameter values, follow the instructions given previously.
Menu “02” (Control)
Gain, Rate and Reset parameters are automatically set during autotuning. However, they can be manually adjusted by the operator. To return the controller to the Run mode, change the menu level access code back to “00” or “01” as previously shown.
Menu “01” (Run — Limited Access Mode)
The only parameter that can be changed at this menu level is the Setpoint Value, using the appropriate Raise or Lower
key. To set or change other parameters, the operator must access another menu level by pressing and holding the Parameter/Access key for 11 seconds.
Menu “00” (Run — Key Lock Mode)
This menu is automatically active when power is first applied. Both display windows are illuminated; however, access is denied to all parameters. To set or change parameters, the operator must access another menu level as instructed pre­viously.
9
Operation
10
Operation
Notes on Alarms
Either [ OUT 1 ] or [OUT 2 ] in menu level “05” (but not both) may be configured as an alarm [ ALr ] if your Series 16 was ordered with a “B”, “S” or “T” type of output module. (With “Y” modules, an alarm may be configured only on [ OUT 2 ]) When one of the two available Outputs is configured as an alarm, the other Output may be used for control .
When the controller is provided with the Dual Alarm option, two independent alarms are automatically enabled for both outputs. DO NOT USE THE [ ALr ] SETTINGS FOR [ OUT 1 ] OR [ OUT 2 ]. Otherwise, follow the regular instructions for configuring the Dual Alarms in menu level “05”.
The Series 16 offers a unique capability that provides for the activation of two software alarms (in addition to the dual alarms) to monitor a total of four possible alarm conditions. To enable these software alarms, set the [ OUT 1 ] and [ OUT 2 ] parameter(s) in menu level “05” to on/off mode [ Ht.O ], [ CL.O ] or [ On.F ]. Set the Setpoint Value to your first alarm point. Switch to menu level “02” and set Spread [ C.Spr ] [ Spr.2 ] to the desired deviation value from the first alarm point. Set [H.HYS] and [C.HYS] to 1. Then switch to menu level “03” and set the desired values for the third and fourth alarm points at [ ALr 1 ] and [ ALr 2 ], respectively. Press the Mode
key to resume operation.
11
Operation
Available Alarm Types [ A1.P.d. ] [ A2.P.d. ]
Selectable at menu level “05”, as either Process [ Pr ] or Deviation [ dE ] and either high or low [ A1.HL ] or [ A2.HL ].
Process Alarm: Activates at preset value independent of setpoint. “High” process alarm activates at and above alarm setting. “Low” process alarm activates at and below alarm setting.
Deviation Alarm: Activates at a preset deviation value from setpoint. “High” or “Low” deviation alarm activates above or below setpoint according to the preset deviation value.
Latching Alarms
The Series 16’s alarms may also be configured as latching alarms by selecting “LAt” in the [ A1.O.P.] or [ A2.O.P.] para­meter selection at menu level “05”.
When a latching alarm has been activated and the alarm condition has been removed, the Mode key must be pressed to unlatch the alarm.
12
KEY
LOCK
SETPOINT
MENU 0 MENU 1 MENU 2 MENU 3 MENU 4 MENU 5
Figure 11. Series 16 Controller Menu Hierarchy
With heater break option, [id.no] changes to [Ht.rd]; [baud] changes to [Ht.SP] in menu level “04”.
= temperature
controller only
= process
controller only
= temperature and
process controller
13
Parameter Descriptions
Series 16 Temperature/Process Controller
Menu “05” Display Parameter Selection Code
SnSr Sensor type Thermocouple:
K c.A JJ Nn Rr Tt SS Platinel II PLII RTD P RTD (decimal range) d
OUt1 Output 1 action Heat PID Ht.P
Heat On/Off Ht.O Alarm ALr
OUt2 Output 2 action Cool PID CL.P
Cool On/Off CL.O Alarm ALr
SN.00 Input Zero Level (0-20mA) U.Su (Unsuppressed)
(4-20mA) Su (Suppressed) Dec.P Decimal Point 999, 99.9, 9.99 FILt Digital Filtering 0.1, 1, 10 OUt1 Output 1 action PID Pid
On/Off On.F
Alarm ALr OUt2 Output 2 action PID Pid
On/Off ON.F
Alarm ALr
The Digital Filtering setting [ FILt ] on the Series 16 process con­troller allows the oper­ator to compensate for noise which may cause the last digits of the PV display to become unstable. Sampling rate is not affected. The set­tings are time con­stants, in seconds, with
0.1 equivalent to “no filtering.”
14
Parameter Descriptions
With the Heater Break Alarm option, [ Id.no ] changes to Heater Current Reading [ Ht.rd ] (indication only) and [ bAUd ] changes to Heater Break Alarm Setpoint [ Ht.SP ] (indication only, either 00-30 A or 00-60 A).
CoL.t* Cooling type Water H2o (non-linear output)
Normal nor (linear output) A1.H.L. Alarm 1 select Enable Lo/HI A1.P.d. Alarm 1 type Process/Deviation Pr/dE A1.O.P. Alarm 1 output Off/Normal/Latching OFF/nor/LAt A2.H.L. Alarm 2 select Enable Lo/HI A2.P.d. Alarm 2 type Process/Deviation Pr/dE A2.O.P. Alarm 2 output Off/Normal/Latching OFF/nor/LAt Unlt Measurement units °F or °C F/C
* For water-cooled extruders, select H2o.
