Atec BOP-1 User Manual

KEPCO’S BOP FAMILY OF
FOUR QUADRANT
BIPOLAR POWER SUPPLIES
146-1971a
AN ISO 9001 COMPANY
BOP 200W and 400W (Linear)
M MODELS: Standard - Analog Meter
200W Models: 20V, 36V, 50V, 100V, 200V
400W Models: 20V, 36V, 50V, 72V, 100V
D MODELS: Digital Meter
L MODELS: Optimized for Inductive Loads
C MODELS: Optimized for Capacitive Loads
-4886 MODELS: GPIB Control
BOP 40W High Voltage (Linear)
500V, 1000V
BOP 1KW (Switch-Mode)
MG MODELS: Standard
6V, 10V, 20V, 25V, 36V, 50V, 72V, 100V
GL MODELS: Optimized for Very Low Ripple and Noise
20V, 36V, 50V
Conventional d-c power supplies operate in a single quadrant of the voltage-current axis, delivering stabilized and adjustable d-c voltage or current to a load. They may be voltage stabilized, meaning that the current varies with the load, or they may be current stabilized, meaning that the voltage varies with the load.
Kepco's BOP operate in all four quadrants of the voltage-current axis, therefore their output may swing seamlessly from negative to positive voltage and the output current may also swing from positive to negative values. The result of this is that BOP will function as a source or a sink, meaning it will either deliver power to a load or absorb power from a load. In order to do that, the BOP is built as a power amplifier with a bipolar output, having a frequency band­width much larger than a regular power supply. The frequency bandwidth is model and option dependent.
In quadrant 1 of the volt-ampere axis, both voltage and current are positive so the BOP power supply is able to deliver power to a load. In quadrant 3 both are negative and the BOP is also a source. In quadrants 2 and 4, however, the voltage and current are of opposite polarity. In these two quadrants the BOP will act as a sink, absorbing power. The sinking may be transient in
nature as BOP absorbs energy stored in reactive elements or it may be steady state, when for example, BOP controls the discharge of a battery or acting as an electronic load, constant current for an external voltage source, or a constant voltage for an external current source.
FOUR-QUADRANT OPERATION
FROM A KEPCO BOP POWER SUPPLY
+ CURRENT
LIMIT
– CURRENT
LIMIT
The BOP 1KW has two primary control channels: voltage or current. Either of these may be controlled from full plus setting to full minus setting. To assure that they will intersect in one of the two source quadrants to form a closed boundary as do conventional unipolar power supplies,four auxiliary limit channels are provided: plus voltage, minus voltage , plus current and minus current. T hese four are controllable from a very small value to the nominal values. Their control does not pass through zero as do the primary voltage and current channels. The intersection of whichever primary control channel is engaged by the load and the respective limit channel does form a closed boundary , and a variable load automatically crosses over from the primary channel to the limit channel.
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA
Tel: (718) 461-7000 • Fax: (718) 767-1102
Email: hq@kepcopower.com • www.kepcopower.com
1000 WATT
BOP 6-125MG 0 to ±6 0 to ±125 0.6 12.5 0.05 1.5 24 1150
BOP 10-75MG 0 to ±10 0 to ±75 1.0 7.5 0.13 2.0 67 976
BOP 20-50MG 0 to ±20 0 to ±50 2.0 5.0 0.40 8.3 200 371
BOP 25-40MG 0 to ±25 0 to ±40 2.5 4.0 0.63 15.8 313 165
BOP 36-28MG 0 to ±36 0 to ±28 3.6 2.8 1.30 25 640 103
BOP 50-20MG 0 to ±50 0 to ±20 5.0 2.0 2.50 50 1250 55
BOP 72-14MG 0 to ±72 0 to ±14 7.2 1.4 5.14 104 2570 33
BOP 100-10MG 0 to ±100 0 to ±10 10.0 1.0 10.0 163 5000 16
BOP 1KW MODEL TABLE
NOTE: When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP. Otherwise the overvoltage protection will shut down the power supply.
d-c OUTPUT RANGE CLOSED LOOP GAIN
VOLTAGE
CHANNEL
GV(V/V)
VOLTAGE
V d-c
CURRENT
A d-c
MODEL CURRENT
CHANNEL
GI(A/V)
VOLTAGE MODE
SERIES RmΩSERIES LµHSHUNT RΩSHUNT C
µF
CURRENT MODE
OUTPUT IMPEDANCE
BOP 1KW (Switch-Mode)
Data subject to change without notice. © 2011 KEPCO, INC. Litho in USA
WHAT IS A 4QUADRANT
POWER SUPPLY?
