These instructions are to be retained by the user.
1 | Introd | uction | 4 |
---|---|---|---|
2 | Rules | & Regulations (Symbols) | 5 |
3 | Techn | ical specifications | 7 |
4 | Dimer | isions | 9 |
5 | Delive | ry package | 10 |
6 | Boiler | description | 10 |
7 | Boiler | photo components list | 11 |
8 | Mount | ing boiler frame | 12 |
U U | 8 1 | Wall frame | 13 |
9 | Conne | acting boiler | 14 |
U | 9.1 | Central heating system | 14 |
0.1 | 15 | ||
0.2 | 15 | ||
9.5 | Valer quarky | 17 | |
9.4 | Cos connection in general | 17 | |
9.5 | 17 | ||
9.5.1 | 17 | ||
9.5.Z | Propane gas connection (LPG) | 11 | |
9.5.3 | House pressure regulator | 18 | |
9.5.4 | Dimensioning of the low pressure gas line | 18 | |
9.5.5 | De-aerating the LPG tank | 18 | |
9.6 | Hot water supply | 19 | |
9.7 | 19 | ||
9.8 | Flue gas exhaust system | 23 | |
9.8.1 | Flue terminal locations | 24 | |
9.8.2 | Dimensioning of the flue gas and air intake duct | 27 | |
9.9 | Fitting the boiler onto the boiler frame | 29 | |
10 | Electri | cal connection | 31 |
10.1 | One controller, OpenTherm and BUS connection | 32 | |
10.2 | Room thermostat volt free connection | 32 | |
10.3 | ATAG Central Heating volt free timer connection | 32 | |
10.4 | ATAG Hot Water volt free timer connection | 32 | |
10.5 | DHW sensor connection | 32 | |
10.6 | ATAG Outside sensor | 32 | |
10.7 | 230V Control Block (230V live output) | 32 | |
10.8 | 230V Control Block (SwL Switched live) | 32 | |
10.9 | Electrical diagram | 33 | |
11 | Fillina | system | 34 |
11.1 | Hot water supply | 34 | |
12 | Boiler | controls | 35 |
12 1 | Controls and explanation of the functions | 36 | |
13 | Comm | issioning the holer | 37 |
10 | 13.1 | Settings | 39 |
13.2 | Parameter chanter | 30 | |
1/ | leolat | ing the boiler | 10 |
15 | Comm | 11 | |
15 | 15 1 | 41 | |
15.1 | 42 | ||
15.2 | 40 | ||
40 | 15.3 | CO and combustion checks | 40 |
10 | Rouur | 48 | |
10.1 | 52 | ||
10.2 | 52 | ||
16.3 | User's instructions | 52 | |
. – | 16.4 | warranty | 52 |
17 | Error ( | codes and fault finding | 53 |
Ann | exA | System water additives | 54 |
Ann | ex B | Declaration of conformity | 55 |
Ann | ex C | Snort parts list | 56 |
Work on the installation should only be carried out by qualified personnel with calibrated equipment and appropriate tools.
These instructions describe the functioning, installation, use and primary maintenance of ATAG central heating boilers for the United Kingdom.
These instructions are intended for the use of Gas Safe registered installers in connection with the installation and putting into operation of ATAG boilers. It is advisable to read these instructions thoroughly, well in advance of installation. Separate instructions for use are supplied with the boiler for users of ATAG central heating boilers. ATAG is not liable for the consequences of mistakes or shortcomings which have found their way into the installation instructions or user's manual. Further, ATAG reserves the right to alter its products without prior notification.
Each boiler is fitted with an identification plate. Consult the details on this plate to verify whether the boiler is compliant with its intended location, e.g.: gas type, power source and exhaust classification.
On completion of the installation the installer or commissioning engineer must fill out and complete the Benchmark Commissioning Checklist found on page 59 of this manual and hand this to the customer for future record keeping. The Benchmark Service Record must also be completed by the service agent following each service call, and return to the customer.
The following regulations apply to installation of ATAG central heating boilers:
Gas Safety (Installation and Use). All gas appliances must by law, be installed by a competent person, eg. Members of Gas Safe Register and in accordance with the current Gas Safety Regulation. Failure to install appliance correctly could lead to prosecution.
All Gas Safe registered installers carry a Gas Safe ID card and have a registration number. You can call Gas Safe Register directly on 0800 408 5577.
In addition to the above regulations this appliance must be installed in compliance with the current IEE Regulations and Building Regulations. Regulations and bye laws of the Local Water Authority and the Current Health and Safety Regulation.
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance
with the manufacturer's instructions by competent persons and that it meets the
requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
The current Electricity at Work Regulation must be complied with and also be in accordance with the relevant and current editions of the British Standards.
The ATAG iC boiler is a certified appliance and must not be modified or installed in any way contrary to this Installation Manual. Manufacturers instructions must not be taken, in any way, as overriding statutory obligations.
The ATAG iC boiler is a central heating boiler with an integrated hot water function. The boiler must be connected according to these instructions and all installation norms in respect of the part of the boiler to be connected.
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
Observe the following rules of safety:
Carry out the following tasks in connection with maintenance, etc. to an already-installed boiler:
See chapter 15 and 16 for further instructions.
Take note of the following when maintenance or adjustments are needed:
- The boiler must be able to function during these activities; for this reason, the boiler's 230V power supply, gas pressure and water pressure must be maintained. Ensure that there is not a source of potential danger during these activities.
The following (safety) symbols may be encountered in these installation instructions and on the boiler (packaging):
Protect packaging and/or contents from damage as a result of insufficient care taken during
Boiler must be stored away from frost.
transport.
Protect the boiler from weather conditions during transport and storage whilst still in its packaging.
If and how to clamp when using transport trucks with clamp equipment.
If and how to transport when using a rolling jack.
The whole packaging is made of recycled materials and can be recycled again.
Transport and place the boiler in its packaging in this position.
Do not to step on or stand on the package.
An assembly or dismantling must be carried out.
Pay extra attention in connection with a particular operation.
Useful tip or advice
ATAG iC-Series | ||||||||
---|---|---|---|---|---|---|---|---|
Com | oi | |||||||
Boiler type | iC 24 | iC 28 | iC 36 | iC 40 | iC Economiser 27 | iC Economiser 35 | iC Economiser 39 | |
Type heat exchanger | iCon1 | iCon1 | iCon2 | iCon2 | iCon1 | iCon2 | iCon2 | |
CE product identification number (PIN) | 0063CQ | 3634 | ||||||
Country of destination | UK | |||||||
Q min input min. CH & DHW (H i ) | kW | 4.5 | 4.5 | 6.2 | 6.2 | 4.5 | 6.2 | 6.2 |
Q n input nominal CH (H i ) | kW | 21.6 | 21.6 | 28.8 | 28.8 | 21.6 | 28.8 | 28.8 |
Q r adjusted input CH (H i ) | kW | 21.6 | 21.6 | 28.8 | 28.8 | 21.6 | 28.8 | 28.8 |
Q min input min. CH & DHW (H s ) | kW | 5.0 | 5.0 | 6.9 | 6.9 | 5.0 | 6.9 | 6.9 |
Q n input nominal CH (H₅) | kW | 24.0 | 24.0 | 32.0 | 32.0 | 24.0 | 32.0 | 32.0 |
Q nw input nominal DHW (H i ) | kW | 23.9 | 27.3 | 35.4 | 37.9 | 28.4 | 36.4 | 38.3 |
Q nw input nominal DHW (H s ) | kW | 26.6 | 30.3 | 39.3 | 42.0 | 31,5 | 40.4 | 42,5 |
P min output min, CH (50/30°C) | kW | 5.0 | 5.0 | 6.9 | 6.9 | 5.0 | 6.9 | 6.9 |
P n output nominal CH (50/30°C) | kW | 23.2 | 23.2 | 31.2 | 31.2 | 23.2 | 31.2 | 31.2 |
P min output min. CH (80/60°C) | kW | 4.4 | 4.4 | 6.1 | 6.1 | 4.4 | 6.1 | 6.1 |
P n output nominal CH (80/60°C) | kW | 21.2 | 21.2 | 28.3 | 28.3 | 21.2 | 28.3 | 28.3 |
Pww output DHW | kW | 23.4 | 26.8 | 34.7 | 37.1 | 30.1 | 38.5 | 40.5 |
Nox class EN15502-1 | 6 | |||||||
O 2 (at full load) | % | 4.7 | ||||||
CO 2 (at full load) | % | 9.0 | ||||||
Temperature class flue | T100 | ) | ||||||
Appliance type | B23, B33, C1 | 3, C33, C43 | C53, C63, C83 | , C93 | ||||
Max. flue resistance at Qnw/Qn | Pa | 130 | 153 | 191 | 143 | 151 | 140 | 148 |
Flue gas temperature CH (80/60°C full load) | °C | 59 | ||||||
Flue gas temperature CH (50/30°C full load) | °C | 34 | ||||||
Flue gas mass flow (full load DHW) | g/s | 10 | 11 | 14 | 15 | 11 | 15 | 15 |
Flue gas temperature CH (36/30°C low load) | . | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Gas categories | 11 2H31 | 7 | ||||||
Gas pressure 2H / 3P |
mbar
m2/br |
2.52 | 2 90 | 2 74 | 20/3 | 2.00 | 2.95 | 4.05 |
V/H
|
2.55 | 2.09 | 3.74 |
4.00
~ 230/ |
50 | 5.65 | 4.05 | |
Degree of protection acc. EN 60529 | V/IIZ | IP |
230/
230/ 230/ |
33 IPX0D) | ||||
Overrun time pump CH | sec | 60 | ||||||
Overrun time pump DHW | sec | 20 | ||||||
P MS water pressure CH min./max. | bar | 0.8 / | 3 | |||||
Flow temperature max. | °C | 80 | ||||||
Available pump height CH | kPa | 25 | 25 | 20 | 20 | 25 | 20 | 20 |
P MW water pressure DHW min./max. | bar | 0.5 / | 8 | |||||
DHW temperature setting (T in =10°C) | °C | 60 | 60 | 60 | 60 | 60 | 60 | 60 |
Threshold DHW | l/min | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
DHW flow (T in =10°C, ΔT=35°C) | l/min | 10.1 | 11.5 | 14.9 | 16.2 | 12.6 | 16.1 | 17.0 |
DHW flow (T in =10°C, ΔT=50°C) | l/min | 6.7 | 7.7 | 10.0 | 10.7 | 8.6 | 11.1 | 11.6 |
SAP Annual Efficiency NG | % | 89.7 | 89.7 | 89.7 | 89.7 | 89.7 | 89.7 | 89.7 |
Weight boiler + jig (empty) | kg | 41 | 41 | 44 | 44 | 43 | 46 | 46 |
Content DHW part | I | 0.3 | 0.3 | 0.3 | 0.3 | 0.6 | 0.6 | 0.6 |
Boiler type | iC 24 | iC 28 | iC 36 | iC 40 | IC Economiser 27 | IC Economiser 35 | IC Economiser 39 | |
---|---|---|---|---|---|---|---|---|
Heat exchanger type | iCon2 | iCon2 | iCon2 | iCon2 | iCon2 | iCon2 | iCon2 | |
O 2 (at full load) | % | 5.1 | ||||||
CO 2 (at full load) | % | 10.3 | ||||||
Pre pressure | mbar | see data pla | ite LPG | |||||
