Atag iC 24, iC 28, iC Economiser Plus 27, iC 36, iC 40, iC Economiser Plus 39, iC Economiser Plus 35, iR, iR 15, iR 40, iR 18, iR 24, iR 32 Installation & Servicing Instructions Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
I n s t a l l a t i o n & S e r v i c i n g
Instructions
iC24
iC28
iC36
iC40
iCEconomiser Plus 27
iCEconomiser Plus 35
iCEconomiser Plus 39
Natural Gas Boilers
Boiler G.C No
iC 24 47-310-19
iC 28 47-310-21
iC 36 47-310-23
iC 40 47-310-25
iC Economiser Plus 27 47-310-27
iC EconomiserPlus 35 47-310-29
iC EconomiserPlus 39 47-310-31
CE PIN 0063CQ3634
These instructions are to be retained by the user.
Explanation of the Control Panel & Buttons
DHW Visible when DHW program is active
Flashing when there is a heat demand for DHW
Error Error indication (accompanied with a code).
Alert Service-mode or blocking
Pump Visible when pump is set to continuously
Flashing when frost program is active
Eco Visible when DHW comfort function is not active
Flame Visible when boiler is active for heating or DHW
Heating Visible when heating program is active Flashing when there is a heat demand for heating
Central heating program (On = +, Off = -)
Setting of boiler temperature (max. fl ow temperature)
+/-function (ancillary function: OK and Escape)
Eco-function DHW on/off . Press 6 seconds for Information
Reset button
DHW program (On = +, Off = -)
Setting of hot water temperature
+/-function (ancillary function: Scroll and +/-function)
Commissioning function (Press both + buttons for 6 seconds)
Pump function (Press both - buttons for 6 seconds)
Information on the water pressure:
The default view of the display shows OK. Press the eco-button for
6 seconds and press the scroll-buttons until A6 is displayed.
The actual water pressure will be shown:
Water pressure too low
Code 118 and spanner symbol visible:
Water pressure is too low (<0.8 bar).
Power is reduced by 20%. The installation should be refi lled.
or
Code 118 and spanner symbol visible:
Water pressure is too low (<0.5 bar).
The boiler is taken out of operation. The installation should be refi lled.
After the installation has been refi lled and if the pressure was below
0.5 bar the de-aeration program will start (Code 105 and spanner
symbol visible). This will last for approx 7 mins.
Water pressure too high
Code 117 and spanner symbol visible:
Water pressure is too high (> 3.0 bar).
The boiler is taken out of operation.
The installation pressure should be reduced by draining water from the heating system.
See chapter 12 for more information about button functions and read-out.
These instructions describe the functioning, installation, use and primary maintenance of ATAG central heating
boilers for the United Kingdom.
These instructions are intended for the use of Gas Safe registered installers in connection with the
installation and putting into operation of ATAG boilers. It is advisable to read these instructions thoroughly,
well in advance of installation. Separate instructions for use are supplied with the boiler for users of ATAG
central heating boilers. ATAG is not liable for the consequences of mistakes or shortcomings which have
found their way into the installation instructions or user’s manual. Further, ATAG reserves the right to alter its
products without prior notifi cation.
When delivering the boiler, give the customer clear instructions concerning its use; present the
customer with the user’s manual and warranty card.
Each boiler is fi tted with an identifi cation plate. Consult the details on this plate to verify whether the boiler is
compliant with its intended location, e.g.: gas type, power source and exhaust classifi cation.
On completion of the installation the installer or commissioning engineer must fi ll out and complete the
Benchmark Commissioning Checklist found on page 59 of this manual and hand this to the customer
for future record keeping. The Benchmark Service Record must also be completed by the service agent
following each service call, and return to the customer.
The following regulations apply to installation of ATAG central heating boilers:
Legislation and Regulations.
Gas Safety (Installation and Use). All gas appliances must by law, be installed by a competent person, eg.
Members of Gas Safe Register and in accordance with the current Gas Safety Regulation. Failure to install
appliance correctly could lead to prosecution.
All Gas Safe registered installers carry a Gas Safe ID card and have a registration number. You can call Gas
Safe Register directly on 0800 408 5577.
In addition to the above regulations this appliance must be installed in compliance with the current IEE
Regulations and Building Regulations. Regulations and bye laws of the Local Water Authority and the
Current Health and Safety Regulation.
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The
purpose is to ensure that customers are provided with the correct equipment
for their needs, that it is installed, commissioned and serviced in accordance
with the manufacturer’s instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate
compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the
Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage
and promote the Scheme.
