Aten eco DC User Manual

eco DC
Energy & DCIM Management Web GUI User Manual
eco DC User Manual
Set the maximum permissible breaker protection in the building circuitry to the current rating specified on the rating plate. Observe all national regulations and safety codes as well as deviations for breakers.
Only connect the PE Device to a grounded power outlet or a grounded system!
Make sure that the total current input of the connected systems does not exceed the current rating specified on the rating plate of the PE Device.
There is a risk of explosion if the battery is replaced with an incorrect type. Dispose of used batteries according to the relevant instructions.

PE Device Safety Notice

User Information

Be sure to register your product at our online support center:
International http://eservice.aten.com

Telephone Support

For telephone support, call this number:
International 886-2-8692-6959
China 86-400-810-0-810
Japan 81-3-5615-5811
Korea 82-2-467-6789
North America 1-888-999-ATEN ext 4988
1-949-428-1111
ii
eco DC User Manual

User Notice

All information, documentation, and specifications contained in this manual are subject to change without prior notification by the manufacturer. The manufacturer makes no representations or warranties, either expressed or implied, with respect to the contents hereof and specifically disclaims any warranties as to merchantability or fitness for any particular purpose. Any of the manufacturer's software described in this manual is sold or licensed as is. Should the programs prove defective following their purchase, the buyer (and not the manufacturer, its distributor, or its dealer), assumes the entire cost of all necessary servicing, repair and any incidental or consequential damages resulting from any defect in the software.
The manufacturer of this system is not responsible for any radio and/or TV interference caused by unauthorized modifications to this device. It is the responsibility of the user to correct such interference.
The manufacturer is not responsible for any damage incurred in the operation of this system if the correct operational voltage setting was not selected prior to operation. PLEASE VERIFY THAT THE VOLTAGE SETTING IS CORRECT BEFORE USE.

Product Information

For information about all ATEN products and how they can help you connect without limits, visit ATEN on the Web or contact an ATEN Authorized Reseller. Visit ATEN on the Web for a list of locations and telephone numbers:
International http://www.aten.com
North America http://www.aten-usa.com
iii
eco DC User Manual
Contents
PE Device Safety Notice. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Online Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Telephone Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
User Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Product Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
About this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viii
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ix
Chapter 1.
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 2.
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installing eco DC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 3.
Logging In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
The Web Browser Main Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Quick Step-by-Step Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Chapter 4.
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dashboard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Widgets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Introduction
Installation
Post-installation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Desktop Service Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
First-time Setup
Page Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Energy
Quick View Color Scale. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Available Power Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Door Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Power Usage Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Rack Power Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
iv
eco DC User Manual
Heat Load Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Thermal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Inlet-Outlet Temperature Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Rack Inlet Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Rack Outlet Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Thermal Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Inlet Differential Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Pressure Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Cold Inlet Dew Point Temperature. . . . . . . . . . . . . . . . . . . . . . . . .37
Cold Inlet Relative Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Humidity Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
All Widgets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Export . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Lock / Unlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Hide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Maximize Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Power Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Banks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Outlet Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Group Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Generate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Power / Thermal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Billing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Adding a Power-on / Power-off Schedule . . . . . . . . . . . . . . . . . . . . . 55
Editing a Power-on / Power-off Schedule . . . . . . . . . . . . . . . . . . . . . . 58
Deleting Schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Chapter 5.
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
User
Accounts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Selecting an Account . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Add User Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
User Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Domain Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Authentication Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
v
eco DC User Manual
External Authentication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Sessions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chapter 6.
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Data Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Firmware Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Power Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Chapter 7.
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Database . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Device
Adding Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Bank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Outlet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Shutdown Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
POP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Adding Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Adding Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Run Upgrade Task Now . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Search & Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Bulk Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
System
Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
SNMP trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
SMTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
SMTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Email Notification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Syslog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
License . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Access. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
vi
eco DC User Manual
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Chapter 8.
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Log
System Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
Device Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
Appendix
Technical Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
International. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113
Trusted Certificates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114
ecoDC Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117
Config Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117
Database Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
Restore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
View License . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Database Migration Tool. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
SSO HTML . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
SSO HTML Sample Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
vii
eco DC User Manual

About this Manual

This user manual is provided to help you get the most out of your eco DC. It covers all aspects of the application, including its installation, configuration, and operation:
Applications covered in this manual include:
Models
eco DC Energy & DCIM Management Web GUI
Product Names
An overview of the information found in the manual is provided below.
Chapter 1, Introduction, Introduces you to the eco DC, its purpose, features, and functions.
Chapter 2, Installation, Provides the necessary steps to install eco DC.
Chapter 3, First-time Setup, Provides the basic operation instructions for
first-time setup of eco DC.
Chapter 4, Energy, Guides you through how to monitor the energy used via ATEN PDUs.
Chapter 5, User, Guides you through how to manage the two different types of user login accounts: administrator and user.
Chapter 6, Device, Covers how to configure the devices, eco PDUs, managed.
Chapter 7, System, Guides you through other system settings of eco DC.
Chapter 8, Log, Describes the system and device logs recorded by eco DC.
Appendix, Provides certificate information and utility details regarding the
eco DC.
Note:
Read this manual thoroughly and follow the installation and operation
procedures carefully to prevent any damage to the unit or connected devices.
ATEN regularly updates its product documentation for new features and
fixes. For an up-to-date eco DC documentation, visit
http://www.aten.com/global/en/
viii

Conventions

This manual uses the following conventions:
Monospaced Indicates text that you should key in.
[ ] Indicates keys you should press. For example, [Enter] means to
press the Enter key. If keys need to be chorded, they appear together in the same bracket with a plus sign between them: [Ctrl+Alt].
1. Numbered lists represent procedures with sequential steps.
Bullet lists provide information, but do not involve sequential steps.
> Indicates consecutive selecting options (such as on a menu or
dialog box). For example, Start menu, and then select Run.
Indicates critical information.
eco DC User Manual
>
Run means to open the Start
ix
eco DC User Manual
This Page Intentionally Left Blank
x
Chapter 1