Menu “04” Display Parameter Allowable Values
Id.no Device ID number 00 to 99
(remote communications)
bAUd Baud, parity and See chart below
data bit selection CAL.L Calibration low Preset at factory CAL.H Calibration high Preset at factory
Available Communications Settings
Display Description
Baud Rate Parity Data Bits Stop Bits
3.o.7 300 odd 7 2
6.o.7 600 odd 7 2
12.o.7 1200 odd 7 2
24.o.7 2400 odd 7 2
3.n.8 300 none 8 1
6.n.8 600 none 8 1
12.n.8 1200 none 8 1
24.n.8 2400 none 8 1
15
Parameter Descriptions
Menu “03” Display Parameter Allowable Values
ALr1 Alarm 1 preset Dependent on sensor range ALr2 Alarm 2 preset Dependent on sensor range
(if ordered) CY.t1 Cycle time output 1 00 to 120 seconds CY.t2 Cycle time output 2 00 to 120 seconds SP.tt Setpoint target time Off/1 to 100 minutes
(ramp-to-setpoint) L.SP.L Lower setpoint limit Dependent on sensor range U.SP.L Upper setpoint limit Dependent on sensor range
L.SCL Low scale setting -1999 to 9999 H.SCL High scale setting -1999 to 9999
Output Type Recommended Setting (seconds)
B (5A/3A) 15 to 120 E (0-20 mA) 00 F (4-20 mA) MUST be set to 00 S (pulsed 20 Vdc) 00 to 120 T (S.S. relay) 15 to 120 Y (5A/3A) N.C. 15 to 120 (Output 2 only)
Setting output cycle time to “00” initiates a 200 ms timebase. A cycle time setting is required for smooth proportional action. Too long a setting will cause proportional ripple; too short will decrease relay contac­tor life.
When changing thermocouple types, be sure to check/adjust upper and lower set­point limit values.
Notes on Setpoint Target Time: The [ SP.tt ] parameter allows the operator to enter a time delay for the
process to reach setpoint temperature (ramp to setpoint), from disabled [ OFF ] or 1 to 100 minutes. When enabled, the ramp sequence starts on power-up. The ramp-to-setpoint feature will also be initiated whenever a new setpoint target time is entered AND the Setpoint Value is 5° F or more from the current process temperature. In operation, the controller’s lower window display will flash or to indicate that it is “ramping” up or down to setpoint. The Setpoint Value cannot be changed during this procedure. After it is finished, the operator can adjust the setpoint temperature to the desired value.
While in ramp startup, the ramp-to-setpoint mode can be aborted and the controller returned to regular operation by pressing the Parameter/Access key until parameters are displayed and then pressing the Mode key once.
Note: Shorter cycle times may be used when driving heater loads directly.
Figure 12. Typical Lag Processes
Immersion Heater
a. Single Lag
Strip Heater
Strip Heater
Tank Wall = Thermal Resistance
Thermal Resistance
Thermal Capacity
Thermocouple
in Well
b. Two Lag
c. Three Lag
a
1
. Single Lag with
Dead Time
Lag
T/C2
T/C1
T/C
Flow
Flow
Flow
Parameter Descriptions
Menu “02” Display Parameter Allowable Values
Gn.o1 Gain Output 1 00 to 400
(PID heat gain)
Gr.o2 Gain Ratio Output 2 0.0 to 2.0
(PID cool gain ratio) H.HYS Heat Hysteresis 01 to 100° C.HYS Cool Hysteresis 01 to 100°
HYS1 Output 1 Hysteresis 1 to 100 units HYS2 Output 2 Hysteresis 1 to 100 units SPr.2 Spread Adjustment, Output 2 0 to 100 units
C.SPr Cool Spread 0 to 100° rAtE PID rate 00 to 900 seconds rSEt PID reset 00 to 3600 seconds dPnG Damping (see notes) Lo, nL, Hi, Off
Setting Rate (Derivative) or Reset (Integral) to [ 00 ] disables that aspect of PID control. The ratio for non-zero settings of rate-to-reset is limited to a minimum of 1:4, i.e., Reset value cannot be set any lower than four times Rate.
The parameters of Heat Hysteresis, Cool Hysteresis and Cool Spread are only avail­able when Output 1 and/or Output 2 are set to on/off mode [Ht.O] or [CL.O]. They replace Gain Output 1 and Gain Ratio Output 2, respectively.
Notes on Damping: The damping parameter is an autotune feature that enables more precise control of setpoint overshoot during recovery from process upsets in which thermal or transfer lag is a factor. See Figure 12. Use the correct setting prior to autotuning to compensate for power and load/sensor coupling characteristics.
Lo = Fast recovery with slight overshoot. For single-lag processes.
Ex. Adequate power and excellent load/sensor coupling.
nL = Normal recovery with no overshoot. For two-lag processes.
Ex. Properly sized heaters or components and good load/sensor coupling.
Hi = Slow recovery with no overshoot. For three-lag processes.
Ex. Overpowered with multiple lags. Poor load/sensor coupling.
Off = Autotune disabled; manual output control.
(This value may exceed 400 during autotuning.)
16
17
Tuning Procedures
Introduction
The Series 16 is an “on demand” autotuning controller that automatically sets PID parameter values (Proportional Band, Reset and Rate) before the process reaches setpoint. A damp­ing setting (menu level “02”) MUST be selected for autotuning to take place. (see Notes on Damping, page 19). The con­troller may also be tuned manually (see page 20).
Autotuning the Series 16 Temperature Controller
1) With the power off and the process at ambient, apply
power and immediately put the controller in Standby mode by holding the key for four seconds until [ StbY ] flashes in the lower display window.
2) Enter the desired Setpoint Value using the appropriate
Raise or Lower key. [ StbY ] will continue to flash.
3) If controller is in menu level “00” or “01”, hold the
Parameter/ Access key for 11 seconds until [ Ac.Cd ] appears. Then change to menu level “05”. Otherwise, press the key once and use the key to select menu level “05”.
4) Press the Parameter/Access key twice until [ SnSr ] is
displayed to make sure that the proper sensor has been selected. Then set the controller’s heating mode or alarm functions by pressing the Parameter/Access key again until [ OUt1 ] is displayed. (If you scroll past it, just continue scrolling until the parameter menu repeats.) Using the appropriate Raise or Lower key, select the one of the following settings according to the require­ments of your process. Note: For autotuning, at least one
output MUST be set to PID mode.
