ATEN PE9222, PE9216, PE7216, PE7214, PE9330 User Manual

...
eco PDU PE Series
PE7214 / PE7216 / PE7324 / PE7328 / PE8121kJ / PE8216 / PE8316G /
PE8324 / PE8324A / PE8324JA / PE9216 / PE9222 / PE9324 / PE9330
Power Distribution Unit
User Manual
www.aten.com
eco PDU PE Series User Manual
FEDERAL COMMUNICATIONS COMMISSION INTERFERENCE STATEMENT: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
CE Warning: This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
NOTE: The KJ and J model series do not meet or qualify for FCC or CE certification, as they are produced for countries outside the FCC’s jurisdiction.
RoHS
This product is RoHS compliant.
SJ/T 11364-2006
The following contains information that relates to China.
ii
eco PDU PE Series User Manual
Set the maximum permissible breaker protection in the building circuitry to the
current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.
Only connect the PE Device to a grounded power outlet or a grounded system! Make sure that the total current input of the connected systems does not exceed
the current rating specified on the rating plate of the PE Device.
There is a risk of explosion if the battery is replaced with an incorrect type.
Dispose of used batteries according to the relevant instructions.
User Information
Online Registration
Be sure to register your product at our online support center:
International http://eservice.aten.com
Telephone Support
For telephone support, call this number:
International 886-2-8692-6959
China 86-10-5255-0110
Japan 81-3-5615-5811
Korea 82-2-467-6789
North America 1-888-999-ATEN ext 4988
United Kingdom 44-8-4481-58923
User Notice
All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer (and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.
The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.
The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE.
PE Device Safety Notice
iii
eco PDU PE Series User Manual
Copyright © 2013 ATEN® International Co., Ltd.
Manual Date: 2013-12-23
NRGence and the NRGence logo are registered trademarks of ATEN International Co., Ltd. All rights reserved.
All other brand names and trademarks are the registered property of their respective owners.
Package Contents
The eco PDU PE Series package consists of:
1 PE7214, PE7216, PE7324, PE7328, PE8121kJ, PE8216, PE8316G, PE8324, PE8324A, PE8324JA, PE9216, PE9222, PE9324, or PE9330 Power Distribution Unit
1 Power Cord (14-port, 16-port, 21-port, and 22-port models only; excluding PE8316G)
1 Mounting Kit
1CD-ROM
1 User Instructions*
Check to make sure that all of the components are present and in good order. If anything is missing, or was damaged in shipping, contact your dealer.
Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation.
* Features may have been added to the eco PDU since this manual was
published. Please visit our website to download the most up-to-date version.
iv
eco PDU PE Series User Manual
Contents
FCC Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
PE Device Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter 1.
Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Comparison Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
eco Sensors Energy Management Software* . . . . . . . . . . . . . . . . . . . .7
Proactive Overload Protection (POP) . . . . . . . . . . . . . . . . . . . . . . . . . .7
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Environment Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Door Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Cable Holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
PE7214B / PE7214G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
PE7216 / PE8216 / PE9216 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
PE8316G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
PE8121kJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PE9222B / PE9222G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
PE7324 / PE8324 / PE9324 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
PE8324A / PE8324JA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
PE7328 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
PE9330 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Port and LED Panel (All models) . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Chapter 2.
Hardware Setup
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
v
eco PDU PE Series User Manual
PDU Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Installation Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Securing the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Securing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Chapter 3.
Basic Operation and First Time Setup
Operation Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
eco Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Changing the Administrator Login . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Moving On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 4.
Logging In
Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
The eco PDU Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Chapter 5.
Energy
Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 6.
User Management
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Administrator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 7.
Log
Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
The System Log Event List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Chapter 8.
Setup
Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Device Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
vi
eco PDU PE Series User Manual
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Working Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Account Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Login String / IP Filter / Mac Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Chapter 9.
PDU
PDU. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Firmware File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Appendix
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
The eco PDU’s Main Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Securing the Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Resetting the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Recovery Procedure:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
PE7214B / PE7214G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
PE7216B / PE8216B / PE9216B . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
PE7216G / PE8216G / PE9216G . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
PE8316G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
PE8121kJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
PE9222B / PE9222G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
PE7324B/J / PE8324B/J / PE9324B/J . . . . . . . . . . . . . . . . . . . . . . . .91
PE8324A / PE8324JA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
PE7324G / PE8324G / PE9324G . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
PE7328B/J / PE7328G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
PE9330B/J / PE9330G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
vii
eco PDU PE Series User Manual
Conventions
This manual uses the following conventions:
Monospaced Indicates text that you should key in.
[ ] Indicates keys you should press. For example, [Enter] means
to press the Enter key. If keys need to be chorded, they appear together in the same bracket with a plus sign between them: [Ctrl+Alt].
1. Numbered lists represent procedures with sequential steps.
Bullet lists provide information, but do not involve sequential
steps.
Indicates selecting the option (on a menu or dialog box, for
example), that comes next. For example, Start means to open the Start menu, and then select Run.
Indicates critical information.
Run
viii
eco PDU PE Series User Manual
Product Information
For information about all NRGence products and how they can help you save money in the data center, visit NRGence on the Web or contact an ATEN Authorized Reseller. Visit ATEN on the Web for a list of locations and telephone numbers
International – http://www.aten.comNorth America – http://www.aten-usa.com
ix
Chapter 1