Introduction

Overview

The ATEN eco DC Web GUI has been developed to work with ATEN PE series green energy power distribution units (PDUs) to effectively increase the efficiency of data centers’ power usage. Eco DC is a web-based GUI allowing users to manage and control PDUs through a web browser. There is no additional software to install or setup steps needed to manage your ATEN PDUs. The eco DC can run in any OS platform allowing users to easily manage the power consumption of a data center through intuitive interface with easy to read graphics.
Coupled with sensor-enabled eco PDUs*, the eco DC web GUI can give you means to assess, diagnose, and estimate how much energy you are using and ultimately save. Following the suggestions generated by the sensor-enabled system allows you to optimize energy usage to save energy without harming your IT equipment’s reliability. The ATEN eco DC web GUI provides secure and centralized (single portal, single login) access, administration, and management for up to 3000 PE devices over the network – local and worldwide – anywhere and anytime.
Because ATEN eco DC offers a single, integrated web-based GUI to manage all your devices, users no longer need to learn the interface for each individual device or remember every device’s IP address, making system management easier and more efficient.
1
eco DC User Manual
By consolidating the management of your ATEN devices, eco DC allows every device to be accessed and controlled by means of a single login. Its ability to manage all outlets in different ATEN devices makes eco DC the ideal solution for the power management of large data centers and branch office server rooms located in several remote locations within the same intranet.
ATEN eco DC is able to automatically discover all ATEN devices within the same intranet and has the ability to monitor/manage them. The web GUI provides monitoring/managing of PE device outlet power ON/OFF/Reboot, sequential ON/OFF of outlet, current / kWH / environmental monitoring at PDU/outlet level, name of outlet, current / kWH / environmental sensor threshold setting/alert, etc., through SNMP. Threshold exceeding alerts are also available through Syslog/SMTP.
* See Compatible Products on eco DC’s web page for a list of compatible
ATEN sensor-enabled eco PDUs.
ATEN’s eco DC offers the full functionality capable of managing the PDUs through SNMP. This allows multiple users to log to the web GUI concurrently to manage PDUs in different authorized room, floors, or buildings, making distributed PDU management much more efficient under one centralized environment. With two levels of authorized user accounts and permissions, users can be configured to monitor and manage different functions of each PDU. Having this new web-based version allows data centers to optimize their performance and centralize their management.
2
Chapter 1. Introduction

Features

Automatic discovery of all ATEN devices within an intranet
Remote real-time power measurement and monitoring
PDU level current / voltage / power dissipation / power consumption
Outlet On / Off / Recycle status
Circuit breaker status monitoring
Windows pop-out to easily monitor the data center’s status’
Remote real-time power outlet management*
Power outlet On / Off / Cycle switching by outlet or user-defined group
Power outlet On / Off / Cycle switching with pre-defined schedule
User-defined outlet level delays for sequential power up
Current / Voltage / Power Dissipation / Power Consumption threshold
level setting
User access assignment for every outlet
Name assignment to individual outlets
Remote real-time environment sensor monitoring
Temperature / Temperature + Humidity reading
Temperature and Humidity threshold level setting
Plotting / Monitoring of all PE devices
Add data center server racks
Add PE devices for each server rack
Manage device / device outlet status for each plot
Essential indices including Rack Intake Temperature, Rack Exhaust
Temperature, Rack Equipment, and Temperature Difference
Power analysis report for optimizing data center energy management –
including power usage, power load, power cost, CO2 cost, power capacity and trends
Exceed threshold alert through SMTP and Syslog
3-phase PDU compatibility — 3-phase power distribution for managing
data centers with heavy workloads
Cascade support — can monitor PDUs cascaded via Ethernet ports (1 x 1
Gb + 1 x 100M)
Syslog provision
3
eco DC User Manual
Two-level password security
Strong security features include password protection and advanced
encryption technologies – 128-bit SSL
Supports online UPS and SNMP Card
Real-time status charts for Current / Voltage / Wattage remote monitoring
Note: Not all functions are supported by all ATEN eco PDU PE models.
Please see , page 6, and your eco PDU PE User Manual for further details.

Requirements

Systems that the eco DC web GUI will be installed on should meet the following requirements:
Server Version Client Version
Operating System Windows 7 / Windows Server 2008 or later
CPU 2.5 GHz Quad Core 2.0 GHz Dual Core
Resolution Larger than 1440 x 900
Memory 8 GB 4 GB
Disk 1 TB NA
Network 1 Gbps Ethernet
4
Chapter 1. Introduction

Sensors

For complete energy management of an instrumented data center with the use of the ATEN eco PDU and eco DC web GUI, you should install 4 sensors for each of the racks in your data center in order to generate a complete energy­efficient data chart. Higher sensor installation density is helpful to generate more accurate data. 8-port models have 2 sensor ports. In this case, Sensor 1 needs to be installed at the intake of the rack (EA1140 or EA1240) and sensor 2 needs to be placed at the exhaust of the IT equipment of the rack (EA1140 or EA1240) or the floor (EA1340).
To get the most complete eco DC web GUI data, the recommended 2 eco PDU unit per rack sensor setup is show in the table, below:
eco PDU Port Location Part Number Sensor
eco PDU 1 Sensor 1 Intake EA1240 Temperature /
Sensor 2 Floor EA1340 Differential Pressure /
eco PDU 2 Sensor 1 Intake EA1240 Temperature /
Sensor 2 Exhaust EA1240 Temperature /
Humidity
Temperature
Humidity
Humidity
5
eco DC User Manual
This Page Intentionally Left Blank
6
Chapter 2

Installation

Before You Begin

The eco DC Web GUI can be downloaded from the ATEN website. The package requires a product key to complete the installation. Once you have downloaded and saved the installation file, follow the instructions below:

Installing eco DC

1. Double-click the eco DC setup file to open the installer. The Introduction window appears:
Click Next to continue.
2. The License Agreement window appears:
Check “I accept the terms of the license agreement” and then click Next to continue.
7
eco DC User Manual
3. The Serial Number window appears:
Enter your serial number and click Next to continue.
4. The Choose Installation Folder window appears:
Use the default directory or click Choose... to specify a location on your computer. Click Next to continue.
5. The Choose Folder Shortcut window appears:
Choose the locations you would like eco DC shortcut icons to be placed. Click Next to continue.
8
Chapter 2. Installation
6. The Configure & Setup window appears:
Key in the eco DC Server name, HTTP port, and HTTPS port, or use the default settings, and click Next to continue.
7. Two more windows will appear informing you that the configuration and server installation is OK. Click Next, and then Continue.
8. The Pre-Installation Summary window appears, review the setup information and click Install to continue.
9
eco DC User Manual
9. When the installation is finished, the Installation Complete window appears. Click Done to exit.
10
Chapter 2. Installation