Input CH DHW (Hi) | kW | 21.6 (23.9) | 21.6 (27.3) | 28.8 (35.4) | 28.8 (37.9) | 21.6 (28.4) | 28.8 (36.4) | 28.8 (38.3) |
Gas consumption max. G31 | kg/h | 1.90 | 2.16 | 2.80 | 2.99 | 2.24 | 2.88 | 3.03 |
Gas consumption max. G31 | m 3 /hr | 1.00 | 1.14 | 1.47 | 1.58 | 1.18 | 1.52 | 1.59 |
Output (80/60°C) | kW | 8.3 - 21.2 | 8.3 - 21.2 | 19.1 - 28.3 | 19.1 - 28.3 | 8.3 - 21.2 | 19.1 - 28.3 | 19.1 - 28.3 |
Output (50/30°C) | kW | 9.0 - 23.2 | 9.0 - 23.2 | 20.8 - 31.2 | 20.8 - 31.2 | 9.0 - 23.2 | 20.8 - 31.2 | 20.8 - 31.2 |
ErP specifications according to European Guid | eline 2010 | )/30/EU | ||||||
---|---|---|---|---|---|---|---|---|
Boiler type | iC 24 | iC 28 | iC 36 | iC 40 | iC Economiser 27 | iC Economiser 35 | iC Economiser 39 | |
Declared load profile DHW | - | XL | XL | XXL | XXL | XXL | XXL | XXL |
Seasonal space heating energy efficiency class | А | А | А | A | А | Α | А | |
Water heating energy efficiency class | А | А | А | А | А | А | А | |
P n Power output | kW | 21 | 21 | 28 | 28 | 21 | 28 | 28 |
Q HE Annual energy consumption | GJ | 69 | 69 | 104 | 115 | 69 | 104 | 115 |
AEC Annual electricity consumption | kWh | 49 | 51 | 52 | 52 | 57 | 52 | 52 |
AFC Annual fuel consumption | GJ | 17 | 17 | 21 | 21 | 20 | 20 | 20 |
η s Seasonal space heating energy efficiency | % | 94 | 94 | 94 | 94 | 94 | 94 | 94 |
η WH Water heating energy efficiency | % | 85 | 84 | 90 | 90 | 94 | 96 | 96 |
L WA Sound power level, indoors | dB | 46 | 46 | 48 | 48 | 46 | 48 | 48 |
P 4 nominal output (80/60°C) | kW | 21.2 | 21.2 | 28.3 | 28.3 | 21.2 | 28.3 | 28.3 |
P 1 30% of nominal output (36/30°C) | kW | 7.2 | 7.2 | 9.6 | 9.6 | 7.2 | 9.6 | 9.6 |
η 4 efficiency at nominal input (GCV) | % | 88.3 | 88.3 | 88.6 | 88.6 | 88.3 | 88.6 | 88.6 |
η 1 efficiency at 30% of the nominal heat input (GCV) | % | 99.4 | 99.4 | 99.6 | 99.6 | 99.4 | 99.6 | 99.6 |
el max | kW | 0.074 | 0.074 | 0.074 | 0.074 | 0.074 | 0.074 | 0.074 |
el min | kW | 0.021 | 0.021 | 0.032 | 0.032 | 0.021 | 0.032 | 0.032 |
P SB | kW | 0.004 | 0.004 | 0.004 | 0.004 | 0.004 | 0.004 | 0.004 |
P stby heat loss | kW | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 |
Q elec Daily electricity consumption DHW | kWh | 0.249 | 0.249 | 0.240 | 0.240 | 0.264 | 0.238 | 0.238 |
Q fuel Daily fuel consumption DHW | kWh | 22.7 | 22.96 | 27.3 | 27.3 | 25.6 | 25.1 | 25.1 |
Temperature Control | Weather | rcompensato | r (outside senso | or) | ||||
Class of temperature control | || | || | || | || | || | 11 | 11 | |
Contribution of temperature control | % | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Packago | ||||||||
Seasonal space heating energy efficiency of package | % | 96 | 96 | 96 | 96 | 96 | 96 | 96 |
CH Package Energy Label | А | А | A | А | Α | Α | Α | |
DHW Package Energy Label | А | А | А | А | А | А | А |
The delivery package of the boiler is composed as follows:
The following components are not present in the boiler packaging as a standard and should be included in the installation according to the requirements:
The ATAG iC is a room sealed, condensing and modulating CH boiler equipped with an integrated bot water. .vlaque
The boiler is equipped with a compact stainless steel heat exchanger with smooth pipes. It is a well thoughtout principle using sustainable materials.
The boiler burns day to supply heat (natural day and LPG versions available). This heat is transferred in the heat exchanger to the water in the CH installation. The rapid cooling off of the flue gases causes condensation. This results in a very high efficiency. The condensate that is formed, has no negative impact on the heat exchanger and it's operation, and is removed through the internal siphon. This feature requires a condensate drain pipe connected to the drain of the building
The boiler is equipped with an intelligent control system. The boiler anticipates on the heat demand of the heating installation or hot water demand. This will cause the boiler to tune its capacity to the installation. This means that the boiler will function longer and at a low level.
If an outside sensor is connected, the control system is able to function, depending on the weather. This means that the control system measures the outside temperature and the flow water temperature. On the basis of this information the control system calculates optimum flow water temperature required for the installation
The boiler has been tested according to valid CE standards and has a CE certificate and >88% Efficient SEDBUK 2009.
Statement: No banned materials including asbestos, mercury, CFC's have or will not be included in /!\ the product.
The installation location of the boiler has to be, and remain, frost-free. The boiler casing is splash water tight (IPX4D) and is suitable to be installed in e.g. a bathroom.
It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the extremely low surface temperature of the boiler casing during operation. Therefore the requirements of BS5440:2 may be disregarded.
The boiler can be mounted practically to any wall with the wall frame and the enclosed fixing equipment. The wall must be flat and of sufficient strength in order to be able to carry the boiler weight with its water content. Above the boiler there must be at least 210 mm working space in order to be able to fit a horizontal concentric flue system to the rear (See chapter 9.8 for more flue options). Make sure there is sufficient service space around the boiler according figure 8.a. The location of the boiler can be determined by using the template.
The wall frame allows the possibility to pre-fit the complete heating and DHW system before fitting the boiler. Also the flue system can be prepared. Finally fitting of the flue system is done after fitting the boiler. See next page for all options for connection the heating, DHW, condensate, flue and gas installation.
Before hanging the boiler to the boiler frame remove the front panel of the boiler first. The front panel is also the air cabinet and is attached to the boiler case with 2 fasteners (A and B) (see figure 8.a).
Note that there is an earth cable (when present) to disconnect when removing the boiler front panel. Free space for removing the connector is about 400 mm. Remember to connect this earth cable (when present) when placing back the boiler front panel and take care the wire does not get stuck between front panel and boiler. Always replace and turn the 2 screws tight in the fasteners A and B.
Service dimensions (in mm)
See chapter 9.8 for further procedure to fit the boiler onto the boiler frame.
Figure 8.a
The boiler frame allows pipe work to be installed behind the boiler.
Note that there are free spaces on the left and right of the expansion vessel. Do not guide pipe work in front of the expansion vessel. The pipe work must be installed at least 10mm inside the front of the frame.
Figure 8.1 a
The boiler has the following connection pipes;
See following chapters for detailed information regarding each connection.
It is advisable to clean all of the boiler's connecting pipes and/or to power flush the installation before connecting it to the boiler.
Connect the central heating system according to the current regulations.
The boiler pipes can be connected to the installation by means of 22mm compression fittings. For connecting to thick-walled pipe (welded or fitted), adapters should be used.
The boiler has a self-adjusting and self-protecting control system for the load. This involves checking the temperature difference between the flow and return water. Table 9.1.a shows the water displacement the circulation pump can deliver for a particular installation resistance.
If the installation resistance is higher than the value stated, the control system will adjust the load until a temperature difference between flow and return water is reached that is acceptable for the control system. When the temperature difference still remains too high the boiler will switch itself off and wait until the high temperature differential between the flow and return water has decreased again.
Pump type | |||||
---|---|---|---|---|---|
Boiler | Water flow ra | ite at ∆T 20°C | Permissible insta | llation resistance | |
type | l/min | l/h | kPa | mbar | |
Grundfos | |||||
iC 24 | UPM3 15-75 | 15.2 | 910 | 25 | 250 |
iC 28 | UPM3 15-75 | 15.2 | 910 | 25 | 250 |
iC 36 | UPM3 15-75 | 20.3 | 1220 | 20 | 200 |
iC 40 | UPM3 15-75 | 20.3 | 1220 | 20 | 200 |
iC Economiser 27 | UPM3 15-75 | 15.2 | 910 | 25 | 250 |
iC Economiser 35 | UPM3 15-75 | 20.3 | 1220 | 20 | 200 |
iC Economiser 39 | UPM3 15-75 | 20.3 | 1220 | 20 | 200 |
Installation resistance
table 9.1.a
The control system will, if an unacceptable temperature difference is detected, repeatedly try to establish a water flow. If this does not succeed, the boiler will block itself (code 154).
Advice: ATAG Heating Technology Ltd recommend the installation of an in-line filter installed into the heating return as close to the boiler as possible. ATAG Heating Technology Ltd recommend the use of the:
ATAG iGuard Magnetic filter 22mm (Plastic) FC000100, (Brass) FC000200, 28mm (Brass) FC000250.
Additives in the installation water are only permitted in consultation with the country distributor. See chapter 9.3 for detailed information.
The iC boilers are featured with a built-in expansion vessel with a capacity of 8 litres and a pre-pressure charge 1 bar. If the expansion vessel size is insufficient for the CH system, an additional expansion must be installed. The additional expansion vessel should, together with the built-in expansion vessel, be sized to the water content of the installation. The pre-pressure charge depends on the height of the installation above the installed expansion vessel. See Table 9.2.a.
Installation height above the expansion vessel | pre-charge pressure of the expansion vessel |
---|---|
5m | 0.5 bar |
10m | 1.0 bar |
15m | 1.5 bar |
table 9.2.a
The pressure relief valve outlet is combined with the condensate outlet (see figure 9.9.e on page 29)
Fill the installation with mains cold water.