3
1
2
4
Using switch-mode technology for low dissipation when sinking power from an active load, the BOP 1KW recuperate the energy for reuse. The key to this is a bi-directional a-c input power factor correcting (PFC) circuit, which allows transparent energy interchange without dissipative internal sinking.
2
YOU CAN MODEL MANY REAL-WORLD PHENOMENA IN WHICH POLARITY OR DIRECTION IS AN ISSUE
RIGHT/LEFT UP/DOWN HOT/COLD
CLOCKWISE/COUNTERCLOCKWISE
CHARGE/DISCHARGE FORWARD/REVERSE
APPLICATIONS FOR KEPCO’S
BOP 1KW
Automotive
Battery and Motor
Simulation and Testing
Wafer Deposition
and Electroplating
Magnet Applications
Particle Beam Correctors and Injectors,
Medical Imaging, etc.
Solar Panel Research and Testing
BOP 1KW FEATURES
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA
Tel: (718) 461-7000 • Fax: (718) 767-1102
Email: hq@kepcopower.com • www.kepcopower.com
BOP 1KW PHYSICAL CHARACTERISTICS
SPECIFICATIONS RATING/DESCRIPTION CONDITION
Dimensions
5.25" x 19" x 21.5" H x W x D
English
133.3 x 482.6 x 546.1 mm
metric
Weight
53 lbs
English
24.1kg
metric
* BOP 6-125MG and BOP 10-75MG only.
BOP 1KW INPUT CHARACTERISTICS
SPECIFICATIONS RATING/DESCRIPTION CONDITION
a-c Voltage
230V a-c
Single phase
nominal
176-264V a-c
range
Current
9.5A (7.5A)* Maximum
176V a-c
6.4A (4.4A)* Maximum
264V a-c
Frequency
Power Factor
Efficiency 65% (56%)* Minimum
when sourcing
Active PFC for
source and sink
50/60 Hz
47-63 Hz
0.99
0.97
Nominal output power
Complies with EN 61000-3-2
nominal
range
source
sink
Switching Frequency 70 KHz ±5%
(50KHz ±5%)*
BOP 1KW PROGRAMMING/DISPLAY CHARACTERISTICS
SPECIFICATIONS RATING/DESCRIPTION CONDITION
Full range output
0.5% to 100%
of nominal range
Direct entry
SCPI
Used for series
and parallel
configurations
Analog Control
-10V to +10V
voltage or current
main channel
+0.05V to +10V
voltage and current
protection limit channel
Digital Control
Display
Panel-mounted keypad
IEEE 488-2 (GPIB)
RS 232
RS 485 (BITBUS)
4" backlit LCD displays
all functions
All parameters read back on
RS 232 and GPIB buses
local
remote
remote
remote
front panel
remote
+ –
+ –
BOP 1KW GENERAL (ENVIRONMENTAL) SPECIFICATIONS
SPECIFICATIONS RATING/DESCRIPTION CONDITION
Temperature
0 to +50°C
Full rated load
operating
Vibration
10mm double amplitude 3-axes, non-operating
5 -10 Hz
-20 to +85°C
storage
2g 3-axes, non-operating
10-55 Hz
Cooling
Two internal fans Exhaust to the rear
Humidity
0 to 95% RH Non-condensing
Shock
20g, 11msec ±50% half sine
Non-operating
Altitude
Sea level to 10,000 ft.
For full specs, visit our Web site at www.kepcopower.com/bophi.htm
• Full 4-quadrant, 1000 watt, source-sink operation.