Mode Output 1 (Heat) Setting Output 2 (Cool) Setting PID [ Ht.P ] [ CL.P ] On/Off [ Ht.O ] [ CL.O ] Alarm [ ALr ] [ ALr ]
Press the Parameter/Access key again to step to out­put 2 [ OUt2 ]. Repeat the selection process for cooling mode or alarm. (If only one output is PID, set the other
output to either On/Off or Alarm.)
For best results in tuning the temperature controller, the setpoint value should be at least 100° F above or below ambient temperature.
While some processes other than heat or cool applications may respond successfully to autotuning procedures, the controller must be manually tuned for most non-temperature processes.
18
Tuning Procedures
5) Press the Parameter/Access key again to display the
Cooling Type parameter [ CoL.t ], and select either Normal/Linear output [ nor ] or Water-Cooled/Non-Linear output [ H2o ].
6) Exit menu level “05” by pressing the Mode key once.
The lower window will flash [StbY]. Now press the Parameter/Access key once. The lower window will display [Ac.Cd ] and [ 05 ]. Press the Lower key twice to select menu level “03”.
7) Press the Parameter/Access key and select Cycle Time
for Output 1 [ CY.t1 ] and Cycle Time for Output 2 [ CY.t2 ]. For Control Output type B, T or Y, enter “15”. For Control Output type E, F or S, enter “00”.
8) Press the Parameter/Access key until Setpoint Target Time
[ SP.tt ] is displayed. Select [ OFF ].
9) Press the Mode key once. The lower window will again
flash [StbY]. Press the Parameter/Access key once and the lower window will display [Ac.Cd ] and [ 03 ]. Press the Lower key once to select menu level “02”.
10) Press the Parameter/Access key and scroll through
the displayed parameters. If Gain Ratio [ Gr.o2 ] is dis­played, set it to [ 1.0 ]. Otherwise, continue scrolling until [dPnG ] appears. Set Damping initially to Normal [ nL ]. (This setting may have to be changed later).
11) Press and hold the Mode key until [ tUnE ] flashes
in the lower display window. The controller is now autotun­ing. When it stops flashing, the autotuning procedure is completed and the controller is ready for your process. As a security measure, you may wish to place the controller in Key Lock “00” or Limited Access “01” Run mode by changing menu levels as instructed previously.
Note: Re-tune controller only from ambient temperature.
Autotuning will not function when process is at setpoint.
19
Before autotuning can take place, you must select a damping setting. If the damping parameter does not appear on the menu, you have not selected a PID option for outputs 1 or 2. Refer back to step (4) and select the proper setting(s).
During autotuning, the process temperature will gradually cycle from ambient to setpoint. When autotuning is complete, the [ tUnE ] display will stop flashing and the Gain, Rate and Reset numbers "learned" will be kept in memory for subsequent startups.
Tuning Procedures
Stops flashing
tUnE
Initiate
Auto-tune
from Stby ambient temperature
(Temp)
(Time)
350°F
SV
Figure 13. Typical
“Autotune”
Temperature Profile.
20
If overcooling exists on heat/cool processes after autotuning, decrease Gain Ratio [ Gr.o2 ] in steps of 0.1 until oscillation is minimal. If cooling is sluggish, increase the value in steps of 0.1 until optimum results are achieved.
Gain ratio [ Gr.o2 ] is the cooling gain expressed as a factor of the heating gain.
Ex. [ Gn.01 ] = 100
Cooling Gain = 50 [ Gr.o2 ] = .5
Tuning Procedures
Manual Tuning Procedure - Temperature Controller (Zeigler-Nichols PID Method)
This tuning method may be used if the spread between ambi­ent temperature and process operating temperature is small. For best results, the use of a recording device is suggested when tuning with this method.
1) Disable any cooling device used.
2) Apply power and place the controller in Standby by
pressing and holding the Mode key for four seconds.
3) Using Raise or Lower key, adjust setpoint to
desired value.
4) Access menu level “02” following instructions given
previously.
5) Using the Parameter/Access key, index to Heat Gain
[ Gn.o1 ]. Select [ 01 ].
6) Index to Gain Ratio [ Gr.o2 ] and select [ 1.0 ].
7) Index to Rate [ rAtE ] and select [ 00 ].
8) Index to Reset [ rSEt ] and select [ 00 ]. Note: In order to
set Reset to [ 00 ] , Rate must first be set to [ 00 ].
9) Change to menu level “03”.
10) Index to Cycle Time 1 [ CY.t1 ] and select the timebase,
in seconds, appropriate to the device being controlled.
21
Tuning Procedures
11) Repeat for Cycle Time 2 [ CY.t2 ].
12) Change to menu level “05”.
13) Set Cooling Type [ CoL.t ] to [ nor ].
14) Press the Mode key once. Setpoint Value will be
displayed. The recording device should now be tracking
process temperature.
15) Double the Gain [ Gn.o1 ] until a small, sustained oscilla-
tion is visible on the recording device’s trace.
16) Measure the period of one cycle of oscillation (“T” on the
diagram below).
17) Divide the period of oscillation (T) by eight (8). The
resulting number is the correct Rate time [ rAtE ] in sec-
onds. Multiply this number by four. This is the correct
Reset time [ rSEt ] in seconds.
18) Multiply the gain (from step #15) by 0.6 and enter this
number as Gain [ Gn.o1 ].
19) Enable the cooling device. If overcooling exists, decrease
the Gain Ratio [ Gr.o2 ] in steps of 0.1 until temperature
oscillation stops. If cooling is sluggish, increase the Gain
Ratio in steps of 0.1 until optimum results are achieved.
22
Tuning Procedures
Manual Tuning Procedure - Process
Controller (Zeigler-Nichols PID Method)
A chart recorder to monitor the process variable is required. The controller must be properly scaled and filtering set as instructed previously.
1) Apply power and place the controller in Standby by holding
the Mode key for four seconds.
2) Adjust the setpoint to the desired value.
3) Access menu level “05” and select one output: [ OUt 1 ]
for reverse-acting control or [ OUt 2 ] for direct-acting control. Set the active output to PID [ Pid ] and the unused output to Alarm [ ALr ] or On/Off [ On.F ].