In most cases, a heating system can be filled with water according to national standards for water and treatment of this water is not necessary.
In order to avoid problems with the CH-installations, the quality of the filling water has to meet the specifications mentioned in table 9.3.a:
If the filling water does not meet the required specifications, you are advised to treat the water to such an extent that it does meet the required specifications.
The warranty becomes invalid, if the installation is not being flushed and/or the quality of the filling water does not meet the specifications recommended by ATAG Heating Technology Ltd. Always contact ATAG Heating Technology Ltd in advance, if things are not clear or you wish to discuss any deviations. Without approval, the warranty becomes invalid.
Parameter | Value |
---|---|
Water type | Potable water |
Softened water | |
рН | 6.0-8.5 |
Conductivity (at 20°C in µS/cm) | Max. 2500 |
Iron (ppm) | Max. 0.2 |
Hardness (°dH / ppm): | |
Installation volume/capacity
<20 l/kW |
1-12 °dH / 17-214 ppm |
Installation volume/capacity
>=20 l/kW |
1-7 °dH / 17-125 ppm |
Oxygen |
No oxygen diffusion allowed during operation.
Max. 5% filling water addition annually |
Corrosion inhibitors | Refer to Additives Attachment |
pH increasing or lowering agents | Refer to Additives Attachment |
Anti-freeze additives | Refer to Additives Attachment |
Other chemical additives | Refer to Additives Attachment |
Solid substances | Not allowed |
Residues of processing water not forming part of the drinking water | Not allowed |
table 9.3.a
Parameter | Value |
---|---|
Water type | Potable water |
рН | 7.0-9.5 |
Conductivity (at 20°C in µS/cm) | Max. 2500 |
Chloride (ppm) | Max. 150 |
Iron (ppm) | Max. 0.2 |
Hardness (°dH / ppm): | 1-12 °dH / 17-214 ppm |
Number of bacterial colonies at 22°C (number/ml). pr
EN ISO 6222 |
Max. 100 |
able 9.3.b
- When the amount of chloride is above the required specifications mentioned above in table 9.3.b, in case of the use of a combi boiler will void the warranty for DHW parts of the boiler.
Potable water: | Tap water compliant with the European drinking water guideline: |
---|---|
98/83/EG dated 3 November 1998. | |
Softened water: | Water with partly de-ionised calcium and magnesium. |
Demi-water: | Virtually completely demineralised water (very low conductivity) |
Distilled water: | Water no longer containing minerals. |
When connecting or using an underfloor heating system, designed with plastic pipes, or plastic pipes are used elsewhere in the installation, one should ensure that the plastic pipes used comply with the DIN 4726/4729 standard. It is set out in this standard that the pipes may not have oxygen permeability higher than 0.1 g/m3.d at 40°C. If the system does not comply with this DIN standard, the underfloor heating component will have to be separated from the central heating appliance by means of a plate exchanger.
No recourse can be made to the terms of the warranty in the event of failure to observe the regulations pertaining to plastic underfloor heating pipes.
The local gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. An existing service pipe must NOT be used without prior consultation with the local gas supplier.
ATAG supplies boilers suitable for natural gas only and boilers for LPG only. Verify the identification plate on the boiler if the boiler is suitable for the gas kind on site. The boilers cannot be converted to another kind of gas.
Make sure that the gas pipe work does not contain dirt, particularly with new pipes.
The complete installation MUST be tested for gas tightness and purged as described in the above code.
The boiler connection is provided with an isolation valve with 22mm compression fitting, into which the gas line can be fitted.
The gas supply must comply to the current Gas Safety, Installation & Use Regulations, in accordance with BS.6891.
The nominal inlet working gas pressure measured at the appliance should be 21 mbar +/- 2 mbar for Nat gas (G20). Allowing for the acceptable pressure loss of 1 mbar across the installation pipework, it can be assumed that a minimum permitted operating pressure of 18 mbar will be delivered to the inlet of the appliance. (Reference BS 6400-1 Clause 6.2 Pressure Absorption). When tested at the gas valve, the pressure drop from the meter to the gas valve must not be more than 4 mbar.
The LPG installation must comply to the current Gas Safety, Installation & Use Regulations, in accordance with BS:6891
The tank must be provided with a high pressure regulator with a minimum capacity of 24 kg/h to reduce the tank pressure from 5 to 1.5 bar. The 1.5 bar high pressure gas line should have a minimum diameter of 15mm. In the high pressure gas line a house pressure regulator must be installed. When tested at the gas valve, the pressure drop from the pressure regulator to the gas valve must not be more than 3.8 mbar.
Each gas appliance which is connected to the propane installation must be provided with its own house pressure regulator. The house pressure regulator is a third party delivery.
The house pressure regulator must have a minimum capacity of 10 kg/h / 37 mbar and a CE certification.
ATAG advices to install the house pressure regulator as close as possible to the boiler. When placing the regulator inside, a discharge drain of ø6mm must be installed. The discharge drain must be directed outdoor. In case of a discharge the gasses will go outside.
If fitting the regulator outside the regulator should be protected against influences of the weather. The (de-) aeration must be positioned downwards (see figure 9.5.3.a)
ATAG advices to install measure points on all gas line parts to have the possibility to check for pressure loss.
Pre-pressure must be adjusted to 37 mbar by means of the house pressure regulator. The maximum permitted closing pressure may be 5 mbar higher than the maximum pre-pressure.
A too high closing pressure in the low pressure gas line can be caused by a high resistance or jam in this gas line. When the closing pressure keeps increasing the valve in the regulator is not closing correctly. In this case the regulator should be replaced
The gas line from the house pressure regulator to the boiler must have the dimensions according the table helow
Boiler type | iC 24 | iC 28 | iC 36 | iC 40 | iC Economiser 27 | iC Economiser 35 | iC Economiser 39 |
---|---|---|---|---|---|---|---|
Diameter gas line | m | m | m | m | m | m | m |
ø15mm | 3 | - | - | - | - | - | - |
ø22mm | 30 | 18 | 18 | 18 | 18 | 18 | 18 |
ø28mm | - | 30 | 30 | 30 | 30 | 30 | 30 |
ATAG advices to inform the gas supplier that a central heating boiler is connected to the LPG tank. For the boiler it is absolutly necessary that the tank is free of air. When not the boiler will give ignition problems and will not function
ATAG advices to measure the content of O2. This value should be lower than 1.3%. Contact the gas supplier in case of doubt.
Connection of the drinking water installation should be done according to the Water Supply (Water Fittings) Regulations and Scottish Water Byelaws.
The ATAG iC boiler is fitted with a stainless steel plate heat exchanger for producing domestic hot water. The boiler does not have a hot water store and in case of a demand for hot water the boiler will heat the domestic water flowing through the plate heat exchanger up to 60°C (adjustable) instantaneous.
The water mains installation must comply with the Water Supply (Water Fittings) Regulations and Scottish Water Byelaws. See also chapter 9.3.
In regions with a water hardness value higher than 200ppm (2.67 mmol/l), calcium deposits should be removed from the plate heat exchanger on a regular basis. If problems occur when using sanitary water with a chlorine content higher than 150 mg/l, no recourse can be made to the terms of the warranty.
In order to prevent calcification ATAG recommends applying a water softener.
ATAG recommends the use of for instance AlphaPhos for cleaning plates exchangers. The hardness of the water is variable in the United Kingdom. The water company can provide exact
information about this.
The domestic water installation can be connected to the boiler by means of 15mm compression fittings. If the mains is fitted with water meter, check valves or loose jumper stop cock, then a DHW expansion device must be fitted.
The boiler is provided with a DHW flow restrictor. The flow restrictor ensures that a quantity of water supplied has a guaranteed temperature of 60 °C (assuming a cold water temperature of 10°C). The amount of water is virtually unaffected by the water pressure.
After installation, check the hot water flow rate with a fully opened hot water tap,
If required the flow restrictor can be removed. See chapter 16.1.
The ATAG condensing boiler has the >88% Efficient SEDBUK 2009 for high energy efficiency in heating and domestic hot water. The ATAG wall hung gas fired condensing boiler contain a siphonic condensate trap to collect and realease condensate. The amount of condensate formed is determind by the type of boiler and the water temperature produced by the boiler.
Use plastic pipework of an internal diameter no less then 19mm ID (typically 22mm OD).
The condensate pipework must fall at least 45mm per metre away from the boiler, taking the shortest practicle route to the termination point.
Support the pipe at least every 50 cm for near horizontal sections and 1 metre for vertical sections. Wherever possible, the condensate pipework should be routed internally to prevent freezing. In order to minimise the risk of freezing during prolonged very cold spells, one of the following methods of terminating condensate drainage pipe should be adopted.
Wherever possible, the condensate drainage pipe should be terminated at a suitable internal foul water discharge point such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. A suitable permanent connection to the foul waste pipe should be used. Figures 9.7.1, 9.7.2(a), 9.7.2(b) show appropriate connection methods.
The possibility of waste pipes freezing downstream of the connection point should be considered when determining a suitable connection point - e.g. a slightly longer pipe run to an internal soil stack may be preferable to a shorter run connecting into a kitchen waste pipe discharging directly through the wall to an external drain.
Where "gravity discharge" to an internal termination is not physically possible (e.g. the discharge point is above the appliance location, or access is obstructed by a doorway), or where very long internal pipe runs would be required to reach a suitable discharge point, the following measures may be adopted.
ain requirements
Drain requirem
Condensate can be removed using a proprietary condensate pump (third party delivery), of a specification recommended by the pump manufacturer. Condensate pump suitable for combined pressure relief valve. The pump outlet should discharge to a suitable internal foul water discharge point, such as (a) an internal soil and vent stack or (b) an internal kitchen or bathroom waste pipe, washing machine waste pipe etc. Figure 9.7.3 shows a typical connection method.
A suitable permanent connection to the foul waste pipe should be used and the manufacturer's detailed installation instructions for the pump should be followed.
The use of an externally-run condensate drainage pipe, terminating at a suitable foul water discharge point or purpose-designed soakaway, may be also be considered; however if this termination method is chosen then the following measures should be adopted
The customer/householder should be advised that even with the above measures this type of installation could freeze, and that if this were to occur then boiler shutdown could result, requiring remedial action - possibly involving a chargeable engineer call-out.
Where there are likely to be extremes of temperature or wind-chill, the use of a proprietary trace-heating system for external condensate drainage pipework, incorporating an external frost thermostat, should therefore be considered. If such a system is used then the installation instructions of the trace heating manufacturer and any specific recommendations regarding pipe diameter, insulation, etc. should be followed. All other relevant guidance on condensate drainage pipe installation should also be followed.