Visit www.centralheating.co.uk for more information.
The current Electricity at Work Regulation must be complied with and also be in accordance with the relevant
and current editions of the British Standards.
The ATAG iC boiler is a certifi ed appliance and must not be modifi ed or installed in any way contrary to
this Installation Manual. Manufacturers instructions must not be taken, in any way, as overriding statutory
obligations.
The ATAG iC boiler is a central heating boiler with an integrated hot water function. The boiler must be
connected according to these instructions and all installation norms in respect of the part of the boiler to be
connected.
The appliance is not to be used by children or persons with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction.
Children being supervised not to play with the appliance.
Observe the following rules of safety:
- All work on the boiler must take place in a dry environment.
- ATAG boilers may never be in operation without their housing, except in connection with maintenance or
adjustments (see Chapter 15 and 16).
- Never allow electrical or electronic components to come into contact with water.
Carry out the following tasks in connection with maintenance, etc. to an already-installed boiler:
- Shut down all programs
- Close the gas isolation valve
- Shut down the 230V power supply
- Close the shut off valve of the boiler’s cold water supply
Take note of the following when maintenance or adjustments are needed:
- The boiler must be able to function during these activities; for this reason, the boiler’s 230V power supply,
gas pressure and water pressure must be maintained. Ensure that there is not a source of potential
danger during these activities.
Following maintenance or other activities; always check the installation of all parts through which
gas fl ows (using leak detection spray).
The following (safety) symbols may be encountered in these installation instructions and on the boiler
(packaging):
Boiler must be stored away from frost.
Protect packaging and/or contents from damage as a result of insuffi cient care taken during
transport.
Protect the boiler from weather conditions during transport and storage whilst still in its packaging.
If and how to clamp when using transport trucks with clamp equipment.
If and how to transport when using a rolling jack.
The whole packaging is made of recycled materials and can be recycled again.
Transport and place the boiler in its packaging in this position.
Do not to step on or stand on the package.
An assembly or dismantling must be carried out.
Pay extra attention in connection with a particular operation.
Useful tip or advice
Disposal of the product
This product should be handed in at a designated collection point, e.g. by handing it in at a duly authorized
reseller when purchasing a similar product, or at an authorized collection site for recycling products wich
contains electrical and electronic equipment (EEE) and batteries and accumulators. Because of the
potentially hazardous substances that usually accompany EEE, improper handling of this type of waste could
have a possible impact on the environment and human health.
Your cooperation in the proper disposal of this product will contribute to the eff ective usage of natural
resources.
For more information on recycling this product, please contact your city offi ce, local waste disposal facilities,
offi cial service for chemical waste or landfi ll site.
The delivery package of the boiler is composed as follows:
- Boiler frame;
- Boiler with cover;
- Automatic air vent (in boiler);
- Safety valve 3 bar (in boiler);
- Three way valve (in boiler);
- Automatic by-pass (in boiler);
- DHW fl ow restrictor (in boiler);
- Economiser (only economiser-versions)
- Expansion vessel 8 litre / 1 bar (in boiler frame);
- Isolation valves with drainpoint (CH 2x, 1x DHW cold)
- Gas isolating valve;
- Filling loop;
- Mains cold water fi lter;
- Fittings consisting of plugs and screws;
- Outside sensor;
- Drawing template;
- Installation instructions;
- User manual;
- Warranty Card.
The following components are not present in the boiler packaging as a standard and should be included in
the installation according to the requirements:
- Flue system;
- External controls.
6 Boiler description
The ATAG iC is a room sealed, condensing and modulating CH boiler equipped with an integrated hot water
supply.
The boiler is equipped with a compact stainless steel heat exchanger with smooth pipes. It is a well thoughtout principle using sustainable materials.
The boiler burns natural gas to supply heat (LPG conversion kits available). This heat is transferred in
the heat exchanger to the water in the CH installation. The rapid cooling off of the fl ue gases causes
condensation. This results in a very high effi ciency. The condensate that is formed, has no negative impact
on the heat exchanger and it's operation, and is removed through the internal siphon. This feature requires a
condensate drain pipe connected to the drain of the building.
The boiler is equipped with an intelligent control system. The boiler anticipates on the heat demand of the
heating installation or hot water demand. This will cause the boiler to tune its capacity to the installation. This
means that the boiler will function longer and at a low level.
If an outside sensor is connected, the control system is able to function, depending on the weather. This
means that the control system measures the outside temperature and the fl ow water temperature. On the
basis of this information the control system calculates optimum fl ow water temperature required for the
installation.