Post-installation Check

After the installation, the eco DC program starts automatically (and starts automatically with every bootup).
To check that the eco DC has started, go to the Services desktop app (shown in Desktop Service Check on page 12) and see if Running is shown under the Status column.
If Running is not shown, you can click Start to start the service.
11
eco DC User Manual
Desktop Service Check
Follow the steps below to go to the Service desktop application:
1. On your windows desktop, search for the keyword Services and click to start this desktop app.
2. Scroll down the list to find the eco DC service.
12
Chapter 3

First-time Setup

Logging In

To log into the eco DC, do the following:
1. Open a web browser and type the following address:127.0.0.1
2. The eco DC login screen appears:
1. Provide a valid Username and Password.
Note: If this is the first time you are logging in, use the default Username:
administrator; and the default Password: password. For security purposes, the system will prompt you to change the password.
2. Use the drop-down menu to select your desired language.
3. Click Login to bring up the main page.
13
eco DC User Manual

The Web Browser Main Page

Once you have successfully logged in, the eco DC user interface Main Page appears. Each of the interfaces is described in the sections that follow. The look of the page varies slightly, depending on which user account is used to log in.
After users log in and are authenticated, the Web Browser Main Page comes up, with the Device - Dashboard page displayed:
Page components are discussed on the next page.
14
Chapter 3. First-time Setup

Page Components

The web page screen components are described in the table below:
No. Item Description
1 Toolbar The toolbar contains the eco DC main operation
2 Sub-toolbar The sub-toolbar contains operational sub-categories
3 Menu The menu section is another sub-category of the
4 Tabs Various tabs are available that can be selected for
5 About About provides information regarding the switch’s
6 Settings Click these buttons to select options relevant to the
7 Interactive Display Panel This is your main work area. The screens that appear
categories. The items that appear here are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
that pertain to the item selected in the toolbar. The items that appear in the sub-toolbar are determined by the user’s type, and the authorization options that were selected when the user’s account was created.
sub-toolbar. It determines which tabs are available.
interactive information/details.
current firmware version.
current session.
reflect your toolbar, sub-toolbar, menu and tab choices.
15
eco DC User Manual

Toolbar

The number and type of icons that appear on the toolbar at the top of the page are determined by the user’s type (Administrator or User) and the permissions assigned when the user’s account was created. The functions associated with each of the icons are explained in the table below:
Icon Function
Energy: This page is used to view and capture information about your
PDU and data center’s energy use. This page is available to all users.
User: This page is used to create and manage Users and Groups. It can also be used to assign devices to them. This tab is available to Administrators who have been given User Management permission. The tab doesn’t appear for other users.
Device: The Device Management page is used to add devices and configure the overall operation of the data center. This page is only available to Administrators who have been given Device Management permission. The tab doesn’t appear for other and users.
System: This page is used to manage various system options which help manage the overall operation of the eco DC web GUI. This page is available to Administrators who have been given System Management permission. The tab doesn’t appear for other and users.
Logs: This page is used to view contents of the log file. This page is available to Administrators who have been given Log permission. The tab doesn’t appear for other and users.
16
Chapter 3. First-time Setup

Settings

The Settings icons appear for all users. There are three icons that appear on the right end of the sub-toolbar. The functions associated with each of the icons are explained in the table below:
Icon Function
Preference: This icon opens a window allowing you to set personal
settings for the current user.
Idle Timeout: Sets the amount of time that can pass before the user is automatically logged out of the web session.
Max Notifications: Sets the maximum number of notifications that can appear when the Notification icon is clicked. You can set which notifications are shown here (see Events, page 112).
Preferred Page For Energy Tab: Use the drop-down menu to select the default sub-toolbar to be displayed for the Energy Toolbar.
Password: Use these settings to create a new password by checking Reset password and then key in the old password, new password, and confirm password.
Discard: Click to exit without saving changes.
Save: Click to save changes.
Notifications: This icon is used to view and delete notifications that
have been setup. Clicking the icon reveals options to view, delete, mark as read and clear all notifications. To select which notifications are received, see Events, page 112.
Exit: Click this icon to log out of the eco DC web session.
17
eco DC User Manual

Quick Step-by-Step Setup

Once you have logged in, you need to define your data center and configure various parameters before you can begin to use ATEN eco DC to monitor and manage your devices. You will need to: add PDUs and configure their threshold settings; setup the layout; add racks, and then add PDUs to the racks.
The steps below provide a quick reference to the sections of the user manual you can refer to in order to do this successfully.
1. Go to Device - Installation, and under the Device tab add ATEN PDUs (see Adding Devices, page 78).
2. Go to Device - Installation, and under the Device tab select PDUs in the sidebar and configure the Threshold Settings for each device (see Devices, page 79).
3. Go to Device - Installation, and under the Layout tab setup the data center by adding a: Data Center, Building, Floor, and then Room (see Layout, page 86).
4. Go to Device - Installation, and under the Layout tab, select a room and add racks to it, and then add the PDUs to the racks (see Adding Racks, page 88).
5. Once you have completed these steps, please proceed to Energy, page 19.
18
Chapter 4

Energy

Overview

The Energy toolbar provides four sub-toolbar options: Dashboard to view real- time power measurements and environment monitoring; Power Control to manage the power of PDUs and outlets; Analysis to generate energy usage reports; and Schedule to create group control tasks.
19
eco DC User Manual

Dashboard

The Dashboard features Widgets and Charts in the Menu. They show the overall energy and environmental information collected about your data center. The Tabs of the interactive display panel lists different tabs depending on your Menu selection. The Widgets menu lists five categories for viewing related data in the main panel: Device, Power, Thermal, Pressure, and Humidity. The Charts menu lists Current, VA, and Wattage. Each tab can be selected to display different types of information about your data center.
In the top right corner are three icons: Lock/Unlock to lock/unlock the position of all widgets on the page; Widget Settings (shown below) allow you to add/ remove widgets and lock their position on the page; and Maximize Window to pop open a new window to display the current data.
Check the widgets listed in Widget Settings to add/remove them from the Dashboard page and click Apply to save.
20
Chapter 4. Energy

Widgets

Widgets on the Dashboard display information about different parts of your data center energy and environmental usage. You can position widgets anywhere on by page by drag-and-drop, after the window has been unlocked using the Lock icon in the top right corner.You can remove widgets from the page by clicking the
Clicking the Diagnosis button opens a new window with detailed information about the data, as discussed in the sections that follow. The pages the follow discuss each of the widgets that can be added to Dashboard for monitoring. In the Diagnosis window use the left sidebar to select a room to view its data.
X
in the top right corner of its window.