Other cold weather protection methods approved or endorsed by boiler manufacturers and/or service organisations may be adopted if these are considered suitable by the parties involved.
If an external soil/vent stack is used as the external termination then the connection method shown in Figure 9.7.4 should be used, together with the measures on insulation etc. as described above and shown in the diagram.
When a rain water downpipe is used as the termination (NB only permissible if this downpipe passes to a combined foul and rainwater drainage system) an air break must be installed between the condensate drainage pipe and the downpipe to avoid reverse flow of rainwater into the boiler should the downpipe itself become flooded or frozen. Figure 9.7.5 shows a suitable connection method.
Where the condensate drainage pipe is terminated over an open foul drain or gully, the pipe should terminate below the grating level, but above water level, in order to minimise "wind chill" at the open end. Pipe drainage will be improved if the end is cut at 45° as opposed to a straight cut. The use of a drain cover (such as those used to prevent blockage by leaves) may offer further protection from wind chill. Figure 9.7.6 shows a suitable connection method.
Where the condensate drain pipe terminates in a purpose-designed soakaway (see BS 6798:2014 or boiler installation manual for soakaway design requirements) any above-ground section of condensate drainage pipe should be run and insulated as described above. Figure 9.7.7 shows a suitable connection method.
Internal condensate drainage pipes run in unheated areas such as lofts, basements and garages should be treated as external pipe.
⚠
Before putting the boiler into operation fill the siphon with 150 ml of water.
The flue gas exhaust system and air supply system consists of:
- Flue gas pipe;
A
The flue gas exhaust system and air supply system must comply with:
The flue gas outlet and air supply installation must comply with the current regulation requirements in accordance with BS:5440 Part 1 and 2.
The appliance concentric connection diameter is 60/100 mm, to which the flue gas outlet and air supply system can be fitted, with or without elbow pieces. The maximum permissible pipe length is set out in Table 9.8.2.a.
For further information about the available components of the flue gas and air supply system we recommend you consult the Flue system literature. Combinations with other brands or systems are, without written permission from ATAG Heating, not permitted.
The ATAG flue gas system is meant, and designed, solely for the use on ATAG central heating boilers adjusted to Nat gas or LPG. For this purpose the CE Certificate has been supplemented under the Gastec nr: 0063CQ3634 The maximum flue gas temperatures are below 70°C (full load 80/60°C).
The proper operation may be adversely influenced by changes of or adjustments to the correct set up. Possible warranty claims will not be honoured if incorrect changes result in non compliance with the installation manual or local rules and regulations.
I
Room sealed syste
The terminal should be located where dispersal of combustion products is not unimpeded and with due regard for the damage or discolouration that might occur to parts of the building in the vicinity (see fig 9.8.1.c).
In certain weather conditions condensation may also accumulate on the outside of the air inlet pipe. Such conditions must be considered and where necessary insulation of the inlet pipe may be required. In cold and/or humid weather water vapour may condense on leaving the flue terminal. The effect of such 'plumeing' must be considered.
The terminal must not be located in a place where it is likely to cause a nuisance, where the terminal is less than 2m (6.6ft) above a pavement or platform to which people have access (including) any balcony or flat roof. The terminal must be protected by a guard of durable material.
Where a terminal is fitted below a window which is hinged at the top, and where the hinge axis is horizontal, and the window opens outwards, the terminal shall be 1m below the bottom of the window opening.
For horizontal flue terminal direct to the rear or side through the wall (only 1 bend and 1 wall terminal) the terminal should be placed horizontal. The flue pipe inside the terminal is fitted in a 3 degrees angle to ensure the condensation water can run back to the boiler. See figure 9.8.1.a.
For longer horizontal sections, the outlet system should always be fitted on an incline (52 mm/m = 3°) sloping down towards the boiler so that no condensation water is able to accumulate in the outlet system. The chances of icicles forming on the outlet is minimised by causing the condensation water to run back towards the boiler. See figure 9.8.1.b.
Figure 9.8.1.a
Figure 9.8.1.b
NI | otoc | • |
---|---|---|
13 | ULES |
The appliance produces a white wisp of condensate (plumeing). This wisp of condensation is harmless, but can be unattractive, particularly in the case of outlets in outside walls.
For wall terminals a plume management kit is available as an option (see fig. 9.8.1.d)
Plume management kit
Terminal position Plume Management Kit (mm) | |
---|---|
1 | Clearance no less than 200 mm from the lowest point of the balcony or overhang. |
2 | 1,200 mm from an opening in a car port on the same wall i.e. door or window leading into dwelling. |
3 | The flue cannot be lower than 1,000 mm from the top of the light well due to the build up of combustion products. |
4 | 1,200 mm between air intake and facing terminal. |
5 | Internal/external corners. The air intake clearance can be reduced to 150 mm providing the flue exhaust outlet has a 300 mm clearance. |
6 |
600 mm distance to a boundary or surface facing a boundary, unless it will cause a nuisance.
BS 5440: Part 1 recommends that care is taken when siting terminals in relation to boundaries. |
The total length of the run of the flue is determined by the flue diameter, including for the connection pipe, elbows fittings and terminal covers etc..
An incorrect dimensioned flue system can lead to disorders. Look at table 9.8.2.a for the choice of the boiler and the corresponding maximum equivalent flue length.
Explanation table 9.8.2.a:
Concentric flue gas system:
maximum noted length L = distance between boiler (from elbow or vertical adapter) and the end of terminal
When using bends the noted value behind every bend should be deducted from the maximum straight length. See example.
Dimensions flu | ue gas | system ar | nd air suppl | y system |
---|
iC 24 iC 2 | 28 iC Economiser 27 | iC 36 | iC 40 | iC Economiser 35 | iC Economiser 39 | |
---|---|---|---|---|---|---|
m | 13 | 6 | ||||
m | -1.0 | -1.0 | ||||
m | -1.6 | -1.6 | ||||
m
m m |
m
m m |
IC 24 IC 26 IC Economiser 27 m 13 m -1.0 m -1.6 | IC 24 IC 26 IC Economiser 27 IC 36 m 13 -1.0 -1.6 | IC 24 IC 26 IC Economiser 27 IC 36 IC 40 m 13 -1.0 -1.6 | IC 24 IC 26 IC Economiser 27 IC 36 IC 40 IC Economiser 35 m 13 6 m -1.0 -1.0 m -1.6 -1.6 |
Туре | iC 24 | iC 28 | iC Economiser 27 | iC 36 | iC 40 | iC Economiser 35 | iC Economiser 39 | |
---|---|---|---|---|---|---|---|---|
Maximum equivalent length (L) | m | 5 | 50 | 45 | ||||
45° bend resistance length | m | -1 | .9 | -1.9 | ||||
87° bend resistance length | m | -3 | 3.0 | -3.0 |
Tabel 9.8.2.a
Example: An iC28 with a concentric flue gas system ø60/100mm has according to the table a maximum flue straight length of 18m In the system that is going to be put in there are 2 x 45° bends, so the maximum flue gas length is 18 – (2 x -1.0) = 16m.
Rear Flue | B (mm) | |
---|---|---|
Min | Max | |
Telescopic flue (FA100105) | 280 | 430 |
Side Flue | B + C (mm) | ||
---|---|---|---|
Min | Max | ||
Telescopic flue (FA100105) | 285 | 435 |
Figure 982a
Note : If it is required to cut an extension, DO NOT cut the end of the inner duct that incorporates the seal joint.
Ensure the inner duct end without the seal joint is cut so that it is flush with the outer duct. Ensure that all cuts are square and free from burrs
Once assembled with the components pushed home, the flue is fully sealed.
When mounting the flue gas system, pay attention to the flow direction (See figure 9.8.2.b). It is not permitted to mount a system upside down and will lead to complaints.
Use a soap solvent or special grease (supplied in the accessory bag with the boiler) to simplify the fitting.
The ATAG flue system used is a push fit flue system, which does not require screws to be fitted at each flue joint.
The flue system must be adequately supported at regular intervals between brackets of no more than 1.0 metres for horizontal sections and no more than 2.0 metres for vertical sections.
After the pipe work of gas, heating installation and DHW installation has been fitted to the boiler frame, the boiler can be placed on the boilerframe
Before hanging the boiler to the boiler frame remove first the cover of the boiler first. The cover is also the air cabinet and is attached to the boiler case with 2 fasteners (A and B) (see figure 8.a).
Note that there is an earth cable (when present) to disconnect when removing the cover from the boiler. Free space for removing the connector is 400mm. Remember to connect this earth cable (when present) when replacing the cover.
Always replace and turn the 2 screws tight in the fasteners A and B after replacing the cover.
Remove furthermore the 6 plastic caps from the boiler connections.
When removing the plastic sealing caps from the pipes, contaminated testing water may be released.
Place mains
/!\
water filter in
3 and 4. Take the boiler and hang it from approx. 50mm higher than the boiler frame vertical downwards on the boiler frame so the fittings will be axial approached.
Turn each nut of the fittings on the boiler connections by hand and tighten each nut with a wrench.
Figure 9.9.d
Take the end of the flexible expansion vessel hose and fit it to the 3/8" boilers expansion vessel connection using a fibre washer.
Figure 9.9.e
Before putting the boiler into operation fill the siphon with 150 ml of water.
The appliance complies with the actual directives. The installation must continue to comply with:
The appliance must be connected to an earthed socket. This must be visible and within reach.
The following general stipulations also apply:
- Should it be necessary to change it, the mains power supply cable may only be replaced with an ATAG mains power supply cable.
The connection terminals are positioned at the back of the control unit:
- Press handle A slightly to the left (see fig. 10.a)
- Turn the control unit downwards.
terminal block
The blue BUS connection can only be used for the ATAG ONE controller (CT000111), an OpenTherm controller or the ATAG 7 Day Two Channel Plug-In Digital Programmer (CT200002).
A volt free on / off room thermostat or a programmable room thermostat with volt free connections can be wired to the black volt free room thermostat connector position.
The ATAG 7 day, Single Channel Digital Wireless Programmer and Room Thermostat (CT200001) or ATAG 24 hour, Single Channel Mechanical Wireless Programmer and Room Thermostat (CT100002) both come with the receiver fitted within a replacement facia panel for the front of the boiler and their volt free plug connects into this Room thermostat volt free connections (black).
The ATAG 24 hour, Single Channel Plug-in Mechanical Timer (CT100001) comes fitted within a replacement facia panel for the front of the boiler and the volt free plug connects into this Central Heating volt free connection (white).
This enables the boiler to be available for heating during the set times of the timer.
A volt free room thermostat is still required to be connected to the Room thermostat volt free connection (Black) to create a demand for heat via a room stat.
This connection enables and disables the boiler to provide hot water during the set times if a specific timer was connected.
N/A not applicable.