Introduction

Overview

As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE7214 / PE7216 / PE7324 / PE7328 / PE8121kJ / PE8216 / PE8316G / PE8324 / PE8324A / PE8324JA / PE9216 / PE9222 / PE9324 / PE9330 eco PDUs are intelligent PDUs that contain 14, 16, 21, 22, 24, 28, or 30 AC outlets and are available in various IEC socket configurations. Models in the advanced PE9 range feature a dedicated 8/14-outlet bank for critical load devices, and both the PE8 and PE9 ranges feature NRGence’s proactive overload protection, which automatically powers off the last outlet that caused the current overload.
NRGence eco PDUs provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors*. The basic characteristics of each model are shown in the table on page 3.
NRGence eco PDUs offer remote power control combined with real-time power measurement – allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device, bank, or outlet level, depending on the model, from practically any location via a TCP/IP connection*.
The power status of each outlet can be set individually, allowing users to switch each device On/Off. The eco PDU also offers comprehensive power analysis reports which can separate departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display.
Installation and operation is fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.
NRGence eco PDU supports any 3rd party V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive
1
Chapter 1. Introduction
and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.
With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.
Note: 1. Sensors are optional accessories. A sensor-enabled installation is
required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. See Optional Accessories, page 9, for further information.
2. eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet access usage.
3. Not all models support all features. See Comparison Chart, page 3, and Specifications, page 83, for full details.
2
eco PDU PE Series User Manual

Comparison Chart

Model Inlet / Cord Outlets
PE7214B NEMA 6-20P
(208V)
14 12 x IEC320 C13 +
2 x IEC320 C19
PE7214G IEC 60320 C20 14 12 x IEC320 C13 +
2 x IEC320 C19
PE7216B NEMA 6-20P 16 14 x IEC 320 C13 +
PE8216B Yes 16/16
2 x IEC 320 C19
Metering
Level
PDU / 1 x Bank / Outlet
PDU / 1 x Bank / Outlet
PDU / 1 x Bank / Outlet
Outlet
Switching
No
No
No
PE9216B Yes 8/16
PE7216G IEC 60320 C20 No
PE8216G Yes 16/16
PE9216G Yes 8/16
PE8316G IEC 60309 32A 16 10 x IEC 320 C19 +
6 x IEC 320 C13
PE8121kJ NEMA L6-15P 21 21 x IEC 320 C13 with
lock
PDU / 2 x Bank / Outlet
PDU / 1 x Bank /
Yes 16/16
Yes 21/21
Outlet
PE9222B NEMA 6-20P
(208V)
PE9222G IEC 60320 C20 22 19 x IEC320 C13 +
PE8324A NEMA L5-30P
(UL)
22 19 x IEC320 C13 +
3 x IEC320 C19
PDU / 1 x Bank / Outlet
PDU / 1 x
3 x IEC320 C19
Bank / Outlet
24 24 x NEMA 5-15R PDU / 2 x
Bank /
Yes 8/22
Yes 8/22
Yes 24/24
Outlet
PE8324JA NEMA L5-30P
(PSE)
24 24 x NEMA 5-15R PDU / 2 x
Bank /
Yes 24/24
Outlet
PE7324B / J NEMA L6-30P 24 21 x IEC 320 C13 +
PE8324B / J Yes 24/24
3 x IEC 320 C19
PDU / 2 x Bank / Outlet
No
PE9324B / J Yes 16/24
PE7324G IEC 60309 32A No
PE8324G Yes 24/24
PE9324G Yes 16/24
3
Chapter 1. Introduction
Model Inlet / Cord Outlets
PE7328B / J NEMA L6-30P 28 24 x IEC 60320 C13 +
PE7328G IEC 60309 32A
4 x IEC 60320 C19
PE9330B / J NEMA L6-30P 30 26 x IEC 60320 C13 +
PE9330G IEC 60309 32A
4 x IEC 60320 C19
Metering
Level
PDU / 2 x Bank / Outlet
PDU / 2 x Bank / Outlet
Outlet
Switching
No
Yes 16/30
Note: For the complete specifications of individual models, including bank-
by-bank outlet details, please reference Specifications, page 83.
4
eco PDU PE Series User Manual