4) Access menu level “02” and set [ Gn.01 ] to 1.0; [ Gr.o2 ] to
1.0; and [ rAtE ] and [ rSEt ] to “00”.
5) Press the Mode key for four seconds until display
flashes [ tUnE ]. Press the Mode key for another four sec­onds and the process will run in closed loop mode.
6) While monitoring the chart, increase Gain [ Gn.o1 ] by dou-
bling the gain number until the process variable becomes unstable. Then decrease Gain until the process oscillations are sustained, neither increasing nor decreasing in ampli­tude as a result of momentary setpoint change.
7) Multiply the Gain from Step (6) by 0.6.
8) Measure the period of one complete cycle of oscillation,
“T”, in seconds.
Calculate and enter these numbers:
Rate [ rAtE ] = T/8 Reset [ rSEt ] = T/2 Gain [ Gn.01 ] = Gain from
Step (6)
On noisy processes, where Rate cannot be used:
Gain [ Gn.01 ] = from Step
(6) x 0.45
Reset [ rSEt ] = T/1.2
Auto/Manual Operation (Standard)
To put the controller in manual mode, set the damping [dPnG] parameter in menu level “02” to [ OFF ]. Press and hold the Mode key for four seconds until the lower display window flashes [ StbY ]. Hold down the Mode key for another four sec­onds to initiate manual operation. The lower display window will flash percentage of output power, from 100 to
-100, alternating with the output controlled (temperature controllers will flash [ HEAt ] or [ CooL], process controllers will flash [ OUt1 ] or [OUt2 ].) To take the controller out of manual mode, press and hold Mode key to four seconds.
Note: The Series 16 controller can only be ordered with one
of
the following Special Functions installed per instrument.
Remote Setpoint Select
If your Series 16 controller was ordered with this option, you may select either of two setpoints for your process. The sec­ond setpoint can be enabled only by an external switch or sig­nal, according to your ordering specifications. The "F2" LED on the front panel will illuminate when a second setpoint is select­ed. If you do not know how your Series 16 was configured, refer to the ordering code and description on page 39.
Special Functions
In manual control mode, error conditions such as A/D errors and open or reversed sensors will be ignored.
23
Special Functions
Option Part # Description
40 External switch wired to terminals 6 and 7
Switch Open: Normal operation, first setpoint enabled Switch Closed: Second setpoint enabled Setpoint Adjustments: Made from front panel
41 External switch wired to terminals 6 and 7
Switch Closed: Normal operation, first setpoint enabled Switch Open: Second setpoint enabled Setpoint Adjustments: Made from front panel
42 0-5 Vdc signal at pins 6 and 7
0 Vdc: First setpoint enabled 5 Vdc: Second setpoint enabled Setpoint Adjustments: Made from front panel
Maximum Input Impedance: 400 ohms @ +5 Vdc , 5 mA
Figure 14. Wiring Diagram for Remote
Setpoint Select Option
24
Special Functions
Process Variable Retransmission
If your Series 16 controller was ordered with this option, you may retransmit the signal representing the process variable for analysis or storage to an external device that accepts ana­log input, such as a chart recorder, datalogger, or process control computer. These outputs are:
Suppressed: 1-5 Vdc/4-20 mAdc
Unsuppressed: 0-5 Vdc/0-20 mAdc
Process Variable Retransmission Specifications
I
out
(current output) = 0-20 mA/4-20 mA
Voltage Headroom = 8 Vdc (standard) 18 Vdc
(for multiple recording devices)
V
out
(voltage output) = 0-5Vdc/1-5 Vdc
I
out
Max = 20 mA
These output values are linear with and dependent upon the sensor being used, i.e., the lowest value of the sensor’s output range corre­sponds to zero or low for the output function.
For voltage output, a jumper must be installed between terminals 13 and 14.
Figure 15. Wiring Diagram for Process
Variable Retransmission
25
The Heater Break Alarm option is not available on controllers with an “F” type output.
With the Heater Break Alarm option, cycle time is limited to greater than 2 seconds.
Special Functions
Heater Break Alarm (Series 16 Temperature Controller)
The heater break alarm option detects failures in the load or power handler and provides an alarm output. It uses an exter­nal current transformer to monitor the load current. If the load current falls below a set current value, the alarm output is activated.
With this option, a heater current reading [ Ht.rd ] from a current transformer is displayed at menu level “04”, along with the preset Heater Current Alarm Setpoint Value [ Ht.SP ], either 00-30 A or 00-60 A.
Current Transformer Specifications
.29 Dia. Opening
INDICATING RANGE: 2 thru 100 A MAX. CONT. CURRENT: 100 A MAX. TRANSIENT CURRENT: 150 A for 5 sec. WORKING CLASS: 600 • FREQUENCY: 50-60 Hz WEIGHT: .5 Oz (14 grams) LEAD WIRE: #22 AWG UL Style 1213 CASE COLOR: Black • CASE MATERIAL: Thermoplastic
Figure 16. Current Transformer Supplied with Heater Break Alarm Option, Part # 580E023UOI
Figure 17. Wiring Diagram for Heater Break Alarm
26
Figure 18. Wire Diagram for 2-Wire Sensor Input with
Transducer Excitation Option
Special Functions
Transducer Excitation
The transducer excitation voltage option is used to produce a constant dc voltage of 10, 12 or 15 Vdc out to an external device, eliminating the need for an additional external power supply. Refer to the ordering code if you do not know which voltage output was specified.
Option Ordering Code Voltage Output
50 10 V 51 12 V 52 15 V 53 5 V
Maximum Current = 22 mA
27
Two communication options are available for the Series 16 which allow interfacing to remote devices utilizing the most common industry standards, RS232 and RS485.
WARNING
Signal ground only. Grounding to frame may damage the controller and void warranty.
Digital Communications
RS232
This method allows bidirectional data transfer via a three­conductor cable consisting of signal ground, receive input and transmit output. It is recommended for communication distances less than fifty feet between the computer terminal and the instrument. Note: Multiple instruments cannot be connected to the same port.
