ATEN PE6324JA2, PE5324kJA, PE6216, PE5216, PE5324 User Manual

...
eco PDU PE Series
PE5216 / PE6216 / PE5324 / PE5324kJA / PE6324 /
PE6324JA2
Power Distribution Unit
User Manual
www.aten.com
eco PDU PE Series User Manual
Warning: This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
FEDERAL COMMUNICATIONS COMMISSION INTERFERENCE STATEMENT: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
RoHS
This product is RoHS compliant.
SJ/T 11364-2006
The following contains information that relates to China.
ii
eco PDU PE Series User Manual
Set the maximum permissible breaker protection in the building circuitry to the
current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.
Only connect the PE Device to a grounded power outlet or a grounded system! Make sure that the total current input of the connected systems does not exceed
the current rating specified on the rating plate of the PE Device.
There is a risk of explosion if the battery is replaced with an incorrect type.
Dispose of used batteries according to the relevant instructions.
User Information
Online Registration
Be sure to register your product at our online support center:
International http://eservice.aten.com
Telephone Support
For telephone support, call this number:
International 886-2-8692-6959 China 86-10-5255-0110 Japan 81-3-5615-5811 Korea 82-2-467-6789 North America 1-888-999-ATEN ext 4988 United Kingdom 44-8-4481-58923
User Notice
All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer (and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.
The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.
The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE.
PE Device Safety Notice
iii
eco PDU PE Series User Manual
Copyright © 2014 ATEN® International Co., Ltd.
Manual Date: 2014-03-24
NRGence and the NRGence logo are registered trademarks of ATEN International Co., Ltd. All rights reserved.
All other brand names and trademarks are the registered property of their respective owners.
Package Contents
The eco PDU PE Series package consists of: 1 PE5216 / PE6216 / PE5324 / PE5324kJA / PE6324 / PE6324JA2 Power
Distribution Unit 1 Power Cord (16-port models only) 1 Mounting Kit 1 User Instructions* 1CD-ROM
Check to make sure that all of the components are present and in good order. If anything is missing, or was damaged in shipping, contact your dealer.
Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU installation.
* Features may have been added to the eco PDU since this manual was
published. Please visit our website to download the most up-to-date version.
iv
eco PDU PE Series User Manual
Contents
FCC, CE Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
SJ/T 11364-2006. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
PE Device Safety Notice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Chapter 1.
Introduction
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Comparison Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Remote Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
eco Sensors Energy Management Software* . . . . . . . . . . . . . . . . . . . .5
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Cable Holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE5216A / PE6216A Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
PE5216B / PE5216G / PE6216B / PE6216G Front View . . . . . . . . . .10
PE5324B / PE5324G / PE6324B / PE6324G Front View . . . . . . . . . .12
PE5324kJA Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
PE6324JA2 Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Readout Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Chapter 2.
Hardware Setup
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
PDU Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Securing the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Securing the Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
v
eco PDU PE Series User Manual
Chapter 3.
Basic Operation and First Time Setup
Operation Methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
eco Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
First Time Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Changing the Administrator Login . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Moving On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Chapter 4.
Browser Operation
Logging In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
The eco PDU Main Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Outlet Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
User Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Administrator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
The System Log Event List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Device Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Device Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Login Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Working Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Account Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Login String / IP Filter / Mac Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Authentication & Authorization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Private Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Firmware File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Backup/Restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Appendix
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
The eco PDU’s Main Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Securing the Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
vi
eco PDU PE Series User Manual
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
IP Address Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
PE5216A / PE6216A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
PE5216B / PE6216B / PE5324B / PE6324B . . . . . . . . . . . . . . . . . . .66
PE5216G / PE6216G / PE5324G / PE6324G . . . . . . . . . . . . . . . . . .67
PE5324kJA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
PE6324JA2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Administrator Login Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
vii
eco PDU PE Series User Manual
About This Manual
This User Manual is provided to help you get the most from your eco PDU system. It covers all aspects of installation, configuration and operation. An overview of the information found in the manual is provided below.
Chapter 1, Introduction, introduces you to the eco PDU system. Its purpose, features and benefits are presented, and its front and back panel components are described.
Chapter 2, Hardware Setup, provides step-by-step instructions for setting up your installation.
Chapter 3, Basic Operation and First Time Setup, explains the procedures that the Administrator employs to set up the eco PDU network environment, and change the default username and password.
Chapter 4, Browser Operation, describes how to log in to the eco PDU with an internet browser, and explains the layout and components of the eco PDU’s user interface.
An Appendix, provides specifications and other technical information regarding the eco PDU.
Conventions
This manual uses the following conventions:
Monospaced Indicates text that you should key in.
[ ] Indicates keys you should press. For example, [Enter] means
to press the Enter key. If keys need to be chorded, they appear together in the same bracket with a plus sign between them: [Ctrl+Alt].
1. Numbered lists represent procedures with sequential steps. Bullet lists provide information, but do not involve sequential
steps.
Indicates selecting the option (on a menu or dialog box, for
example), that comes next. For example, Start means to open the Start menu, and then select Run.
Indicates critical information.
viii
Run
eco PDU PE Series User Manual
Product Information
For information about all NRGence products and how they can help you save money in the data center, visit NRGence on the Web or contact an ATEN Authorized Reseller. Visit ATEN on the Web for a list of locations and telephone numbers
International – http://www.aten.comNorth America – http://www.aten-usa.com
ix
eco PDU PE Series User Manual
This Page Intentionally Left Blank
x
Chapter 1

Introduction

Overview

As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage. The NRGence PE5216 / PE6216 / PE5324 / PE5324kJA / PE6324 / PE6324JA2 eco PDUs are intelligent PDUs that contain 16 or 24 AC outlets and are available in various IEC or NEMA socket configurations.
They provide secure, centralized, intelligent, power management (power on, off, cycle) of data center IT equipment (servers, storage systems, KVM switches, network devices, serial data devices, etc.), as well as the ability to monitor the center's health environment via sensors*. The basic characteristics of each model are shown in the table on page 3.
NRGence eco PDUs offer remote power control combined with real-time power measurement - allowing you to control and monitor the power status of devices attached to the PDUs, either at the PDU device or outlet level, from practically any location via a TCP/IP connection.
The power status of each outlet can be set individually, allowing users to switch each device On/Off. The eco PDU also offers comprehensive power analysis reports which can separate departments and locations, providing precise measurements of current, voltage, power and watt-hour in a real-time display.
Installation and operation is fast and easy: plugging cables into their appropriate ports and user-friendly browser-based configuration and management is all that is entailed. Since the eco PDU firmware is upgradeable over the Net, you can stay current with the latest functionality improvements simply by downloading updates from our website as they become available.
NRGence eco PDU supports any 3rd party V1, V2, V3 SNMP Manager Software and NRGence eco Sensors (eco PDU Manager Software). eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it.
(Continues on next page.)
1
eco PDU PE Series User Manual
(Continued from previous page.)
With its advanced security features and ease of operation, the eco PDU is the most convenient, most reliable, and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible.
Note: 1. Sensors are optional accessories. A sensor-enabled installation is
required to generate a more comple te energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. See Optional Accessories, page 7, for further infor mation.
2. eco PDUs are primarily designed for access via Intranet; extra network security protection is suggested for Internet access usage.
2

Comparison Chart

Chapter 1. Introduction
Model Inlet / Cord Outlets
PE5216A IEC 320 PE6216A Yes
C20
16 14 x NEMA 5-15R
2 x NEMA 5-20R
Metering
Level
PDU No
PE5216B 14 x IEC 320 C13 PE6216B Yes
2 x IEC 320 C19
Outlet
Switching
No
PE5216G No PE6216G Yes
PE5324B NEMA L6­PE6324B Yes
30P
24 21 x IEC 320 C13
3 x IEC 320 C19
Bank No
PE5324G IEC 60309 No PE6324G Yes
PE5324kJA NEMA L5-
30P
PE6324JA2 NEMA L5-
24 24 x NEMA 5-15R
Bank No
Twist Lock
24 24 x NEMA 5-15R Bank Yes
30P
Amps
Per
Total
Port
12A /
16A
16A
(UL),
20A
(Max.)
10A /
15A
15A
(TUV-
CB),
16A
(Max)
12A 24A
(UL),
30A
(Max)
10A /
30A
15A
(TUV-
CB),
32A
(Max)
14A 30A
24A
12A
(UL),
30A
(Max)
Note: For the complete specifications of individual models, please reference
Specifications, page 65.
3
eco PDU PE Series User Manual