When a weather compensation sensor (supplied with the boiler) is used, the two wires from the outside sensor get wired into the plug supplied with the sensor and connect onto the orange connector position.
If a live, neutral or earth wire is required for an external clock/programmer these can be taken from the (L) live, (N) Neutral or (E) earth 230V live output connections on the 230v control terminal block. If an external 230V clock/programmer is used, then a switched live is required from the control(s) to connect to the 230V control terminal block in position (SwL) Switched live to fire up the boiler.
If a 230V room thermostat is used, then a switched live is required from the control(s) to connect to the 230V control terminal block in position (SwL) Switched live to fire up the boiler. This could be in series after the clock/programmer to the room stat, then to SwL on the 230V control terminal block.
Figure 10.7.a
The central heating installation needs to be filled with potable water according to the requirements in chapter 9.3 'Water guality'. For filling or topping up the installation use the filling loop according to the following procedure (see figure 11.a);
1 | Attach the filling loop pipe to the filling loop assembly (between position 1 and 2); |
---|---|
2 | Open the filling loop valves A and B; |
3 | Slowly fill the central heating system up to 1.0 – 1.2 bar; (at the bottom left a pressure gauge indicates the water pressure in the central heating system) |
4 | Close the filling loop valves A and B; |
5 | Vent the entire heating installation starting at the lowest point; |
6 | Check the water pressure and top up if necessary to 1.0 – 1.2 bar; |
7 | Check the filling loop valve is closed; |
When powering up the boiler (described in chapter 13) an automatic de-aeration program will run to vent the boiler. During this program the pressure in the central heating needs to be checked, and when necessary, topped up again.
It may take some time before all the air has disappeared from a filled installation. Certainly during the first week sounds may be audible that indicate air. The automatic air vent in the boiler will let this air escape, causing the water pressure to drop during this period and water will need to be refilled again.
Always remove the filling loop pipe after filling or topping up the heating system and close the connections with the cap nut (3)
Figure 11.a
Fill the hot water supply by opening the cold mains isolation valve.
Bleed the hot water installation by opening all hot water taps one at a time. Leave each tap to run until all air has disappeared from the supply.
Flush with a minimum of 10 litres to rinse any residual contaminants from the hot supply and boiler.
Before the electrical power is switched on, it helps to know the operation of the boiler in advance. On this page the controls are described in short. The next page describes the button functions and the symbols on the display.
The boiler is equipped with self-managing control system. This control system takes over a large part of the manual settings, which simplifies the start-up of the installation considerably.
After filling the installation and switching on the electrical power supply a short start-up program is activated. This shows all digits, boiler type and software version and the automatic de-aeration program is activated. The automatic de-aeration program lasts for approx. 7 minutes and stops automatically. The boiler fires up for DHW to bring the primary heat exchanger to the set comfort temperature. Then the boiler will switch on for the enabled program (CH or DHW) (See chapter 11 'Filling and bleeding boiler and installation').
If a hot water tap is opened the flow sensor measures (F1) the amount drawn off. Depending on the desired DHW temperature and volume the controls will calculate an output. This realises the desired water temperature in an efficient way. The hot water sensor (T3) will adjust any minor deviations caused by temperature fluctuations so that even under these circumstances the desired temperature is constant.
Outside sensor T4
Flow sensor T1
Return sensor T2 DHW sensor T3 Flue sensor T5 NTC1k (25°C) NTC10k (25°C) Temperature Resistance Temperature Resistance [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.474 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.264 36 6.271 6 2.186 38 |
Resistance ta | ble sensors | ATAG iC-, iS- an | d iR-series |
---|---|---|---|---|
Return sensor T2
DHW sensor T3 Flue sensor T5 NTC1k (25°C) Temperature Resistance [°C] [Ohm] (°C) -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.8171 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 | Outside sensor | · T4 | Flow sensor T1 | |
DHW sensor T3
Flue sensor T5 NTC1k (25°C) NTC10k (25°C) Temperature Resistance Temperature Resistance [°C] [Ohm] [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 3 |
Return sensor T | 2 | ||
Flue sensor T5 NTC1k (25°C) Temperature Resistance Temperature Resistance [°C] [Ohm] [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 | DHW sensor T3 | |||
NTC1k (25°C) NTC10k (25°C) Temperature Resistance Temperature Resistance [°C] [Ohm] [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.477 -5 3.600 16 14.988 -4 3.435 18 13.674 -5 3.600 16 14.988 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 < | Flue sensor T5 | |||
Temperature Resistance Temperature Resistance [°C] [Ohm] [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.799 | NTC1k (25°C) | NTC10k (25°C) | ||
[°C] [Ohm] [°C] [Ohm] -10 4.574 -10 55.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.8271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1 | Temperature | Resistance | Temperature | Resistance |
-10 4.574 -10 5.047 -9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 | [°C] | [Ohm] | [°C] | [Ohm] |
-9 4.358 0 32.555 -8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 | -10 | 4.574 | -10 | 55.047 |
-8 4.152 10 19.873 -7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 | -9 | 4.358 | 0 | 32,555 |
-7 3.958 12 18.069 -6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.6271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 | -8 | 4,152 | 10 | 19.873 |
-6 3.774 14 16.447 -5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 | -7 | 3.958 | 12 | 18.069 |
-5 3.600 16 14.988 -4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 | -6 | 3.774 | 14 | 16.447 |
-4 3.435 18 13.674 -3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 | -5 | 3.600 | 16 | 14.988 |
-3 3.279 20 12.488 -2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 | -4 | 3,435 | 18 | 13.674 |
-2 3.131 22 11.417 -1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 | -3 | 3 279 | 20 | 12 488 |
-1 2.990 24 10.449 0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 | -2 | 3,131 | 22 | 11.417 |
0 2.857 26 9.573 1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 | -1 | 2,990 | 24 | 10.449 |
1 2.730 28 8.779 2 2.610 30 8.059 3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 | 0 | 2.857 | 26 | 9.573 |
1 | 1 | 2 730 | 28 | 8 779 |
3 2.496 32 7.406 4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 | 2 | 2 610 | 30 | 8 059 |
4 2.387 34 6.811 5 2.284 36 6.271 6 2.186 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.125 70 1.753 23 1.081 72 1.638 24 1.040 | 3 | 2 496 | 32 | 7 406 |
1 | 4 | 2 387 | 34 | 6 811 |
5 2.867 38 5.779 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 | 5 | 2.001 | 36 | 6 271 |
0 2.103 40 5.330 7 2.093 40 5.330 8 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 | 6 | 2.204 | 38 | 5 779 |
1 2.004 42 4.921 9 1.920 44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 | 7 | 2.100 | 40 | 5 330 |
9 1.320 1.44 4.547 10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.876 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 | 8 | 2.000 | 40 | 4 921 |
10 1.840 46 4.205 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 | 9 | 1 920 | 44 | 4 547 |
10 1.040 48 3.892 11 1.763 48 3.892 12 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 | 10 | 1.840 | 46 | 4 205 |
11 1.690 50 3.605 13 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 < | 11 | 1 763 | 48 | 3 892 |
12 1.621 52 3.343 14 1.555 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.057 30 827 86 1.037 35 687 88 974 40 575 9 | 12 | 1.690 | 50 | 3 605 |
10 1.557 54 3.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 13 | 1.621 | 52 | 3 343 |
14 1.000 04 0.102 15 1.492 56 2.880 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 10 | 1.555 | 54 | 3 102 |
13 1.432 58 2.607 16 1.433 58 2.677 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 15 | 1 492 | 56 | 2 880 |
10 1.375 60 2.371 17 1.375 60 2.490 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 10 | 1 433 | 58 | 2.000 |
11 1.010 00 2.430 18 1.320 62 2.318 19 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 10 | 1 375 | 60 | 2.077 |
10 1.268 64 2.159 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 18 | 1 320 | 62 | 2 318 |
10 1.203 04 2.133 20 1.218 66 2.013 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 10 | 1 268 | 64 | 2 159 |
20 1.210 00 2.510 21 1.170 68 1.878 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.007 30 827 86 1.037 35 687 88 974 40 575 90 915 | 20 | 1 218 | 66 | 2.100 |
21 1.175 00 1.575 22 1.125 70 1.753 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 20 | 1 170 | 68 | 1 878 |
22 1.125 10 11.135 23 1.081 72 1.638 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 22 | 1 125 | 70 | 1 753 |
25 1.040 74 1.531 24 1.040 74 1.531 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 23 | 1.081 | 70 | 1.638 |
27 1.040 74 1.331 25 1.000 76 1.433 26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 23 | 1 040 | 74 | 1.530 |
26 962 78 1.341 27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 25 | 1.040 | 76 | 1 4 3 3 |
27 926 80 1.256 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 25 | 962 | 70 | 1 341 |
21 320 30 1.230 28 892 82 1.178 29 858 84 1.105 30 827 86 1.037 35 687 88 974 40 575 90 915 | 20 | 926 | 80 | 1 256 |
29 858 84 1.178 30 827 86 1.037 35 687 88 974 40 575 90 915 | 21 | 802 | 80 | 1 179 |
20 300 827 86 1.037 30 827 86 1.037 35 687 88 974 40 575 90 915 | 20 | 858 |
02
Q/ |
1 105 |
35 687 88 974
40 575 90 915 |
29 | 827 |
94
88 |
1.103 |
40 575 90 915 | 30 | 687 | 88 | 974 |
40 | 575 | 90 | 915 |
Resistance table
table 12.a
With a demand from the heating controls after DHW demand, the boiler activates its 1 minute delay period. This is to prevent the heat exchanger from losing its heat too quickly in the event of a hot water demand. Then the pump starts and after 30 seconds the gradient control becomes
active. The starting point of the gradient control is the currently existing flow temperature. A Delta-T control (25K) ensures a stable control according to heat request.
If the flow temperature is below the T-set value of 20°C the boiler will immediately start.
If during a demand from the heating the burner switches off, because the desired flow temperature is exceeded, there will be an anti-cycle time in operation for 5 minutes. This means that the burner switches on again after 5 minutes if there is still a demand from the heating.
The ATAG iC is equipped with boiler sensors of 10kOhm. The resistance value and corresponding temperature are shown in the accompanying table.
Setting the hot water temperature.
Briefly press + or – ; the display will show the flashing preset value; Briefly press + or – to change the set value. Each change becomes active directly.
Hot water program OFF: Press – until the lowest value is reached and then press – again. The display is showing - - .
Switching on works in reverse order.
Setting the CH water temperature: Briefly press + or – : the display will show the flashing preset value: Briefly press + or – to change the set value. Each change becomes active directly.
CH program OFF: Press – until the lowest value is reached and then press – again. The display is showing - -Switching on works in reverse order.
