CONTACT INFORMATION OF THE FACTORY:
MACHINERY PLANT “ASTRA” AB
ULONŲ G. 33, LT62161 ALYTUS, LITHUANIA
TEL.: +370 315 75449
EMAIL: INFOASTRA.LT
WWW.ASTRAGAS.LT
WARRANTY AND POST-WARRANTY REPAIR CARD .................................................. 24
DECLARATION OF CONFORMITY ..........................................................................25
Page 3
INSTALLATION AND OPERATION MANUAL
This user manual was compiled following the requirements of EN 12171 “Heating systems in buildings. Procedure for the
preparation of documents for operation, maintenance and use. Heating systems not requiring a trained operator”.
1. SAFETY REQUIREMENTS
1.1. The room where the boiler is to be installed should be ventilated.
1.2. Free inow of air into the room should be ensured.
1.3. The boiler ue connection with the chimney should be tight. Do not heat up the boiler with leaking ue connections!
1.4. The boiler should be installed in a closed heating system with a closed (membranous) expansion vessel, the volume of
which should be no less than 10% of the total volume of the heating system (including the boiler) (the volume of the
expansion vessel can be calculated according to the standard EN 12828 annex D).
1.5. A safety valve for no more than 2 bar response pressure should be tted onto the boiler in the heating system for the
boilers Astra H-25E, Astra H-32E, and a maximal response pressure of 2,5 bar for the boiler Astra H-45E (please see
Chapter 5, “Requirements for connection of the boiler to the heating system”).
1.6. Remove the accumulated soot and resin from the boiler ues, as instructed in this manual.
1.7. The room where the boiler is installed should have re-extinguishing tools: re extinguishers, sand box, shovel and
other tools.
1.8. Do not place ammable materials on or near the boiler.
1.9. Connect the boiler to the electric system only via a three-pole plug plugged into an adequate three-pole socket with
earthing. Protect connection cable from damages.
1.10. Observe operation of temperature control devices and gauge readings when operating the boiler. In case of faulty
operation of the boiler, stop operation and remove the fault.
1.11. Kindle the boiler and put the rewood into the boiler only as indicated in Chapter 7 of this manual.
1.12. Keep children away from the boiler! The boiler can be serviced only by adults.
1.13. Before kindling the boiler, check if the heating system is lled with water and deaerated.
1.14. The operating pressure in the heating system should not exceed the following:
• 2 bar – for boilers Astra H-25E, Astra H-32E;
• 2,5 bar – for boiler Astra H-45E.
1.15. The electrical connections are factory tested and the following parameters were conrmed:
• integrity of the protective circuit – electrical resistance of the protective circuit does not exceed 0.1;
• resistance of the electrical insulation – at least 1.0 M;
• resistance of electrical insulation was checked at 50 Hz, 1 000 V voltage.
3
Page 4
2. TECHNICAL DESCRIPTION
• GENERAL VIEW OF THE BOILER
1
A
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
B
8
9
152
2
5
3
4
578
C
170
6
7
16
10
11
1005
12
13
120
65
14
15
1208
1133
D
17
21
1230
262
230
40
L*
200
470
17
18
19
22
20
12
23
24
25
26
Fig. 1 General view of the boiler
A – front view; B – lateral view; C – top view; D - section.