Features

Power Distribution

Space saving 0U rack mount design with rear mountingIEC or NEMA outlet models3 digit 7-segment front panel LED shows Current / IP Address for PDU /
Bank
Remote users can monitor PDU / Bank status via web pages on their
browsers
Safe shutdown supportSeparate power for the unit's own power and its power outlets. The user
interface is still accessible even when an overload condition trips the devices' circuit breaker

Remote Access

Remote power control via TCP/IP and a built in 10/100 Ethernet portNetwork Protocols: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP,
NTP, DNS, auto sense, Ping
eco PDU Power Management software – eco SensorsSupports SNMP Manager V1, V2 & V3

Operation

Local and Remote power outlet control (On, Off, Power Cycle) by
individual outlets (PE6 models)
Supports multiple power control methods – Wake on LAN, System after
AC Back, Kill the Power
Power-on sequencing – users can set the power on sequence and delay
time for each port to allow equipment to be turned on in the proper order
Easy setup and operation via a browser-based user interfaceMultibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera,
Netscape)
RTC support to keep the timer running during times of no power.Up to 8 user accounts and 1 administrator account.
4
Chapter 1. Introduction

Management

Power status measurement at the PDU/Bank levelLED indicators for current and IP address at the PDU device and/or Bank
levels.
Real-time aggregate current, voltage, and power and power dissipation
displayed in a browser-based UI for monitoring at the PDU level (PE5216 / PE6216) and at the bank level (PE5324 / PE5324kJA / PE6324 / PE6324JA2)
Environment monitoring – supports external temperature / humidity /
differential pressure sensors for rack environment monito ring
Current and voltage threshold settingNaming support for outletsUser outlet access assignment on an outlet-by-outlet basis.Event logging and syslog supportUpgradeable firmware Multilanguage support: English, Traditional Chinese, Simplified Chinese,
Japanese, German, Italian, Spanish, French, Russian, Korean, Portuguese.

Security

Two-level password securityStrong security features include strong password protection and advanced
encryption technologies – 128 bit SSL
Remote authentication support: RADIUS

eco Sensors Energy Management Software*

Automatic discovery of all PE devices within the same intranetRemote real-time power measurement and monitoringReal-time environment sensor monitoringPlotting/monitoring of all PE devicesExceed threshold alert through SMTP and System logPower Analysis report
Note: eco Senors is designed to work wit h NRGence PDUs, and is bundled
with all PE series packages.
5
eco PDU PE Series User Manual

Requirements

Browsers accessing the eco PDU unit must support SSL 128 bit
encryption.
For cold booting of attached computers, the computer's BIOS must
support Wake on LAN or System after AC Back.
For Safe Shutdown:
The computer must be running Windows (Windows 2000 or higher) or
Linux.
The Safe Shutdown program (available by download from our website
or on the software CD included), must be installed and running on the computer.
6
Chapter 1. Introduction

Optional Accessories

Sensors

Sensors are optional accessories. You can use the eco PDU unit without sensors. However, if you want to have complete energy management of an instrumented data center with the use of the eco PDU, you would need to use eco Sensors software and install 4 sensors for each of the racks to generate a complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. 16/24-port models have 2 sensor ports. In this case, Sensor 1 needs to be installed at the intake of the rack and sensor 2 needs to be placed at the exhaust of IT equipment of the rack. A sensor­enabled installation is required to generate a more complete energy-efficient data and chart. Higher sensor installation density is helpful to generate more accurate data. Available sensors are show in the table, below:
Sensor Part Number
Temperature EA1140 Temperature / Humidity EA1240 Differential Pressure / Temperature EA1340
Sensor Management
Sensors can be managed via the eco PDU’s built-in graphical user interface (GUI) or with the NRGence eco Sensors software that can be downloaded from the ATEN website. The download link can be found on the software CD provided with the eco PDU package.

Cable Holders

Cable holders are optional accessories. For added safety, use ATEN Lok-U­Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Use only the ATEN Lok-U-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.
Part Number Description
2X-EA07 Lok-U-Plug Cable Holder (10 pcs) 2X-EA08 Lok-U-Plug Installation Tool (4 pcs)
7
eco PDU PE Series User Manual
PE5216A
PE6216A
1
2
3
4
5
8
3
4
8
6
7

Components

PE5216A / PE6216A Front View

8
Chapter 1. Introduction
No. Item Description
1 Power Inlet The power cord that connects the unit to an AC
2 Circuit Breaker
Pushbutton
3 Power Outlets* 2 x NEMA 5-20R 4 14 x NEMA 5-15R 5 Sensor Ports External sensors plug into these two RJ-11 ports. 6 LAN Port and LEDs The cable that connects the eco PDU to the LAN
7 Readout Section, LEDs
and Reset Switch
8 Outlet Status LEDs [PE6216A only] These LEDs indicate outlet status.
power source plugs into this IEC 320 C20 socket. As a safety measure, if there is an overcurrent
situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
Details of this section are provided on page 18.
Lights ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
outlets. See Securing the Cables, page 23, for furth e r inf o r m ation.
9
eco PDU PE Series User Manual
PE5216B / G
PE6216B / G
1
2
3
4
5
8
3
4
8
6
7

PE5216B / PE5216G / PE6216B / PE6216G Front View

10
Chapter 1. Introduction
No. Item Description
1 Power Socket The power cord that connects the unit to an AC
2 Circuit Breaker
Pushbutton
3 Power Sockets* 2 x IEC 320 C13 4 14 x IEC 320 C19 5 Sensor Ports External sensors plug into these two RJ-11 ports. 6 LAN Port and LEDs The cable that connects the eco PDU to the LAN
7 Readout Section, LEDs
and Reset Switch
8 Outlet Status LEDs [PE6216 models only] These LEDs indicate outlet
power source plugs into this IEC 320 C20 socket. As a safety measure, if there is an overcurrent
situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
Details of this section are provided on page 18.
status. Lights ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
sockets. See Securing the Cables, page 23, for further information.
11
eco PDU PE Series User Manual
PE5324B / G
PE6324B / G
1
2
3
4
5
8
3
4
6
7
3
4
8
8

PE5324B / PE5324G / PE6324B / PE6324G Front View

12
Chapter 1. Introduction
No. Item Description
1 Power Cord Plug the power cord into your AC source. 2 Circuit Breakers (Bank 1
and Bank 2)
3, 4 Power Sockets* 3 x IEC 320 C19
5 Sensor Ports External sensors plug into these two RJ-11 ports. 6 LAN Port and LEDs The cable that connects the eco PDU to the LAN
7 Readout Section, LEDs
and Reset Switch
8 Outlet Status LEDs [PE6324 only] These LEDs indicate outlet status.
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
21 x IEC 320 C13
plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
Details of this section are provided on page 18.
Lights ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
sockets. See Securing the Cables, page 23, for further information.
13
eco PDU PE Series User Manual
1
2
3
4
3
5
6
3
7
7
7

PE5324kJA Front View

14
Chapter 1. Introduction
No. Item Description
1 Power Cord Plug the power cord into your AC source. 2 Circuit Breakers (Bank 1
and Bank 2)
3 Power Sockets* 24 in total (24 x NEMA 5-15R Twist Lock)
4 Sensor Ports External sensors plug into these two RJ-11 ports. 5 LAN Port and LEDs The cable that connects the eco PDU to the LAN
6 Readout Section, LEDs
and Reset Switch
7 Output Power Indicator This LED lights steady to indicate output power for
As a safety measure, if there is an overcurrent situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Bank 1–1: 8 x NEMA 5-15R Twist Lock Bank 1–2: 8 x NEMA 5-15R Twist Lock Bank 2: 8 x NEMA 5-15R Twist Lock
plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
Details of this section are provided on page 18.
the related bank.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
sockets. See Securing the Cables, page 23, for further information.
15
eco PDU PE Series User Manual
1
2
3
3
3
4 5
6
7
7
7