The boiler has been tested according to valid CE standards and has a CE certifi cate and >88% Effi cient
SEDBUK 2009.
10
Statement: No banned materials including asbestos, mercury, CFC's have or will not be included in
the product.
Install the boiler in a boiler room in accordance to the actual local regulations BS5440-2:2009.
The installation location of the boiler has to be, and remain, frost-free. The boiler casing is splash water tight
(IPX4D) and is suitable to be installed in e.g. a bathroom.
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is
installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due
to the extremely low surface temperature of the boiler casing during operation. Therefore the requirements of
BS5440:2 may be disregarded.
The boiler can be mounted practically to any wall with the wall frame and the enclosed fi xing equipment. The
wall must be fl at and of suffi cient strength in order to be able to carry the boiler weight with its water content.
Above the boiler there must be at least 210 mm working space in order to be able to fi t a horizontal
concentric fl ue system to the rear (See chapter 9.8 for more fl ue options). Make sure there is suffi cient
service space around the boiler according fi gure 8.a. The location of the boiler can be determined by using
the template.
The wall frame allows the possibility to pre-fi t the complete heating and DHW system before fi tting the boiler.
Also the fl ue system can be prepared. Finally fi tting of the fl ue system is done after fi tting the boiler. See next
page for all options for connection the heating, DHW, condensate, fl ue and gas installation.
Before hanging the boiler to the boiler frame remove the front panel of the boiler fi rst. The front panel is also
the air cabinet and is attached to the boiler case with 2 fasteners (A and B) (see fi gure 8.a).
Note that there is an earth cable (when present) to disconnect when removing the boiler front panel.
Free space for removing the connector is about 400 mm. Remember to connect this earth cable
(when present) when placing back the boiler front panel and take care the wire does not get stuck
between front panel and boiler. Always replace and turn the 2 screws tight in the fasteners A and B.
Service dimensions (in mm) Figure 8.a
See chapter 9.8 for further procedure to fi t the boiler onto the boiler frame.
- Position the boiler frame against the wall using the template and a level.
- Use the level for horizontal positioning and checking the vertical position.
- Drill 4x ø10mm holes, 60mm deep
- Press the nylon wall plug (ø10x55mm) in the holes
- Mount the boiler frame to wall with the 4 coach screws (ø8x60mm) using a 13mm wrench
The boiler frame allows pipe work to be installed behind the boiler.
Note that there are free spaces on the left and right of the expansion vessel. Do not guide pipe work
in front of the expansion vessel. The pipe work must be installed at least 10mm inside the front of the
frame.
= free space for piping
ATAG i-Serie template and iC-Range boiler frame Figure 8.1.a
The boiler is provided with isolation valves on the fl ow and return pipe to which the installation can be
connected by means of 22mm compression fi ttings;
- The gas pipe.
The boiler is provided with an isolation gas valve to which the gas line can be fi tted with 22mm
compression fi tting;
- The condensation drain pipe.
It consists of a 25mm fl exible plastic pipe. The drain pipe can be connected to this by means of an open
connection;
- The fl ue gas exhaust system and air supply system.
It consists of a concentric connection 60/100 mm.
- Cold and hot water pipes.
The boiler is provided with a isolation valve on the cold water inlet. The DHW installation can be
connected by means of 15mm compression fi ttings.
See following chapters for detailed information regarding each connection.
It is advisable to clean all of the boiler’s connecting pipes and/or to power fl ush the installation
before connecting it to the boiler.
9.1 Central heating system
Connect the central heating system according to the current regulations.
The boiler pipes can be connected to the installation by means of 22mm compression fi ttings. For connecting
to thick-walled pipe (welded or fi tted), adapters should be used.
The boiler has a self-adjusting and self-protecting control system for the load. This involves checking the
temperature diff erence between the fl ow and return water. Table 9.1.a shows the water displacement the
circulation pump can deliver for a particular installation resistance.
If the installation resistance is higher than the value stated, the control system will adjust the load until a
temperature diff erence between fl ow and return water is reached that is acceptable for the control system.
When the temperature diff erence still remains too high the boiler will switch itself off and wait until the high
temperature diff erential between the fl ow and return water has decreased again.
Pump typeGrundfos UPM3 15-75
iC 24iC 28iC36iC 40iC Economiser Plus 27iC Economiser Plus 35iC Economiser Plus 39
The control system will, if an unacceptable temperature diff erence is detected, repeatedly try to establish a
water fl ow. If this does not succeed, the boiler will block itself (code 154).