• Energy recuperation, during sink-mode, through a patented bi-directional PFC circuit.
• Meets the EN61000-3-2 harmonic limits. A built-in EN55011 Class A input EMI filter is provided.
• High efficiency switch-mode operation.
• Output voltage from ±6V to ±100V.
• Full digital control with built-in standard GPIB. Compatible with IEEE 488.2. Accepts standard SCPI commands. VISA driver provided. Also supports RS 232 bus.
• Large graphic LCD, displays settings and output voltage and current.
• Keypad control from front panel with menu to access functions.
• Calibration adjustments are made via the remote interface or locally from the keypad and are stored in non-volatile memory. Calibration is password protected.
• CE; Complies with the requirements of the Low Voltage Directive 73/23/EEC, the Marking and Declaration Directive 93/28/EEC, and the EMC Directive 89/336/EEC.
• Built-in complex waveform generator.
• Parallel (max. 5 units) or Serial (max. 3 units) connection of identical units. Parallel and Series connecting cables are required; contact factory for pricing.
3
BOP 1KW ALLOW FOR AUTOMATIC CREATION AND DISPLAY OF VARIOUS WAVEFORMS AND COMPLEX PATTERNS
The 1000-watt models have an internal w aveform generator that allows a user to combine segments of a sinusoidal waveform, triangular waveform, a ramp, a saw tooth waveform and a square 50% duty cycle pulse, plus d-c to create a variety of arbitrary waveforms . 3,933 of points per basic waveform can be programmed with arbitrary phase relationships. The resulting waveshape can be repeated from 1 to 255 times. The waveshape can also be executed indefinitely until a stop command is received. The wave­shape graphics are displayed on the front panel-mounted LCD display , which also shows both settings and actual d-c output values. The programmed waveshapes can be used to control either voltage or current with both positive and negative values. It is possible to reproduce an a-c sinusoid with differing degrees of distortion or dropouts for test purposes. Alternatively, varying amounts of “noise” can be added to a d-c output to gauge the effect on a test subject.
Sine Waveform
Triangle W aveform
Complex Sine Waveform
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA • Tel: (718) 461-7000 • Fax: (718)767-1102
Email: hq@kepcopower.com • www.kepcopower.com
For full specs, visit our Web site at www.kepcopower.com/bophi.htm
BOP 1KW OUTPUT CHARACTERISTICS
SPECIFICATIONS RATING/DESCRIPTION CONDITION
Type of Stabilizer
Voltage/Current 4-quadrant Switch mode
Output stage
Switching Frequency
Voltage Stabilization in Voltage Mode
Source Adjustment Range
100KHz ±5%
-100% to +100% of rating
-100% to +100% of rating
0-50°C
voltage
current
Sink Adjustment Range
-100% to +100% of rating
-100% to +100% of rating
0-50°C,
recuperated energy is
sent back into line for
general reuse
voltage
current
0.05% of rating
0.1% of rating
0.02% of rating
0.02%/°C of rating
2% Eomax p-p
0.2% Eomax rms
min-max
input voltage
0-100% load current
0.5 - 8 hours
0-50°C
Includes switching
noise
source effect
load effect
time effect (drift)
temperature effect
ripple
noise
Current Stabilization in Current Mode
0.05% of rating
0.2% of rating
0.02% of rating
0.02%/°C of rating
2% Iomax p-p
0.2% Iomax rms
min-max
input voltage
0-100% load current
0.5 - 8 hours
0-50°C
Includes switching
noise
source effect
load effect
time effect (drift)
temperature effect
ripple
noise
Error Sensing
0.25 volts per wire
Above rated output
Output Common Mode Voltage
Series Operation
Output Protection Limiting
Output Stage Protection
300V
Master/slave
Voltage and current
limited in four quadrants
Output overvoltage/
overcurrent,
heat sink overtemperature,
switchers overcurrent
Input Stage Protection (PFC)
Internal overvoltage,
undervoltage, overcurrent,
heat sink overtemperature,
fan inoperative
Triggers latched shutdown protection of the output module
and PFC stage.