PE6324JA2 Front View

16
Chapter 1. Introduction
No. Item Description
1 Power Cord Plug the power cord into your AC source. 2 Circuit Breakers (Bank 1
and Bank 2)
3 Power Sockets* 24 in total (24 x NEMA 5-15R)
4 Sensor Ports External sensors plug into these two RJ-11 ports. 5 LAN Port and LEDs The cable that connects the eco PDU to the LAN
6 Readout Section, LEDs
and Reset Switch
7 Output Status LEDs These LEDs indicate outlet status. Lights
2 x 16A Slim Breakers. As a safety measure, if there is an overcurrent
situation regarding the device’s power, the circuit breakers will trip. Press the button to recover normal operation.
Bank 1–1: 8 x NEMA 5-15R Bank 1–2: 8 x NEMA 5-15R Bank 2: 8 x NEMA 5-15R
plugs in here. The Link and LAN LEDs are built into the LAN port:
Link: Lights GREEN to indicate that a connection via the eco PDU's RJ-45 Ethernet port has been established. Flashes to indicate data is being transmitted.
LAN: Lights ORANGE to indicate 10 Mbps data transmission speed. The LED lights GREEN to indicate 100 Mbps data transmission speed.
Details of this section are provided on page 18.
ORANGE for powered on. Off for powered off.
Note: Holes for ATEN Lok-U-Plug cable holders are located around the
sockets. See Securing the Cables, page 23, for further information.
17
eco PDU PE Series User Manual
SENSOR 1
SENSOR 2
RESET
PDU! CURRENT!
IP! ADDRES
POWER
TFMFDU
S
1
2
3

Readout Section

No. Item Description
1 Readout Section
2LEDs
3 Reset Switch
The selection (PDU Current / IP Address) appears in the first part
of the display window.
PDU Current / IP Address appear in the second part of the display
window
The LEDs above the items indicate which one the readout relates
to.
Press the button next to the first display window to cycle the
selection between the items.
These LEDs indicate status for Power, PDU Current, IP address and Sensors
This switch is recessed and must be pushed with a thin object, such as the end of a paper clip.
Press and release to reboot the device.Press and hold for more that three seconds to reset the eco
PDU to its factory default settings
18
Chapter 2
1. Important safety information regarding the placement of this device is provided on page 59. Please review it before proceeding.
2. Make sure that power to all the devices you will be connecting have been turned off. You must unplug the power cords of any computers that have the Keyboard Power On function.

Hardware Setup

Before You Begin

Rack Mounting

The eco PDU can be mounted in a 0U configuration on the side of a rack. To rack mount the device, use the rack mounting brackets that came with your device. The brackets can be mounted either near the top and bottom of the back panel, or the top and bottom ends of the device, as shown in the diagram below:
Note: The eco PDU model shown in the diagram is for rack mounting
reference only.
19
eco PDU PE Series User Manual
Floor
Floor

PDU Placement

For safety reasons the eco PDU should not be installed with the power sockets facing directly up or down, and thus should only be installed with the power sockets facing out from a vertical position as shown below:
Right
20
Wrong
Chapter 2. Hardware Setup

Installation

To set up your eco PDU installation, refer to the installation diagram on the next page (the numbers in the diagram correspond to the numbered steps), and do the following:
1. For each device you want to connect, use its power cable to connect from the device's AC socket to any available outlet on the eco PDU. Use ATEN Lok-U-Plug cable holders to secure them.
Note: See Securing the Cables, page 23, for details.
2. Plug the cable that connects the eco PDU to the LAN into the eco PDU's LAN port.
3. If you are using sensors in your eco PDU installation, connect them to the sensor ports on the unit’s front panel.
Note: Sensors are optional. Please see Optional Accessories, pag e 7, and
the detailed sensor installation diagrams later in this chapter for further information.
4. Connect the eco PDU's power cord to an AC power source.
Note: We strongly advise that you do not plug the eco PDU into a multi
socket extension cord, since it may not receive enough amperage to operate correctly .
Once you have finished these installation steps, you can turn on the eco PDU and the connected devices.
Note: We strongly recommend using cable ties and cable bars to safely and
securely route the cables attached to the front of the unit.
21
eco PDU PE Series User Manual
3
4
2
1
1
22
Chapter 2. Hardware Setup

Securing the Cables

For added safety, use ATEN Lok-U-Plug cable holders to secure the cables from your attached devices in place on the eco PDU unit. Secure the cable holders using the specially designed holes around the individual power outlets, as shown below:
Note: 1. Cable holders are an optional accessory. See Cable Holders, page 7.
2. Use only the ATEN Lok-U-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous.
23
eco PDU PE Series User Manual

Securing the Sensors

Connect the sensors to the eco PDU’s front panel sensor ports and secure them using sensor mounts, tie wraps, and adhesive cable tie holders. If you use a tie wrap to secure the sensor, tighten the tie wrap over the recessed channel on the sensor, as shown in the following diagram:
Note: 1. The sensors shown in the above diagram are for reference purposes
only. The sensors for the eco PDU may look slightly different.
2. Depending on the model and type of sensor, sensor mounts, tie wraps, and adhesive cable tie holders may or may not be provided in the package.
24
Chapter 3
Basic Operation and
First Time Setup

Operation Methods

NRGence eco PDU models provide three methods to access and manage your installation: Browser, eco Sensors (eco PDU Management Software), and SNMP.
Note: The following sections of this chapter contain information concerning
Browser operation. For eco Sensors operation, please reference the separate eco Sensors User Manual. The eco Sensors software and User Manual can be downloaded from the ATEN website.

Browser

NRGence s can be accessed and controlled via any supported Internet browser from any platform. See First Time Setup, page 26, and the following sections in this chapter, for full details.

eco Sensors

All eco PDUs support eco Sensors (eco PDU Manager Software). NRGence eco Sensors provides you with an easy method for managing multiple devices, offering an intuitive and user-friendly Graphical User Interface that allows you to configure a PDU device and monitor power status of the equipment connected to it. NRGence eco Sensors can be downloaded from the ATEN website, along with a separate eco Sensors User Manual.

SNMP

NRGence eco PDUs support any 3rd party V1, V2, V3 SNMP Manager Software. SNMP Management Information Database (MIB) files for the eco PDU device can be found on the software CD provided with the eco PDU package.
25
eco PDU PE Series User Manual

First Time Setup

Once the eco PDU installation has been cabled up, the next task the Administrator needs to perform involve configuring the network parameters, changing the default Super Administrator login settings, and adding users.
The easiest way to accomplish this is to log in over the Net with a browser.
Note: 1. Since this is the first time you are logging in, use the default
Username: administrator; and the default Password: password. For security purposes we recommend changing them to something unique (see Changing the Administrator Login, page 28).
2. For remote methods of getting lo gged in to the network, see IP Address Determination, page 63.
After you successfully log in, the eco PDU Outlet Access/Connections page appears:
Note: Operation details are discussed in Outlet Access, page 32, in the next
chapter. For further setup information, continue with this chapter
26
Chapter 3. Basic Operation and First Time Setup

Network Configuration

To set up the network, do the following:
1. Click the Device Management tab.
2. The interface displays the Device Configuration page. A screen similar to
the one below appears:
3. Fill in the fields according to the information provided under Device Configuration, page 40.
27
eco PDU PE Series User Manual

Changing the Administrator Login

To change the default Administrator username and password, do the following:
1. Click the User Management tab.
The User Management page has a detailed list of users – with more information about them – in the large central panel:
2. In the Administrator Information section, reset the name and password fields to something unique, then click Save (at the bottom of the page.)
Note: If you forget the Administrator’s name or password, short the
mainboard jumper to restore the default Administrator account. See see Administrator Login Failure, page 70 in the Appendix for full details.