1. Front control panel; 2. Primary air inlet nozzles with regulation dampers; 3. Duct with ventilator; 4. Secondary air inlet nozzle with the regulation
damper; 5. Handle of the upper ue damper; 6. Doors of the combustion chambers; 7. Adjustable support legs; 8. Flue cleaning cap; 9. Flue pipe; 10. Flue
temperature sensor; 11. Turbulence plates; 12. Lower opening to the ue; 13. Return water pipe; 14. Damper of the upper opening to the ue; 15. Primary
air inlet openings; 16. Water drain nippel; 17. Flow water pipe; 18. Sensor sleeve of the safety temperature limiter 95°C valve; 19. Sensors of the electronic
controller and safety ventilator shutdown 95°C thermostat; 20. Rooftop cover; 21. Pipes of the cooling serpentine connection; 22. Combustion chambers;
wooden briquettes, kW263345
Boiler class according to EN 303-5333
Class of protection against electric impact111
Eciency rate, %86,485,986,8
Power of the cooling serpentine, kW151515
Water volume in the boiler, l637885
Setting range of the temperature regulator, °C60-8560-8560-85
Maximum operating draught in the ue, mbar0,300,300,30
Working pressure of water in the system, bar, max2,02,02,5
Testing pressure of the boiler, bar3,03,04,0
Max. allowable water temperature in the boiler, °C108108108
Max. allowable operating water temperature in the boiler, °C959595
Electric characteristics:
voltage, V / frequency, Hz220/50220/50220/50
average power used, W405050
Level of electric protection of the boilerIP30IP30IP30
height, mm123012301230
Dimensions:
width, mm615615615
depth, mm7659501000
Weight of the boiler, kg, 270310380
Flow and return connection diameter1½”1½”1½”
Volume of the fuel chamber, l90130140
Dimensions of the loading aperture, mm350x285350x285350x285
Flue gas duct diameter, mm152152152
Length of wood pieces, mm330500550
Average temperature of the ue gases at the nominal heat output, °C164164184
Resistance of the water tract, mbar9,310,813,8
5
Page 6
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
1. DEGIKLISG-18.00.003
1
H-25EH-32E
H-45E
Katilo tipasKeraminis
elementas
1. DEGIKLISG-18.00.003K-30.00.007ŠK-50.07.001
1
1
1
2.SKELTUVASG-18.00.002ŠK-50.00.010
1
1
3.SEGMENTAIG-18.00.004
4
4
4
H-25EH-32E
H-45E
Katilo tipasKeraminis
elementas
1
• CERAMIC ELEMENTS OF THE BOILER
The boiler has ceramic elements of three types: ceramic burner 1, ceramic chopper 2 and four ceramic segments 3 (Fig. 2).
The chopper 2 must be moved to the back wall of the boiler chamber during operation of the boiler, segments 3 – resting upon
the front and rear edges of the chopper. If needed, the ceramic burner 1 can be removed. For this purpose, use a screwdriver to
remove the sealing rope from between the ceramic burner and the frame of the boiler, then this ceramic insert can be removed.
Turbulence plates – a technology invented and patented by
“Astra” engineers, used for capturing more heat from the hot
exhaust smoke. It forces the exhaust smoke to hold, become
turbulent and thus transfer more heat to the adjacent heat
exchanger. The core of the device consists of the turbulence
plates, positioned at an angle in the rectangular-shaped ue
channel of the boiler. The inspection aperture 1 is installed on
the top part of the ue channel (Fig. 3), covered with a screwon cover with a gasket. This aperture is used for cleaning the
ue channel and placing/removing the turbulence plates.
The turbulence plates 2, shown in Fig. 3, maintain their
position in the ue due to their force of gravity alone. They
are inserted into the ue channel or removed using a poker
3, which is provided with the boiler. Poker 3 (Fig. 3) is bent
at an angle of approximately 80° to the handle, so that the
hooked plate does not slide o. In order to be able to hook
the turbulence plate 2 with a poker, a hole has been made in
its upper part for hooking with a poker. The plate rests upon
2
the heat exchanger 4 of the boiler ue on four supports: two
bottom and two upper supports. When inserting the plate 2
with a poker 3 into the ue channel, rst the lower position
is found, and after slightly loosening the poker, yet without
removing it from the hole, the plate is allowed to descent
onto the opposite side of the heat exchanger due to the force
of gravity until it touches the wall of the heat exchanger with
6
Page 7
INSTALLATION AND OPERATION MANUAL
its upper supports. Then the tool can be removed and the next plate can be installed in a similar way.
Turbulence plates decrease the temperature of the exhaust smoke. The boiler can be operated without the plates, but then
greater losses of heat through the chimney will occur.
3. INTENDED USE
The heating boiler is designed for the heating of residential and public buildings, manufacturing shops and other buildings
where a closed heating system has been installed. Control and regulation devices are installed in the boiler, which automatically
maintain the set water temperature, ensure economically ecient usage of the boiler and safe operation.
Boilers of this type are designed to burn wood, partially generating gases. Gas is extricated (generated) from the burning
rewood in the upper combustion chamber of the boiler and burned in the lower chamber. The intensity of gas generation
and combustion is regulated by the frequency and duration of air inow into the combustion chambers.
Advantages of the boiler are the following:
• gas generating combustion ensures eective burning of wood and a high eciency coecient since the burning process
takes place at a high temperature of 900°C;
• the heat output of the boiler can be regulated within the range of 40-100%. The boiler is automatically controlled using an electronic
regulator, by switching the ventilator inowing into the combustion chambers o or on, or by regulating the speed of its rotation;
• the combustion period of one fuel load is long due to the large volume of the fuel chamber;
• the turbulence plates installed in the ue of the boiler enhance heat exchange in the boiler and reduce the temperature
of the smoke in the chimney;
• it is sucient to remove the ashes 1-2 times per week.