Quick View Color Scale

The Diagnosis sections of Widgets use the same color scale, but with different units for each reading. For example, the Power Consumption page, under the Power, displays a scale from 0.7 – 4.3 kWh, as shown below:
Selecting a color in the scale highlights the racks with that particular reading.
Check Select All to view each rack in a color according to its reading. The racks are displayed in a color related to their status on the various scales.
21
eco DC User Manual

Device

Available Power Capacity
Displays the Average % of available power for all the racks. The Available Power Capacity uses a standard formula for rack devices:
Total Power Capacity (KWh) - Power in Use (KWh) = Available Power Capacity (KWh).
Click Diagnosis to open a window with options to view additional rack data:
22
Chapter 4. Energy
You can click each rack to display the percentage of available power for that rack. The colors represent the available power capacity for each rack displayed in 5% increments. Uncheck Select All and click a color to view the racks which are recording data within that 5% range. Use to jump to a device’s Power Control page.
Current
Displays the real-time measurement of the two devices with the minimum and maximum Current, and the average Current measurement of all devices.
23
eco DC User Manual
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Current reading for that rack. The colors represent the average, maximum, and minimum Current readings. Use to jump to a device’s Power Control page.
24
Chapter 4. Energy
Door Status
Door Open displays the open/close status of each cabinet door installed with a door sensor (EA1440, EA1441, or EA1442). GREEN: Rack Door is Closed. GRAY: No Door Sensor Installed. ORANGE: Rack Door is Open.
Click Diagnosis to open a window with options to view additional rack data:
You can click the Open, N/A, or Close radio buttons to display the racks with that reading. The colors represent the data shown readings above. After selecting a rack, use to jump to a device’s Power Control page.
25
eco DC User Manual
Power Usage Efficiency
The PUE is the ratio of the total energy used by the data center to the energy delivered to connected equipment. PUE is the inverse of data center infrastructure efficiency (DCIE).
PUE Reading DCIE Level of Efficiency
3.0 or higher 33% Very Inefficient
2.5 40% Inefficient
2.0 50% Average
1.5 67% Efficient
1.2 83% Very Efficient
26
Chapter 4. Energy
Rack Power Threshold
This displays the power threshold levels of each rack in four categories: Critical, Warning, Missing, and Normal.
Click Diagnosis to open a window with options to view additional rack data:
You can click each device in a rack to display all reading for that device. The colors represent the number of racks at different readings, as shown above. Use the radio buttons to highlight racks at each reading. After clicking a rack, use
to jump to a device’s Power Control page.
27
eco DC User Manual
Voltage
Displays the real-time measurement of the two devices with the minimum and maximum Voltage, and the average Voltage measurement of all devices.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Voltage reading for that rack. The colors represent the average, maximum, and minimum Voltage readings. Use to jump to a device’s Power Control page.
28
Chapter 4. Energy

Power

Power Consumption
Displays the real-time measurement of the two devices with the minimum and maximum Power Consumption, and the average Power Consumption measurement of all devices.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Power reading for that rack. The colors represent Power readings ranges. Select a tab to view Power Consumption by a particular time range. Use to jump to a device’s Power Control page.
29
eco DC User Manual
Heat Load Density
Displays the real-time measurement of the two racks with the minimum and maximum Heat Load Density, and the average Heat Load Density measurement of all racks.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Heat Load Density reading for that rack. The colors represent Heat Load Density ranges. Use to jump to a device’s Power Control page.
30
Chapter 4. Energy

Thermal

Inlet-Outlet Temperature Rise
This page displays the real-time inlet-outlet temperature rise values, at the minimum, maximum and the average reading. The color scale displays a range from 2–20 °C.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Inlet-Outlet Temperature Rise reading for that rack. The colors represent Inlet-Outlet Temperature Rise ranges. Use
to jump to a device’s Power Control page.
31
eco DC User Manual
Rack Inlet Temperature
This page displays the real-time rack inlet temperature values, at the minimum, maximum and average reading.The color scale displays a range from 10–45°C.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Rack Inlet Temperature reading for that rack. The colors represent Rack Inlet Temperature ranges. Use to jump to a device’s Power Control page.
32
Chapter 4. Energy
Rack Outlet Temperature
This page displays the real-time rack outlet temperature values, at the minimum, maximum, and average reading.The color scale displays a range from 10–45°C.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Rack Outlet Temperature reading for that rack. The colors represent Rack Outlet Temperature ranges. Use to jump to a device’s Power Control page.
33
eco DC User Manual
Thermal Status
This page displays the real-time thermal status values, at the minimum, maximum, and average reading.The color scale displays a range from 10– 45°C.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Thermal reading for that rack. The colors represent the average, maximum, and minimum Thermal readings. Use to jump to a device’s Power Control page.
34
Chapter 4. Energy

Pressure

Inlet Differential Pressure
This page displays the real-time inlet differential pressure values, at the minimum, maximum, and average readings. The color scale displays a range from 0–200 Pa.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Inlet Differential Pressure reading for that rack. The colors represent the average, maximum, and minimum Inlet Differential Pressure readings. Use to jump to a device’s Power Control page.
35
eco DC User Manual
Pressure Status
This page displays the real-time pressure values, at the minimum, maximum, and average reading. The color scale displays a range from 0–200 Pa.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Pressure Status reading for that rack. The colors represent the average, maximum, and minimum Pressure Status readings. Use to jump to a device’s Power Control page.
36
Chapter 4. Energy