Moving On

After setting up the network and changing the default Administrator username and password, you can proceed to other administration activities – including adding users. This is covered in the next chapter.
28
Chapter 4

Browser Operation

Logging In

The eco PDU can be accessed via a supported Internet browser from any platform.
Note: Browsers must support SSL 128 bit encryption.
To access the eco PDU do the following:
1. Open your browser and specify the IP address of the eco PDU you want to
access in the browser's URL location bar.
Note: You can get the IP address from the eco PDU administrator, or see
IP Address Determination, page 63, for information about setting it up yourself.
2. If a Security Alert dialog box appear s, accept the certificate – it can be
trusted. The Login page appears:
3. Provide a valid Username and Password (set by the eco PDU
administrator), and select your language. (Options are: English [default]; Traditional Chinese; Simplified Chinese; Japanese; German; Italian; Spanish; French, Russian, Korean, Portuguese).
4. Then Click Login to bring up the browser Main Page.
29
eco PDU PE Series User Manual

The eco PDU Main Page

After you have successfully logged in, the eco PDU Main Page comes up with the Outlet Access Connections page displayed:
Note: The screen depicts an Administrator’s page. Depending on a user’s type
and permissions, and your PE model, not all of these elements appear.
30
Chapter 4. Browser Operation

Page Components

The web page screen components are described in the table, below:
No. Item Description
1 Tab Bar The tab bar contains the eco PDU’s main operation
2 Menu Bar The menu bar contains operational sub-categories
3 Sidebar The Sidebar provides a tree view listing of outlets
4 Help Connects to on-line help at the ATEN website for the
5 Logout Click this button to log out of your eco PDU session. 6 Interactive Display Panel This is your main work area. The screens that
categories. The items that appear in the tab bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
that pertain to the item selected in the tab bar. The items that appear in the menu bar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
that relate to the various tab bar and menu bar selections.
device’s configuration and operation.
appear reflect your menu choices and Sidebar node selection.
31
eco PDU PE Series User Manual

Outlet Access

Connections

When you log in to the eco PDU, the interface opens with its default selection of the Outlet Access tab; and the Connections menu. The contents of the PDU
Status and Outlet Status sections are displayed in the main panel.
Note: Only enabled eco PDU models will display the Outlet Status submenu
section. Other models provide only PDU Status monitoring. See Comparison Chart, page 3, for which models support PDU and Outlet Status or PDU Status only monitoring.
32
Chapter 4. Browser Operation
PDU Status
All eco PDU models support PDU device level monitoring. The PDU Status section allows you to set up a power management configuration for the PDU device as a whole:
PDU Threshold Settings
These fields are used to set the maximum, minimum, and fluctuation threshold settings for Aggregate Current, Voltage, Power, and Aggregate Power Dissipation. If a range falls below the minim um set ting, or exceeds the maximum setting an alarm is triggered.
Breaker status (ON / OFF) displays here.Power Factor displays a ratio between real and virtual power, providing a
power performance value based on external power sources (i.e. not related to the eco PDU device).
Voltage Frequency is displayed here in Hz.On / Off / Reboot
You can manually turn the device On and Off from this page by clicking the radio buttons. To Reboot the device, enable the Reboot checkbox and click on Save (located at the bottom of the page).
Sensor 1 / Sensor 2
If you have sensors installed in your installation, use these fields to set the maximum, minimum, and fluctuation threshold settings for Temperature, Humidity, and Pressure.
Note: Sensors are optional accessories. Check with your dealer for
information about NRGence eco Sensors software.
33
eco PDU PE Series User Manual
Outlet Status
If your eco PDU models supports outlet level power management, manual On/ Off/Reboot switching can be performed on this page.
On / Off / Reboot
Y ou can manually turn the outlet On and Off from this page by clicking the radio buttons. To Reboot the outlet, enable the Reboot checkbox and click on Save (located at the bottom of the page).
Sidebar
When an outlet is manually powered off, its number also appears grayed-out in the side bar, as below:
34
Chapter 4. Browser Operation

Configuration

The Configuration page is used to configure the settings of the eco PDU at the individual power outlet level:
This page lets you set up the power management configuration for the selected outlet. The meanings of the field headings are given in the following table
:
Heading Meaning
Outlet Name Each outlet can be given a distinctive name. The maximum number
Confirmation Required
of characters is 15. If this option is enabled (there is a check in the checkbox), a dialog
box comes up asking you to confirm a power operation before it is performed. If it is disabled (there is no check in the checkbox), the operation is performed without confirmation.
(Continues on next page.)
35
eco PDU PE Series User Manual
(Continued from previous page.)
Power ON Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see Outlet Status, page 34), before it turns on the power to the outlet.
Note: The default delay time is 0 seconds; the maximum is 999 seconds. When a series of outlets are scheduled to be powered up, they turn on in sequence with a default delay of 10 milliseconds between each outlet.
Power OFF Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see Outlet Status, page 34), before it turns off the power to the outlet.
For the System after AC Back option (see below), after the delay time expires, the eco PDU waits another fifteen seconds, then shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is 999 seconds.
Remote Turn ON Method
Use the drop-down menu to select one of the choices, below: Wake on LAN: This is a Safe Shutdown and Restart option. If this
is selected, when an Outlet is turned Off, the eco PDU first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the eco PDU waits for the amount time set in the Power On Delay field, then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On.
Note: For Safe Shutdown and Restart, the computer must be running Windows (98 or higher), or Linux, and the Safe Shutdown program (available by download from our website), must be install ed and running on the computer.
System after AC Back: This is a Safe Shutdown and Restart
option. If this is selected, when an Outlet is turned Off, the eco PDU first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down.
When the Outlet is turned On, the eco PDU waits for the amount time set in the Power On Delay field, then sends power to the server. When the server receives the power, it turns itself on.
Note: For Safe Shutdown and Reboot, the computer must be running Windows (98 or higher), or Linux, and the Safe Shutdown program (available by download from our website), must be install ed and running on the computer.
Kill the Power: If this option is selected, the eco PFDU waits for
the amount time set in the Power Off Delay field, and then turns the Outlet's power Off. Turning the power off performs a cold (non-safe) shutdown.
MAC Address In order to use either of the Safe Shutdown and Restart methods
the MAC address of the computer connected to the outlet must be filled in here.
When you have finished making your configuration settings, click Save.
36
Chapter 4. Browser Operation

User Management

When you select the User Management tab the screen comes up with Administrator Information and User Information displayed in the main panel.
The eco PDU supports one Administrator account and up to eight User accounts.
Note: 1. Each account can support 2 login sessions
2. The eco PDU supports a total of 3 concurrent login sessions.

Administrator Information

This section is used to set the Administrator name and password. Only Administrators can view this section. For details, see Changing the Administrator Login, page 28.
37
eco PDU PE Series User Manual

User Information

To add a user, do the following:
1. Select the user type in the Managem ent drop-down menu.
2. Key in a name and password in the Name and Password fields.
3. Set the outlet-by-outlet permissions of the user in the Outlet field.
4. Set the Management field to Enable.
5. Click Save to save your settings.
Note: Values must be entered in both the Name and Password fields in
order to enable an account.
The various options are explained in more detail in the following table:
Field Description
Management The Management field allows you to Enable or Disable a
Name From 1 to 16 characters are allowed depending on the
Password From 1 to 16 characters are allowed depending on the
Outlet This field allows you to set the outlet-by-outlet permissions of
user’s account:
Enable – stores the user account (see User Information,
page 38
Disable – disables the user account
Account Policy settings. See Account Policy, page49.
Account Policy settings. See Account Policy, page49.
the user. Click on the user/port icon to cycle through the three permissions options, as follows:
User has complete access to this outlet.
User has read-only access to this outlet.
User has no access to this outlet.
Save Click this button to save your operation or changes
38
Chapter 4. Browser Operation
Log
The eco PDU keeps a record of transactions that take place on its installation, and stores up to 128 events at one time. The System Log page provides a powerful array of filters and functions that allow you to view and export the log file data, as well as be informed by email of specified events as they occur.

The System Log Event List

Clicking on a device in the Sidebar displays its log events in the main
panel’s log event list.
Clicking the Refresh button brings the log list up to date with the latest
events.
The entry box to the right of the Refresh button lets you set the number of
events to display per page. Simply key in the number of your choice.
The top right of the main panel shows the total number of pages in the log
file, and what page you are currently viewing.
The buttons on the bottom row function as follows:
Clear – click to erase the contents of the log event listFirst Page – click to go to the first page of the log event listPrevious Page – click to move to the previous page of the log event
list
Next Page – click to move to the next page of the log event listLast Page – click to move to the last page of the log event listExport Log – click to save the contents of the log event list to file.
39
eco PDU PE Series User Manual

Device Management

The Device Management page allows administrators and users with device management permission to configure and control overall eco PDU operations.