4. TRANSPORTATION, STORAGE, UNPACKING
The heating boiler is to be transported and packaged in accordance with the documentation of the manufacturer, protected
from precipitation and dust. It can be transported only in vertical position, fastened to avoid sliding and falling. If the boiler
is transported in other than vertical position, decorative surfaces may be damaged, cladding battered, control and regulation
equipment broken, built-in ceramic inserts may fall down and splinter. The heating boiler should be carefully loaded, unloaded
and transported, without any signicant impact.
The boiler should also be stored in a vertical position. It is not allowed to put one boiler on top of another, as a packaging
frame is not designed for this purpose. The boiler should be stored in a closed room protected from precipitation. The air
humidity of the room should not exceed 80%, in order to avoid condensate forming on the surfaces of the boiler. Storage
temperature may vary from -40°C to +60°C.
If the boiler was transported or stored in minus temperatures, then before it is kindled, it should be kept in plus temperature
for no less than 2 hours.
After the heating boiler is delivered to the site, take o the packing frame and polyethylene lm, unscrew boiler bolts and,
fastening to the packaging base, remove the boiler from the packaging base.
Open the doors of the boiler and check if all elements listed in a delivery kit are included.
The delivery kit consists of the following: boiler - 1 pc.; poker - 1 pc.; scraper - 1 pc.; operation manual - 1 pc.; support legs - 4 pcs.
Check if painted surfaces have not been damaged during transportation, if the components are not bent and if control and
regulation equipment is intact. In case you notice any inadequacies, present your claims to the vendor company.
7
Page 8
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
234
1. Į kanalizaciją;
2. Terminis apsauginis vožtuvas;
3. Filtras;
4. Vanduo iš vandentiekio. Slėgis 2-6 bar. Temperatūra °C;
5. Terminio apsauginio vožtuvo sensorius.
5. INSTALLATION
• ACCUMULATION TANK
These solid fuel boilers are intended to be fully loaded during the operation; the most ecient mode of their exploitation is at the
nominal or maximum heat output. It is advisable to install an accumulation tank of sucient size in their proximity, which could
accumulate the excessive heat. If the boiler is operated without the accumulation tank, its lifetime can be shortened because, in
such a case, a relatively low temperature of the outowing water is maintained in the boiler (65-70°C). Therefore, the temperature
of the water returning to the boiler from the heating system is as low as 55-60°C. More water vapour condenses in the boiler at such
operating temperatures, more tar accumulates on the internal walls of the boiler and metal corrosion intensies. When operating
the boiler with an accumulation tank, it is possible and advisable to maintain constantly maximum temperature of outowing and
returning water, respectively 85°C and 72°C, then condensation of water vapour and metal corrosion will be signicantly lower.
Recommended capacity of the accumulation tank is approximately 50 litres per 1 kW of nominal power of boiler:
Boiler modelAstra H-25EAstra H-32EAstra H-45E
Required volume of the accumulation tank, litres120015002000
The boiler is to be operated only with an emergency cooling system installed!
• DESCRIPTION OF THE EMERGENCY COOLING SYSTEM DIAGRAM
A thermostatic safety temperature limiter 95°C valve (Fig. 4)
protects the boiler form the overheating. If the water temperature
in the boiler exceeds 95°C, the valve automatically opens the ow of
5
1
cold water from the public water supply network through the cooling
serpentine, where it absorbs the excessive heat energy and ows out
into the sewage. The sensor of the valve with the external thread ½”
is screwed onto the socket on the rear wall of the boiler.
Technical data of the thermostatic safety valve are the
following: Opening temperature - 95°C; Maximum operating
temperature- 110°C; Operating pressure - 10 bar; Bulb of the
sensor - L=142 mm, external thread ½“.
The emergency cooling system protecting the
boiler from overheating cannot be used for heating
domestic water.
Fig. 4 Connection diagram of the emergency cooling system
1. To sewage; 2. Thermostatic safety temperature limiter 95°C
valve; 3. Filter; 4. Water from public water supply, pressure 2-6 bar,
temperature 12°C; 5. Sensor of the thermostatic safety temperature
limiter 95°C valve.
consumption. Both circles operate independently and interact in the accumulation tank. The heat production circle consists
of a boiler, Laddomat 21 thermostatic mixing unit with a circulation pump installed in it, expansion vessel, ttings and
• DESCRIPTION OF THE HOUSE HEATING SYSTEM
SCHEME
The house heating system with an accumulation tank could be
divided functionally into two circles: heat production and heat
accumulation tank. The intended use of this circle is to charge the accumulation tank only. To charge the tank, the boiler could
operate on its maximum heat output and outowing water temperature 85°C. That mode of boiler operation is optimal for
the boiler and combustion process itself.