Features

Power Distribution

Space saving 0U rack mount design with rear mountingVarious IEC outlet models2 digit 7-segment front panel LED shows PDU/Phase / Bank / Outlet ID3 digit 7-segment front panel LED shows Current / Voltage / Power
Dissipation, IP address, and readings from up to 4 environment sensors
Safe shutdown supportSeparate power for the unit's own power and its power outlets – the user
interface is still accessible even when an overload condition trips the devices' circuit breaker
Dedicated 8/14-outlet bank for critical load devices (PE9 models only:
PE9216/PE9324 8 outlets; PE9222/PE9330 14 outlets) – always powered on
Proactive overload protection (POP) (PE8 / PE9 models only) –
automatically powers off the last outlet that caused the current overload (see Proactive Overload Protection (POP), page 7)

Remote Access

Remote power control via TCP/IP and a built in 10/100 Ethernet portNetwork Protocols: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP,
NTP, DNS, auto sense, Ping
Remote users can monitor outlet status via web pages on their browserseco PDU Power Management software – eco SensorsSupports SNMP Manager V3

Operation

Local and Remote power outlet control (On, Off, Power Cycle) by
individual outlets (PE8 / PE9 models)
Supports multiple power control methods – Wake on LAN, System after
AC Back, Kill the Power
Power-on sequencing – set the power on sequence and delay time for each
outlet to allow equipment to be powered on in the correct order
Easy setup and operation via a browser-based user interfaceMultibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera)
5
Chapter 1. Introduction
RTC support to keep the timer running during times of no powerUp to 8 user accounts and 1 administrator account

Management

Power metering and monitoring at the PDU / Bank / Outlet levelLED indicators for current, voltage, power dissipation at the PDU / Bank /
Outlet levels
Real-time aggregate current, voltage, and power and power dissipation
displayed in a browser-based UI for monitoring at the PDU, bank and outlet level (14-port, 16-port*, 21-port, and 22-port models offer 1 bank metering; 24-port, 28-port, 30-port, and PE8316G models offer 2 bank metering)
Alert notification for selected events (On, Off, Recycle, Failure, exceeding
threshold settings, etc.), via blinking LEDs (locally), SMTP, SNMP trap notification
Supports Management Information Base (MIB) files for SNMPEnvironment monitoring – supports external temperature / humidity /
differential pressure sensors for rack environment monitoring
Door Sensor support – allows the monitoring of rackmount enclosure door
access to notify users when a door has been opened.
Current and voltage threshold settingNaming support for outletsUser outlet access assignment on an outlet-by-outlet basisEvent logging and syslog supportUpgradeable firmware Multilanguage support – English, Traditional Chinese, Simplified
Chinese, Japanese, German, Italian, Spanish, French, Russian, Korean, Portuguese
*PE8316G has 2 bank metering

Security

Two-level password securityStrong security features include strong password protection and advanced
encryption technologies – 128 bit SSL
Remote authentication support: RADIUS
6
eco PDU PE Series User Manual

eco Sensors Energy Management Software*

Automatic discovery of all PE devices within the same intranetRemote real-time power measurement and monitoringReal-time environment sensor monitoringPlotting/monitoring of all PE devicesExceed threshold alert through SMTP and System logPower Analysis report
Note: eco Sensors is designed to work with NRGence PDUs, and is bundled
with all PE series packages.