Device Configuration

This page presents information about the selected device, as described in the following sections:
General
Item Meaning
PDU Name This field lets you give the device a unique name. Simply delete
whatever is in the text box and key in the name of your choice. Click Save (located at the bottom of the page) to save the new
name. MAC Address This item displays the eco PDU’s MAC address. Firmware Version This item displays the current firmware version number. You can
reference it to see if there are newer versions available on the
ATEN website. Rack Location
Name
This field lets you give the rack location a unique name for easy
reference.
40
Chapter 4. Browser Operation
Service Ports
As a security measure, if a firewall is being used, the Administrator can specify the port numbers that the firewall will allow. If a port other than the default is used, users must specify the port number as part of the IP address when they log in. If an invalid port number (or no port number) is specified, the eco PDU will not be found.
Select whether to allow only secure browser logins, as show below:
An explanation of the fields is given in the table below:
Field Explanation
HTTP The port number for a browser login. The default is 80. HTTPS The port number for a secure browser login. The default is 443.
Note: 1. Valid entries for all of the Service Ports are from 1–65535.
2. The service ports cannot have the same value. You must set a different value for each one.
3. If there is no firewall (on an Intranet, for example), it doesn’t matter what these numbers are set to, since they have no effect.
41
eco PDU PE Series User Manual
IPv4 Configuration
The PDU’s IPv4 IP and DNS addresses (the traditional method of specifying IP addresses) can either be assigned dynamically (DHCP), or a fixed IP address can be specified.
For dynamic IP address assignment, select the Obtain IP address
automatically radio button. (This is the default setting.)
To specify a fixed IP address, select the Set IP address manually radio
button and fill in the IP address with values appropriate for your network.
For automatic DNS Server address assignment, select the Obtain DNS
Server address automatically radio button.
To specify the DNS Server address manually, select the Set DNS server
address manually radio button, and fill in the addresses for the Preferred
and Alternate DNS servers with values appropriate for your network.
Note: 1. If you choose Obtain IP address automatically, when the device starts
up it waits to get its IP address from the DHCP server. If it hasn’t obtained the address after one minute, it automatically reverts to its factory default IP address (192.168.0.60.)
2. If the device is on a network that uses DHCP to assign network addresses, and you need to ascertain its IP address, see IP Address Determination, page 63, for information.
3. Specifying the Alternate DNS Server address is optional.
42
Chapter 4. Browser Operation
Event Notification
The Event Notification section is divided into three sections: SMTP Settings; SNMP Trap Receivers; and Syslog Server. Each section is described below.
SMTP Settings
To have the eco PDU device email reports from the SMTP server to you, do the following:
1. Enable the Enable report from the following SMTP server, and key in the IP address of your SMTP server.
2. If your server requires authentication, put a check in the My server requires authentication checkbox.
3. Key in the appropriate account information in the Account Name, Password, and From fields.
Note: Only one email address is allowed in the From fields, and it cannot
exceed 64 characters.)
4. Key in the email address (addresses) of where you want the event reports sent to in the To field.
Note: If you are sending the report to more than one email address,
separate the addresses with a semicolon or comma, depending on the specified mail server. The total cannot exceed 256 characters.
43
eco PDU PE Series User Manual
SNMP Trap Receivers
Up to four SNMP management stations can be specified. If you want to use SNMP trap notifications, do the following:
1. Check Enable SNMP Trap.
2. Select which version of SNMP you want to use.
3. Key in the IP address(es) and the service port number(s) of the computer(s) to be notified of SNMP trap events. The valid port range is 1–65535. The default port number is 162.
Note: Make sure that the port nu mber you specify here m a tches the port
number used by the SNMP receiver computer .
4. Key in the community value(s) if required for the SNMP version.
5. Key in the auth/privacy password(s) that correspond to each of the stations.
44
Chapter 4. Browser Operation
Syslog Server
To record all the events that take place on eco PDU devices and write them to the eco PDU Syslog server, do the following:
1. Check Enable Syslog Server.
2. Key in the IP address and the port number of the Syslog server. The valid
port range is 1-65535. The default port number is 514.
45
eco PDU PE Series User Manual

Date/Time

The Date/Time dialog page sets the eco PDU time parameters:
Set the parameters according to the information described below.
Time Zone
To establish the time zone that the eco PDU is located in, drop down the
Time Zone list and choose the city that most closely corresponds to where it is at.
If your country or region employs Daylight Saving Time (Summer Time),
check the corresponding checkbox.
46
Chapter 4. Browser Operation
Manual Input
Use this section to specify the eco PDU’s date and time manually.
Click the calendar icon and click the calendar entry for the date.Key the time into the Time field, using the HH:MM:SS (hours, minutes,
seconds) format.
Note: This section is only enabled when auto adjustment (in the Network Time
section) is disabled (the checkbox is unchecked).
As an alternative to specifying the date and time by entering them into the date and time fields, you can click to put a check in the Sync with PC checkbox, in which case the eco PDU will take its date and time settings from the locally connected PC.
Network Time
To have the time automatically synchronized to a network time server, do the following:
1. Check the Enable auto adjustmen t checkbox.
2. Drop down the time server list to select your preferred time server
– or – Check the Preferred custom server IP checkbox, and key in the IP address
of the time server of your choice.
3. If you want to configure an alternate time server, check the Alternate time
server checkbox, and repeat step 2 for the alternate time server entries.
4. Key in your choice for the number of days between synchronization
procedures.
Finishing Up
When you have finished making your settings on this page, click Save. After you have saved your changes, if you want to synchronize immediately,
click Adjust Time Now.
47
eco PDU PE Series User Manual

Security

The Security page controls access to the eco PDU device.

Login Failures

Allowed sets the number of consecutive failed login attempts that are
permitted from a remote user.
Timeout sets the amount of time a remote user must wait before
attempting to login again after exceeding the number of allowed failures.

Working Mode

If ICMP is enabled, the eco PDU device can be pinged. If it is not
enabled, the device cannot be pinged. The default is Enabled.
When you have finished making your settings on this page, click Save.
48
Chapter 4. Browser Operation

Account Policy

The Account Policy section governs policies in regard to usernames and passwords.
Check a policy and enter the required information in the appropriate fields.
Item Description
Minimum Username Length Sets the minimum number of characters required for
a username. Acceptable values are from 1–16.
Minimum Password Length Sets the minimum number of characters required for
a password. Acceptable values are from 1–16.
Password Must Contain At Least Checking any of these items requires users to include
Disable Duplicate Login Check this to prevent users from logging in with the
at least one of the specified items in their password. Note: This policy does not affect existing user
accounts. Only new user accounts created after this policy has been enabled, and users required to change their passwords are affected.
same account at the same time.
49
eco PDU PE Series User Manual

Login String / IP Filter / Mac Filter

Login String
The Login String entry field is used to specify a login string (in addition to the IP address) that users must include when accessing the eco PDU device with a browser. For example:
192.168.0.126/abcdefg
The following characters are allowed:
0–9 a–z A–Z ~ ! @ $ * ( ) _ ‘ ,
The following characters are not allowed:
& ^ { } ‘ ’ < > | " % ” : / ? # \ [Space] + - = [ ] ; Compound characters (É Ç ñ ... etc.)
Note: 1. There must be a forward slash between the IP address and the string.
2. If no login string is specified here, anyone will be able to access the eco PDU device login page using the IP address alone. This makes your installation less secure.
For security purposes, we recommend that you change this string occasionally.
50
Chapter 4. Browser Operation
IP Filter / MAC Filter
If any filters have been configured, they appear in the IP Filter and/or MAC Filter list boxes.
IP and MAC Filters control access to the eco PDU based on the IP and/or MAC addresses of the client computers attempting to connect. A maximum of 5 IP filters and 5 MAC filters are allowed.
To enable IP and/or MAC filtering, click to put a check mark in the IP Filter Enable and/or MAC Filter Enable checkbox.
If the include button is checked, all the addresses within the filter range are
allowed access; all other addresses are denied access.
If the exclude button is checked, all the addresses within the filter range
are denied access; all other addresses are allowed access.
Adding Filters
To add an IP filter, do the following:
1. Click Add. A dialog box sim ilar to the one belo w appears:
2. Specify the filter address in the dialog box (for example, 192.168.0 .2 00),
then click OK. A second dialog box, similar to the one below, appears:
51
eco PDU PE Series User Manual
3. To filter a single IP address, key in the same address as the start IP. To filter a continuous range of addresses, key in the end number of the range (for example, 192.168.0.225).
4. After filli ng in the address, click OK.
Repeat these steps for any additional IP addresses you want to filter.
To add a MAC filter, do the following:
1. Click Add. A dialog box similar to the one below appears:
2. Specify the MAC address in the dialog box (for example, 001074670000), then click OK.
Repeat these steps for any additional MAC addresses you want to filter.
IP Filter / MAC Filter Conflict
If there is a conflict between an IP filter and a MAC filter – for example, where a computer’s IP address is allowed by the IP filter but its MAC address is excluded by the MAC filter – then that computer’s access is blocked.
In other words, if either filter blocks a computer, then the computer is blocked, no matter what the other filter is set to.
Modifying Filters
To modify a filter, select it in the IP Filter or MAC Filter list box and click Modify. The Modify dialog box is similar to the Add dialog box. When it comes up, simply delete the old address(es) and replace it with the new one(s).
Deleting Filters
To delete a filter, select it in the IP Filter or MAC Filter list box and click Delete.
52
Chapter 4. Browser Operation