8
Page 9
INSTALLATION AND OPERATION MANUAL
Automatic
Air Outlet
Heating System Supply
Programmable
Heating System
Processor
TM
3-Way
Servo Drive
M
Mixing Valve
Return
Heating System Return
T
Overow
Valve
Hot Water
Filter
Manometer
Thermometer -
TM
Return ValveValvePressure Relief
With Valve
Pump
Manometer
Air Outlet
Accumulation Tank
T
TM
Pump Control
Thermostatic
Domestic Water
Preparation
Thermostatic
Mixing Valve
From Water Supply
T
Switch
Thermometer
T
Other Notations:
Valve
Heat productionHeat consumption
Domestic Water
Recirculation
Water Heating
Flow
Control
Valve
Air Outlet
Pump
Control
Flow
Control
Valve
TM
Heating Boiler
Fig. 5 Principle scheme of the house heating system including heat accumulation
9
Automatic Water
Membrane
Expansion Vessel
Addition Valve
Water Supply
Laddomat 21
Thermostatic Mixing Valve
C!
o
T
Min 65
Page 10
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
The heat consumption circle uses the heat accumulated in the tank. The circle consists of a room thermostat or a programmed
control processor, room or/and outside temperature sensors, 3-way servo drive, mixing valve, underoor heating system,
radiators, piping, ttings. The programmed processor controls a 3-way mixing valve, which allows more or less heat (45-60°
C) into the radiators, according to demand. This way of heat consumption allows the heating of the house as long as the tank
stores heat independently from the boiler.
• REQUIREMENTS FOR CONNECTION OF THE BOILER TO THE HEATING SYSTEM
The following requirements should be fullled when installing the boiler:
• The boiler should be installed in a closed heating system with a closed membranous expansion vessel, the volume of which should
be no less than 10% of the total volume of the system. A closed heating system is a kind of system with no free access to atmospheric
air, which actuates corrosion. Due to this, drainage of water from the system without an important reason is undesirable, e. g. in
summer. It is also necessary to ensure watertightness of the system in order to need fewer rells with fresh water containing free
oxygen. The quantity of the additional water let in should not exceed 5% of the system water volume per year;
• The boiler is connected to the heating system through connection pipes 17 – water supplied to the heating system and
13 – water returning from the heating system (Fig. 1);
• Internal threads G 1½” of the ow pipe 17 and the return pipe 13;
• There is a nipple 16 for water lling or draining from the boiler (Fig. 1);
• Internal thread G ½” of the nipple 16;
• A pressure relief valve conforming to norm EN1268-1 is to be installed in the heating system as close to the boiler as
possible at a location easy to reach by hand;
• pressure relief valves and control devices must conform to the following technical characteristics:
InstrumentTechnical characteristicsType of boiler
Pressure relief valveConnection diam. does not exceed ½”, set opening pressure 2 bar Astra H-25E , Astra H-32E
Pressure relief valve
Connection diam. does not exceed ¾”, set opening pressure 2,5 bar
Astra H-45E
Thermometer-manometer Range of temperature 0-120°C, pressure 0 – 4.0 barAll boilers
There must be no ball valves installed between the boiler and the pressure relief valve.
• Water from the pressure relief valve should be conducted via an otake pipe. It should be conducted in a way that will
allow the water passing through the pressure relief valve to ow safely, avoiding exposure of people and electrical parts of
the boiler. The diameter of the otake pipe should be no less than the diameter of the otake opening connection nipple
of the safety valve. The total length of the otake pipe should not exceed 2 m. No more than 2 elbow joints at angles of
90° are to be used when installing this duct. No ball, mixing or other valves are to be installed in the water otake pipe.
This otake pipe is to be installed in a way that will make the ow of the passing water visible. If part of the pipe installed
is hidden, e. g., in a sewerage pipe, then such a pipe should have a special funnel enabling visual observation of the otake
ow of water.
Operation of the pressure relief valve is to be checked at least once a month. The valve is opened
for a short period of time, by turning its head, to reveal a small amount of the otake water. If this is not
done periodically, the parts of the valve can stick together due to high temperature and fail to open, when
required. In case the safety valve fails to open in an emergency situation, serious damage to the boiler and
the heating system can occur as well as hazard to the health and life of people.
10
Page 11
INSTALLATION AND OPERATION MANUAL
In order to guarantee natural water circulation of water in the boiler, the pipework between the boiler
and the mixing valve in the line boiler–mixing valve–boiler is to be of the same diameter and correspond to
the diameter of the connection pipes of the boiler.