The boiler is NOT equipped with a built-in internal fi lter.
Advice: ATAG Heating Technology Ltd recommend the installation of an in-line fi lter installed into the
heating return as close to the boiler as possible. ATAG Heating Technology Ltd recommend the use
of the:
ATAG iGuard Magnetic fi lter 22mm (Plastic) FC000100, (Brass) FC000200, 28mm (Brass) FC000250.
The boiler is not suitable for installations that are equiped with “open” expansion tanks.
Additives in the installation water are only permitted in consultation with the country distributor. See
chapter 9.3 for detailed information.
9.2 Expansion vessel
The iC boilers are featured with a built-in expansion vessel with a capacity of 8 litres and a pre-pressure
charge 1 bar. If the expansion vessel size is insuffi cient for the CH system, an additional expansion must be
installed. The additional expansion vessel should, together with the built-in expansion vessel, be sized to the
water content of the installation. The pre-pressure charge depends on the height of the installation above the
installed expansion vessel. See Table 9.2.a.
The (additional) expansion vessel should be connected as closely as possible in the return pipe near
the boiler.
Installation height above the expansion vesselpre-charge pressure of the expansion vessel
5m0.5 bar
10m1.0 bar
15m1.5 bar
The pressure relief valve outlet is combined with the condensate outlet (see fi gure 9.9.e on page 29).
table 9.2.a
9.3 Water quality
Fill the installation with mains cold water.
In most cases, a heating system can be fi lled with water according to national standards for water and
treatment of this water is not necessary.
In order to avoid problems with the CH-installations, the quality of the fi lling water has to meet the
specifi cations mentioned in table 9.3.a:
If the fi lling water does not meet the required specifi cations, you are advised to treat the water to such an
extent that it does meet the required specifi cations.
The warranty becomes invalid, if the installation is not being fl ushed and/or the quality of the fi lling
water does not meet the specifi cations recommended by ATAG Heating Technology Ltd. Always
contact ATAG Heating Technology Ltd in advance, if things are not clear or you wish to discuss any
deviations. Without approval, the warranty becomes invalid.
Installation:
- The use of groundwater, demi-water and distilled water is prohibited. (on the next page you will fi nd an
explanation of these defi nitions)
- If the mains water quality meets the specifi cations mentioned in table 9.3.a, you can start fl ushing the
installation before installing the device.
- Whilst fl ushing, corrosion products (magnetite), fi tting products, cutting oil and other undesirable products
have to be removed.
- Another possibility is to remove the pollution by installing a fi lter. The fi lter type has to fi t the type and
grain size of the pollution. ATAG Heating Technology Ltd recommends fi lter usage.
- In this case, the whole piping system should be taken into consideration.
- The CH-installation has to be properly vented before using the system. For that purpose, we refer to the
commissioning chapter.
- If a regular water top up is required (>5% on an annual basis), then there is a structural problem and
an installer has to solve the problem. Regularly adding fresh water to the system also adds additional
calcium and oxygen implying that magnetite and calcium residues can continue. The result may be
blockages and/or leakages.
- The use of anti-freeze and other additives requires periodical quality checks of the fi lling water in
accordance with the period laid down by the additives supplier.
- Chemical additions are to be avoided and should only be used after ATAG Heating Technology Ltd has
approved their corresponding use.
- Should you wish to achieve the required water quality by using chemical additives, then this is your own
responsibility. The warranty on the product delivered by ATAG Heating Technology Ltd expires, if the
water quality does not meet ATAG Heating Technology's specifi cations or the chemical additives have not
been approved by ATAG Heating Technology Ltd.
- On installation and during additions or changes at a later stage, ATAG Heating Technology Ltd
recommends to keep a record of the type of water used, its quality at the time, and if applicable, which
additives and quantities were added.
ParameterValue
Water typePotable water
Softened water
pH6.0-8.5
Conductivity (at 20°C in µS/cm)Max. 2500
Iron (ppm)Max. 0.2
Hardness (°dH / ppm):
Installation volume/capacity
<20 l/kW
Installation volume/capacity
>=20 l/kW
OxygenNo oxygen diff usion allowed during operation.
