POWER & ENERGY LOGGER
PEL 100 Series
Models PEL 102 & PEL 103
TM
ETHERNET
FEATURES
•
Simple to use, single-, dual- (split-phase)
and three-phase (Y, ∆) power & energy loggers
•
Provides all the necessary functions for
Power and Energy data logging for 50Hz, 60Hz,
400Hz and DC distribution systems
•
Current measurements from 200mA up to
10,000A using flexible current sensors
•
Automatic recognition of the connected current
sensors/probes
•
Power measurements: VA, W and var
•
Energy measurements VAh, Wh (source/load
indication) and varh (including quadrant indication)
•
Record cost of energy usage
• Power Factor (PF), Cos (ϕ), Tan (Φ) and DPF
• Total Harmonic Distortion (THD) for voltages
and currents
•
Harmonics up to the 50th order for 50/60Hz
voltages and currents and 7th order for 400Hz
•
Simultaneous RMS measurements of each phase
@ 128 samples/cycle and DC
•
Bright blue, four line LCD on Model PEL 103
(3 phases shown simultaneously)
• Storage of measured and calculated values
on a SD-Card or SDHC-Card
• Configuration of current and voltage ratios
to external PT and CT ratios
• USB, LAN, and Bluetooth communication
• Includes DataView® software for data
storage, real-time display, analysis and report
generation with supplied pre-defined or custom
templates
NEW!
Economical, compact and
simple to use!
KEy FEATURES oF ThE pEl 103 diSplAy
Measured Phase
Indicator
Information
Display
Bar
Bargraph
(Load factor Min - Max). The
bargraph indicates
the percentage
(0% to 100%) of full
range or full load
as programmed
into the PEL by the
user through the
®
DataView
Mode Selection
Display Bar
software.
Measurements
or Page Title
Top And BoTTom diSplAy BARS indicATE ThE Following
TOP DISPLAY BAR
ICON DESCRIPTION
Phase Sequence reversal indicator or missing
phase (displayed in 3-Phase distribution systems)
Data available for recording (non-display indicates
possible internal problem)
Power Quadrant Indication
BOTTOM DISPLAY BAR
Measurement Mode (Real-time values)
Power and Energy Mode
Harmonics Mode
Min/Max Mode
Information Mode
Not used
pRodUcT inclUdES
Models PEL 102 & PEL 103
Models PEL 102 and PEL 103 include:
Small Classic Tool Bag, Three MiniFlex
MA193-10-BK Sensors (included with select
models), 5 ft USB Cable, Four Black Test Leads
and Alligator Clips, Power Cord, 12 Color-coded
ID Markers, Multifix Mounting System, Safety
Card for the PEL, Sensor Compliance Sheet, 2
GB SD-Card with USB-SD-Card Reader,
Quick Start User Guide and USB Stick
with DataView
Measurement Values
Measurement
Units
®
and User Manual.
®
Technical Assistance (800) 343-1391 www.aemc.com
POWER & ENERGY LOGGER
PEL 100 Series
SpEciFicATionS
GENERAL
Sampling Frequency
Data Storage Rate
Demand Period Storage Rate
Recorded Parameters
(Single- and Poly-Phase)
Event Log
Front Panel Indicator LEDs
Storage Capacity
INPUTS Voltage
Current
ELECTRICAL
VOLTAGE MEASUREMENT RANGE RESOLUTION * ACCURACY (% of Reading)
50/60Hz
Single-Phase RMS Voltages
Phase-to-Phase RMS Voltages
400Hz
Single-Phase RMS Voltages
Phase-to-Phase RMS Voltages
DC
PT Ratios
CURRENT MEASUREMENT
Current Probe: MiniFlex
CT Ratios
POWER MEASUREMENTS
Active Power (P)*
Reactive Power (Q)*
Apparent Power (S)*
Power Factor
Tangent φ (active/reactive power ratio)
ENERGY MEASUREMENTS
Active Energy (EP)
Reactive Energy (EQ)
Apparent Energy (ES)
THD
Individual Harmonics
External Supply
Back-Up Power Source / Charge Time
Battery Life
MECHANICAL
Communication Ports
Dimension/Weight
Case / Index of Protection
Mounting / Security
DISPLAY
Display Type for Model PEL 103
ENVIRONMENTAL / SAFETY
Operating Temperature / Relative Humidity
Storage Temperature
Safety Rating / CE Rating
* Maximum value is current probe dependent. ** Computers with Class II Bluetooth will restrict range to 40ft. Computers without Bluetooth will require a Class I or Class II Bluetooth radio
adapter.
*** Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.
®
Sensor MA193***
Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status
2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB) formatted FAT32 are supported
42.5 to 69Hz
100 to 1000rms 0.1V ±0.2% Rdg ± 0.2V
100 to 2000Vrms 0.1 to 1V ±0.2% Rdg ± 0.4V
340 to 460Hz
100 to 600Vrms 0.1V ±1% Rdg ± 1V
200 to 1200Vrms 0.1 to 1V ±1% Rdg ± 1V
100 to 1000V 0.1V ±1% Rdg ± 3V (typical)
Programmable from 50V to 65,0000V 0.01V to 0.1V
200mA to 100Arms 1 to 100mA ±1% ± 50mA
20 to 400Arms 10 to 100mA ±1% ± 0.2A
100 to 2000Arms 0.1 to 1A ±1% ± 1A
500 to 10,000Arms 0.1 to 1A ±1%
Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / Yes
Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF
Tracks and records status changes and error messages along with recorded data
3 current input channels via custom 4 pin jacks that accept AEMC® probes and sensors
-2 to 2GW 0.001W ±0.5% Rdg ± 0.005% Pnom
-2 to 2Gvar 0.001var ±1% Rdg ± 0.01% Qnom
0 to 2GVA 0.001VA ±0.5% Rdg ± 0.005% Snom
-1 to +1 0.001 ± 0.05
-3.2 to +3.2 0.001 ± 0.02
0 to 4 x 10
0 to 4 x 10
0 to 4 x 10
2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness and contrast
18
18
18
Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / IP54 non operating
Embedded magnets on back side, keyhole slot on back side / Kensington anti-theft system
-4° to 122°F (-20° to 50°C) with batteries; -4° to 158°F (-20° to 70°C without batteries)
128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz)
1 per second
User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes)
V, I, W, VA, var, PF, Tan, Wh, Vah, varh, THD (V and I),
3 voltage input channels via 4mm safety banana jacks
Programmable from 1:1 to 25,000:1 (probe dependent)
1varh ±2% Rdg
± 655%
1 to 50 displayed in percentage; 1 to 7 at 400Hz
110V/250V (10%) @ 50/60Hz; 400Hz
Rechargeable 8.4V NiMH battery pack / Approximately 5 hours
Provides up to 30 minute ride through upon power loss
USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **
10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / <1kg
32° to 122°F (0° to 50°C) / up to 85%
Models PEL 102 & PEL 103
–
– –
1Wh ±0.5% Rdg
1Vah ±0.5% Rdg
±0.1Hz
–
CATALOG NO. DESCRIPTION
2137.51 Power & Energy Logger Model PEL 102 (no LCD, w3 MA193-10-BK sensors)
2137.52 Power & Energy Logger Model PEL 103 (with LCD, w3 MA193-10-BK sensors)
2137.61 Power & Energy Logger Model PEL 102 (no LCD, no sensors)
2137.62 Power & Energy Logger Model PEL 103 (with LCD, no sensors)
Technical Assistance (800) 343-1391 www.aemc.com