Atec OCS500N6F User Manual

DATA SHEET > OCS 500N6F series > 20130618
OCS 500N6F SERIES
SIMULATOR FOR FAST AND SLOW DAMPED OSCILLATORY WAVES AND RINGWAVE
FOR TESTS ACCORDING TO ...
> ANSI/IEEE C37.90 > ANSI/IEEE C62.41 > EN 61000-4-10 > EN 61000-4-12 > EN 61000-4-18 > IEC 60255-22-1 > IEC 61000-4-10 > IEC 61000-4-12 > IEC 61000-4-18 > IEC 61850-3 > IEC 62052-11
OCS 500N6FX - COMPACT TESTERS FOR FAST/SLOW DAMPED OSCILLATORY WAVES AND RINGWAVE
The OCS 500N6F series includes the test capabilities for fast damped oscillatory waves at 3MHz/10MHz/30MHz up to 4.4kV and is extendable for slow damped oscillatory waves at 100kHz/1MHz up to 3.0kV (as per EN/IEC 61000-4-18) and for ringwave up to 6kV as per EN/IEC 61000-4-12. Damped Oscillatory Waves are repetitive transients mainly occurring in power, control and signal cables installed in high voltage and medium voltage stations, divided into slow and fast damped oscillatory waves. The Ringwave is a non-repetitive damped oscillatory transient occurring in low-voltage power, control and signal lines supplied by public and non-public networks.
HIGHLIGHTS
> Fully automated single box test system
APPLICATION AREAS
INDUSTRY
RESIDENTIAL
> Single DUT port > Fast Damped Oscillatory Waves up to 4.4kV
COMPONENTS
RENEWABLE ENERGY
> Slow Damped Oscillatory Waves up to 3kV
(option)
> Ringwave up to 6kV (option)
MEDICAL
BROADCAST
www.emtest.com © EM TEST > PAGE 1/5
DATA SHEET > OCS 500N6F series > 20130618
TECHNICAL DETAILS
MODEL SELECTION
THREE IN ONE - THE OCS 500N6F COMBINES DAMPED OSCILLATORY WAVES AND RINGWAVE
The basic equipment includes the fast damped oscillatory generator with 3MHz, 10MHz and 30MHz for up to 4.4kV acc. IEC 61000-4-18.
The OCS 500N6F comes with a built-in coupling/ decoupling network for either single phase or three-phase and is rated for currents of 16A or 32A per line.
Optional Modules: Slow Damped Oscillatory Waves with 100kHz/1MHz reach up to 3kV. The module comply with EN/IEC 61000-4-18 and also with the requirements to test protective relays as per ANSI/IEEE C39.70. Ringwave Module with capability of up to 6kV complies with the Ringwave requirements of IEC 61000-4-12 ANSI/IEEE C62.41 standard.
SOFTWARE
IEC.CONTROL SOFTWARE FOR CONTROL AND DOCUMENTATION
Outstanding user convenience, clearly structured windows and operation features and the EM TEST standards library along with the flexibility to generate user specific test sequences very easily are the main features of iec.control software. The software is automatically configured according to the connected EM TEST generators. Extensive reporting capabilities help the user to create test reports that meet international requirements. iec.control is supported by Windows 2000, Windows XP, Windows Vista and Windows 7. Remote control is achieved either via USB or GPIB. iec.control supports a wide range of GPIB cards both of National Instruments.
AUXILIARY DEVICES
CNV 504N5 - COUPLING NETWORK FOR SIGNAL/DATA LINES
The CNV 504N5 is a 4-wire coupling/decoupling network for the application of the Damped Oscillatory Waves on to signal/data lines as required EN/IEC 61000-4-18 with a 200ohm source impedance.
OPERATION
EASY TO OPERATE
Front panel menu and function keys enable the user to program his test routines quickly and accurately. The cursor allows fast control of all test parameters of the programmed routine, thus test procedures are simplified and confidence is generated that every step is carried out correctly.
