Minuteman Model LPC-100
Ultra-Compact, Portable Load Bank
100 KW
Rated for Continuous Operation
Ultra-Compact, Portable, Easy to
Transport and Operate
Large Load Capacity – up to 100 KW
Lightweight Aluminized Steel
Enclosure – only 78 lbs. [35 kg]
Load Cables and Hard Shell
Travel Case are Included
Convenient Operator Controls
with Digital Metering and Data
Logging Software Included
The Avtron Minuteman Load Bank is a portable, self-
contained AC resistive load bank designed for indoor use.
The Minuteman Load Bank is the new
standard in ultra-compact, portable
load banks! The load bank provides
up to 100 KW resistive load at 480
VAC or 240 VAC, 3 phase, 60 Hz. This
versatile load bank weighs only 78
lbs. [35 kg], is lightweight and ultracompact. The load bank is also rated
for continuous operation, unlike most
competitive units.
The Minuteman Load Bank features
horizontal air discharge to provide a
low profile design. Fully-rated, quickconnect load terminals and simple
operation allow the load bank to be
set up and operated by a single technician, saving valuable time in the
field. The load bank controls and cooling fans are powered by any standard
120 VAC, single phase wall outlet with
detachable line cord provided.
An integral control panel is provided
for load bank operation and includes
the necessary controls and status
indicators. The load bank also includes the Avtron Advanced Digital
Monitoring System (ADMS)™ as a
standard feature. The ADMS meter
provides faceplate digital display of
Volts, Amps, Frequency, and KW.
Data Logging Software (included at
no additional cost) allows Real Time
Data Acquisition and trending of all
meter parameters from your Laptop
power test solutions
PC or PDA. An Infrared/USB interface
cable is included for “Plug and Play”
convenience.
Legendary Avtron quality combined
with simple operation and maintenance will provide years of trouble
free service.
Avtron’s extensive line of Load Bank
and Industrial Resis tor Products are
solid performers used throughout
the world.
For total technical support or
additional information, please
contact Avtron at (216) 573-7600
or LBsales@avtron.com.
Minuteman Portable Load Bank (Model LPC-100)
OUTLINE DRAWING:
1.50 [38.00]
1.38 [35.00]
23.75
[603.00]
CONTROL POWER
CONNECTOR
21.33 [541.00]
THIS
END
UP
DO
NOT
TILT
WARNING
B15896
AVTRON
AIR INTAKE SIDEAIR EXHAUST SIDE
CAUTION
LOAD CONNECTION
CONNECTORS
10.98 [278.00]
REFER TO OWNERS MANUAL FOR SINGLE PHASE
LOAD CONNECTION AND METERING INSTRUCTIONS
KW LOAD STEPS
MINUTEMAN
LPC-100D LOAD BANK
WARNING: LOAD CABLES MUST BE INSTALLED
AND LOCKED IN PLACE PRIOR TO CONNECTION
TO GENERATOR OR POWER SOURCE
ABC
WARNING: WHEN
OPERATING
SINGLE PHASE,
PROTECTIVE
GND
PLUG MUST BE
INSTALLED IN
AIRFLOW
PHASE C
SPECIFICATIONS:
CONTROL POWER: The load bank requires control power of 120 VAC,
single phase, 60 Hz (line cord provided).
CONTROLS: The operator control panel includes a MASTER LOAD ONOFF switch, individual load step ON-OFF industrial toggle switches, a
CONTROL POWER ON-OFF switch, and a LOAD VOLTAGE selector switch.
TWIST DRAW LATCHES
WHEELS
25.75 [654.00]
16.25 [413.00]
30.25
[768.00]
10.25 [260.00]
RETRACTABLE
HANDLE
EXTENSION
COOLING: The resistive elements are air-cooled by eight high velocity
muffin fans.
LOAD CABLES: The load bank includes a 10' [3048] cable set with fullyrated, quick-connect load terminals.
TRAVEL CASE: The load bank comes standard with a hard-shelf
protective travel case on casters with a telescoping handle.
DIGITAL METERING: Avtron Advanced Digital Monitor ing System
(ADMS)™ is provided for display of Volts, Amps, Frequency, and KW.
ADMS™ also includes Data Logging Software at no additional cost.
SAFETY FEATURES: The Minuteman Load Bank features multiple-array
overtemperature protection and wrong voltage detection circuitry. Load
Bus is short circuit protected by main line fuses (one for each phase).
WEIGHT:
Load Bank is approximately 78 lbs. [35 kg]
Load Bank, Case, & Cable Set is approximately 140 lbs. [63.5 kg]
ADMS™ is a trademark of Avtron LoadBank, Inc.
Communicator EXT™ is a trademark of Electro Industries/GaugeTech.
All dimensions are in inches [millimeters]. Specifications subject to change without notice.
LPC-100 RATINGS:
THREE PHASE
at 480 or 240 VAC
load steps are 12.5, 12.5, 25, 25, &
25 KW for a total of 100 KW
at 208 VAC
load steps are 10, 10, 20, 20, & 20 KW
for a total of 80 KW
SINGLE PHASE
at 120 VAC
load steps are 1.7, 1.7, 3.3, 3.3, &
3.3 KW for a total of 13.3 KW
at 240 VAC
load steps are 6.6, 6.6, 13.2, 13.2, &
13.2 KW for a total of 52.8 KW
Quality System Certied to ISO 9001
6255 Halle Drive • Cleveland, Ohio, U.S.A. 44125-4615 • 216.573.7600 • FAX 216.573.5953
www.avtronloadbank.com • LBsales@avtron.com Bulletin 440 • Rev. C