The RS232 port is optically isolated to eliminate ground loop problems. Typically, “Data Out” of the computer/terminal connects to the “RCV” terminal. “Data In” connects to the “XMT” terminal. If shielded cable is used, it should be connected to the frame ground at one end only. Signal ground is to be connected at appropriate ground terminals (refer to wiring diagram, page 28).
RS485
The RS485 multipoint capability allows up to 32 controllers to be connected together in a half-duplex network or up to 100 controllers with an appropriate communications repeater. This method allows bidirectional data transfer over a shielded twisted pair cable. The twisted pair cable is a transmission line; therefore, terminating resistors are required at the most distant ends of the line to minimize reflections (typically 60 ohms from each line to signal ground). The RS485 circuit is fully optically isolated, eliminating ground loop problems. Parallel drops from the transmission lines should be kept as
28
Digital Communications
short as possible; however, the line may be daisy-chained at each controller. The polarity of the line is important and each device will specify an “A” (+) and “B” (-) connection.
Note: Call factory for a recommended RS485 converter.
Figure 19. Wiring
diagram for digital communications.
*One PC to one controller
only
29
Digital Communications
Table 1. Communications Parameter List (Temperature Controller)
Parameter No. Description Display Minimum Maximum
00 Process Value nnnn Sensor Dependent 01 Setpoint nnnn Low Limit High Limit 02 Access Code Ac.Cd 00 05 03 Gain Output 1 Gn.o1 00 400 04 Gain Ratio 2 Gr.o2 0.0 2.0 05 Rate rAtE 00 900 06 Reset rSEt 00 3600 07 Heat Hysteresis H.HYS 01 100 08 Cool Hysteresis C.HYS 01 100 09 Cool Spread C.SPr 00 100 10 Damping dPnG 00 Low/Normal/High 11 Alarm 1 ALr1 Range Dependent 12 Alarm 2 ALr2 Range Dependent 13 Cycle Time 1 CY.t1 00 120 14 Cycle Time 2 CY.t2 00 120 15 Setpoint Target Time Sp.tt 00 (OFF) 100 16 Low Setpoint Limit L.SP.L Sensor Dependent 17 High Setpoint Limit U.SP.L Sensor Dependent 18 Controller ID Id.no 00 99 19 Baud Rate bAUd 300 2400
Table 2. Communications Parameter List (Process Controller)
Parameter No. Description Display Minimum Maximum
00 Process Value nnnn Low Scale High Scale 01 Setpoint nnnn Low Scale High Scale 02 Access Code Ac.Cd 00 05 03 Gain Output 1 Gn.o1 00 400 04 Gain Ratio 2 Gr.o2 0.0 2.0 05 Rate rAtE 00 900 06 Reset rSEt 00 3600 07 Hysteresis 1 HYS.1 01 100 08 Hysteresis 2 HYS.2 01 100 09 Spread 2 SPr.2 00 100 10 Damping dPnG 00 Low/Normal/High 11 Alarm 1 ALr1 Low Scale High Scale 12 Alarm 2 ALr2 Low Scale High Scale 13 Cycle Time 1 CY.t1 00 120 14 Cycle Time 2 CY.t2 00 120 15 Setpoint Target Time Sp.tt 00 (OFF) 100 16 Low Scale L.SCL -1999 9999 17 High Scale H.SCL -1999 9999 18 Controller ID Id.no 00 99 19 Baud Rate bAUd 300 2400
Table 3. Serial Communications Data Format
Baud Baud Parity Data Stop Code Rate Bits Bits 0 300 Odd 7 2 1 600 Odd 7 2 2 1200 Odd 7 2 3 2400 Odd 7 2 4 300 None 8 1 5 600 None 8 1 6 1200 None 8 1 7 2400 None 8 1
30
Digital Communications
Interface Examples
This section describes the protocol for communication between an Series 16 controller and either a video display ter­minal or computer ( referred to below as “the host”). Message strings may be of two types — commands to con­troller or responses from controller.
General Comments
One host and multiple controllers may be interconnected on a single bus. The host may send commands to any controller and may receive responses from any controller. Each controller on the bus is assigned an identification code between 00 and 99. No two controllers on a given bus may have the same identification code. Controllers are not capable of communicating with other controllers.
Every valid message begins with a pound-sign (#) character.
Every valid message ends with a carriage-return (<CR>) character.
A valid message is composed of: Start Message, Controller ID Code, Command, Parameter and Data.
Every response begins with a line-feed (<LF>) character and ends with a carriage-return, line-feed pair (<CRLF>).
#[controller id] [command] [parameter number]<new value><units> [CR]
Start of
message
End of
message
Up to TWO
Numeric
Characters
00 to 99
Up to TWO
Numeric
Characters
00 to 99
Up to SIX
Characters
ONE Leading
Sign
‘-’,‘+’ or
Space and
FOUR
Numeric
Characters
with decimal
for decimal
parameters
OPTIONAL
OPTIONAL
ONE
Character
Upper case
or Lower
case R Read MModify EEnter
ONE Character F Deg F
C Deg C UPROCESS
SENSOR None for default Temperature units or NON­THERMAL parameters
N ON
(Select)
F OFF
(Deselect)
?STATUS
0 Standby 1 Autotune 2 Manual 3 Ramp 9Version
(Status Only)
SPECIAL
COMMANDS
31
Digital Communications
Figure 20. General Communications Message Format
Caution:
Modifying parameter #19 (Baud Rate) by host may cause
loss of data link.
Example: For Standby “On”, type #01N0[CR].
