Atec CMC-156 User Manual

CMC 156 EP: 3 Phase Voltage + 3 Phase Current Test Set
Voltage generators/-amplifiers
Setting range
3-phase AC (L-N) 3 x 0 ... 127.5 V 1-phase AC (L-L) 1 x 0 ... 255 V DC (L-N) 3 x 0 ... ±127.5 V
Power
75
14 0
1 2 7 . 5
255
Output voltage / V
0
1-phase AC (L-L)
3-phase AC (L-N)
1-phase AC (L-N)
Output power / VA
Accuracy
2
error < 0.015 % rd. 3 + 0.005 % rg. 3 typ. at 0 ... 127.5 V error < 0.04 % rd. + 0.01 % rg. guar. at 0 ... 127.5 V
Distortion (THD+N)
4
< 0.015 % typ., < 0.05 % guar. Resolution 6 mV Connection 4 mm (0.16 in) banana sockets/comb. socket
Current generators/-amplifiers
Setting range
3-phase AC (L-N) 3 x 0 ... 12.5 A 1-phase AC (3L-N) 1 x 0 ... 27 A DC (3L-N) 1 x 0 ... ±30 A
Power
3-phase AC (L-N) 3 x 40 VA at 12.5 A 1-phase AC (3L-N) 1 x 75 VA at 27 A 1-phase AC (L-L) 1 x 75 VA at 12.5 A DC (3L-N) 1 x 60 W at ±12.5 A
75
14 0
1 2 7 . 5
255
Output voltage / V
0
1-phase AC (L-L)
3-phase AC (L-N)
1-phase AC (L-N)
Output power / VA
Accuracy
5
error < 0.015 % rd. + 0.005 % rg. typ.
at 0 ... 12.5 A
error < 0.04 % rd. + 0.01 % rg. guar.
at 0 ... 12.5 A Distortion (THD+N)
4
< 0.025 % typ., < 0.05 % guar. Ranges 1.25 A / 12.5 A Resolution (for respective range) 50 µA / 500 µA Resolution 500 µA Max. compliance voltage (L-N)/(L-L) 4 VRMS, 6 Vpk / 8 VRMS, 12 Vpk Connection 4 mm (0.16 in) banana sockets/comb. socket
At only 9.8 kg / 22 lbs, the CMC 156 EP is the smallest and lightest solution for three-phase testing of numerical relays. Its high precision makes it also the perfect device (class 0.05 % Working Standard) for testing and calibrating meters, transducers and other measurement equipment.
Generators, general
Frequency
range sine signals 10 ... 1000 Hz range transient signals DC ... 3.1 kHz accuracy/-drift ±0.5 ppm / ±1 ppm resolution 5 µHz
Phase
angle range - 360° ... +360° resolution 0.001°
error at 50/60 Hz < 0.005° typ., < 0.02° guar. Bandwidth (-3dB) 3.1 kHz Simulated
power S, P (calibration of energy meters)
accuracy
6
error < 0.05 % rd. 3 typ., < 0.1 % rd. guar. at 10-63 Hz, 50 ... 127.5 V, and 0.1 ... 12.5 A
temperature drift 0.001 % / °C typ.. < 0.05 % / °C guar.
Low level outputs
Setting range 6 x 0 ... 5 VRMS Max. output current 2 mA Accuracy error < 0.025 % typ., < 0.1 % guar. Resolution 250 µV Distortion (THD+N)
4
< 0.015 % typ., < 0.05 % guar. Unconventional CT/VT simulation linear Isolation SELV Usability completely independent from internal
amplifier outputs Connection 16 pin combination socket (rear side)
Binary Inputs
Number 10 Trigger criteria Toggling of potential-free contacts or DC
voltage compared to threshold voltage Input characteristics 0 ... +250 VDC threshold or potential-free Ranges (in RMS values) 250 VDC Resolution of threshold 1.5 V Sample rate 10 kHz (resolution 100 µs) Time stamping accuracy ±0.00015 % of rd.
3
±70 µs Max. measuring time infinite Counting function < 3 kHz at pulse width > 150 µs Galvanic isolation 2 galvanically isolated groups (4 + 6) Max. input voltage 250 VDC Connection 4 mm (0.16 in) banana sockets or measure-
ment combination socket
Counter inputs 100 kHz
Number 2 Max. counting frequency 100 kHz Pulse width > 3 µs Threshold voltage 6 V Voltage hysteresis 2 V Max. input voltage ±30 V Isolation SELV Connection 16 pin combination socket (rear side)
Technical Data
1
CMC 156 EP
Binary outputs, relays
Type potential-free relay contacts, software
controlled Number 4 Break capacity AC
Vmax: 250 VAC / Imax: 8 A / Pmax: 2000 VA Break capacity DC Vmax: 300 VDC / Imax: 8 A / Pmax: 50 W Connection 4 mm (0.16 in) banana sockets
Binary outputs, transistor
Type open collector transistor outputs Number 4 Update rate 10 kHz Imax 5 mA Connection 16 pin combination socket (rear side)
DC voltage measuring input
Measuring range 0 ... ±10 V Accuracy
error < 0.01 % rg.