Recover by cycling
power off, then on or
by pressing RESET
at the front panel
Maximum of 3 identical units, up to 300V max.
Parallel Operation
Master/slave
Output to chassis
ground
Transient Recovery in Voltage Mode
5% of nominal output nominal voltage,
50% load step
maximum excursion
200 μsec Return within 0.1%
of set voltage
recovery
time
Maximum of
5 identical units
Input circuit breaker
overcurrent
Trips circuit breaker to
shut off unit
Small Signal Bandwidth
2 KHz maximum
voltage channel
800 Hz maximum
(600 Hz Maximum)
(1)
current channel
Rise/Fall Time
250/200 μsec
voltage channel
0.7/1.2 mSec
current channel
Into short circuit
Into nominal
resistive load
Into short circuit
Into nominal
resistive load
4
(1) BOP 6-125MG only.
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA • Tel: (718) 461-7000 • Fax: (718)767-1102
Email: hq@kepcopower.com • www.kepcopower.com
USING KEPCO BOP 1KW FOR SOLAR DEVICE TESTING
Demonstration Application Interface Showing User Inputs
and Rendered I-V Curve Output
The K epco BOP 1KW provides a one-step solution for test and characterization of solar cells and solar panels. A free LabView subvi allows rapid characterization of the solar device using only the BOP 1KW, eliminating the need for separate DVMs to measure voltage and current. T he subvi is designed for both I-V Trace and Dark I-V testing, and can be plugged in or easily adapted to existing LabView test applications, even those previously using two DVMs. This solution offers lower cost, greater throughput and increased ROI when testing solar devices.
BOP 1KW SOLAR DEVICE TESTING FEATURES AND BENEFITS
• SOLAR DEVICE TESTING - Both I-V Trace and Dark I-V Tests supported.
• FLEXIBILITY - KEPCO BOP 1KW LabView Driver allows Solar Device testing while maintaining full functionality of the BOP 1KW Instrument Power Supply features.
• FASTER THROUGHPUT- 20mS per point.
• ROI - Test setups are quick and easy, require no special programming for synchronization, require no dedicated engineering resources to design and/or maintain components comprising a custom solution.
• LOWER COST AND SIMPLICITY - No need to purchase, maintain and calibrate two DVMs - Simplifies calibration, test setup and operation; no trigger connections needed.
• RELIABILITY - With all triggering and measurements done within BOP 1KW there are no synchronization or noise issues.
• PROVEN TECHNOLOGY - Enhancement of proven BOP 1KW technology.
• ENERGY CONSERVATION- Employs energy recuperation as well as active Power Factor Correction (PFC).
NOTE: When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP. Otherwise the overvoltage protection will shut down the power supply.
For other volt-ampere combinations, consult factory.
1000 WATT
BOP 20-50GL 0 to ±20 0 to ±50 2.0 5.0 0.02% 0.01%
BOP 36-28GL 0 to ±36 0 to ±28 3.6 2.8 0.02% 0.01%
BOP 50-20GL 0 to ±50 0 to ±20 5.0 2.0 0.02% 0.01%
BOP-GL 1000 WATT MODEL TABLE
d-c OUTPUT RANGE CLOSED LOOP GAIN
VOLTAGE
CHANNEL
E
o MAX V d-c
I
o MAX
A d-c
MODEL CURRENT
CHANNEL
RIPPLE AND NOISE
VOLTAGE
rms
CURRENT
rms
The BOP-GL series models are a standard modification of the 1KW that have been optimized for exceptionally low current ripple and noise and improved stability (drift and temperature), making them ideal for driving inductive loads such as large magnets or motors. These bipolar power supplies pass smoothly through zero without switching to provide true ± voltage and ± current.
BOP 1KW GL SERIES OPTIMIZED FOR VERY LOW RIPPLE AND NOISE
5
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA • Tel: (718) 461-7000 • Fax: (718)767-1102
Email: hq@kepcopower.com • www.kepcopower.com
The Kepco Model BOP 500M and BOP 1000M are high voltage power sources, up to ±500V or ±1000V, respectively.