Humidity

Cold Inlet Dew Point Temperature
This page displays the real-time cold inlet dew point temperature values, at the minimum, maximum, and average reading. The color scale displays a range from 0–15 °C.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Cold Inlet Dew Point Temperature reading for that rack. The colors represent Cold Inlet Dew Point Temperature ranges. Use to jump to a device’s Power Control page.
37
eco DC User Manual
Cold Inlet Relative Humidity
This page displays the real-time cold inlet relative humidity values, at the minimum, maximum, and average reading. The color scale displays a range from 10–90%.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Cold Inlet Relative Humidity reading for that rack. The colors represent Cold Inlet Relative Humidity ranges. Use to jump to a device’s Power Control page.
38
Chapter 4. Energy
Humidity Status
This page displays the real-time humidity values, at the minimum, maximum, and average reading. The color scale displays a range from 0–90%.
Click Diagnosis to open a window with options to view additional rack data:
You can click each rack to display the Humidity Status reading for that rack. The colors represent the average, maximum, and minimum Humidity Status readings. Use to jump to a device’s Power Control page.
39
eco DC User Manual

All Widgets

The All Widgets page displays widgets from every category listed in the tabs.
40
Chapter 4. Energy

Charts

The Charts menu lets you put data group information against time into a chart. The data group information available are Current, VA, Wattage, Temperature, and Humidity. Use the tabs to choose which particular information chart(s) are displayed.
You can place up to 4 data group’s information into a single chart for comparison, and create up to 32 charts. An example is shown:
4 data group’s current information is shown in the top-most chart while only 1 data group’s is shown in the bottom-most chart.
The button “Real-time” is a drop-down menu button. Click the menu for a list of available time periods the information is to be displayed, and click to select your option:
41
eco DC User Manual
When you move your mouse over a chart, the chart’s border becomes blue and extra options become available (top right corner). An example is shown:

Export

When you click the Export icon, a pop-up window appears. An example is shown:
42
Chapter 4. Energy
To get a report,
1. Enter a name for the Author field.
2. Click the End time field to select the date and time the data collection
ends.
3. Click to check/uncheck the Report types (multiple selection available).
4. Click to check/uncheck the Groups involved.
5. Click Apply.
The report will be a pdf file. Choose a way you wish to open the file. An example of the report is shown:
43
eco DC User Manual

Settings

When you click the Settings icon, a pop-up window appears for you to modify the chart’s settings. An example is shown:
After your modifications, click Apply to save the changes.

Delete

If you wish to delete the chart, click the Delete icon. A system confirmation message will pop-up as shown:
44
Chapter 4. Energy

Lock / Unlock

When you click this icon, you can toggle this chart between locked and unlocked. When unlocked, you can drag the chart around to re-arrange its position. The chart at the chart position you wish to drag to must also be unlocked. An example of moving a chart is shown:
If you wish to unlock/lock all the charts, click the lock icon on the top right corner of the interactive panel.

Hide

If you wish to hide the chart from displaying, click this icon.
To unhide the hidden charts, click the Chart Selection icon on the top right corner of the interactive panel for a list of charts. An example is shown:
Check the chart you wish to unhide and click Apply to bring it back.
45
eco DC User Manual

Maximize Window

Click this icon to expand the current interactive panel to view the charts.
Interactions are exactly the same except the page is bigger and that there’s a Full Screen icon to expand the interactive panel into full screen.
46
Chapter 4. Energy

Power Control

The Power Control sub-toolbar selection allows you to perform manual power management at the device or outlet level and displays detailed energy and environmental information about your data center.
Note: Not all eco PDU PE models support outlet level power management.
Please see , page 6, and your User Manual for further details.
Click on a device in the side bar and its page appears with the Voltage, Current, Power, Power Dissipation information displayed at the PDU, Bank and Outlet level:
The top bar on the page displays the PDU name, IP address, online status, and the ON, OFF and Reboot options to manually power manage the device.

Sensors

This section is view only and provides status information about the sensors.

Banks

Use the ON, OFF and Reboot options to manually power manage the banks.

Outlet Status

Use the ON, OFF and Reboot options to manually power manage the individual outlet.
47
eco DC User Manual

Group Control

The Group tab allows you to perform simultaneous manual power management at the outlet level on data groups that you have already created.
Note: 1. See Data Group, page 91, for details about creating groups for power
management control.
2. Not all models support outlet level power management. Please see , page 6, and your User Manual for further details.
Click on a group in the side bar and its page appears, as below:
The sidebar provides predefined groups that can be selected to manage outlets that are grouped together. Use ON, OFF and Reboot on the top bar to reboot outlet groups; or use the same power options listed next to the outlets in the main panel to manage the power of individual outlets.
48
Chapter 4. Energy

Analysis

The Analysis page allows you to create Power, Thermal and Billing reports to better understand energy use, environmental factors and costs associated with your data center.