32
Digital Communications
Figure 21. Sample Communications Commands
READ MESSAGE TO CONTROLLER READ RESPONSE FROM CONTROLLER
MODIFY COMMAND TO CONTROLLER MODIFY RESPONSE FROM CONTROLLER
ENTER COMMAND TO CONTROLLER ENTER RESPONSE FROM CONTROLLER
‘#01R00<CR>’‘
<LF>
#01R00 = 0120F<CR><LF>’
Controller Id
Parameter Number
End of Message
Read
Command
Start of Message
‘#01M01 0200F<CR>’
Controller Id
Parameter Number
Units
Value read from controller
Units
End of
message
Start of Message
New Value
‘space’ for
Positive
Modify Command
‘#01E01 0200F<CR>’
Controller Id
Parameter Number
Units
End of
message
Start of Message
New Value
‘space’ for
Positive
Enter Command
‘<LF>#01M00 = 0200F<CR><LF>’
Modified Value
Units
‘<LF>#01E00 = 0200F<CR><LF>’
Entered Value
Units
SAMPLE: READ, MODIFY, ENTER COMMANDS
STANDBY ‘ON’ COMMAND TO CONTROLLER STANDBY RESPONSE FROM CONTROLLER
STANDBY ‘OFF’ COMMAND TO CONTROLLER STANDBY RESPONSE FROM CONTROLLER
STANDBY ‘?’ COMMAND TO CONTROLLER STANDBY RESPONSE FROM CONTROLLER
‘#01N0<CR
>
‘<LF>#01N0<CR><LF>’
Controller Id
STANDBY
End of Message
ON (Select)
Command
Start of Message
‘#01F0<CR
>
Controller Id
STANDBY
End of Message
Command Executed
‘<LF>#01F0<CR><LF>’
Command Executed
‘<LF>#01F0<CR><LF>’
Standby STATUS is ‘off’
Standby STATUS is ‘on’
OFF (Deselect)
Command
Start of Message
‘#01?0<CR
>
Controller Id
STANDBY
End of Message
Status REQUEST
Command
Start of Message
N
Figure 22. Requesting a Parameter from a Controller
33
Caution:
Wherever possible, avoid using the “Enter” command and use “Modify” or “Read” instead. The “Enter” command makes permanent changes to the NOVRAM in the Series 16’s microprocessor, and after accepting a maximum capacity of 100,000 “Enter” statements, it will have to be returned to the factory and replaced.
Communications Notes
1. The controller will respond with <LF>ERROR<CR><LF>
for messages containing invalid/incorrect commands, parameter number or data (with decimal, if needed).
2. Process Value is a read-only parameter; therefore, a mod-
ify or enter command for Process Value will result in a <LF>ERROR<CR><LF> response.
3. For modify or enter command: if the new value is out of
the parameter’s range, the controller will default to the highest or lowest allowable parameter value.
4. Parameters with decimal data must contain a decimal
character in the data portion of the message.
5. Ramp “on” command (Setpoint Target Time) will not be
executed if ramp time is set to zero or absolute deviation between Setpoint and Process Value is less than or greater than 5 temperature or process units.
6. Autotune, manual and ramp commands are mutually
exclusive, i.e., selecting manual while autotune is enabled will abort the autotune mode.
7. If the controller is in Standby mode, selecting autotune,
manual or ramp will de-select Standby.
8. Setpoint should not be modified while the controller is in
autotune or ramp mode.
9. The Setpoint Value enter command should not be execut-
ed while the controller is in manual mode.
34
Error Codes
Display Problem Action
[ Err.H ] Open sensor Check sensor and wiring
Check type of sensor Recalibrate
[ Err.L ] Reversed sensor Check sensor and wiring
Check type of sensor Recalibrate
[ Err.O ] A/D error Return to factory
[ Err.J ] A/D error Return to factory
- - - - Display out-of-range Sensor over- or under-range
Recalibration
Your Series 16 has been calibrated at the factory, and need not be adjusted during the life of the controller unless sensor type is changed from thermocouple to RTD, or vice versa. In the event that recalibration is warranted, follow these proce­dures.
1) Access menu level “05” as previously instructed and
select the sensor type.
2) Use a calibrator with a range appropriate for the unit to be
calibrated and set the range, and a low or zero value.
3) Access menu level “04” and then the Parameter/Access
key until [ CAL.L ] is displayed. Then, press the Raise
or Lower key until the number in the controller’s upper (PV) display window matches the indicated value of the calibration instrument.
4) Enter a value on the calibration instrument corresponding
with the high-end value of the sensor range (span).
5) Again, in menu level “04”, press the Parameter/Access
key until [ CAL.H ] is displayed. Then, press the Raise
or Lower key until the number in the controller’s upper (PV) display window matches the indicated value of the calibration instrument.
6) Repeat steps 3 through 5 until all readings agree.
7) Return the controller to regular operation by pressing the
Mode key.
Only qualified individuals utilizing the appropriate calibration equip­ment should attempt recalibration of the controller. For assistance, contact your Athena repre­sentative or call 1-800-782-6776.
35
Warranty/Repair Information
Two-Year Limited Warranty
Other than those expressly stated herein, THERE ARE
NO OTHER WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AND SPECIFICALLY EXCLUDED BUT NOT BY WAY OF LIMITATION, ARE THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY.
IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE RETURN OF THE AMOUNT OF THE PURCHASE PRICE PAID BY THE PURCHASER AND UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE PRICE STATED FOR THE EQUIPMENT IS A CONSIDERATION IN LIMITING SELLER’S LIABILITY. NO ACTION, REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS OF THIS AGREEMENT MAY BE BROUGHT BY PURCHASER MORE THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.
SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND BUYER’S REMEDY IS LIMITED TO EITHER (i) REPAIR OR REPLACEMENT OF THE DEFECTIVE PART OR PRODUCT, OR AT SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND REFUND OF THE PURCHASE PRICE, AND SUCH REMEDY SHALL BE BUYER’S ENTIRE AND EXCLUSIVE REMEDY.
Unit Repairs
It is recommended that units requiring service be returned to an authorized service center. Before a controller is returned for service, please consult the service center nearest you. In many cases, the problem can be cleared up over the tele­phone. When the unit needs to be returned, the service center will ask for a detailed explanation of problems encountered and a Purchase Order to cover any charge. This information should also be put in the box with the unit. This should expedite return of the unit to you.