3
typ., < 0.05 % rg. guar. Input impedance 1 MW Connection 4 mm (0.16 in) banana sockets or measure-
ment combination socket
DC current measuring input
Measuring range 0 ... ±20 mA Accuracy error < 0.01 % rg.
3
typ.,
< 0.05 % rg. guar. Input impedance 15 W Connection 4 mm (0.16 in) banana sockets or measure-
ment combination socket
Power supply
Nominal input voltage 110 – 240 VAC, 1-phase Permissible input voltage 99 ... 264 VAC Nominal frequency 50/60 Hz Permissible frequency range 47 ... 63 Hz Power consumption < 600 VA Rated current 6 A Connection Standard AC socket (IEC 60320)
Environmental conditions
Operation temperature 0 ... +50 °C (+32 ... +122 °F) Storage temperature -25 ... +70 °C (-13 ... +158 °F) Humidity range Relative humidity 5 ... 95 %,
Vibration IEC 60068-2-6 (20 m/s
non-condensing
2
at 10 ... 150 Hz)
Shock IEC 60068-2-27 (15 g/11 ms half-sine)
Safety Standards, Electromagnetic Compatibility
EMC The product adheres to the electromagnetic
compatibility (EMC) Directive 2004/108/EC (CE conform).
Emission Europe EN 61326-1; EN 61000-6-4; EN 61000-3-2/3
International IEC 61326-1;IEC 61000-6-4; IEC 61000-3-2/3
USA FCC Subpart B of Part 15 Class A
Immunity Europe EN 61326-1; EN 61000-6-2;
EN 61000-4-2/3/4/5/6/11
International IEC 61326-1;IEC 61000-6-2;
IEC 61000-4-2/3/4/5/6/11
Safety The product adheres to the low voltage
Directive 2006/95/EC (CE conform).
Europe EN 61010-1 Insulation of PC and SELV
interfaces complies with EN 60950-1
International IEC 61010-1
USA UL 61010-1
Canada CAN/CSA-C22.2 No 61010-1-04
Miscellaneous
Weight 9.8 kg (21.6 lbs) Dimensions (W x H x D,
(without handle) PC connection
7
343 x 145 x 268 mm (13.5 x 5.7 x 10.6 in)
parallel port (D-Sub 25 connector) Signal indication (LED) > 42 V for voltage outputs Hardware diagnostics Self diagnostics upon each start up Galvanic separated groups The following groups are galvanically
separated from each other: mains, voltage/
current amplifier output, binary input Protection All current and voltage outputs are
fully overload and short circuit proof and
protected against external high-voltage
transient signals and over temperature
Ordering Information
CMC 156 EP with Test Universe Software
VE001616 CMC 156 EP Basic VE001617 CMC 156 EP Protection VE001618 CMC 156 EP Advanced Protection VE001619 CMC 156 EP Meter VE001621 CMC 156 EP Measurement VE001622 CMC 156 EP Universal
1
Guaranteed values valid over one year within 23 °C ±5 °C (73 °F ±10 °F), in the
frequency range of 10 ... 100 Hz at nominal value, analog measurement inputs at full-scale value. Specifications for three-phase systems under symmetrical conditions (0°, 120°, 240°)
2
R
: 0 ... 0.5 W
load
3
rd. = reading, rg. = range
4
THD+N: Values at 50/60 Hz with 20 kHz bandwidth
5
R
: > 250 W
load
6
Data are valid for set value from 0.1 ... 12.5 A (current amplifier group A or B) at
50/60 Hz Permissible load current outputs: Range 1.25 A: 0 … 1 W and max. 1 VA, cos j = 0.5 … 1
Range 12.5 A: 0 … 0.5 W and max. 6 VA, cos j = 0.5 … 1
Permissible load voltage outputs: max. 10 VA at 50 V … full scale voltage, cos j = 0.5 … 1
7
For the control of CMC 156 EP via the USB port of the PC, a CMUSB-P USB to
Parallel Converter is included in delivery
Loading...