Requesting current data:
Press the eco-button for 6 seconds in order to obtain the following value using the scroll buttons Flow water temperature in °C DHW temperature in T-set temperature (calculated) in °C A4 Flue gas temperature (only if a flue gas sensor is connected) in °C Outside temperature (only if an outside sensor is connected) in °C Water pressure in bai DHW flow in I/min. A8 Ionisation current in uA rpm of fan (x100)
turn to the standard view press ESC
The reset button allows the boiler to restart if an error has occurred. In case of an error the A symbol is displayed with a XXX code. In other cases the Reset button does not function and will not respond to operation See chapter 17 for a brief overview of codes
Both + buttons = Commissioning-mode for checking the CO.
Make sure before the boiler is put into operation that the boiler and installation have been fully vented. Vent the gas line and open the gas isolation valve to the boiler. The boiler requires no adjustment of the burner pressure and quantity, because it is self-regulatory and has been set in the factory and should not be reset.
Turn on the boiler electrical supply; When the boiler starts up for the first time the following will be shown: - (power on) All digits (segment test) 0 (parameter 9: from factory 0) 1 (boilertype: parameter 8) 03 followed by 03 (software version part 1 and software version part 2)
The code 105 appears on the display; The 7 minute de-aeration cycle starts; Vent the entire heating installation starting at the lowest point; Check the water pressure and top up if necessary to 1.0 – 1.2 bar; Check the filling loop if it is closed;
The iC boiler is s | upplied with a pressure sensor. This sensor control has following settings |
---|---|
0.5 bar: | below this pressure the burner is blocked for operation |
0.5 to 0.8 bar: | boiler output reduced to max. 80% |
0.8 to 3.0 bar: | boiler fully functional |
3.0 bar: | above this pressure the boiler is blocked for operation. |
Next to this the pressure sensor is used to set the boiler free before every start. Before the burner is set free the boiler does a pump check, it checks for an increase in pressure when the pump starts. If there is an increase of water pressure, the boiler will fire up. If there is no increase the burner is blocked.
If the water pressure drops below 0.8 bar code 118 will appear in the display; The de-aeration program starts (code 105) when the water pressure has been below
0.5 bar. Between 0.5 and 0.8 bar the display shows code 118 and the boiler will run on a reduced output of max. 80%
The automatic de-aeration program will take approx. 7 minutes and will be followed by the default display (OK) if the water pressure is above 0.8 bar.
The boiler will switch on immediately to reach the desired pre-heat temperature (approx. 50°C) of the hot water supply (Comfort setting).
The DHW program is always active after start-up. This is indicated by If there is hot water request, this is indicated by a flashing will be activated. The circulation pump will start and the boiler will switch on 6 .
By default the hot water supply is set to Comfort. A change to Eco is possible by means of pressing the eco-button. On the display appear 'eco'. The eco-position will result in a possible longer DHW waiting time, because the boiler will not being fired up for pre-heating the hot water supply.
The CH program is always active after start-up.
This is indicated by the 1
If there is heat request, it is indicated by a flashing IIII and the heating will be put into operation 6 .
The circulation pump will switch on and the boiler will switch on after 1 to 2 minutes.
When there is no more heat requested the radiator symbol m may be solid or flashing, but the flame b symbol will disappear. The pump will continue to run due to the pump over run feature (overrun time confirmed in technical specification table page 7).
С
By default the boiler is set in such a manner that the pump will switch on in case of a heat request for CH or DHW. Switching on and off is managed entirely by the control system.
If there is danger of frost damage to the CH installation and there is no outside sensor
connected, it is advisable to let the pump run continuously.
By pressing both - buttons at the same time for 8 seconds the pump can be switched on continuously.
If the pump is set to continuously this is displayed by 💥 .
If an outside sensor is connected, then the controls will regulate the pump:
If there is no outside sensor connected, and if the (T1) flow sensor registers a temperature of 5°C or below in the boiler, the boiler will fire up. The boiler keeps on firing until the temperature reaches 10°C (measured on the flow sensor) and the boiler switches off again.
In this mode the 💥 symbol will flash.
When the boiler is installed, it is in principle ready to be put into service. Most settings of the control system are already programmed from factory. Only parameter P0 (kind of heating installation) has to be checked and set, if necessary, to adjust the boiler to the connected installation.
To change this setting, proceed as follows:
1. Press the OK button for 3 seconds.
The display shows 'P0';
When you want to change more settings proceed with step 6: When you are ready press the ESC button until the default display is shown again.
6. Press the Scroll button to select another parameter:
The display shows the selected parameter again
Par. | Factory setting | Description | Range |
---|---|---|---|
P0 | 1 |
|
1-4 |
P1 | max |
Maximum power CH in %
Can only be reduced. 0 = low load |
0 - max |
P2 | max | Pump, max. percentage | XX - 100% |
P3 | min | Pump, min. percentage | min - XX / XX* |
P4 | 0% | Correction factor fan speed. Do not change! | |
P5 |
5 (NG)
0 (LPG) |
Gradient speed CH | 0 - 15 (0=off) |
P6 | 24 | Heating line CH-water temperature (see also heating line graph) | 1 - 30 |
P7 | 25 |
Summer-Eco temperature (only when outside sensor is connected)
Heating program switch off at set outside temperature |
8 - 30 |
P8 | 1 |
Boiler type.
Do not change!
1 = Natural gas fired boiler, 2 = Boiler with flue non-return valve, 3 = Propane gas fired boiler |
1-3 |
P9 | 0 | Service-parameter. Do not change! |
* Depending of connected type of boiler control
In some situations it may happen that the entire boiler has to be deactivated. With the 2 function buttons for the DHW program and the CH program the boiler is put out of service.
Hot water program OFF: Press – until the lowest value is reached and then press – again. The display shows -- and the middle is off.
Switching on with the + button takes place in reverse order.
CH program OFF: Press – until the lowest value is reached and then press – again. The display is showing -- and the upper is off.
Switching on with the + button takes place in reverse order.
ATAG recommends to leave the electrical power supply on, so that the circulation pump and the three-way valve are activated automatically once every 24 hours in order to prevent jamming.
If there is danger of frost it is advisable in this case to drain the boiler and/or installation. (See following chapter)
Work on the installation and/or boiler should only be carried out by qualified personnel with calibrated equipment.
At the time of commissioning, complete all revelant sections of the Benchmark Checklist located on At the inside back pages of the document.
For maintenance of the boiler the cover has to be removed. Unscrew the 2 locking screws from the fasteners at the top of the boiler unlock the fasteners and remove the cover in a forward motion. See figure 16.a
Note that there is an earth cable (when present) to disconnect when removing the boiler front panel. Free space for removing the connector is about 400 mm. Remember to connect this earth cable (when present) when placing back the boiler front panel and take care the wire does not get stuck between front panel and boiler. Always replace and turn the 2 screws tight in the fasteners A and B.
Changing settings, such as the burner pressure and the amount of air flow, is superfluous. Only in case of a failure or when replacing the gas block, venturi and/or fan, the CO, percentage should be checked.
Always check all gas carrying parts for leaks (with a leak detection spray) after (maintenance) work to the boiler.
Close the relevant commissioning valves during the maintenance activities. See figure 15.a.
Reassembly takes place in reverse order.
The CO, check consists of 2 steps or, if necessary, 3 steps:
Step 1:Check on full loadStep 2:Check on low loadStep 3:Adjustment (if necessary).
The CO2 setting is preset at the factory on all boilers. A calibrated CO2 control measurement must be carried out during commissioning.
- Ensure that the boiler is in operation and that the heat, which it produces, can be discharged.
You can set the full load of the boiler as follows:
After this check has been done, once more test the CO2 value at low load (see Step 2 on page 42). If there are any deviations in the result, then these must be corrected (see Step 3 on page 43).
CO 2 check on full load (Step 1) | ||||
---|---|---|---|---|
Full load | Natural gas (G20) | Propane (G31) | ||
00 | Nominal 9,0% | Nominal 10,3% | ||
Minimum 8,6%, maximum 9,6% | Minimum 9,9%, maximum 11,0% |
Values are valid with closed cover/air box.
The low load of the boiler can be set by you as follows:
The CO2 value at low load must be lower than the CO2 value at full load. The measuring procedure must be carried out until a constant measuring result is achieved. Please contact ATAG if the values should lie outside of the applicable tolerances.
- Press the ESC button ( IIII button). The device switches off The display shows for 2 seconds code 180 or 181.
This completes the procedure.
The maximum duration of the commissioning function, without interruption, is 8 minutes.
CO 2 check on low load (Step 2) | ||||||
---|---|---|---|---|---|---|
Low load | Natural | gas (G20) | Propane (G31) | |||
Full load recorded | Accepted low range | Full load recorded | Accepted low range | |||
9.6% | 9.3% - 7.5% | 11.0% | 10.9% - 8.9% | |||
9.5% | 9.2% - 7.5% | 10.9% | 10.8% - 8.9% | |||
9.4% | 9.1% - 7.5% | 10.8% | 10.7% - 8.9% | |||
9.3% | 9.0% - 7.5% | 10.7% | 10.6% - 8.9% | |||
9.2% | 8.9% - 7.5% | 10.6% | 10.5% - 8.9% | |||
CO 2 Example readings | 9.1% | 8.8% - 7.5% | 10.5% | 10.4% - 8.9% | ||
9.0% | 8.7% - 7.5% | 10.4% | 10.3% - 8.9% | |||
8.9% | 8.6% - 7.5% | 10.3% | 10.2% - 8.9% | |||
8.8% | 8.5% - 7.5% | 10.2% | 10.1% - 8.9% | |||
8.7% | 8.4% - 7.5% | 10.1% | 10.0% - 8.9% | |||
8.6% | 8.3% - 7.5% | 10.0% | 9.9% - 8.9% | |||
9.9% | 9.8% - 8.9% |
Adjust the gas value only in case the measured values lies out of range of the values mentioned in the table on previous page.
Please observe the following rotating direction:
Leaend
Adjustment of the gas valve in case the measured values lies out of range of the values on full load (Step 3) | |||
---|---|---|---|
Full load | Natural gas (G20) Propane (G31) | ||
CO 2 | 9,0% | 10,3% |
Values are valid with closed cover/air box.
The integrity of the flue system and performance of the boiler can be checked via the flue turret sample points shown in diagram 15.2.a.
A – Flue gas sample point B – Air intake sample point Figure 15.2.a
The case must be on the boiler and the boiler made to run at maximum output.
- Press the ESC button ( IIII button).
The device switches off.
The display shows for 2 seconds code 180 or 181. This completes the procedure.
NOTE: The air gas ratio valve is factory set and must not be adjusted during commissioning unless this action is recommended following contact with the manufacturer.
If any such adjustment is recommended and further checking of the boiler is required the installer/service engineer must be competent to carry out this work and to use the flue gas analyser accordingly.