ACCESSORIES
MS 100N - MAGNETIC FIELD COIL FOR DAMPED OSCILLATORY MAGNETIC FIELDS
The MS 100N is a 1sqm magnetic field coil as specified in IEC/EN 61000-4-10. Its design allows easy moving of the coil. The field coil is adjustable in height and allows for 360degr rotation. The MS 100N is directly connected to the corresponding HV output of the OCS 500N6 to generate damped oscillatory magnetic fields as per IEC/EN 61000-4-10, up to level 5.
www.emtest.com © EM TEST > PAGE 2/5
DATA SHEET > OCS 500N6F series > 20130618
TECHNICAL DETAILS
OCS 500N6F MAIN-UNIT MODELS
OCS 500N6F With built-in CDN
AC 250V / 16A DC 250V / 10A
OCS 500N6F.1 With built-in CDN
AC 250V / 32A DC 250V / 20A
OCS 500N6F.2 With built-in CDN
AC 3x440V / 16A DC 250V / 10A
OCS 500N6F.3 With built-in CDN
AC 3x440V / 32A DC 250V / 20A
FAST DAMPED OSCILLATORY MODULE
FAST DAMPED OSCILLATORY WAVES AS PER IEC/EN 61000-4-18
SLOW DAMPED OSCILLATORY MODULE (OPTION)
SLOW DAMPED OSCILLATORY WAVES AS PER IEC/EN 61000-4-18 (OPTION)
Voltage (o.c.) at HV output
Voltage (o.c) at line output
Rise time 75ns ± 20% Oscillation
frequencies Decaying Peak 5 to be > 50% of peak 1 value
Source impedance 200ohm ± 20% Polarity Positive, negative Repetition rate Max. 50/s for 100kHz and
Burst duration At least 2s
250V - 3,000V ± 10%
250V - 2,500V ± 10%
100kHz and 1MHz ± 10%
Peak 10 to be < 50% of peak 1 value
Max. 500/s for 1MHz
Voltage (o.c.) at HV output
Rise time 5ns ±30% Oscillation
frequencies Decaying Peak 5 to be > 50% of peak 1 value
Source impedance 50ohm ±20% Polarity Positive, negative Repetition rate Max. 5,000/s ±10% Burst duration 50ms ±20%, at 3MHz
Burst period 300ms ±20% Short-circuit
current Rise time current
waveform
Decaying (current) Peak 5 to be > 25% of peak 1 value
450V - 4,400V ±10%
3MHz, 10MHz and 30MHz, ±10%
Peak 10 to be < 50% of peak 1 value
15ms ±20%, at 10MHz 5ms ±20%, at 30MHz
9A - 88A ±20%
< 330ns at 3MHz < 100ns at 10MHz < 33ns at 30MHz
Peak 10 to be < 25% of peak 1 value
RINGWAVE MODULE (OPTION)
RINGWAVE AS PER IEC/EN 61000-4-12 AND ANSI/IEEE C62.41 (OPTION)
Voltage (o.c.) 250V - 6,000V ± 10% Rise time 0.5us ± 30% Oscillation
frequency Decaying Ratio of peak 2 to peak 1: 0.4 - 1.1
Source impedance 12ohm and 30ohm ± 20%
Peak current (s.c.) Max. 500A @ 12ohm or
Rise time < 1us Oscillation
frequency
100kHz ± 10%
Ratio of peak 3 to peak 2: 0.4 - 0.8 Ratio of peak 4 to peak 3: 0.4 - 0.8
200ohm for I/O lines (CNV 504N5)
Max. 200A @ 30ohm internally; Max. 30A @ 200ohm, with CNV 504N5
100kHz ± 10%
Polarity Positive, negative Repetition rate 1 to 60 transients per minute
www.emtest.com © EM TEST > PAGE 3/5
DATA SHEET > OCS 500N6F series > 20130618
TECHNICAL DETAILS
GENERAL SPECIFICATION
TRIGGER CIRCUIT
Release of pulses Automatic, manual, external Synchronization 0° - 360°, resolution 1°
OUTPUT
Direct Via HV-safety lab connectors Coupling mode Line to line
Line(s) to ground (PE) DUT supply OCS 500N6F AC: 250V/16A; 50/60Hz
DC: 250V/10A OCS 500N6F.1 AC: 250V/32A; 50/60Hz
DC: 250V/20A OCS 500N6F.2 AC: 3x440V/16A; 50/60Hz
DC: 250V/10A OCS 500N6F.3 AC: 3x440V/32A; 50/60Hz
DC: 250V/20A
GENERAL DATA
INTERFACE
Optical interface Opto link, 3 m cable
USB A connector
Parallel interface IEEE 488, addresses 1 - 30
GENERAL DATA
Dimensions, weight