This document is based on information available at the time of its publication. While efforts have been made to render accuracy to its content, the information contained herein does not cover all details or variations in hardware, nor does it provide for every possible contingency in connection with installation and maintenance. Features may be described herein which are not present in all hardware. Athena Controls assumes no obligation of notice to holders of this document with respect to changes subsequently made.
Proprietary information of Athena Controls, Inc. is furnished for customer use only. No other use is authorized without the written permission of Athena Controls, Inc.
36
Technical Specifications
Performance
Accuracy ±0.2% of full scale, ± one digit Setpoint Accuracy 1 degree/0.1 degree Temperature Stability 5 µV/°C max; 3 µV/°C typical TC Cold End Tracking 0.05° C/°C ambient Noise Rejection Common mode >100 dB
Series Mode >70 dB
Process Sampling Rate 10 Hz (100 ms)
Inputs
Thermocouple K, J, N, R, T, S,
Maximum lead resistance 100 ohms for rated accuracy
RTD Platinum 2- and 3-wire, 100 ohms at
0° C, DIN curve standard (0.00385)
Linear 0-50 mV/10-50 mV, 0-5 V/1-5 V
0-20 mA/4-20 mA
Input Impedances
0-50 mV/10-50 mV: 1 K ohm ± 1% 0-5/1-5 V: 100 K ohms ± 1% 0-20 mA/4-20 mA: 2.5 ohms ± 1% 0-10 V/2-10 V: 200 K ohms
37
Technical Specifications
Outputs
#1 Reverse acting (heating or alarm) #2 Direct acting (cooling or alarm) B Relay, 5 A @ 120 Vac resistive
3 A @ 240 Vac E 0-20 mAdc F 4-20 mAdc, 500 ohms max. S 20 Vdc pulsed T Solid-state relay, 120/240 Vac,
zero voltage-switched,
1 A continuous, 10 A surge @ 25° C Y (Output 2 only) N.C. Relay, 5 A @ 120 Vac resistive
3 A @ 240 Vac
Alarms
Electromechanical relay, 5 A @ 120 Vac,
3 A @ 240 Vac (Output 1 OR 2 only)
Dual-Alarm option: Two solid-state
relays, 120/240 Vac, zero voltage-
switched, 1 A continuous, 10 A surge
@ 25°C
Control Characteristics
Setpoint Limits Limited to configured range Alarms Adjustable for high/low; selectable
process or deviation Rate 0 to 900 seconds Reset 0 to 3600 seconds Cycle Time 0.2 (zero setting) to 120 seconds
38
Technical Specifications
Gain 0 to 400 Gain Ratio 0 to 2.0 (in 0.1 increments) Control Hysteresis 1 to 100 units (on/off configuration) Cool Spread, Output 2 0 to 100° F/C (above setpoint) (Temperature Controller) Spread 2, Output 2 0 to 100 units (above setpoint) (Process Controller) Damping Selectable (low, normal, high, off) Setpoint Target Time 0 (off) to 100 minutes (Ramp-to-Setpoint) Autotune Operator-initiated from front panel Manual Operator-initiated from front panel
General
Line Voltage 115 to 230 V ±10%, 50-60 Hz
115 to 300 Vdc ±10% (Auto-Polarity) Display Dual, 4-digit 0.36" (9.2 mm) LED dis­play
Process Value: Orange
Setpoint Value/Menu: Green Power Consumption Less than 6 VA (@ 120/240 Vac) Panel Cutout 1.771" x 1.771" (45 mm x 45 mm) Depth Behind Panel 3.937" (100 mm) Front Panel Rating NEMA 4X Operating Temperature 32 to 131° F (0 to 55° C) Humidity Conditions 90% R.H. max., non-condensing Parameter Retention Solid-state, non-volatile memory Connections Input and output via barrier strip
with locking terminals Contacts Twin bifurcated
39
Ordering Codes
Output 1
Code
0 = None B= Relay F = 4-20 mA S = Pulsed 20 Vdc T= S.S. Relay E = 0-20 mA
Output 2
Code
0 = None B = Relay F = 4-20 mA S = Pulsed 20
Vdc T= S.S. Relay E = 0-20 mA Y= N.C.
Mechanical
Relay
Contacts
Output #2
0nly
Options
Standard Options 00 = None
Dual Alarms
10 = S.S. Relay 20 = Floating Transistor
Open Collector Switch 21 = 24 Vdc drive 22 = S.S. Relay - N.C.
Communications
30 = RS-232 31 = RS-485
Remote Setpoint Select (w/ alarm)
40 = Switch Close 41 = Switch Open 42 = 5 volt Input
Transducer Excitation
50 = 10 Vdc 51 = 12 Vdc 52 = 15 Vdc
Process Variable Retransmit Signal
60 = 4-20 mA 61 = 1-5 Vdc 62 = 0-20 mA 63 = 0-5 Vdc
Heater Break Alarm
70 = 5-30 Amps 71 = 10-60 Amps
Model 16
Input Range Code
"K" TC 0 to 2460° F KF "K" TC -18 to 1349° C KC "J" TC 0 to 1400° F JF "J" TC -18 to 760° C JC "N" TC 0 to 2370° F NF "N" TC -18 to 1299° C NC "R" TC 0 to 3200° F RF "R" TC -18 to 1760° C RC "T" TC -200 to 600° F TF "T" TC -129 to 316° C TC "S" TC 0 to 3200° F SF "S" TC -18 to 1760° C SC Platinel II 0 to 2372° F LF Platinel II -18 to 1300° C LC 100 ohm RTD -328 to 1562° F PF 100 ohm RTD -200 to 850° C PC 100 ohm RTD -199.0 to 450.0 ° F DF 100 ohm RTD -128.8 to 232.2° CDC 1 to 5 V Scaleable L1 10 to 50 mV Scaleable L2 4 to 20 mA * Scaleable L3 0 to 5 V Scaleable L4 0 to 50 mV Scaleable L5 0 to 20 mA* Scaleable L6 0 to 10 V Scalable L7 2 to 10 V Scalable L8 0 to 1V Scalable L9
Special Options -
See List If NONE: Enter 00 (Consult Factory)
Quick Setup Instructions - Series 16 Temperature Controller
Experienced users, already familiar with mounting and wiring the Series 16 may use these condensed instruc­tions to autotune the controller and get started quickly.