For full specs, visit our Web site at www.kepcopower.com/bophv.htm.
BOP 200W AND 400W (Linear)
BOP 200W AND 400W FEATURES
• Source 100% and sink 50% of the output power rating.
• Separate control circuits for voltage and current with automatic crossover between main channel and limit channel.
• Controls and flag signals accessible through a 50-terminal port at the rear.
• Zeroable preamplifier available for scaling and summing external signals.
• Optional digital control via GPIB or RS 232. Add suffix -4886.
• Parallel and Series connection of identical models.
• Mounting in standard 19" racks RA 37: 3/4 rack size Mounting "ears" supplied: full rack size
APPLICATIONS FOR KEPCO’S BOP 200W AND 400W
Automotive
Battery and Motor Simulation and Testing
Wafer Deposition and Electroplating
Magnet Applications
Beam Steering, Medical Imaging, etc.
Solar Panel Research and Testing
For full specs, visit our Web site at www.kepcopower.com/bop.htm.
Their output is capable of both sustained d-c and the replication of arbitrary a-c waveforms. Voltage and current outputs can be controlled smoothly and linearly through the entire rated plus and minus ranges, passing smoothly through zero with no polarity switching.
The BOP 200W and 400W are high-speed operational amplifiers with full 4-quadrant, bipolar operation.
BOP 40W HIGH VOLTAGE (Linear)
These combine the capabilities of fast programmable power supplies with a Class A output stage, which can respond bi-directionally from zero. They can be operated in either a “voltage stabilizing” or “current stabilizing” mode. To realize the full high speed potential of the BOP HV, the load characteristics should be mainly resistive. Load capacitance and inductance up to 0.01µF and 0.5mH can be tolerated without performance deterioration.
CLOSE LOOP GAIN
VOLTAGE CURRENT
MODEL
(3)
CHANNEL CHANNEL OUTPUT IMPEDANCE
d-c OUTPUT RANGE G
V
G
I
VOLTAGE MODE CURRENT MODE
Eomax. Iomax. (V/V) (mA/V)
SERIES R
SERIES L
(1)
SHUNT R
SHUNT C
(2)
BOP 500M ±500V ±80mA 50 8.0 0.05Ω 5mH 100MΩ 0.3μF
BOP 1000M ±1000V ±40mA 100 4.0 0.2Ω 50mH 400MΩ 0.4μF
BOP HIGH VOLTAGE MODEL TABLE
(1) For determining dynamic impedance in voltage mode. (2) For determining dynamic impedance in current mode. (3) To specify digital display, substitute the suffix “DM” for “M.”
(1) Optional digital control va GPIB or RS232. Add suffix -4886. (2) For determining dynamic impedance in voltage mode. (3) For determining dynamic impedance in current mode. (4) Same size as 400W models. (5) To specify digital display, substitute the suffix letter “D” for the suffix letter “M.”