Corrosion inhibitorsRefer to Additives Attachment
pH increasing or lowering agentsRefer to Additives Attachment
Anti-freeze additivesRefer to Additives Attachment
Other chemical additivesRefer to Additives Attachment
Solid substancesNot allowed
Residues of processing water not forming part of the
drinking water
table 9.3.a
1-12 °dH / 17-214 ppm
1-7 °dH / 17-125 ppm
Max. 5% fi lling water addition annually
Not allowed
Water quality in DHW facility
ParameterValue
Water typePotable water
pH7.0-9.5
Conductivity (at 20°C in µS/cm)Max. 2500
Chloride (ppm)Max. 150
Iron (ppm)Max. 0.2
Hardness (°dH / ppm):1-12 °dH / 17-214 ppm
Number of bacterial colonies at 22°C (number/ml). pr
EN ISO 6222
table 9.3.b
- When the amount of chloride is above the required specifi cations mentioned above in table 9.3.b, in case
of the use of a combi boiler will void the warranty for DHW parts of the boiler.
Water type defi nition:
Potable water: Tap water compliant with the European drinking water guideline:
98/83/EG dated 3 November 1998.
Softened water: Water with partly de-ionised calcium and magnesium.
Demi-water: Virtually completely demineralised water (very low conductivity)
Distilled water: Water no longer containing minerals.
When connecting or using an underfl oor heating system, designed with plastic pipes, or plastic pipes are
used elsewhere in the installation, one should ensure that the plastic pipes used comply with the DIN
4726/4729 standard. It is set out in this standard that the pipes may not have oxygen permeability higher
than 0.1 g/m³.d at 40°C. If the system does not comply with this DIN standard, the underfl oor heating
component will have to be separated from the central heating appliance by means of a plate exchanger.
No recourse can be made to the terms of the warranty in the event of failure to observe the
regulations pertaining to plastic underfl oor heating pipes.
9.5 Gas connection in general
The local gas supplier should be consulted, at the installation planning stage, in order to establish the
availability of an adequate supply of gas. An existing service pipe must NOT be used without prior
consultation with the local gas supplier.
ATAG supplies boilers suitable for natural gas only. Verify the identifi cation plate on the boiler if the
boiler is suitable for the gas kind on site.
For use with propane gas, the LPG conversion kit has to be installed, see separate conversion
instructions.
Make sure that the gas pipe work does not contain dirt, particularly with new pipes.
The complete installation MUST be tested for gas tightness and purged as described in the above
code.
The boiler connection is provided with an isolation valve with 22mm compression fi tting, into which the gas
line can be fi tted.
9.5.1 Natural gas connection (NG)
The gas supply must comply to the current Gas Safety, Installation & Use Regulations, in accordance with
BS.6891.
The nominal inlet working gas pressure measured at the appliance should be 21 mbar +/- 2 mbar for Nat
gas (G20). Allowing for the acceptable pressure loss of 1 mbar across the installation pipework, it can
be assumed that a minimum permitted operating pressure of 18 mbar will be delivered to the inlet of the
appliance. (Reference BS 6400-1 Clause 6.2 Pressure Absorption). When tested at the gas valve, the
pressure drop from the meter to the gas valve must not be more than 4 mbar.
9.5.2 Propane gas connection (LPG)
For use with propane gas, the LPG conversion kit has to be installed, see separate conversion instructions.
The LPG installation must comply to the current Gas Safety, Installation & Use Regulations, in accordance
with BS:6891
Installing of a LPG installation should only be done by a registered LPG installer.
The tank must be provided with a high pressure regulator with a minimum capacity of 24 kg/h to reduce
the tank pressure from 5 to 1.5 bar. The 1.5 bar high pressure gas line should have a minimum diameter of
15mm. In the high pressure gas line a house pressure regulator must be installed. When tested at the gas
valve, the pressure drop from the pressure regulator to the gas valve must not be more than 3.8 mbar.
Each gas appliance which is connected to the propane installation must be provided with its own
house pressure regulator. The house pressure regulator is a third party delivery.
The house pressure regulator must have a minimum capacity of 10 kg/h / 37 mbar and a CE certifi cation.
ATAG advices to install the house pressure regulator as close as possible to the boiler. When placing the
regulator inside, a discharge drain of ø6mm must be installed. The discharge drain must be directed outdoor.
In case of a discharge the gasses will go outside.
If fi tting the regulator outside the regulator should be protected against infl uences of the weather. The (de-)
aeration must be positioned downwards (see fi gure 9.5.3.a).
ATAG advices to install measure points on all gas line parts to have the possibility to check for pressure loss.
example propane installation fi gure 9.5.3.a
Pre-pressure must be adjusted to 37 mbar by means of the house pressure regulator. The maximum
permitted closing pressure may be 5 mbar higher than the maximum pre-pressure.