Generate

The Generate tab allows you to establish the parameters and schedule for the reports that you want to create. Select a report type in the sidebar and then click Add Task to begin configuring the report.
The Generate Report fields are explained in detail in the following table:
Field Explanation
Menu The menu provides three options to generate reports:
Power – to create reports based on power usage.
Thermal – to create reports based on temperature.
Billing – to create reports based on costs.
Add Task Clicking Add Task opens a window that provides options to generate
Modify Check boxes in the main panel to select tasks then click Modify to
Delete Check boxes in the main panel to select tasks then click Delete to
Stop Click Stop if you want to stop a task thats in the process of being
custom reports about your data center’s energy and environmental usage.
make changes to them.
remove it from the list.
generated.
49
eco DC User Manual
Field Explanation
Generate Now
Select a task in the main panel by checking its box and then click Generate now to create the report. Once completed, the report will appear in the Completed Reports tab.
Power / Thermal
After you click Add Task a window opens to configure the report parameters:
T
he Power and Thermal fields are explained in the following table:
Field Explanation
Report Type Use the radio buttons to select a report type:
Data Group Report– to create a report based on groups of devices.
Room – to create a report based on all devices in a room.
Information Use the Title and Author fields to enter information about the custom
report. Use the Type drop-down menu to select how often to generate a report: Once, Daily, Weekly, Monthly, or Yearly.
Report Duration
50
Allows you to generate the report based on a time frame.
Enter the Start / Generate (when you want the report to begin/end), the
Period (options are hour, day, week, month, or quarter) and the Duration (1–24), then use the Keep Report For drop-down menu to
select the amount of time to pass before the report is deleted. Select Permanent to keep the report indefinitely.
Chapter 4. Energy
Field Explanation
Add Click Add to add up to four device groups or rooms for which the report
will be generated about.
Unit When Data Group (Power reports only) is selected you need to
Select Charts / Tables
Generate After entering the parameters, click Generate to add the report to the
configure these three parameters to generate customized reports related to your data center’s energy costs.
Use the check boxes to select the type(s) of information you want to collect for the report. The more options that are selected the longer the report will take to generate.
list.
Billing
After you click Add Task a window opens to configure the Billing parameters:
T
he Billing fields are explained in the following table:
Field Explanation
Add Click Add to add up to four device groups for which the billing report
Information Use the Title and Author fields to enter information about the custom
will be generated about.
report. Use the Type drop-down menu to select how often to generate a report: Once, or Monthly.
51
eco DC User Manual
Field Explanation
Report Duration
Billing Rates Use the radio button to select the type of rate:
Generate After entering the parameters, click Generate to add the report to the
Select the month to run the report and the time to generate the report. Use the Keep Report For drop-down menu to select the amount of time to pass before the report is deleted. Select Permanent to keep the report indefinitely.
Single Rate – to create a report based on a single dollar figure. Use the Billing Type drop-down menu to select:
Total: a report based on all rack devices.
Rack: a report based per rack with a subtotals.
Dual-Rate – to create a report based on two different figures: Peak and Non-peak rates. Enter the time Peak rates start and the number of hours that the peak rate runs. Use the Billing Type drop-down menu to select:
Total: a report based on all rack devices.
Rack: a report based per rack with a subtotals.
list.
52
Chapter 4. Energy

Reports

The Reports tab allows you to view or save reports that you’ve created.
Select a report type in the sidebar, check the box of the report(s) you want to view or save, and click Open or Save as to respectively begin viewing the report in a new window (the browser’s pop-up blocker must be disabled) or export the report as a PDF or Excel file.
53
eco DC User Manual
Main Panel
Schedules List

Schedule

The Schedule page allows you to power on and/or power off outlets at regular intervals or on a specified time.

Overview

A schedule page contains a schedules list and a main panel.
Schedules list: shows a list of created schedules.
Main panel:
List view: click to show a list of created schedules with
information such as the target group (of outlets), execution status, and the interval type.
Configuration view: click a schedule from the sidebar to show the
schedule settings.
54
Chapter 4. Energy

Adding a Power-on / Power-off Schedule

1. In the eco DC main page, go to Energy > Schedule.
2. In the sidebar, click . This window appears.
3. Configure the following settings.
Name: Name the task.
Typ e: Click the drop-down menu to select an interval type.
Once: powers on or off the target outlet(s) on a specified date and
time.
Daily: powers on and off the target outlet(s) daily at specified
times.
Weekly: powers on and off the target outlet(s) weekly at specified
times and days of the week.
Ye a r l y : powers on and off the target outlet(s) at specified times and
days of the week, with exceptions on specified dates.
Target Group: Click Browse to select a target group for the task. To
add a data group, go to Device > Data Group.
55
eco DC User Manual
Scheduling:
Once: Click to select On Time or Off Time, and then click on the
date to specify the date and time in a pop-up calendar. Click Apply to save the setting.
Daily: Click to select On Time and then click on the time to set the
on-time in a pop-up menu. Click Apply to save the setting. Repeat these steps to configure the off-time.
56
Chapter 4. Energy
Weekly: Click to select one or more On Time and then click on the
time(s) to set the on time(s) in a pop-up menu. Click Apply to save the setting. Repeat these steps to configure their off-time(s).
Ye a r l y :
In the Regular tab, click to select one or more On Time and then click on the time(s) to set the on time(s) in a pop-up menu. Click Apply to save the setting. Repeat these steps to configure their off­time(s).
57
eco DC User Manual
In the Exception tab, add the dates and times when the schedule needs to change.
4. Click Save.

Editing a Power-on / Power-off Schedule

1. In the eco DC main page, go to Energy > Schedule.
2. In the sidebar, click a schedule. The settings page appears.
For example:
3. Configure the settings as required.
4. Click Apply to save the configuration.
58
Chapter 4. Energy

Deleting Schedules

Use one of the following ways to delete schedules.
From the schedule page, click to switch to list view, click to select
one or more schedules, and click Delete on the top right.
From the sidebar, click a schedule, and then click .
59
eco DC User Manual
This Page Intentionally Left Blank
60
Chapter 5

User

Overview

When you select User from the toolbar the Accounts screen appears. eco DC supports two types of user accounts: Administrator and User. There are four sub-toolbar selections available from the User’s tab: Accounts, Authentication Services, and Sessions.
61
eco DC User Manual

Accounts

To add an account, do the following:
+
1. Click
2. In the User Information section, key in a Login name and Password, and select the Authentication Server. This screen is the same as when the account is selected from the sidebar.
. The Add New User Account page appears:
3. In the Type section, select the user type. Options are: Administrator and User.
Note: Administrators have full access rights by default; users have, by
default, no access rights apart from “View Only” where they only have access to the Energy toolbar. If they are assigned group permission, on the other hand, they can access almost everything (see Selecting an Account, page 63).
4. In the Access Permissions section, set the permissions of Administrator accounts. To set the device-by-device permissions for an account, open the user’s page from the sidebar and select the Device Access tab.
5. Click Save to save your settings.
62
Chapter 5. User
Selecting an Account
The Basic, Group Membership and Device Access tabs appears when you select a user account from the Menu. Use these tabs to edit this account’s permission to view and manage devices and groups. The Device Access tab do not appear for Administrator accounts as they have full permissions.
Basic
This tab lets you configure the user information, type and permission. An example is shown below:
Click Apply if you wish to apply the changes you’ve made.
Group Membership
This tab displays the group(s) the user account belongs to. An example is shown:
63
eco DC User Manual
If you wish to add this user to a particular group, click Add on the top right corner. A list of available groups will be displayed in the dialog box as shown in the example below:
Check the box(es) you wish to add the user account to and click Add.
If you wish to delete the user from the group, check the box on the Group Membership tab and click Delete.
64
Chapter 5. User
Device Access
This tab displays the device(s) the user account has access to. An example is shown:
To add device access for the account individually, do the following:
1. Click Add on the top right corner. The Add Device Access Rights dialog
window appears:
2. In the All column, check the boxes of the devices you want to allow the
user to access. When the user logs in, these devices will appear in the sidebar.
65
eco DC User Manual
Note:
If a user is given more access rights via Group Membership, the
accessible devices will appear in Energy > Power Control > Device tab.
Administrators have full access rights by default; users have no device
or group access rights by default. User accounts only have access to the Energy tab with view status and power control options.
3. Click Add. When you are finished, click X.
4. After adding devices they appear listed on the Device Access tab.
66
Chapter 5. User