200 WATT
BOP 20-10M 0 to ±20 0 to ±10 2.0 1.0 0.04 40 20 0.05
BOP 36-6M 0 to ±36 0 to ±6 3.6 0.6 0.12 20 36 0.03
BOP 50-4M 0 to ±50 0 to ±4 5.0 0.4 0.25 50 50 0.02
BOP 100-2M 0 to ±100 0 to ±2 10.0 0.2 1.0 60 100 0.03
BOP 200-1M
(4)
0 to ±200 0 to ±1 20.0 0.1 4.0 1200 200 0.03
400 WATT
BOP 20-20M 0 to ±20 0 to ±20 2.0 2.0 0.02 10 20 0.5
BOP 36-12M 0 to ±36 0 to ±12 3.6 1.2 0.06 50 36 0.4
BOP 50-8M 0 to ±50 0 to ±8 5.0 0.8 0.125 100 50 0.15
BOP 72-6M 0 to ±72 0 to ±6 7.2 0.6 0.24 200 72 0.1
BOP 100-4M 0 to ±100 0 to ±4 10.0 0.4 0.5 200 100 0.1
BOP 200W AND 400W MODEL TABLE
d-c OUTPUT RANGE CLOSED LOOP GAIN
VOLTAGE
CHANNEL
GV(V/V)
VOLTAGE
V d-c
CURRENT
A d-c
MODEL
(1) (5)
CURRENT CHANNEL
GI(A/V)
VOLTAGE MODE
SERIES RmΩSERIES L
µH
(2)
SHUNT RKΩSHUNT C
µF
(3)
CURRENT MODE
OUTPUT IMPEDANCE
6
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA • Tel: (718) 461-7000 • Fax: (718)767-1102
Email: hq@kepcopower.com • www.kepcopower.com
OPTIMIZE BOP 200W AND 400W FOR DRIVING INDUCTIVE LOADS TO 1HENRY
BOP INDUCTIVE LOAD SPECIFICATIONS
BANDWIDTH (DC TO F-3dB)
INDUCTIVE LOAD, 2mH
RESISTIVE
LOAD, NOMINAL
RISE/FALL
TIME
(2)
BOP 20-20ML 0 to ±20V, 0 to ±20A
MODEL /
SPECIFICATION
(1)
BOP 36-6ML 0 to ±36V, 0 to ±6A
BOP 36-12ML 0 to ±36V, 0 to ±12A
BOP 50-4ML 0 to ±50V, 0 to ±4A
BOP 50-8ML 0 to ±50V, 0 to ±8A
12 KHz
LOAD EFFECT
RESISTIVE LOAD,
NOMINAL
(4)
3 ppm/Hz2.5 KHz 33μS
BOP 72-6ML 0 to ±72V, 0 to ±6A
BOP 100-2ML 0 to ±100V, 0 to ±2A
BOP 100-4ML 0 to ±100V, 0 to ±4A
RECOVERY TIME
CONSTANT AT STEP LOAD
(3)
180μS
BOP 20-10ML 0 to ±20V, 0 to ±10A
11.2 KHz 12 ppm/Hz4.1 KHz 35μS 220μS
12 KHz 4 ppm/Hz5 KHz 30μS 210μS
12.7 KHz 3 ppm/Hz6.8 KHz 28μS 100μS
1.43 KHz 20 ppm/Hz1.8 KHz 245μS 280μS
10.6 KHz 7 ppm/Hz4.9 KHz 31μS 200μS
2.6 KHz 50 ppm/Hz2.7 KHz 125μS 200μS
3.5 KHz 47 ppm/Hz5.0 KHz 84μS 250μS
1.2 KHz 70 ppm/Hz1.7 KHz 220μS 280μS
For digital meters, substitute the letter D for M when ordering - example: BOP 20-10DL.
For GPIB control of the BOP, add the suffix 4886 after the letter L in the model name ­example: BOP 20-10ML4886.
(1) All specifications listed are for inductive load models in Current Mode.
All other specifications are identical to the standard BOP. (2) 10% - 90%, nominal resistive load. (3) Short-circuit, nominal resistive load. (4) Load effect increases nonlinearly with frequency from the typical 0.5 mA in DC full scale
(same as the standard unit) at the average rate listed.
As an option (L suffix), Kepco’s 200W (except BOP 200-1M) and 400W BOP models may be optimized for driving inductive loads. These BOP units are designed to operate in a stable manner in Current or Current Limit Mode for loads up to 1 Henry . T h ey are also stable with any R-L series load combination.
To prevent voltage limit operation, the equivalent impedance of the R-L series load at the working frequency, must be lower than the nominal resistive load value (nominal output voltage/nominal output current).
All specifications of the unit in voltage mode are unchanged from the standard model. T he specifications listed in the table to the right are for inductive load models in Current Mode. All other specifications are identical to the standard BOP.
In current mode the bandwidth of the BOP is reduced when operating with a resistive load. Correspondingly, the rise and fall time of the unit is increased (model dependent). Further, it is possible to reduce the bandwidth in current mode in a predictable way, using one customer installed component on the rear programming connector of the BOP (see Bandwidth Correction Chart).