A too high closing pressure in the low pressure gas line can be caused by a high resistance or jam in this gas
line. When the closing pressure keeps increasing the valve in the regulator is not closing correctly. In this
case the regulator should be replaced.
9.5.4 Dimensioning of the low pressure gas line
The gas line from the house pressure regulator to the boiler must have the dimensions according the table
below.
Pump typeGrundfos UPM3 15-75
iC 24iC 28iC36iC 40iC Economiser Plus 27iC Economiser Plus 35iC Economiser Plus 39
Diameter gas linemmmmmmm
ø15mm3 - - - - - -
ø22mm30181818181818
ø28mm - 303030303030
Dimensioning low pressure gas line table 9.5.4.a
9.5.5 De-aerating the LPG tank
When placing a new or revised LPG tank the tank must always be de-aerated.
ATAG advices to inform the gas supplier that a central heating boiler is connected to the LPG tank. For the
boiler it is absolutely necessary that the tank is free of air. When not the boiler will give ignition problems and
will not function.
ATAG advices to measure the content of O2 . This value should be lower than 1.3%. Contact the gas
supplier in case of doubt.
Connection of the drinking water installation should be done according to the Water Supply (Water Fittings)
Regulations and Scottish Water Byelaws.
The ATAG iC boiler is fi tted with a stainless steel plate heat exchanger for producing domestic hot water. The
boiler does not have a hot water store and in case of a demand for hot water the boiler will heat the domestic
water fl owing through the plate heat exchanger up to 60°C (adjustable) instantaneous.
The water mains installation must comply with the Water Supply (Water Fittings) Regulations and Scottish
Water Byelaws. See also chapter 9.3.
In regions with a water hardness value higher than 200ppm (2.67 mmol/l), calcium deposits should
be removed from the plate heat exchanger on a regular basis. If problems occur when using sanitary
water with a chlorine content higher than 150 mg/l, no recourse can be made to the terms of the
warranty.
In order to prevent calcifi cation ATAG recommends applying a water softener.
ATAG recommends the use of for instance AlphaPhos for cleaning plates exchangers.
The hardness of the water is variable in the United Kingdom. The water company can provide exact
information about this.
The domestic water installation can be connected to the boiler by means of 15mm compression fi ttings.
If the mains is fi tted with water meter, check valves or loose jumper stop cock, then a DHW expansion device
must be fi tted.
The boiler is provided with a DHW fl ow restrictor. The fl ow restrictor ensures that a quantity of water supplied
has a guaranteed temperature of 60 °C (assuming a cold water temperature of 10°C). The amount of water
is virtually unaff ected by the water pressure.
After installation, check the hot water fl ow rate with a fully opened hot water tap,
If required the fl ow restrictor can be removed. See chapter 16.1.
9.7 Condensation drain pipe
The ATAG condensing boiler has the >88% Effi cient SEDBUK 2009 for high energy effi ciency in heating and
domestic hot water. The ATAG wall hung gas fi red condensing boiler contain a siphonic condensate trap to
collect and realease condensate. The amount of condensate formed is determind by the type of boiler and
the water temperature produced by the boiler.
Condensate pipework.
Use plastic pipework of an internal diameter no less then 19mm ID (typically 22mm OD).
Routing of the pipework,
The condensate pipework must fall at least 45mm per metre away from the boiler, taking the shortest
practicle route to the termination point.
Support the pipe at least every 50 cm for near horizontal sections and 1 metre for vertical sections.
Wherever possible, the condensate pipework should be routed internally to prevent freezing. In order to
minimise the risk of freezing during prolonged very cold spells, one of the following methods of terminating
condensate drainage pipe should be adopted.
Internal pipework
Wherever possible, the condensate drainage pipe should be terminated at a suitable internal foul water
discharge point such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe,
washing machine waste pipe etc. A suitable permanent connection to the foul waste pipe should be used.
Figures 9.7.1, 9.7.2(a), 9.7.2(b) show appropriate connection methods.
The possibility of waste pipes freezing downstream of the connection point should be considered when
determining a suitable connection point - e.g. a slightly longer pipe run to an internal soil stack may be
preferable to a shorter run connecting into a kitchen waste pipe discharging directly through the wall to an
external drain.
Where “gravity discharge” to an internal termination is not physically possible (e.g. the discharge point is
above the appliance location, or access is obstructed by a doorway), or where very long internal pipe runs
would be required to reach a suitable discharge point, the following measures may be adopted.