Atec T-R-PCU1 User Manual

PCU1-SP
Primary Current
PCU1-LT
Injection Systems
PCU1-SP & NLU5000 with
optional trolley
Features (PCU1-LT and PCU1-SP)
5kA maximum output current (higher overload currents for 2s)
Multi-function digital timing system
Digital true RMS memory ammeter
Solid state switching
2000A and 5000A loading units
Three range outputs on loading units
Rugged, compact design
Optional trolley mounting of system
PCU1-SP Additional Features
Secondary injection up to 100A
Direct reading CT ratio and polarity
The PCU1 series are
medium powered primary current injection systems offering output currents up to 5000A. The system consists of a separate control unit containing all metering and control functions and a loading unit that provides the high current output. The PCU1-LT and PCU1­SP are ideally suited to primary current injection, stability testing and circuit breaker testing. In addition, the SP version offers direct-reading CT ratio and polarity tests and a 100A secondary injection output. T&R also offer the higher-powered PCU1-HP and PCU2.
Feature PCU1-LT PCU1-SP PCU2
Primary injection
Max output power
Secondary injection CT ratio/polarity test
Two loading units are available, delivering a maximum output current of 2000A or 5000A. Each loading unit has three output taps to allow for a wide range of load impedances. For example, the NLU5000 may be configured to either give a maximum current of 5000A on the 2.3V range, 2500A on the 4.6V range or 1250A on the 9.2V range.
ü ü ü
11.5kVA 40s
û ü û û ü û
11.5kVA 40s
20kVA
5 min
The control units are rated at 11.5kVA with a 2 second overload capability of 23kVA using pulse mode. All metering is digital and a memory facility is provided to hold the current reading when the output trips or is switched off. The current is thyristor controlled and is automatically switched off when the device under test trips.
The PCU1 systems have a high accuracy timing system, allowing timing tests to be carried out to a resolution of 1ms. Selection for normally open or normally closed contacts is automatic, and the status of the contacts is shown on the front panel.
Output current Range Output state
Timer Auxiliary metering
Timing modes are available to test under and over current devices, re-closers, under and over voltage devices, current trips and circuit breakers. A full range of high current output leads are available to complement the system in a range of lengths.
1.000kA 5kA On
000.000s 5000.:5ACT
23
PCU-LT/PCU1-SP Control Unit Specification
Loading Unit Current Metering
The AC output current is metered by a true RMS memory ammeter (acquisition time 200ms) with a liquid crystal display. The current metering has 3 ranges corresponding to 10%, 50% and 100% of the maximum rating of the loading unit. In addition, a 200% metering range is enabled in pulse mode.
NLU2000 Range Full scale Resolution Accuracy
10% 200.0A 0.1A ±0.5%rdg+5d* 50% 1000A 1A ±0.5%rdg+5d* 100% 2000A 1A ±0.5%rdg+5d* 200% 4000A 1A ±1%rdg+5d**
NLU5000 Range Full scale Resolution Accuracy
10% 500.0A 0.1A ±0.5%rdg+5d*1 50% 2500A 1A ±0.5%rdg+5d*1 100% 5000A 1A ±0.5%rdg+5d*1 200% 10kA 10A ±1.5%rdg+5d*2
*1
1.5% rdg+5d in pulse mode *2selected in pulse mode
Timing System
The PCU1 systems have a flexible timing system with two contact inputs and 5 operating modes. Each contact circuit automatically selects for N/O or N/C contacts, and the status of each contact input is shown by an LED. The timing channels may also be triggered by a dc voltage between 24 and 240V.
Secondary Injection Output (PCU1-SP only)
The secondary current injection output on the unit has two taps, allowing the injection of currents up to 100A.
Output Range Continuous Intermittent current current 5min on*5 1 min on*5
0-5V 33A 67A 100A 0-16V 10A 20A 30A
*5
All on times must be followed by an off time of 15 minutes
Metering Range Resolution Accuracy Current trip
10.00A 0.01A ±0.5%rdg+5d 10.5A
20.00A 0.01A ±0.5%rdg+5d 21A
100.0A 0.1A ±0.5%rdg+5d 100A The output is protected by electronic trips and a circuit breaker.
Supply Requirements
230V±10%, 45-65Hz 1ph 11.5kVA max (23kVA overload for 2s)
Control Unit Standard Accessories
Mains lead (5m), loading unit power and metering leads (5m), operating manual and spare fuses.
Dimensions
PCU1-SP/PCU1-LT 450(w) x 275(h) x 305mm(d) NLU2000/NLU5000 450(w) x 275(h) x 370mm(d) incl. terminals
Weight
PCU1-LT 23kg PCU1-SP 26kg NLU5000 55kg NLU2000 50kg
Timer resolution 1ms Timer full scale 999.999s Timer accuracy ±0.01%rdg+2d (4d current mode) Contact O/C voltage 24V Contact S/C current 20mA Vdc input range 24-240Vdc
Timer mode Timer start Timer stop
Internal Start ‘On’ button Contact Single contact Contact 1 Contact 1 Dual contact Contact 1 Contact 2 Current operated *3 Current >20% rng Current <20% rng Pulse mode 0.2s *4 ‘On button’ 0.2s Pulse mode 0.5s *4 ‘On button’ 0.5s Pulse mode 1s *4 ‘On button’ 1s Pulse mode 2s *4 ‘On button’ 2s
Contact 1
I<20% range
Off Setting position
*3
Current operated mode is used to time circuit breakers with no
auxiliary contacts. The timer is started when the current exceeds 20% of the selected metering range (e.g. 100A on the NLU5000 500A range). The timer stops when the current falls.
*4
Pulse mode applies current to the load for a maximum of the
specified time. If contact set 1 changes state or the current drops below 20% of the metering range during the pulse time, the timer is stopped. The maximum output current is increased in pulse mode. The maximum obtainable current is set by the impedance of the test object and output leads.
Temperature Range
Storage -20°C to 60°C, Operating 0°C to 45°C
Protection and Safety
The PCU1 series and loading units are CE marked and are designed to meet the requirements of BS EN61010. The system is protected by electronic trips on the outputs, circuit breakers on the mains input, control unit output and secondary injection output (PCU1-SP only). The unit also has a duty cycle trip on the loading unit output and the loading unit has comprehensive thermal protection.
Optional Loading Unit Specifications
Two loading units are available to provide a range of output currents suitable for different primary injection tasks. Each loading unit has three output taps allowing current injection into a wide range of loads of differing impedances. Optional output lead sets are also available (see www.trtest.com for details).
NLU5000 Loading Unit Intermittent Ratings
Output Maximum current Voltage* Cont. 5 min 1 min 40s
2.3V 1500A 3000A 4500A 5000A
4.6V 750A 1500A 2250A 2500A
9.2V 375A 750A 1125A 1250A
NLU2000 Loading Unit Intermittent Ratings
Output Maximum current Voltage* Cont. 5 min 1 min 40s
3.5V 600A 1200A 1800A 2000A
6.9V 300A 600A 900A 1200A
13.8V 150A 300A 450A 500A
Note: Due to the company’s continuous research programme, the information above may change at any time without prior notificatio n. Please check that you have the most recent data on the product.
24
T&R Test Equipment Ltd, 15-16 Woodbridge Meadows, Guildford, Surrey, GU1 1BJ, UK
Tel: +44 (0)1483 207428 Fax: +44 (0)1483 511229 email: sales@trtest.com
www.trtest.com
PCU1-LT-SP Data Sheet rev 4 28/12/05