Atec AEMC-SR752 User Manual

AC Current Probe Model SR752 (pdf) 10/05 Rev. 04
Technical Assistance (800) 343-1391 www.aemc.com1of 4
AC Current Probe Model SR752
The Model SR752 is designed for use in industrial and utility environments. The unique ergonomic design allows it to easily clamp onto cables or small bus bars. It is built to the highest safety and performance standards including the CE Mark and is UL approved for Canada and United States.
Excellent transformation and low phase shift, plus a broad frequency response, permit accurate measure­ments of current for power and power quality measurements. The high quality magnetic cores and uniform windings provide sensitivity for very low level current measurements, as well as measurements up to 1200A
AC.
The Model SR752 provides an accurate voltage of 1mV/A. This voltage output enables instruments without current ranges to measure, display and log currents through an AC voltage range or measure very low AC.

Features

Measurement range of
1mA to 1200A
AC
Large jaw opening accommodates
conductors up to two 500MCM conductors
Ergonomic design and easy
operation
Conforms to EN 61010, 600V Cat. III
safety standard
Low phase shift for power
measurements
Available with mV output signals
Designed for DMMs, recorders,
loggers, oscilloscopes, power and harmonic meters
• UL approved for Canada and United States
• Double Insulation
CE Mark

Applications

Power quality measuring
Low industrial loads
Measuring around cable bundles
Power load monitoring
Waveform analysis
AC Current Probe Model SR752 (pdf) 10/05 Rev. 04
Technical Assistance (800) 343-1391 www.aemc.com2of 4

Specifications

MODELS SR752
ELECTRICAL
Nominal Range 1000A Measurement Range 1mA to 1200A Transformation Ratio Voltage output Output Signal 1mV
AC/AAC
(1VAC @ 1000A)
Accuracy (1000A Range)
1mA to 100mA 3% of Reading ± 5µV
0.1 to 1A 2% of Reading ± 3µV 1 to 10A <1% of Reading
10 to 100A 0.5% of Reading
100 to 1200A 0.3% of Reading
Phase Shift (1000A Range)
1 to 10A ≤2°
10 to 100A ≤1°
100 to 1200A ≤0.7°
Overload 1200A for 40 min ON,
20 min OFF
Frequency Range 30Hz to 5kHz; current derating above 1kHz using the formula: 1000A x 1F (in kHz) Load Impedance 100kΩ min Working/Common
Mode Voltage
600Vrms Cat. III
Output Termination 5 ft Lead
MECHANICAL
Operating Temperature -14° to 122°F (-10° to 50°C) Storage Temperature -4° to 158°F (-20° to 70°C) Operating Relative
Humidity
0 to 85% @ 35°C
Jaw Opening 2.25" (57mm) max Maximum Conductor Size 2.05" (52mm) Maximum Bus Bar Size One 1.95 x 0.19" (50 x 5mm) Dimensions 4.37 x 8.50 x 1.77" (111 x 216 x 45mm) Weight 1.21 lbs (550g) Polycarbonate Material Handles: Polycarbonate + ABS, Gray, UL94 V0. Jaws: Polycarbonate, Red, UL94 V0
SAFETY
Electrical EN 61010-2-032
UL Approval Yes – Canada and United States
Double Insulation Yes
CE Mark Yes
Note: Reference conditions:
23 ± 3°K, 20 to 75% RH, 48 to 65Hz, external magnetic field <40A/m, no DC component, no external current carrying conductor, test sample centered. Load impedance 1Ω.