These quick setup instructions are not meant as a substitute for reading the full instruction manual. Please be sure to read through the manual for specific details of operation and, most importantly, for safety precautions. If you have questions, or experience problems with setting up your controller, consult the full instruction manual first and, if you still need assistance, contact your Athena representative or call 1-800-782-6776.
Access Raise Lower Mode
1. Apply power. After self-check display stops, immediately place the controller into Standby mode by
pressing and holding the key for four seconds until [ StbY ] flashes.
2. Press key until [Ac.Cd. ] flashes. (This can take anywhere from one to eleven
seconds, depending on the menu level at which the controller is currently set.)
3. If the controller is not at menu level “05”, press or until “05” appears.
4. Press until [ SnSr ] flashes. Then use or to select Sensor Type. NOTE: Unless otherwise instructed, the following steps require that you first press the Parameter/Access
key, and then the Raise or Lower key to select the appropriate
parameter value.
5. Select Heating Mode or Alarm on Output 1 [ OUt 1 ].
[ Ht.P ] = PID [ Ht.O ] = On/Off [ ALr ] = Alarm
Repeat for Cooling Mode on Output 2 [OUt 2 ]. [ CL.P ] = PID [ CL.O ] = On/Off [ ALr ] = Alarm
Important: If only one output is PID, set the other output to either On/Off or Alarm.
6. Select Cooling Type [ CoL.t ].
[ nor ] = standard/no cooling [ H2o ] = water-cooled extruders
7. Select Alarm [ AI.H.L.], either [ HI ] or [ Lo ].
8. Select Alarm Type [ A1.P.d. ], either Process [ Pr ] or Deviation [ dE ].
9. Select Alarm Operation [ Al.O.P.], either Normal [ nor ], Latching [ LAt ] or Off [ OFF ].
10. Repeat Steps 7 through 9 for Alarm 2, if applicable.
11. Select Temperature Units [ Unlt ], either [ F ] or [ C ], then press Mode key once to display setpoint.
Use or keys to select Setpoint Value.
12. Press key once to return controller to [ Ac.Cd ] display.
13. Press key twice to select menu level “03”.
14. Select Alarm Trip Points [ ALr1 ] and/or [ ALr2 ], if applicable. Note: This menu parameter will not appear
if Alarm Operation (Step #9) is set to [ OFF ].
15. Select Cycle Times [ CY.t1 ] and/or [ CY.t2 ] as follows:
For Control Output Type — Select Cycle Time (in seconds)
B15 E00 F00 S00 T15 Y 15 (Output 2 only)
16. Scroll to Setpoint Target Time [ SP.tt ] and set to [ OFF ].
17. Select Lower Setpoint Limit [ L.SP.L ] and Upper Setpoint Limit [ U.SP.L ] to the desired value.
18. Press Mode key once, then key once to restore [ Ac.Cd ] display. Change to menu level “02”.
19. Use the key to scroll through to the Damping menu parameter [ dPnG ]. Select normal [ nL ]. Note:
If your process is subject to thermal lag.
20. Press and hold the key until [ tUnE ] appears. When the display stops and the Setpoint Value
appears, the controller is tuned. For safety and security purposes, you may want to change to key-lock­out menu level “00” or Limited Access Run menu level “01” before beginning your process operations.
40
41
Keep This Information in a Safe Place
Configured Parameters Reference Card
Series 16/18/19/25 Temperature Controllers
Model Number Zone Location
Firmware Version No.
(Displayed when the controller is powered up after all the segments on both lines of the display have been
tested.)
Dear Customer:
Please keep this information handy – in case your controller should lose its configured initial parameter values or for easy reference when setting up a new controller. After auto-tuning, and when your controller is controlling well,
we suggest you write the displayed value for each of the menu parameters below. If you do not use a listed parameter, indicate “N/A”. Using this information to document your parameter set­tings could reduce your downtime. If you have any questions, or need further assis­tance, please contact Athena Controls Technical Support:
Toll-free (in USA): 800.782.6776 Te lephone: 610.828.2490 Fax: 610.828.7084 E-Mail: techsupport@athenacontrols.com
Website: athenacontrols.com
Configured Parameters Reference Information
Series 16/18/19/25 Temperature Controllers
Menu 2 Menu 3 Menu 5
Menu 4
42
NOTES
43
Keep This Information in a Safe Place
Configured Parameters Reference Card
Series 16/18/19/25 Temperature Controllers
Model Number Zone Location
Firmware Version No.
(Displayed when the controller is powered up after all the segments on both lines of the display have been
tested.)
Dear Customer:
Please keep this information handy – in case your controller should lose its configured initial parameter values or for easy reference when setting up a new controller. After auto-tuning, and when your controller is controlling well,
we suggest you write the displayed value for each of the menu parameters below. If you do not use a listed parameter, indicate “N/A”. Using this information to document your parameter set­tings could reduce your downtime. If you have any questions, or need further assis­tance, please contact Athena Controls Technical Support:
Toll-free (in USA): 800.782.6776 Te lephone: 610.828.2490 Fax: 610.828.7084 E-Mail: techsupport@athenacontrols.com
Website: athenacontrols.com
Configured Parameters Reference Information
Series 16/18/19/25 Temperature Controllers
Menu 2 Menu 3 Menu 5
Menu 4
44
NOTES
For technical assistance, call toll free
1-800-782-6776 (in the U.S.) or 610-828-
2490 (from anywhere in the world), or
e-mail techsupport@athenacontrols.com.
Athena Controls, Inc.
5145 Campus Drive
Plymouth Meeting, PA 19462 USA
Toll-free: 800.782.6776
Tel: 610.828.2490
Fax: 610.828.7084
techsupport@athenacontrols.com
athenacontrols.com
900M006U00 REV “C” - 082405
Loading...