If the boiler requires conversion to operate with a different gas family (e.g. conversion from natural gas to LPG) separate guidance will be provided by the boiler manufacturer
The boiler manufacturer's installation instructions should have been followed, gas type verified and gas supply pressure/rate checked as required prior to commissioning.
As part of the installation process, especially where a flue has been fitted by persons other than the boiler installer , visually check the integrity of the whole flue system to confirm that all components are correctly assembled, fixed and supported. Check that manufacturer's max. flue lengths have not been exceeded and all guidance has been followed (e.g. Gas Safe Technical Bulletin TB008 where chimney/flues are in voids).
The flue gas analyser should be of the correct type, as specified by BS 7967
Prior to its use, the flue gas analyser should have been maintained and calibrated as specified by the manufacturer. The installer must have the relevant competence for use of the analyser.
Check and zero the analyser IN FRESH AIR as per analyser manufacturer's instructions. Key:
CO = carbon monoxide CO 2 = carbon dioxide O 2 = oxygen ppm = parts per million Combustion ratio = The CO reading measured in ppm divided by the CO2 reading first converted to ppm GU(I&U)R = Gas safety (Installation & use) Regulation.
ATAG Heating Technology advises on an interim service inspection with a flue gas analyser. A full strip down service is recommended at regular intervals or where analyser readings are not within correct safety standards.
Required tools:
In order to perform maintenance, the following actions have to be taken:
Note that there is an earth cable (when present) to disconnect when removing the boiler front panel. Free space for removing the connector is about 400 mm. Remind to connect this earth cable (when present) when placing back the boiler front panel and take care the wire does not get stuck between front panel and boiler. Always replace and turn the 2 screws tight in the fasteners A and B.
Figure 16.a
The cover also doubles as air box:
- Clean the air box/cover with a cloth and a non-abrasive cleaner;
The degree of pollution resedue in the siphon is an important indication for the need of maintenance
Reassembly takes place in reverse order.
Fiaure 16.b
Disconnect the electrical connections from the fan (5):
- After removing the burner cassette (8) the non return valve (12) becomes visible. Check that the non return valve entire circumference closes / seals completely. The valve should be able to move freely from fully open to fully closed (see fig. 16.e). Replace the non return valve if the valve does not seal properly. Follow the instructions supplied with the new part.
If the inside of the boiler casing is heavily polluted with dust, it is likely that the fan impeller is also polluted. To clean the fan, it has to be removed from the upper tray and the venturi. Clean the impeller with a soft brush and a vacuum cleaner. Replace the gasket and take care that the new gasket is installed properly when reassembling the fan parts.
Fiaure 16.h
Reassembly takes place in reverse order.
Check the heat exchanger for pollution. Clean it if necessary with a soft brush and a vacuum cleaner. Avoid any pollution falling down.
Reassembly takes place in reverse order.
During installation pay attention to the correct position of the clamp bars. These have to be in a vertical position.
Replacing the ignition electrode is necessary when the pins are worn. If the inspection hole is damaged, the entire ignition electrode has to be replaced.
It is replaced as follows:
Reassembly takes place in reverse order.
Put the boiler back into operation and carry out a flue gas analysis (see page 34).
Always put back the cover after (maintenance) work and secure it with screws A and B. Remind to connect this earth cable (when present) when placing back the boiler front panel and take care the wire does not get stuck between front panel and boiler. Always replace and turn the 2 screws tight in the fasteners A and B.
Please contact your installer or ATAG Heating Technology Ltd. for further details. Contact details can be found on the back page of this manual.
After servicing, complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back page of the document.
If required the flow restrictor can be removed as follows:
In the event that parts require replacement, use only genuine parts supplied by ATAG Heating Technology Ltd.
Advise the user that for continued efficient and safe operation, the boiler should be serviced at least once a year by qualified servicing company. It is important and strongly recommended that arrangements are made for a maintenance agreement with a qualified servicing company to ensure regular servicing of the boiler.
Please contact ATAG Heating Technology Ltd. for further details. Contact details can be found on the back page of this manual.
For the warranty conditions we refer to the Warranty Card that is supplied with the boiler.
A detected failure is indicated on the display in blocking or error messages.
- Blocking code with spanner symbol
Error is temporary and will cancel itself or will lock the boiler after several attempts (error)
- Error code with bell symbol
Error means a lock on the boiler and can only be remedied by a reset and/or intervention by a service technician.
Example of display of error message
When the filling water requirements as referred to in chapter Water Quality have been met, certain additives are allowed for the below mentioned applications and related dosage. Warranty on ATAG delivered installation products expires, if these additives and concentrations are not used in accordance with this annex.
Additive type | Supplier and specifications | Max. concentration | Application |
---|---|---|---|
Corrosion inhibitors |
ATAG Central Heating Protector.
Build Cert Approved |
500 ml / 100 litres | Suitable for mixed metal and plastic systems. Prevents corrosion and limscale. |
Sentinel X100 Corrosion resistant
protection agent of CH systems Kiwa certified |
1-2 I/100 litres CH water content |
Aqueous solution of organic
and inorganic agents preventing corrosion and scale forming |
|
Fernox F1 Protector Corrosion
resistant protection agent of CH systems Kiwa certified KIWA-ATA K62581, Belgaqua certified Cat III |
500 ml can or 265 ml Express /
100 litres CH water content |
Preventing corrosion and scale forming | |
Anti-freeze |
Kalsbeek
Monopropyleneglycol / propane- 1,2-diol + inhibitors AKWA-Colpro KIWA-ATA Nr. 2104/1 |
50% w/w | Anti-freeze |
Tyfocor L
Monopropyleneglycol / propane- 1,2-diol + inhibitors |
50% w/w | Anti-freeze | |
Sentinel X500
Monopropyleneglycol + inhibitors Kiwa certified |
20-50% w/w | Anti-freeze | |
Fernox Alphi 11
Monopropyleneglycol + inhibitors Kiwa certified KIWA-ATA K62581, Belgaqua certified Cat III |
25-50% w/w |
Anti-freeze in combination with F1
Protector |
|
System cleaners |
ATAG Central Heating Universal
Cleaner |
500 ml / 100 litres |
Suitable for mixed metal and
plastic systems. Disperses sludge, limescale and other deposits. |
Sentinel X300
Solution of phosphate, organic heterocyclic compounds, polymers and organic bases Kiwa certified |
1 litre / 100 litres |
For new CH installations Removes
oils/grease and flow control agents |
|
Sentinel X400
Solution of synthetic organic polymers |
1-2 litres / 100 litres |
For cleaning existing CH-
installations Removes sediments. |
|
Sentinel X800 Jetflo
Aqueous emulsion of dispersants, moistening agents and inhibitors |
1-2 litres / 100 litres |
For cleaning new and existing CH-
installations Removes iron and lime-related sediments. |
|
Fernox F3 Cleaner
Liquid pH neutral universal cleaner for pre-commissioning new systems |
500 ml / 100 litres |
For cleaning new and existing
CH-installations Removes sludge, limescale and other debris. |
|
Fernox F5 Cleaner, Express
pH neutral universal cleaner concentrate for pre-commissioning new systems |
295 / 100 litres |
For cleaning new and existing
CH-installations Removes sludge, limescale and other debris. |
ATAG support the use of inhibitors suitable for mixed metal applications that keep the pH level between 6 and 8. Dosage levels as per manufacturers instructions. Preferred inhibitor suppliers are ATAG Heating Technology, Fernox and Sentinel.
Hereby declares ATAG Verwarming Nederland BV that,
the condensing boiler types: | ATAG | ||
---|---|---|---|
iC24 | iC28 | iC36 | iC40 |
iC Economiser 27 | iC Economiser 35 | iC Economiser 39 |
are in conformity with the provisions of the following EC Directives, including all amendments, and with national legislation implementing these directives:
Directive | Used standa | ards | |||
---|---|---|---|---|---|
Gas Appliance Directive | 2009/142/E | C | EN15502-1: | 2012 | |
EN15502-2; | 2012 | ||||
EN60335-1: | 2011 | ||||
EN60335-2- | 102:2010 | ||||
Boiler Efficiency Directive | 92/42/EEC | EN677: 199 | 8 | ||
- | EN132031/2:2014 | ||||
Low Voltage Directive | 2014/35/EU | EN60335-2-102 :2010 | |||
C C | EN60335-1: | 2011 | |||
EMC Directive | 2014/30//EU | J | EN60335-2- | 102 :2010 | |
EN61000-3- | 2: 2009 | ||||
EN61000-3- | 3: 2008 | ||||
EN55014-1: | 2011 | ||||
EN55014-2: | 2008 | ||||
Ecodesian Directive | 2009/125/E | С | EN 15036-1 | :2006 | |
- | EN 13203-2 | · 2014 | |||
EN 15502-1 | 2012 | ||||
Labelling Directive | 2010/30/EU | . 2012 | |||
- | |||||
Report numbers | GAD | BED | LVD | EMC D | |
• | 141000634 | 141000634 | 141000634 | 141000634 |
and that the products are in conformity with EC type-examination certificate number E0430, as stated by KIWA-Gastec Certification BV, Apeldoorn, The Netherlands.
