Atec MIT1020-2 User Manual

MIT520/2 and MIT1020/2
5 kV and 10 kV Insulation Resistance Testers
MIT520/2 and MIT1020/2
5 kV and 10 kV Insulation Resistance Testers
n
CAT IV 600 V
n
Mains or battery powered
n
Variable test voltage from 50 to 5000 or
10,000 V
n
n
Measures to 15 TΩ (5 kV) and 35 TΩ
(10 kV)
n
RS232 and USB download of results to
Megger Download Manager
DESCRIPTION
The new 5 and 10 kV insulation resistance testers from Megger are designed specifically to assist you with the testing and maintenance of high voltage electrical equipment. IEEE 43-2000 recommends the use of 10 kV for motor windings rated above 12 kV and the Megger MIT1020/2 facilitates this. The case is incredibly rugged and easy to carry, being made of tough polypropylene and achieving an ingress protection rating of IP65. In addition, the model number is marked on both sides of the case for ease of identification in stores or vehicles.
The instruments have a large easy to read backlit LCD display making it equally suitable for use in both bright sunlight and poorly lit environments. Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant. In addition, the elapsed time of the test is displayed constantly, removing the need for separate timers. Adjustable timers and limit alarms are included.
n
On board memory for results storage
The instrument is fitted with a guard terminal to enhance accuracy. The guard test lead is included as standard with the instrument.
To further enhance the flexibility of the instruments both have the facility to set the test voltage in steps from 50 V to the maximum output voltage avoiding the expense of several insulation resistance testers to meet your application needs.
These IR instruments are designed to meet the highest safety standards and meet the requirements of EN61010. In addition, the instrument measures the voltage at the terminals and if this is above 50 V then the instrument will display the high voltage warning and inhibit testing. At the end of the test the instrument will automatically discharge the energy transferred to the equipment during the test phase.
The MIT520/2 and MIT1020/2 are equally suited to routine testing and diagnostic regimes being pre-programmed with IR, PI, DAR, SV and DD profiles.
The instrument can test when being powered by the mains or its internal rechargeable battery, a great benefit when site conditions are unknown or long term testing is required.
The controls of the instrument are clear and unambiguous and a “quick start” guide is included in the lid of the instrument removing the need to carry bulky manuals under site conditions.
MIT520/2 and MIT1020/2
5 kV and 10 kV Insulation Resistance Testers
SPECIFICATION
Voltage input range
85-265 V rms, 50/60 Hz, 60 VA
MIT520/2 battery life
Typical capacity is 6 hours continuous testing at 5 kV with a 100 MΩ load
MIT1020/2 battery life
Typical capacity is 4 hours continuous testing at 10 kV with a 100 MΩ load
MIT520/2 test voltages
50 V to 1 kV in 10 V steps, 1 kV to 5 kV in 25 V steps
MIT1020/2 test voltages
50 V to 1 kV in 10 V steps, 1 kV to 10 kV in 25 V steps
MIT520/2 accuracy (23 °C, 5 kV)
5000 V 2500 V 1000 V 500 V 250 V
±5% to 1 TΩ 500 GΩ 200 GΩ 100 GΩ 50 GΩ ±20% to 10 TΩ 5 TΩ 2 TΩ 1 TΩ 500 GΩ
MIT1020/2 accuracy (23 ºC, 10 kV)
10 kV 5000 V 2500 V 1000 V 500 V 250 V
±5% to 2 TΩ 1 TΩ 500 GΩ 200 GΩ 100 GΩ 50 GΩ ±20% to 20 TΩ 10 TΩ 5 TΩ 2 TΩ 1 TΩ 500 GΩ
Guard
2% error guarding 500 kΩ leakage with 100 MΩ load
Display range
Digital display (3 digits) 10 kΩ to 15 TΩ (MIT520/2) to 35 TΩ (MIT1020/2) Analogue display 100 kΩ to 1 TΩ
Short circuit/charge current
3 mA @ 5 kV (MIT520/2) or 10 kV (MIT1020/2)
Capacitor charge time
<3 seconds per µF at 3mA to 5 kV (MIT520/2) <5 seconds per µF at 3mA to 10 kV (MIT1020/2)
Memory capacity
32 kB
Test regimes
Auto IR, PI, DAR, SV and DD.
Interface
RS232 and USB
Data store
Voltage, test time, leakage current, resistance, PI, DAR, DD, capacitance and time constant
Real time output
Serial, once per second of test voltage, current and resistance
Operating temperature
-20 °C to 50 °C
Storage temperature
-25 °C to 65 °C
Ingress protection (lid closed)
IP65
Humidity
90% RH non-condensing at 40 °C
Safety
Meets the requirements of IEC61010-1 CATIV 600 V
EMC
Meets the requirements of IEC61326-1
Dimensions
305 x 194 x 360 mm (12.7 x 6 x 14.2 inches)
Weight
7.1 kg (16lb) approx.
Capacitor discharge time
<120ms per µF to discharge from 5000 V to 50 V (MIT520/2) <250ms per µF to discharge from 10000 V to 50 V (MIT1020/2)
Capacitance measurement (above 500 V)
10 nF to 50 µF (dependent on measurement voltage)
Capacitance measurement accuracy (23 °C)
±5% ±5 nF
Voltage output accuracy (0 °C to 30 °C)
+4%, -0%, ±10 V of nominal test voltage at 1 GΩ load
Current measurement range
0.01 nA to 5 mA
Current measurement accuracy (23 °C)
±5% ±0.2 nA at all voltages
Default voltmeter range:
50-600 V a.c. or d.c. Accuracy (23 ºC) + or -2% + or -1 V
Interference rejection MIT520/2 1 mA per 250 V up to a maximum of 2 mA MIT1020/2 1 mA per 600 V up a maximum of 2 mA
Timer range
Up to 99 minutes and 59 seconds from start of test 15 second minimum setting for test voltage 1000 V 30 second minimum setting for test voltage <1000 V