Groups

This page displays the user groups you have previously created.
In the menu, you can also choose the “Domain Group” tab to show the groups according to the domain.
Add User Group
To add a user group, click the + icon above the menu:
Enter the appropriate information and click Save.
67
eco DC User Manual
User Group
2 tabs will be shown (Groups and Group Members) in the interactive display panel after clicking a user group in the menu.
Basic
You can configure the group’s information, type and permissions in this tab. An example is shown:
Click Apply if you wish to apply the changes you’ve made.
Group Members
This tab displays all the group members of this group. An example is shown:
To delete the user from the group, check the box on the Group Members page and click Delete.
68
Chapter 5. User
If you wish to add group members, click Add for the dialog window shown below:
Check the box of the users you wish to add and click Add.
Domain Group
The page below is an example of the Domain Group:
To delete a domain group, check the group’s box and click Delete.
69
eco DC User Manual
Add Domain Group
To add a domain group, click the + icon for the dialog window below:
Select the Authentication Server, check/uncheck the group’s type and permissions and click Select User.
Select the user you wish to add by checking the box and click Apply.
70
Chapter 5. User

Authentication Services

Clicking the Authentication Services sub-toolbar brings you to the information list. An example is shown:
Clicking one of the servers in the menu allows you to configure the external authentication server’s information or the password policy of the eco DC. By default, the eco DC authentication service appears in the menu and cannot be deleted.
Click eco DC in the menu and the Password Policy page appears:
Minimum username length (1-64)
Minimum password length (1-32)
Password expires after
(1-999)
Enter the minimum number of characters required for usernames.
Enter the minimum number of alpha/numeric characters required for passwords.
Enter the number of days that can pass before users are forced to create a new password.
71
eco DC User Manual
Enforce password history (0-9)
Password must contain upper letters
Password must contain lower letters
Password must contain numbers
Password must contain symbols
Enter the number of unique passwords that must be used before an old password can be used again.
Check this box to require users to have at least one uppercase letter in their password.
Check this box to require users to have at least one lowercase letter in their password.
Check this box to require users to have at least one number in their password.
Check this box to require users to have at least one symbol (!, @, #, $, %, ^, &, *) in their password.
External Authentication
Click any of the external authentication servers in the menu and the configuration page for the server will be shown in the interactive display panel. The page corresponds to the page shown in the Add Authentication Server page below.
To add an authentication server, do the following:
1. Click
+
. The Add New Authentication Server page appears:
2. In the Basic Information section, key in a Server name and Description, and select a Server Type:
72
Chapter 5. User
Active Directory
Fill in the IP address, Port and Base DN.
Select Use SSL in Trust All Mode or Do not use SSL.
Select Browse with user credentials and enter the Username and Password; or User must input credentials when browsing.
LDAP
Fill in the IP/Domain, Port and Base DN.
Select Use SSL in Trust All Mode or Do not use SSL.
Fill in the Key attribute, Object class, Full name attribute.
Fill the User RDN.
Select Browse with user credentials and enter the Username and Password; or User must input credentials when browsing.
73
eco DC User Manual
RADIUS
Fill in the IP/Domain, and Port.
Select the Authentication type and fill in the Shared secret and Confirmed shared secret.
TACA SC+
Fill in the IP/Domain, and Port.
Select the Authentication type and fill in the Shared secret and Confirmed shared secret.
3. Click Save to save your settings.
74
Chapter 5. User

Sessions

The Session page lets the administrator see at a glance which users are currently logged into the eco DC, and provides information about each of their sessions.
Note: 1. The Session page isn’t available for ordinary users.
2. The sort order of the information displayed can be changed by clicking the column headings.
The meanings of the headings at the top of the page are fairly straightforward. The Client IP heading refers to the IP address that the user has logged in from; the Login Time tells you when the user logged in, and the Idle heading lists how long the account has been inactive.
This page also gives the administrator the option of forcing a user logout by selecting the username and clicking End Session at the top right corner of the main panel.
75
eco DC User Manual
This Page Intentionally Left Blank
76
Chapter 6

Device

Overview

The Device tab allows you to configure each device and define your data center by Data Center, Building, Floor, Room, and Rack. You can also define detailed parameters, such as Device Threshold Settings, at the PDU and outlet level and eco Sensors settings. See the following sections for more detailed information.
Note: 1. At least one rack must be installed and defined for eco DC to work.
2. Not all functions (such as outlet level monitoring) are supported by all models. Please see , page 6, and your eco PDU User Manual for details
77
eco DC User Manual

Installation

The Installation sub-toolbar options allows you to view and configure devices and define the layout of your data center. This page opens to the Device tab in the menu which lists all the devices in your data center:

Adding Devices

To add devices, do the following:
+
1. On the sidebar, click parameters and search for devices on the network:
2. In the Search PDU Devices section, select the device type (ATEN PDU, ATEN UPS, etc.) from the drop-down menu, key in the Start IP (v4) and Search Number.
3. Enter the information under Default SNMP Agent Settings and click Next.
4. When a list of devices appears, check the device boxes and click Add.
78
. The New Device page appears to configure
Chapter 6. Device