Proactive Overload Protection (POP)

The PE8121kJ, PE8216, PE8316G, PE8324, PE8324A, PE8324JA, PE9216, PE9222, PE9324, and PE9330 models feature NRGence’s exclusive Proactive Overload Protection (POP) technology. Effective on all non-critical outlets, this added safety feature automatically powers off the last outlet that caused the current overload.
POP mode is engaged when the current exceeds the set threshold maximum value, powering off the outlet. The LED display shows POP and a beeper sounds. Press any button for two seconds to clear POP mode and power the outlet back on.
7
Chapter 1. Introduction

Requirements

Browsers accessing the eco PDU unit must support SSL 128 bit
encryption.
For cold booting of attached computers, the computer's BIOS must
support Wake on LAN or System after AC Back.
For Safe Shutdown:
The computer must be running Windows (Windows 2000 or higher) or
Linux.
The Safe Shutdown program (available by download from our website
or on the software CD included), must be installed and running on the computer.
8
eco PDU PE Series User Manual

Optional Accessories

Environment Sensors

For complete energy management of an instrumented data center with the use of the eco PDU and eco Sensors software, you should install 4 sensors for each of the racks in your data center in order to generate a complete energy-efficient data chart. Higher sensor installation density is helpful to generate more accurate data. 8/16-port models have 4 sensor ports. Higher sensor installation density is helpful to generate more accurate data.
To get the most complete eco Sensors Dashboard data, the recommended 4­sensor setup is show in the table, below:
Port Location Part Number Sensor
Sensor 1 Intake EA1140 or
Sensor 2 Intake
Sensor 3 Exhaust
Sensor 4 Exhaust
or Floor EA1340 Differential Pressure
EA1240
Temperature or Temperature / Humidity

Door Sensor

All models in the PE7xxx/PE8xxx/PE9xxx range feature a 4-pin dry contact port for door sensors that supports the monitoring of rackmount enclosure door access to notify users when a door has been opened.
See the table below for information about the two available door sensors. Please contact your ATEN dealer for purchasing information:
Port Part Number Sensor
Door Sensor EA1440 Photo Sensor
EA1441 Inductive Proximity Sensor
Sensor Management
Sensors can be managed via the eco PDU’s built-in graphical user interface (GUI) or with the NRGence eco Sensors software that can be downloaded from the ATEN website. The download link can be found on the software CD provided with the eco PDU package.
9
Chapter 1. Introduction

Cable Holders

Cable holders are optional accessories. For added safety, use ATEN Lok-U­Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Use only the ATEN Lok-U-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.
Part Number Description
2X-EA07 Lok-U-Plug Cable Holder (10 pcs)
2X-EA08 Lok-U-Plug Installation Tool (4 pcs)
10
eco PDU PE Series User Manual
1
2
3
4
5

Components

PE7214B / PE7214G

11
Chapter 1. Introduction
No. Item Description
1 Power Outlets* 14 in total (12 x IEC320 C13 + 2 x IEC320 C19)
Bank 1-1: Outlet 1–14; 12 x C13 + 2 x C19
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDsEnvironmental Sensor PortsLAN PortDoor Sensor PortReset Switch
Full details of this section are provided on page 23.
3 Circuit Breaker
Pushbutton
4 Power Inlet The power cord that connects the unit to an AC
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Warning: See Resetting the Circuit Breaker, page 79 for important information about resetting a tripped circuit breaker.
power source plugs into this socket.
B models connect to a NEMA 6-20P (208V)
source
G models connect to an IEC 60320 C20 source
5 Output Power Indicator This LED lights steady to indicate output power for
the related bank.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
outlets. See Securing the Cables, page 35, for further information.
12
eco PDU PE Series User Manual
1
2
5
3
4
1
5
5
PE7216
PE8216
PE9216