Date 15 May 2016 Signature Drs. C. Berlo Full name CEO
Adres: Galileïstraat 27, 7131 PE Lichtenvoorde • Postadres: Postbus 105, 7130 AC Lichtenvoorde Telefoon: +31(0) 544 391777, Fax: +31(0) 544 391703 E-mail: info@atagverwarming.com Internet: http://www.atagverwarming.nl
Description | Qty | ATAG Pt. No. |
---|---|---|
Heat exchanger iCon1 | 1 | S4863100 |
Heat exchanger iCon2 | 1 | S4863200 |
Pump Grundfos UPM3 15-75 | 1 | S4856100 |
Boiler control LMU iC | 1 | S4864300 |
Fan iCon 1 | 1 | S4858300 |
Fan iCon 2 | 1 | S4858400 |
Expansion tank 8L | 1 | S4854300 |
Gas valve | 1 | S4856300 |
Burner complete iCon1 | 1 | S4849100 |
Burner complete iCon2 | 1 | S4849200 |
Plate hex iCon1 | 1 | S4851300 |
Plate hex iCon2 | 1 | S4851400 |
Three way valve motor | 1 | S4855500 |
Condensate tray iCon1 | 1 | S4863400 |
Condensate tray iCon2 | 1 | S4863500 |
Igniter & gasket | 1 | S4863600 |
DHW flow sensor | 1 | S4746800 |
Water pressure sensor | 1 | S4466300 |
Igniter transformer | 1 | S4851000 |
Cable harness combi & system | 1 | S4863900 |
Air vent | 1 | S4419110 |
Siphon complete set | 1 | S4863700 |
Igniter cables | 1 | S4863800 |
NTC flow | 1 | S4891600 |
NTC DHW | 1 | S4746100 |
Flex hose expansion vessel | 1 | S4856900 |
Maintenance Set iCon1 | 1 | S4867900 |
Maintenance Set iCon2 | 1 | S4868000 |
Silencer iCon 1 & 2 | 1 | S4847800 |
Gasket condensate tray iCon1 | 1 | S4854600 |
Gasket condensate tray iCon2 | 1 | S4854700 |
NTC return | 1 | S4746000 |
Connector roomstat (Black) | 1 | S4745100 |
Fuse T3,15 250V 3pcs | 1 | S4749200 |
Gasket pump 2pcs | 1 | S0009000 |
Clamp bar long | 1 | S4850900 |
Safety relieve valve | 1 | S4852500 |
Pressure gauge analogue | 1 | S4868100 |
Gasket set PHE (4 pcs) | 1 | S4743800 |
3 way diverter cartridge | 1 | S4828700 |
Connector OpenTherm (Blue) | 1 | S4745000 |
Connector External Safety | 1 | S4745200 |
Connector Outside Sensor (Salmon Pink) | 1 | S4745400 |
Hose coupling 3/8"-Drain off | 1 | S4867400 |
Flow Restrictor 10 I/m Yellow | 1 | S4762000 |
Flow Restrictor 12 I/m Brown | 1 | S4748500 |
Flow Restrictor 15 I/m Blue | 1 | S4774600 |
Flow Restrictor 17.5 I/m Green | 1 | S4779600 |
Mains water inlet filter | 1 | S4878200 |
Flue Gas Non Return Valve | 1 | AA07400U |
It is a requirement that the boiler is installed and commissioned to the manufacturers instructions and the data fields on the commissioning checklist completed in full.
To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation.
To maintain the boiler guarantee it is essential that the boiler is serviced annually by a Gas Safe registered engineer who has been trained on the boiler installed. The service details should be recorded on the Benchmark Service Interval Record and left with the householder.
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturer's instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer's statutory rights.
Customer name: Telephone number: | |||||||||||||||||
Address: | |||||||||||||||||
Boiler make and model: | |||||||||||||||||
Boiler serial number: | |||||||||||||||||
Commissioned by (PRINT NAME): | Gas Sat | fe regis | ster num | ber: | · | ||||||||||||
Company name: | Telepho | ne nur | nber: | ||||||||||||||
Company address: | |||||||||||||||||
Commis | ssionin | g date: | |||||||||||||||
To be completed by the customer o | on receipt of a Bu | ilding Regul | ations | Complian | ce Certif | icate* | |||||||||||
Building Regulations Notification Num | ber (if applicable) | : | |||||||||||||||
CONTROLS (tick the appropriate box | ies) | ||||||||||||||||
Room th | nermos | tat and pro | grammer | /timer | P | rogram | nmab | ole roc | om th | ermost | at | ||||||
Time and temperature control to heating Load/wea | compens | sation | Ū | Optimum start control | |||||||||||||
Time and temperature control to hot w | vater | Cylinder th | nermos | tat and pro | grammer | /timer | Comł | oinati | on Boile | er | |||||||
Heating zone values | Fitted | Not required | |||||||||||||||
Hot water zone valves | Fitted | Not required | |||||||||||||||
Fitted | Not required | ed be | |||||||||||||||
Fitted | Not required | ||||||||||||||||
Provide |
bd
hd |
||||||||||||||||
. u | |||||||||||||||||
The system has been flushed and cle | aned in accordance | ce with BS759 | 33 and | boiler mani | ufacturer | 's instr | uctions | Ye | es | ||||||||
What system cleaner was used? | |||||||||||||||||
What inhibitor was used? | Qu | antii | iy | lit | res | ||||||||||||
Has a primary water system filter been | n installed? | Yes | Ν | lo | |||||||||||||
CENTRAL HEATING MODE measure | e and record: | ||||||||||||||||
Gas rate | n | n³/hr | OR | fť | ³/hr | ||||||||||||
Burner operating pressure (if applicab | vle) | n | nbar | ( | OR Gas i | nlet pre | essure | m | bar | ||||||||
Central heating flow temperature | °C | ||||||||||||||||
Central heating return temperature | °C | ||||||||||||||||
COMBINATION BOILERS ONLY | |||||||||||||||||
Is the installation in a hard water area | (above 200ppm) | ? | · | Yes | N | lo | |||||||||||
If yes, and if required by the manufact | turer, has a water | scale reducer | been f | fitted? | Yes | N | lo | ||||||||||
What type of scale reducer has been | fitted? | - | |||||||||||||||
DOMESTIC HOT WATER MODE Me | asure and Record | • | |||||||||||||||
Gas rate | n | n³/hr | OR | ff | ³/hr | ||||||||||||
Burner operating pressure (at maximum rate) | mbar OR Gas i | nlet pressure at maximum rate | mba | ||||||||||||||
( Ous I | indic | °C | |||||||||||||||
Hot water has been checked at all out | tlete | Voc | Tom | porati |
|
||||||||||||
Water flow rate | 163 | Terri | Jerall | 1/r |
|
||||||||||||
- | |||||||||||||||||
The condensate drain has been instal | led in accordance | with the man | ufactur | er's instruc | tions and | d/or BS | 65546/BS | 6798 | Ye | es | |||||||
ALL INSTALLATIONS | |||||||||||||||||
Record the following: | At max. rate: | C | 0 | ppm | AND | CO/ | CO₂ | Ratio | 2 | ||||||||
At min. rate: (v | where possibl | e) ( | 0 | ppm | AND | CO/ | CO₂ | Ratio | 2 | ||||||||
The heating and hot water system cor | mplies with the ap | propriate Buil | ding Re | egulations | Yes No reaction of the stress of t | ||||||||||||
The boiler and associated products ha | ave been installed | and commiss | sioned i | in accordar | nce with t | the ma | nufacture | er's ins | tructions | Ye | es | ||||||
The boiler and associated products have been installed and commissioned in accordance with the manufacturer's instructions Yes The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes | |||||||||||||||||
The manufacturer's literature, includin | ig Benchmark Che | ecklist and Se | rvice R | ecord, has | been ex | plained | d and left | with th | e custom | er | Ye | es | |||||
Commissioning Engineer's Signature | |||||||||||||||||
Customer's Signature | |||||||||||||||||
(To confirm satisfactory demonstration | and receipt of m | anufacturer's | literatu | re) | Image: Image | ||||||||||||
., | _ | 7 | |||||||||||||||
*All installations in England and Wales | must be notified t | o Local Autho | rity Bui | ilding Contr | rol (LABC | C) eithe | er directly | or thro | ough a | De | ?//( | :// | ma | r | r |
All Installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer.
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer's instructions. Always use the manufacturer's specified spare part when replacing controls.
SERVICE 01 | Date: | SER | VICE 02 | Date: | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Engineer name: | Engineer | name: | I | ||||||||||
Company name: | Company name: | ||||||||||||
Telephone No: | Telephone No: | ||||||||||||
Gas safe | register No: | Gas safe register No: | |||||||||||
At max. rate: | CO ppm | AND | CO₂ % | At max. rate: | CO ppm | AND | CO 2 % | ||||||
Record: | At min. rate: (Where Possible) | CO ppm | AND | CO 2 % | Record: | At min. rate: (Where Possible) | CO ppm | AND | CO 2 % | ||||
Commen | s: | Commen | ts: | ||||||||||
Signature | Signature | 9 | |||||||||||
SER | Date: | VICE 04 | Date: | ||||||||||
Engineer | name. | Engineer | name. | ||||||||||
Company | name: | Company | v name: | ||||||||||
Telenhon | No: | Telephon | e No: | ||||||||||
Gas safe | register No . | Gas safe | register No: | ||||||||||
Sus sale | At max_rate | CO nom | CO2 % | At max_rate: | CO nom | CO2 % | |||||||
Record: | At min rate: (Where Describe) | CO2 % | Record: | At min rate: (Where Docsible) | CO2 % | ||||||||
Commen | s. min. rate. (where rossible) | 002 /0 | Commen | te. | 002 /0 | ||||||||
Commen | .5. | ||||||||||||
Signature | Signature | ||||||||||||
Signature | - | ||||||||||||
SER | VICE 05 | Date: | VICE 06 | Date: | |||||||||
Engineer | name: | Engineer name: | |||||||||||
Company | name: | Company name: | |||||||||||
Telephon | e No: | Telephon | Telephone No: | ||||||||||
Gas safe | register No: | Gas safe register No: | |||||||||||
Booord | At max. rate: | CO ppm | AND | CO2 % | Boord | At max. rate: | CO ppm | AND | CO2 % | ||||
Record. | At min. rate: (Where Possible) | CO ppm | AND | CO2 % | Recolu. | At min. rate: (Where Possible) | CO ppm | AND | CO2 % | ||||
Commen | is: | Commen | ts: | ||||||||||
Signature | Signature | 9 | |||||||||||
Data | Data | ||||||||||||
SERVICE U/ | Date: | Эск | Date: | ||||||||||
Engineer | name: | Engineer | name: | ||||||||||
Company | name: | Company name: | |||||||||||
Telephon | e No: | Telephone No: | |||||||||||
Gas safe | register No: | Gas safe | register No: | ||||||||||
Record. | At max. rate: | CO ppm | AND | CO₂ % | Record | At max. rate: | CO ppm | AND | CO2 % | ||||
At min. rate: (Where Possible) | CO ppm | AND | CO₂ % | At min. rate: (Where Possible) | CO ppm | AND | CO 2 % | ||||||
Commen | S: | Commen | ts: | ||||||||||
Signature | Signature | 2 | |||||||||||
SERVICE 09 Date: | Date: | SER | VICE 10 | Date: | |||||||||
Engineer | name: | Engineer | name: | I | |||||||||
Company name: | |||||||||||||
Telephone No: | |||||||||||||
Gas safe | register No | Gas safe | register No: | ||||||||||
545 3416 | At max_rate | CO nom | CO2 % | At max_rate: | CO nom | CO2 % | |||||||
Record: | At min_rate: (Mhore Bossible) | Record: | |||||||||||
Commen | C. IIIII. Idle. (Where Possible) | phin | AND | 002 70 | te: | phin | 002 70 | ||||||
Commen | lið. | ||||||||||||
| | | |||||||||||||
Signature | Ciarat | ||||||||||||
Signature | 5 |
*All installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer. Installation & Servicing instructions ATAG iC-Range
مت ATAG Heating Technology Ltd. • 47 Castle Street • Reading • Berkshire RG1 7SR م Phone: 0800 254 5061 • E-mail: info@atagheating.co.uk • Internet: www.atagheating.co.uk