BOP INDUCTIVE LOAD - BANDWIDTH CORRECTION
BOP 20-20ML
EXTERNAL CAPACITOR
(ACROSS PINS 16 AND 18 OF PC 12 PROGRAMMING CONNECTOR)
MODEL
0.01 μF 0.02 μF 0.05 μF 0.1 μF 0.2 μF 0.5 μF 1 μF
4.0 KHz 2.4 KHz 1.0 KHz 0.57 KHz 0.30 KHz 0.12 KHz 0.07 KHz
BOP 20-10ML 4.1 KHz 2.3 KHz 1.0 KHz 0.57 KHz 0.27 KHz 0.11 KHz 0.06 KHz
BOP 36-6ML 4.0 KHz 2.5 KHz 1.0 KHz 0.55 KHz 0.25 KHz 0.12 KHz 0.06 KHz
BOP 36-12ML 4 KHz 2.4 KHz 1 KHz 0.57 KHz 0.27 KHz 0.11 KHz 0.06 KHz
BOP 50-4ML 1.4 KHz 1.2 KHz 0.7 KHz 0.47 KHz 0.25 KHz 0.11 KHz 0.06 KHz
BOP 50-8ML 3.6 KHz 2.1 KHz 0.93 KHz 0.54 KHz 0.29 KHz 0.12 KHz 0.06 KHz
BOP 72-6ML 1.75 KHz 1.3 KHz 0.75 KHz 0.47 KHz 0.26 KHz 0.11 KHz 0.06 KHz
BOP 100-2ML 1.8 KHz 1.4 KHz 0.8 KHz 0.51 KHz 0.27 KHz 0.11 KHz 0.06 KHz
BOP 100-4ML 1.0 KHz 0.8 KHz 0.6 KHz 0.4 KHz 0.23 KHz 0.11 KHz 0.06 KHz
For more information on the
BOP Inductive Load Models visit
www.kepcopower.com/bop-ind.htm
APPLICATIONS FOR KEPCO’S
BOP INDUCTIVE LOAD MODELS
Motor Testing
Testing of Magnetic Components
Coils, Speakers, etc.
Industrial Applications with
Inductive Loads
Driving CRT Coils
Cryogenic Applications
Correcting Magnets for
Medical Imaging or
Particle Accelerators
200 WATT
400 WATT
200 WATT
400 WATT
7
OPTIMIZE BOP 200W AND 400W FOR DRIVING CAPACITIVE LOADS TO 10 MILLI-FARADS
8
For digital meters, substitute the letter D for M when ordering - example: BOP 20-20DC.
For GPIB control of the BOP, add the suffix 4886 after the letter C in the model name ­example: BOP 20-20MC4886.
(1) All specifications listed are for capacitive load models in Voltage Mode. (2) For BOP 20-20MC, DC: nonuniformities of the frequency response creates a larger 3-dB bandwidth
for the resistive load than for the standard BOP.
(3) Nonuniformities of the frequency response for the standard 10μF load create a larger 3-dB bandwidth
than for the resistive load. (4) 10% - 90%, with nominal resistive load. (5) Load between infinity and nominal resistive values.
As an option (C suffix), Kepco's 200 Watt (except BOP 200-1M) and 400 Watt BOP models may be optimized for driving capacitive loads.
These BOP units are designed to operate in a stable manner in voltage or voltage limit mode for capacitive loads up to 10mF. They are also stable when driving any R-C parallel combination where load R is nominal value and C is 10mF. Load R (nominal value) = nominal output Voltage/nominal output Current (e.g., BOP 36-6MC, R = 36/6 = 6 Ohms). To prevent current limit operation, the equivalent impedance of the R-C parallel load circuit at the working frequency must be greater than the nominal R value.
Static specifications representing accuracy for various influence parameters are identical to the standard BOP models. Ripple and noise specifications are better (approximately 50% lower) for the C option units compared to the standard BOP.
In voltage mode, with a resistive load, the bandwidth of the BOP Capacitive Load is reduced versus the standard model, while the response time is increased (except the 20V model: see Specifications Chart). The frequency response variations can be practically eliminated by reducing the bandwidth in voltage mode in a predictable manner using an internal user-installed component to increase the internal compensation capacitance (see Bandwidth Correction Chart).