Devices

The Devices tab lists all the PDUs in your data center. You can select devices to configure the settings by selecting them in the sidebar, or by double-clicking the devices in the main panel. When a device is selected, its first tab appears:
Device
Device Info This section displays the Name, IP/Domain, Model and
Rack information for configuration.
SNMP Agent Settings Configure the SNMP Agent settings here.
Threshold Set the device threshold settings (min.–max), using the
Sensor Location Type Select the sensors’ locations from the drop-down menus.
Door Sensor Type Select the door sensor type from the drop-down menu.
Apply Click Apply to save the settings.
parameters provided, for:
Aggregate Current
Voltage
Aggregate Power
Aggregate Power Dissipation
Note: For these settings to appear click the Advanced Settings radio button.
79
eco DC User Manual
Bank
Device Info This section displays the device Name, IP/Domain, Model and Rack
information.
Threshold Enter the bank Name, and use the drop-down menu to configure
Apply Click Apply to save the settings.
multiple banks individually, or check Apply to all banks to configure all banks with the same settings. Set the outlet threshold settings (min.– max), using the parameters provided, for:
Current
Voltage
Power
Power Dissipation
Note: Depending on your device, not all these options may be available.
80
Outlet
Chapter 6. Device
Device Info This section displays the device Name, IP/Domain, Model and Rack
Threshold Use the Outlets drop-down menu to select the outlet to configure, or
Apply Click Apply to save the settings.
information.
use Apply to all outlets to configure the same settings for all outlets. Set the outlet threshold settings (min.–max), using the parameters provided, for:
Aggregate Current
Voltage
Aggregate Power
Aggregate Power Dissipation
Select one of the three choices for the Shutdown Method from the drop-down menu – see Shutdown Methods, page 81, for details.
Set MAC address and Delay Time On/Off for the selected method.
Shutdown Methods
The three available shutdown methods are explained in detail below:
Kill the Power – If this option is selected, the device waits for the amount
time set in the Power Off Delay field, and then turns the Outlet's power Off. Turning the power off performs a cold (non-safe) shutdown.
Wake on LAN – This is a Safe Shutdown and Restart option. If this is
selected, when an Outlet is turned Off, the device first sends a message to the computer telling it to prepare for a shutdown; it then waits for the
81
eco DC User Manual
amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down to standby mode.
Likewise, when the Outlet is turned On, the device waits for the amount time set in the Power On Delay field, then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On.
Note: For Safe Shutdown and Restart, the computer must be running
Windows (Windows 98 or higher), and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.
System after AC Back – This is a Safe Shutdown and Restart option. If
this is selected, when an Outlet is turned Off, the Device first sends a message to the computer telling it to prepare for a shutdown; it then waits for the amount time set in the Power Off Delay field to give the OS time to close down before the computer is powered down.
When the Outlet is turned On, the device waits for the amount time set in the Power On Delay field, then sends power to the server. When the server receives the power, it turns itself on.
Note: For Safe Shutdown and Reboot, the computer must be running
Windows (Windows 98 or higher), and the Safe Shutdown program (available by download from our website), must be installed and running on the computer.
82
Sensor
Chapter 6. Device
Device Info This section displays the device Name, IP/Domain, Model and Rack
Threshold Settings
Apply Click Apply to save the settings.
information for configuration.
This section provides the threshold settings for Sensors 1-4. Check Apply to same Model to use the same settings for all sensors connected to the same PDU model as the one you are configuring. Set the sensor threshold settings (min.–max), using the parameters provided, for:
Temperature
Humidity
Pressure
83
eco DC User Manual
POP
Depending on the ATEN PDU model, this tab may or may not appear, and different options will be available. Please refer to the user manual of the ATEN PDU selected for instructions on the available options.
Device Info This section displays the device Name, IP/Domain, Model and Rack
information for configuration.
POP (Proactive Overload Protection) Settings
Apply Click Apply to save the settings.
84
This section provides the settings to configure Proactive Overload Protection for outlets. Check the Enable POP modes to use these feature. See the user manual of the selected PDU for details of the POP features and how to configure the settings.
UPS
If you choose a UPS device, this tab will appear.
Chapter 6. Device
Device Info This section displays the device Name, IP, Model, Rack and UPS F/W
SNMP Agent Settings
Apply Click Apply to save the settings.
version information.
For fields that can be entered, enter a parameter between the specified range. For fields that have drop-down menu, select from the available options.
Battery
The battery tab allows you to do battery self-test for the UPS.
Device Info This section displays the device Name, IP, Model, and Rack information.
Battery Self-test
Select the test type and click Start to start the test.
85
eco DC User Manual

Layout

The Layout tab is for configuring the layout of your data center. The sidebar provides a tree-view list of the data center and its building(s), floor(s), and room(s).
Each level of the layout provides energy and basic information about that level of the data center. This information includes the number of PDUs, the average voltage, average aggregate power, and the number of buildings, floors, rooms and racks.
86
Chapter 6. Device
Adding Layout
There is a hierarchy which must be followed when adding the layout, meaning you must add one before the other, in this order: Data Center - Building - Floor - Room. You can add multiple Data Centers with multiple buildings, floors and rooms. At the room level you can configure the racks which contain the PDUs.
To add a layout, do the following:
1. On the menu, click
2. Use the drop-down menu to select the Typ e: Data Center. Key in the
Name, Country, City and Address. Click Apply.
3. In the menu, select the Data Center and click
down menu and select Building. Key in the Name, Country, City and Address. Click Apply.
4. In the menu, select the Building and click
down menu and select Floor. Key in the Name, Country, City and Address. Click Apply.
5. In the menu, select the Floor and click
menu and select Room. Key in the Name, Country, City and Address. Click Apply.
+
. The Create Data Center Layer window appears:
+
again. Use the Type drop-
+
again. Use the Type drop-
+
again. Use the Type drop-down
6. You can add additional buildings, floors and rooms at each level. Once the
Rooms have been added, you can select them to add racks to your data center.
87
eco DC User Manual
Adding Racks
To add racks to a room, do the following:
1. In the sidebar, select a Room. A grid appears:
2. Click Edit. A page appears to add racks to the room. Use the bar options to Select and Change, Zoom and Pan, Auto Fit, and set the Layout’s grid size.
3. Right-click on a square and how the rack is to be positioned:
88
Chapter 6. Device
4. Enter the number of racks to add, and click Apply. The racks appear in the
position that you selected. You can drag-and-drop, delete, copy, and paste racks. Add racks until you’ve completed the design of your data center.
5. To add devices, double-click a rack and click
+
.
89
eco DC User Manual
6. Select the device(s) and click Add.
7. After adding all the devices to each rack, click Exit.
8. On the Room page, click racks to view the list of devices. Racks without devices appear gray.
90
Loading...