Authentication & Authorization

The Authentication & Authorization page is used to set up login authentication and authorization management from external sources.
Disable Local Authentication
Selecting this option will disable login authentication locally on the eco PDU. The device can only be accessed using RADIUS authentication.
53
eco PDU PE Series User Manual
RADIUS Settings
To allow authentication and authorization for the eco PDU device through a RADIUS server, do the following:
1. Check Enable.
2. Fill in the IP addresses and servi ce port numbers for the Preferred and Alternate RADIUS servers. The default port number for the Preferred server is 1812; the default port number for the Alternate server is 1645.
Note: Make sure that the port nu mbers you specify here m atch the port
numbers used by the RADIUS servers.
3. In the Timeout field, set the time in seconds that the eco PDU device waits for a RADIUS server reply before it times out.
4. In the Retries field, set the number of allowed retries for attempting to connect to the RADIUS server.
5. In the Shared Secret field, key in the character string that you want to use for authentication between the eco PDU device and the RADIUS Server.
6. On the RADIUS server, set the entry for each user as follows:
su/xxxx
Where xxxx represents the Username given to the user when the account was created on the eco PDU device. The user’s access rights are the ones assigned for the eco PDU device, as well. (See User Information, page 38.)
Note: su/user supports view ports only; su/administrator supports all eco PDU
functions.
54
Chapter 4. Browser Operation

Private Certificate

When logging in over a secure (SSL) connection, a signed certificate is used to verify that the user is logging in to the intended site. For enhanced security, the Private Certificate section allows you to use your own private encryption key and signed certificate, rather than the default ATEN certificate.
There are two methods for establishing your private certificate: generating a self-signed certificate; and importing a third-p a rty certificate authority (CA) signed certificate.
Generating a Self-Signed Certificate
If you wish to create your own self-signed certificate, a free utility – openssl.exe – is available for download over the web.
Obtaining a CA Signed SSL Server Certificate
For the greatest security, we recommend using a third party certificate authority (CA) signed certificate. To obtain a third party signed certificate, go to a CA (Certificate Authority) website to apply for an SSL certificate. After the CA sends you the certificate and private encryption key, save them to a convenient location on your computer.
Importing the Private Certificate
To import the private certificate, do the following:
1. Click Browse to the right of Private Key; browse to where your private
encryption key file is located; and select it.
2. Click Browse to the right of Certificate; browse to where your certificate
file is located; and select it.
3. Click Upload to complete the procedure.
Note: 1. Clicking Restore Default returns the device to using the default
ATEN certificate.
2. Both the private encryption key and the signed certificate must be imported at the same time.
When you have finished making your settings on this page, click Save.
55
eco PDU PE Series User Manual

Maintenance

The Maintenance function is used to upgrade the eco PDU’s firmware, and to backup and restore the device’s configuration settings.

Firmware File

When you click the Maintenance tab, the display opens with the Firmware Upgrade menu page, which looks similar to the one below:
A description of the items shown in this panel are given in the table, below:
Item Description
Check Main Firmware Version
Name Lists all of the eco PDU devices. Click to put a check in the
F/W Version Displays the eco PDU’s current firmware version. Filename As new versions of the firmware become available, they are
Upgrade Click this button to upgrade the firmware of the selected devices.
56
If you enable Check Main Firmware Version, the eco PDU’s current firmware level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.
checkbox of the device’s whose firmware you want to upgrade.
posted on our website and can be downloaded to a convenient location on your computer. Click the Browse button to select the downloaded upgrade file.
Chapter 4. Browser Operation
Upgrading the Firmware
To upgrade the firmware refer to the screenshot on the preceding page, and do the following:
1. Go to our website and downlo a d the new fi rm ware file to a convenient location on your computer.
2. Click the Browse button; navigate to where the firmware file is located and select it.
3. Click Upgrade to start the upgrade procedure. If you enabled Check Main Firmware Version the current firmware
level is compared with that of the upgrade file. If the current version is equal to or higher than the upgrade version, a popup message appears, to inform you of the situation and stops the upgrade procedure.
If you didn't enable Check Main Firmware Version, the upgrade file is
installed without checking what its level is.
Once the upgrade completes successfully, the switch resets itself.
4. Log in again, and check the firmware version to be sure it is the new one.
Firmware Upgrade Recovery
Should the eco PDU’s firmware upgrade procedure fail, and the device becomes unusable, the following firmware upgrade recovery procedure will resolve the problem:
1. Power off the device.
2. Press and hold the Reset Switch in (see page 8).
3. While holding the Reset Switch in, power the switch back on.
This causes the switch to use the original factory installed main firmware version. Once the switch is operational, you can try upgrading the main firmware again.
57
eco PDU PE Series User Manual

Backup/Restore

Selecting Backup/Restore on the menu bar gives you the ability to back up the switch’s configuration and user profile information:
Backup
To backup the device’s settings do the following:
1. In the Password field, key in a password for the file.
Note: Entering a password is optional. If you do enter a password, make a
note of it, since you will need it to be able to restore the file.
2. Click Save.
3. When the browser asks what you wan t to do wi th the file, select Save to disk; then save it in a convenient location.
Restore
To restore a previous backup, do the following:
1. Click Browse; navigate to the file and select it.
Note: If you renamed the fil e , you can leave the new name. There is no
need to return it to its original name.
2. In the Password field, key in the same password that you used to save the file.
Note: If you did not set a password when you created the backup file, you
can omit this step.
3. Select as many of the options that are presented as you wish to restore.
4. Click Restore. After the file is restored, a message appears to inform you that the
procedure succeeded.
58