In Current Mode the dynamic specifications are almost identical for all BOP C option models: 3-dB bandwidth of 4.9kHz and rise/ fall time of 72µsec (lower bandwidth and higher rise/fall time than the standard BOP models).
For more information on the BOP Capacitive Load Models visit
www.kepcopower.com/bop-cap.htm
APPLICATIONS FOR KEPCO’S
BOP CAPACITIVE LOAD MODELS
Solar Cell/Panel
Research and Testing
Driving and Testing
Piezo-Electric Devices
Capacitor Testing
Driving and Testing
Capacitive Transducers
Industrial or Lab Applications
with Capacitive or
Capacitive-Resistive Loads
BOP CAPACITIVE LOAD SPECIFICATIONS
BANDWIDTH (DC TO F-3dB)
CAPACITIVE
LOAD, 10uF
(3)
RESISTIVE
LOAD, NOMINAL
(2)
RISE/FALL
TIME
(4)
BOP 20-10MC 0 to ±20V, 0 to ±10A
MODEL /
SPECIFICATION
(1)
BOP 36-12MC 0 to ±36V, 0 to ±12A
BOP 50-4MC 0 to ±50V, 0 to ±4A
BOP 72-6MC 0 to ±72V, 0 to ±6A
BOP 100-4MC 0 to ±100V, 0 to ±4A
12 KHz 14 KHz 32μS
RECOVERY TIME
AT STEP LOAD
(5)
100μS
BOP 36-6MC 0 to ±36V, 0 to ±6A
13.5 KHz 16.3 KHz 32μS 95μS
BOP 20-20MC 0 to ±20V, 0 to ±20A
4.8 KHz 5.3 KHz 75μS 225μS
13.5 KHz 16 KHz 30μS 95μS
BOP 50-8MC 0 to ±50V, 0 to ±8A
9 KHz 11 KHz 38μS 160μS
11.5 KHz 15 KHz 35μS 100μS
6.5 KHz 8.3 KHz 60μS 184μS
6.0 KHz 8.0 KHz 66μS 190μS
200 WATT
400 WATT
KEPCO, INC. • 131-38 SanfordAvenue• Flushing, NY 11355 USA • Tel: (718) 461-7000 • Fax: (718)767-1102
Email: hq@kepcopower.com • www.kepcopower.com
BOP CAPACITIVE LOAD - BANDWIDTH CORRECTION
BOP 36-6MC
INTERNAL USER-INSTALLED CAPACITOR
MODEL
1 nF 2.2 nF 4.7 nF 15 nF 33 nF 47 nF 100 nF
12.1 KHz 10 KHz 7.8 KHz 3.5 KHz 2.2 KHz 1.4 KHz 0.5 KHz
BOP 20-20MC 4.6 KHz 4.4 KHz 3.2 KHz 1.3 KHz 0.7 KHz 0.6 KHz 0.5 KHz
BOP 20-10MC 11.5 KHz 9 KHz 7.5 KHz 3.5 KHz 2.2 KHz 0.5 KHz
BOP 36-12MC 12 KHz 10 KHz 7.6 KHz 3.5 KHz 2.2 KHz 1.4 KHz 0.5 KHz
BOP 50-4MC 11 KHz 9 KHz 7 KHz 3 KHz 1.5 KHz 1 KHz 0.5 KHz
BOP 50-8MC 8.5 KHz 8 KHz 6.5 KHz 4.5 KHz 3 KHz 1.5 KHz 0.5 KHz
BOP 72-6MC 6.5 KHz 6.0 KHz 5.3 KHz 2.7 KHz 1.4 KHz 0.9 KHz 0.5 KHz
BOP 100-4MC 6.0 KHz 5.4 KHz 4.2 KHz 2.5 KHz 1.5 KHz 1.1 KHz 0.5 KHz
The listed bandwidth values are for C option units in Voltage Mode, nominal resistive load.
1.3 KHz
200 WATT
400 WATT
Loading...