Supply voltage 115/230V +10/-15% Fuses 2 x T2AT (230V); 2 x T4AT (115V)
19"/9HU, approx. 32kg (1-phase) 19"/9HU, approx. 50kg (3-phase)
OPTIONS
ACCESSORIES COUPLING NETWORK
CRO trigger 5V trigger signal for oscilloscope
MEASUREMENTS
Ring wave Peak voltage and peak current in LCD
TEST ROUTINES
Quick Start Immediate start; easy-to-use and
fast Standard Test
routines
User Test routines Change polarity after n pulses
As per IEC 61000-4-18
As per IEC 61000-4-12, Level 1 - 4
Manual Standard Test routine
As per ANSI/IEEE C62.41
As per IEC 61000-4-10, Level 1 - 5
Change coupling after n pulses
Change voltage after n pulses
Change phase angle after n pulses
CNV 504N5.1 Coupler for 4 signal/datalines for
damped oscillatory waves 100kHz and 1MHz as per IEC 61000-4-18, 50V/4A
CNV 504N5.3 Coupler for 4 signal/datalines for
damped oscillatory waves 100kHz and 1MHz as per IEC 61000-4-18, 250V/4A
CNV 508N4 Coupler for 4 pairs (8 wires) as per
IEC 60255-22-1, 250V/4A
CNV 508N4.1 Coupler for 4 pairs (8 wires) as per
IEC 60255-22-1, 250V/16A
HFK Capacitive coupling clamp as per
IEC 61000-4-4
MS 100N Magnetic Field coil for EN/IEC
61000-4-10 application
ACCESSORIES SOFTWARE, VERIFICATION
iec.control Remote control and documentation
software with library of standards
CA OCS F Kit Load resistor set for fast damped
oscillatory wave verification, KW 0R1 load resistor 0.1ohm, KW 1000 load resistor 1000ohm, CA MC F Adapter to match KW 0R1 and KW 1000 to the supply output of the OCS 500N6F
www.emtest.com © EM TEST > PAGE 4/5
DATA SHEET > OCS 500N6F series > 20130618
COMPETENCE WHEREVER YOU ARE
CONTACT EM TEST DIRECTLY
Switzerland
EM TEST (Switzerland) GmbH > Sternenhofstraße 15 > 4153 Reinach > Switzerland Phone +41 (0)61/7179191 > Fax +41 (0)61/7179199 Internet: www.emtest.ch > E-mail: sales.emtest@ametek.com
Germany
EM TEST GmbH > Lünener Straße 211 > 59174 Kamen > Deutschland Phone +49 (0)2307/26070-0 > Fax +49 (0)2307/17050 Internet: www.emtest.com > E-mail: info.emtest@ametek.de
France
EM TEST FRANCE > Le Trident - Parc des Collines > Immeuble B1 - Etage 3 > 36, rue Paul Cézanne > 68200 Mulhouse > France Phone +33 (0)389 31 23 50 > Fax +33 (0)389 31 23 55 Internet: www.emtest.fr > E-mail: info@emtest.fr
Poland
EM TEST Polska > ul. Ogrodowa 31/35, 00-893 Warszawa > Polska Phone +48 (0)518 64 35 12 Internet: www.emtest.com/pl > E-mail: info_polska.emtest@ametek.de
Information about scope of delivery, visual design and technical data correspond with the state of development at time of release. Technical data subject to change without further notice.
USA / Canada
EM TEST USA > 9250 Brown Deer Road > San Diego > CA 92121 Phone +1 (858) 699 1685 > Fax +1 (858) 458 0267 Internet: www.emtest.com > E-mail: sales.emtest@ametek.com
P.R. China
E & S Test Technology Limited > Rm 913, Leftbank > No. 68 Bei Si Huan Xi Lu > Haidian District > Beijing 100080 > P.R. China Phone +86 (0)10 82 67 60 27 > Fax +86 (0)10 82 67 62 38 Internet: www.emtest.com > E-mail: info@emtest.com.cn
Republic of Korea
EM TEST Korea Limited > #405 > WooYeon Plaza > #986-8 > YoungDeok-dong > Giheung-gu > Yongin-si > Gyeonggi-do > Korea Phone +82 (31) 216 8616 > Fax +82 (31) 216 8616 Internet: www.emtest.co.kr > E-mail: sales@emtest.co.kr
www.emtest.com © EM TEST > PAGE 5/5