Appendix

Safety Instructions

General

This product is for indoor use only.Read all of these instructions. Save them for future reference.Follow all warnings and instructions marked on the device.Do not place the device on any unstable surface (cart, stand, table, etc.). If
the device falls, serious damage will result.
Do not use the device near water.Do not place the device near, or over, radiators or heat registers.The device cabinet is provided with slots and openings to allow for
adequate ventilation. To ensure reliable operation, and to protect against overheating, these openings must never be blocked or covered.
The device should never be placed on a soft surface (bed, sofa, rug, etc.) as
this will block its ventilation openings. Likewise, the device should not be placed in a built in enclosure unless adequate ventilation has been provided.
Never spill liquid of any kind on the device.Unplug the device from the wall outlet before cleaning. Do not use liquid
or aerosol cleaners. Use a damp cloth for cleaning.
The device should be operated from the type of power source indicated on
the marking label. If you are not sure of the type of power available, consult your dealer or local power company.
To prevent damage to your installation it is important that all devices are
properly grounded.
The device is equipped with a 3-wire grounding type plug. This is a safety
feature. If you are unable to insert the plug into the outlet, contact your electrician to replace your obsolete outlet. Do not attempt to defeat the purpose of the grounding-type plug. Always follow your local/national wiring codes.
The equipment should be installed near the wall socket outlet and the
disconnect device (appliance coupler) should be readily accessible.
Do not allow anything to rest on the power cord or cables. Route the
power cord and cables so that they cannot be stepped on or tripped over.
59
eco PDU PE Series User Manual
To help protect your system from sudden, transient increases and
decreases in electrical power, use a surge suppressor, line conditioner, or uninterruptible power supply (UPS).
Position system cables and power cables carefully; Be sure that nothing
rests on any cables.
When connecting or disconnecting power to hot pluggable power supplies,
observe the following guidelines: Install the power supply before connecting the power cable to the
power supply.
Unplug the power cable before removing the power supply.If the system has multiple sources of power, disconnect power from the
system by unplugging all power cables from the power supplies.
Never push objects of any kind into or through cabinet slots. They may
touch dangerous voltage points or short out parts resulting in a risk of fire or electrical shock.
Do not attempt to service the device yourself. Refer all servicing to
qualified service personnel.
If the following conditions occur, unplug the device from the wall outlet
and bring it to qualified service personnel for repair.
The power cord or plug has become damaged or frayed.Liquid has been spilled into the device.The device has been exposed to rain or water.The device has been dropped, or the cabinet has been damaged.The device exhibits a distinct change in performance, indicating a need
for service.
The device does not operate normally when the operating instructions
are followed.
Only adjust those controls that are covered in the operating instructions.
Improper adjustment of other controls may result in damage that will require extensive work by a qualified technician to repair.
Do not connect the RJ-11 connector marked “Sensor” to a public
telecommunication network.
60
Appendix

Rack Mounting

Before working on the rack, make sure that the stabilizers are secured to
the rack, extended to the floor, and that the full weight of the rack rests on the floor. Install front and side stabilizers on a single rack or front stabilizers for joined multiple racks before working on the rack.
Always load the rack from the bottom up, and load the heaviest item in the
rack first.
Make sure that the rack is level and stable before extending a device from
the rack.
Use caution when pressing the device rail release latches and sliding a
device into or out of a rack; the slide rails can pinch your fingers.
After a device is inserted into the rack, carefully extend the rail into a
locking position, and then slide the device into the rack.
Do not overload the AC supply branch circuit that provides power to the
rack. The total rack load should not exceed 80 percent of the branch circuit rating.
Make sure that all equipment used on the rack – including power strips and
other electrical connectors – is properly grounded.
Ensure that proper airflow is provided to devices in the rack.Ensure that the operating ambient temperature of the rack environment
does not exceed the maximum ambient temperature specified for the equipment by the manufacturer
Do not step on or stand on any device when servicing other devices in a
rack.

The eco PDU’s Main Power Cord

Use the power cord supplied with this package. If it becomes necessary to replace the cord supplied with this package, be sure to use a cord of at least the same standard as the one provided.

Securing the Power Cables

To secure the cables in the eco PDU’s power outlets, use only the
ATEN Lock-Your-Plug cable holders that have been specifically designed to work with the eco PDU. Using any other kind of cable securing device could be highly dangerous. Please contact your ATEN dealer for information about ATEN Lock-Your-Plugs.
61
eco PDU PE Series User Manual

Technical Support

International

For online technical support – including troubleshooting, documentati on,
and software updates: http://eservice.aten.com
For telephone support, see Telephone Support, page iii

North America

Email Support support@aten-usa.com Online
Technical Support
Telephone Support 1-888-999-ATEN ext 4988
When you contact us, please have the following information ready beforehand:
Product model number, serial number, and date of purchase.Yo ur computer configuration, including operating system, revision level,
expansion cards, and software.
Any error messages displayed at the time the error occurred.The sequence of operations that led up to the error.Any other information you feel may be of help.
Troubleshooting Documentation Software Updates
http://www.aten-usa.com/support
62
Appendix

IP Address Determination

If you are an administrator logging in for the first time, you need to access the eco PDU in order to give it an IP address that users can connect to. There are two methods to choose from. In each case, your client computer must be on the same network segment as the eco PDU. After you have connected and logged in you can give the device its fixed network address. (See Device Management, page 40.)

Method 1:

For computers running Windows, an IP address can be determined and/or assigned with the IP Installer utility. The utility can be obtained from the
Download area of our web site or from the software CD. Look under Driver/ SW, and the model of your device. After downloading the utility to your
computer, do the following:
1. Unzip the contents of IPInstaller.zip to a directory on your hard drive.
2. Go to the directory that you unzipped th e IPInstaller program to and run
IPInstaller.exe. A dialog box similar to the one below appears:
(Continues on next page.)
63
eco PDU PE Series User Manual
(Continued from previous page.)
3. Select the device in the Device List.
Note: 1. If the list is empty, or your device doesn't appear, click
Enumerate to refresh the Device List.
2. If there is more than one device in the list, use the MAC address to pick the one you want. The eco PDU's MAC address is located on its bottom panel.
4. Select either Obtain an IP address automatically (DHCP), or Specify an IP address. If you chose the latter, fill the IP Address, Subnet Mask, and Gateway fields with the information appropriate to your network.
5. Click Set IP.
6. After the IP address shows up in the Device List, click Exit to end the program.

Method 2:

1. Set your computer's IP address to 192.168.0.XXX
Where XXX represents any number or numbers except 60. (192.168.0.60) is
the default address of the eco PDU.)
2. Specify the device’s default IP address (192.168.0.60) in your browser, and you will be able to connect.
3. Assign a fixed IP address for the device (see IPv4 Configuration, page 42), that is suitable for the network segment that it resides on.
4. After you log out, reset your computer's IP address to its original value.
5. Once you have logged in, go to Network Settings to set up the permanent IP environment (see IPv4 Configuration, page 42).

Method 3:

ALTUSEN eco Sensors allows you to determine/assign an IP address in order to configure a PDU device and monitor power status of the equipment connected to it. ALTUSEN eco Sensors can be obtained from the Download area of the ATEN web site.
64

Specifications

PE5216A / PE6216A

Function PE5216A PE6216A
Power Outlets Direct 16 Connectors Power Inlet 1 x IEC 320 C20
Power
Outlets
Sensor 2 x RJ-11 LAN 1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs Outlet Status NA 16 (Orange)
PDU Current / IP 2 (Green) Current / IP Address 3-digit 7-segment (Orange) Power 1 (Blue) LAN 10/100M 1 (Orange / Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker Button 1 x Pushbutton I/P Rating 100–120V~; 50–60Hz; 16A (UL), 20A (Max.) Power Capacity 2.4kW O/P Rating Per Port NEMA 5-15R 100–120V~; 50–60Hz; 12A (UL), 15A (Max.)
Total 100–120V~; 50–60Hz; 16A (UL), 20A (Max.) Environment Operating Temperature
Storage Temperature
Humidity 0–80% RH Non-condensing Physical
Properties
Housing Metal
Weight 3.5 kg 3.7 kg
Dimensions (L x W x H) 132.48 x 6.60 x 4.40 cm
NEMA 14 x NEMA 5-15R; 2 x NEMA 5-20R IEC NA
Link 1 (Green)
NEMA 5-20R 100–120V~; 50–60Hz; 16A (UL), 20A (Max.)
o
0–50
C
o
-20–60
C
Appendix
65
eco PDU PE Series User Manual

PE5216B / PE6216B / PE5324B / PE6324B

Function PE5216B PE6216B PE5324B PE6324B
Power Outlets Direct 16 24 Connectors Power Inlet / Cord 1 x IEC 320 C20 (inlet) 1 x NEMA L6-30P (cord)
Power
Outlets
Sensor 2 x RJ-11 LAN 1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs Outlet Status NA 16 (Orange) NA 24 (Orange)
PDU Current / IP 2 (Green) Current / IP Address 3-digit 7-segment (Orange) Power 1 (Blue) LAN 10/100M 1 (Orange / Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker 2 x UL 489 Breaker Button 1 x Pushbutton I/P Rating 100–240V~; 50–60Hz;
Power Capacity 4.2kW 6.2kW O/P Rating Per Port IEC 320 C13 100–240V~; 50–60Hz;
Total 100–240V~; 50–60Hz; 16A
Environment Operating Temperature
Storage Temperature
Humidity 0–80% RH Non-condensing Physical
Properties
Housing Metal
Weight 3.5 kg 3.7 kg 6.0 kg 6.3 kg
Dimensions (L x W x H) 132.48 x 6.60 x 4.40 cm 177.50 x 6.60 x 4.40 cm
NEMA NA IEC 14 x IEC 320 C13
Link 1 (Green)
IEC 320 C19 100–240V~; 50–60Hz;
2 x IEC 320 C19
16A (UL), 20A (Max.)
12A (UL), 15A (Max.)
16A (UL), 20A (Max.)
(UL), 20A (Max.)
100–240V~; 50–60Hz; 24A
o
0–50
C
o
-20–60
21 x IEC 320 C13
3 x IEC 320 C19
100–240V~; 50–60Hz;
24A (UL), 30A (Max.)
100–240V~; 50–60Hz;
12A (UL), 15A (Max.)
100–240V~; 50–60Hz;
12A (UL), 15A (Max.)
(UL), 30A (Max.)
C
66
Appendix