PE7216 / PE8216 / PE9216

Note: The PE7216 / PE8216 / PE9216 unit components are identical except
for the outlet LEDs – the PE7216 has none; the PE8216 has 16; and the PE9216 has 8, as shown by number 9 above.
13
Chapter 1. Introduction
No. Item Description
1 Power Outlets* 16 in total (14 x IEC 320 C13 + 2 x IEC 320 C19)
Bank 1-1: Outlet 1–8: 7 C13; 1 x C19 Bank 1-2: Outlet 9–16: 7 x C13; 1 x C19
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDsEnvironmental Sensor PortsLAN PortDoor Sensor PortReset Switch
Full details of this section are provided on page 23.
3 Circuit Breaker
Pushbutton
4 Power Inlet The power cord that connects the unit to an AC
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Warning: See Resetting the Circuit Breaker, page 79 for important information about resetting a tripped circuit breaker.
power source plugs into this socket.
B models connect to a NEMA 6-20P sourceG models connect to an IEC 60320 C20 source
5 Outlet Status LEDs PE8216 (x 16) and PE9216 (x 8) only.
These LEDs indicate outlet status. Lights ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
outlets. See Securing the Cables, page 35, for further information.
14
eco PDU PE Series User Manual

PE8316G

1
5
2
1
5
15
3
4
Chapter 1. Introduction
No. Item Description
1 Power Outlets* Total : 6 x IEC320 C13 + 10 x IEC320 C19
Bank 1: Outlet 1–8; 3 x C13 + 5 x C19 Bank 2: Outlet 9–16; 3 x C13 + 5 x C19
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDsEnvironmental Sensor PortsLAN PortDoor Sensor PortReset Switch
Full details of this section are provided on page 23.
3 Circuit Breakers As a safety measure, if there is an overcurrent
4 Power Cord Plug the cord into an AC power source.
situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Warning: See Resetting the Circuit Breaker, page 79 for important information about resetting a tripped circuit breaker.
B models connect to a NEMA L6-30P sourceG models connect to an IEC 60309 32A source
5 Outlet Status LEDs These 16 LEDs indicate outlet status.
Lights ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
outlets. See Securing the Cables, page 35, for further information.
16
eco PDU PE Series User Manual

PE8121kJ

1
1
5
5
2
1
5
17
3
4
Chapter 1. Introduction
No. Item Description
1 Power Outlets* 21 in total (21 x IEC 320 C13)
Bank 1-1: Outlet 1–7 Bank 1-2: Outlet 8–14 Bank 1-3: Outlet 15-21
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDsSensor PortsLAN PortDoor Sensor PortReset Switch
Full details of this section are provided on page 23.
3 Circuit Breaker
Pushbutton
4 Power Inlet The power cord that connects the unit to an AC
5 Outlet Status LEDs These 21 LEDs indicate outlet status.
As a safety measure, if there is an over current situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Warning: See Resetting the Circuit Breaker, page 79 for important information about resetting a tripped circuit breaker.
power (NEMA L6-15P) source plugs into this socket.
Lights ORANGE for powered on. Off for powered off.
18
eco PDU PE Series User Manual

PE9222B / PE9222G

1
2
6
19
1
5
3
4
Chapter 1. Introduction
No. Item Description
1 Power Outlets* 22 in total (19 x IEC320 C13 + 3 x IEC320 C19)
Bank 1-1: Outlet 1–14; 12 x C13 + 2 x C19 Bank 1-2: Outlet 15–22; 7 x C13 + 1 x C19
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDsSensor PortsLAN PortDoor Sensor PortReset Switch
Full details of this section are provided on page 23.
3 Circuit Breaker
Pushbutton
4 Power Inlet The power cord that connects the unit to an AC
As a safety measure, if there is an over current situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Warning: See Resetting the Circuit Breaker, page 79 for important information about resetting a tripped circuit breaker.
power source plugs into this socket.
B models connect to a NEMA 6-20P (208V)
source
G models connect to an IEC 60320 C20 source
5 Outlet Status LEDs These 8 LEDs indicate outlet status.
Lights ORANGE for powered on. Off for powered off.
6 Output Power Indicator This LED lights steady to indicate output power for
the related bank.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
outlets. See Securing the Cables, page 35, for further information.
20
eco PDU PE Series User Manual
1
2
5
3
4
PE7324
PE8324
PE9324
1
1
5
5
5
5

PE7324 / PE8324 / PE9324

Note: The PE7324 / PE8324 / PE9324 unit components are identical except
for the outlet LEDs – the PE7324 has none; the PE8324 has 24; and the PE9324 has 16, as shown by number 5 above.
21