PE5216G / PE6216G / PE5324G / PE6324G

Function PE5216G PE6216G PE5324G PE6324G
Power Outlets Direct 16 24 Connectors Power Inlet / Cord 1 x IEC 320 C20 (inlet) 1 x IEC 60309 (cord)
Power
Outlets
Sensor 2 x RJ-11 LAN 1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs Outlet Status NA 16 (Orange) NA 24 (Orange)
Bank Current / IP 2 (Green) Current / IP Address 3-digit 7-segment (Orange) Power 1 (Blue) LAN 10/100M 1 (Orange / Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Non-fuse Breaker 2 x UL 489 Breaker Button 1 x Pushbutton I/P Rating 100–240V~; 50–60Hz;
Power Capacity 3.7kW 7.4kW O/P Rating Per Port IEC 320 C13 100–240V~; 50–60Hz; 10A 100–240V~; 50–60Hz; 10A
Total 100–240V~; 50–60Hz;
Environment Operating Temperature
Storage Temperature
Humidity 0–80% RH Non-condensing Physical
Properties
Housing Metal
Weight 3.5 kg 3.7 kg 6.0 kg 6.3 kg
Dimensions (L x W x H) 132.48 x 6.60 x 4.40 cm 177.50 x 6.60 x 4.40 cm
NEMA NA IEC 14 x IEC 320 C13
Link 1 (Green)
IEC 320 C19 100–240V~; 50–60Hz; 15A 100–240V~; 50–60Hz; 15A
2 x IEC 320 C19
16A (Max.)
15A (Max.)
-20–60oC
21 x IEC 320 C13
3 x IEC 320 C19
100–240V~; 50–60Hz;
32A (Max.)
100–240V~; 50–60Hz;
30A (Max.)
o
0–40
C
67
eco PDU PE Series User Manual

PE5324kJA

Function PE5324kJA
Power Outlets Direct 24 Connectors Power Cord 1 x NEMA L5-30P
Power
Outlets
Sensor 2 x RJ-11 LAN 1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs Outlet Status NA
PDU Current / IP 2 (Green) Current / IP Address 3-digit 7-segment (Orange) Power 1 (Blue) LAN 10/100M 1 (Orange / Green)
Sensor 2 (Green) Outlet Power Indicator 3 (Red)
Switches Reset 1 x Semi-recessed Pushbutton
Power 2 x UL489 Breaker Button 1 x Pushbutton I/P Rating 100–120V~; 50–60Hz; 30A (Max.) Power Capacity 3kw (Max) O/P Rating Per Port NEMA 5-15R 100–120V~; 50–60Hz; 14A (PSE), 15A (Max.)
Total 100–120V~; 50–60Hz; 30A (Max), 28A (PSE) Environment Operating Temperature
Storage Temperature
Humidity 0–80% RH Non-condensing Physical
Properties
Housing Metal
Weight 6.50 kg
Dimensions (L x W x H) 177.50 x 6.60 x 4.40 cm
NEMA Total: 24 x NEMA 5-15R Twist Lock
IEC NA
Link 1 (Green)
Bank 1–1: 8 x NEMA 5-15R Twist Lock Bank 1–2: 8 x NEMA 5-15R Twist Lock
Bank 2: 8 x NEMA 5-15R Twist Lock
o
0–50
C
-20–60oC
68
Appendix

PE6324JA2

Function PE6324JA2
Power Outlets Direct 24 Connectors Power Cord 1 x NEMA L5-30P
Power
Outlets
Sensor 2 x RJ-11 LAN 1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs Outlet Status 24 (Orange)
PDU Current / IP 2 (Green) Current / IP Address 3-digit 7-segment (Orange) Power 1 (Blue) LAN 10/100M 1 (Orange / Green)
Sensor 2 (Green)
Switches Reset 1 x Semi-recessed Pushbutton
Power 2 x 16A Slim Breakers Button 1 x Pushbutton I/P Rating 100–120V~; 50–60Hz; 24A (UL) 30A (Max) Power Capacity 3.6kw VA (Max) 2.9kw VA (UL de-rated) O/P Rating Per Port NEMA 5-15R 100–120V~; 50–60Hz; 15A (Max); 12A (UL de-rated)
Total 100–120V~; 50–60Hz; 24A (UL); 30A (Max) Environment Operating Temperature
Storage Temperature
Humidity 0–80% RH Non-condensing Physical
Properties
Housing Metal
Weight TBD
Dimensions (L x W x H) 177.50 x 6.60 x 4.40 cm
NEMA Total: 24 x NEMA 5-15R
Link 1 (Green)
Bank 1–1: 8 x NEMA 5-15R Bank 1–2: 8 x NEMA 5-15R
Bank 2: 8 x NEMA 5-15R
o
0–50
C
-20–60oC
69
eco PDU PE Series User Manual

Administrator Login Failure

If you are unable to perform an Administrator login (because the Username and Password information has become corrupted, or you have forgotten it, for example), you can clear the login information with the following procedure:
1. Power off the eco PDU and remove its housing.
2. Short the jumper lab eled J3 (PIN10 and PIN9).
3. Power on the eco PDU.
4. After the beep indicates successfully powered on, power off the switch.
5. Remove the jumper cap from J3.
6. Close the housing and start the eco PDU. After you start, you can use the default Username and Password to log in.
70
Appendix

Limited Warranty

ATEN warrants this product against defects in material or workmanship for a period of one (1) year from the date of purchase. If this product proves to be defective, contact ATEN's support department for repair or replacement of your unit. ATEN will not issue a refund. Return requests can not be processed without the original proof of purchase.
When returning the product, you must ship the product in its original packaging or packaging that gives an equal degree of protection. Include your proo f of purchase in th e packaging and the RMA number clearly marked on the outside of the package.
This warranty becomes invalid if the factory-supplied serial number has been removed or altered on the product.
This warranty does not cover cosmetic damage or damage due to acts of God, accident, misuse, abuse, negligence or modification of any part of the product. This warranty do es not cover damage due to improper operation or maintenance, connection to improper equipment, or attempted repair by anyone other than ATEN. This warranty does not cover products sold AS IS or WITH FAULTS.
IN NO EVENT SHALL ATEN'S LIABILITY EXCEED THE PRICE PAID FOR THE PRODUCT. FURTHER, ATEN SHALL NOT BE RESPONSIBLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING FROM THE USE OF THE PRODUCT, ITS ACCOMPANYING SOFTWARE, OR ITS DOCUMENTATION. ATEN SHALL NOT IN ANY WAY BE RESPONSIBLE FOR, WITHOUT LIMITATION, LOSS OF DATA, LOSS OF PROFITS, DOWNTIME, GOODWILL, DAMAGE OR REPLACEMENT OF EQUIPMENT OR PROPERTY, AND ANY EXPENSES FROM RECOVERY, PROGRAMMING, AND REPRODUCTION OF ANY PROGRAM OR DATA.
ATEN makes no warranty or representation, expressed, implied, or statutory with respect to its products, contents or use of this documentation and all accompanying software, and specifically disclaims its quality, performance, merchantability, or fitness for any particular purpose.
ATEN reserves the right to revise or update its product, software or documentation without obligation to notify any individual or entity of such revisions, or update.
For details about extended warranties, please contact one of our dedicated value added resellers.
71
eco PDU PE Series User Manual
This Page Intentionally Left Blank
72
Loading...