• CIRCUIT DIAGRAM OF THE BOILER
220 V
P
N
L
M
P
N
L
P
L
N
123456789101112
NLL1L13L14NL3NL4
L1
L
L13
L14
L13
L2
N
F
NL
L1NL2L3L4P
X1
S1S2SK
KR
X2
U
123
U
Fig. 6 Circuit diagram of the boiler
S1 - power supply switch; S2 - ventilator switch; SK - emergency ventilator shutdown 95°C thermostat; F - fuse; M - ventilator;
- circulation pump of the heating system; KR - electronic controller; U
- water temperature sensors; U3- ue gas temperature sensor
1,2
X3
U
• An electric installation with earthing, in accordance with the electric safety regulations in force, is to be installed when
connecting the electric part of the boiler.
Protect the isolation of the mains cable against damage.
11
Page 12
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
• CONNECTION OF THE
CIRCULATION PUMP
In order to insure a continuous ow
of water, a circulation pump is to be
installed in the system, on the return
water pipe behind the mixing valve.
The electronic controller of the boiler
controls the pump. Before connecting
the circulation pump, remove the
rooftop cover of the boiler (Fig. 7).
The cover is removed in the following
sequence: 1) unscrew two fastening
bolts, 2) push the cover backwards, 3)
raise the backside of the cover and then
lift it up. Push a circulation pump wire
through a vacant hole in the rear panel
of the rooftop. Connect the wire of the
circulation pump to the 12-way electric terminal connector, contacts No 11 and 12, marked with the sign (See Fig. 6
“Circuit diagram of the boiler”). Connect the earthing wire of the pump to the contact No. 1 on the same connector.
Fig. 7 Removing the rooftop cover of the boiler
1. Unscrew bolts; 2. Push the cover backwards; 3. Lift the backside of the cover.
2
3
1
1
3
2
• VENTILATOR AND AIR INLETS INTO THE COMBUSTION CHAMBERS
To access the ventilator, unscrew a fastening nut and remove the front cover of the boiler. The opening of the ventilator
is protected with a losely hanged damper which opens by force of airow during operation of the appliance. A duct of the
ventilator has three nozzles: the upper two 2 (Fig. 1) is intended for primary air inlet, the lower one 4 (Fig. 1) is for secondary
air supply to the combustion chambers. All the air inlet nozzles are equipped with regulation dampers. The dampers have
already been tuned during fabrication and needs an additional adjustment only if some special conditions of the boiler
installation occur. The adjustment of the dampers should be implemented by professional boiler installers.
• CONTROLLING THE TEMPERATURE OF WATER RETURNING TO THE BOILER
It is absolutely necessary to maintain the temperature of the water returning from the heating system to the boiler at a
constant level, no less than 65°C, as this will prolong the lifetime of the boiler and will make the combustion process more
eective. This is because when a constant high temperature of water returning to the boiler is maintained, there arises
signicantly less water vapour condensation inside the boiler. The heavy water condensation is harmful to the boiler, because
deposits of tar, pitch and soot accumulate on the walls of the heat exchanger, causing intense metal corrosion. Moreover, the
resulting layer of soot impedes eective heat transfer and the eciency of the boiler falls.
In order to maintain the temperature, we recommend installing the small circulation circle together with a Swedish-made
thermoregulation device, “Laddomat 21-60”. Make sure that the “Laddomat” is supplied with the 78°C or 72°C thermostat
cartridge. The mentioned temperature is the one at which the valve of the device opens completely. However, the actual
temperature of the water returning from the system and getting into the boiler after mixing, is 5-6°C lower. The higher the
temperature of the return water is, the better it is for the boiler. Thermoregulation devices of other manufacturers could be
used for maintaining the temperature of the returning water as well.
• HEATING OUTPUT, WATER TEMPERATURE AND WATER FLOW RELATIONSHIP
The heating output supplied to a heating system depends directly upon the dierence of ow and return water temperatures
12
Page 13
INSTALLATION AND OPERATION MANUAL
t and the intensity of the water ow circulating
through the boiler. The boiler will fail to reach
the desired temperature of the ow water if
the returning water temperature is too cold
or the circulation pump is too powerful. This
will happen because the boiler will be forced
to produce a larger heating output than it has
been designed for. The most eective boiler
operation occurs when the dierence between
the ow and return water temperatures is 1214°C. If the boiler is forced to operate with a 20°C or even greater temperature dierence, it will work ineectively, consume
too much of fuel, and the combustion period of one fuel load will consequently shorten. If the previously mentioned dierence
of temperatures is kept less than 10°C, the fuel in the boiler will again burn ineciently and fume because of a lack of air
supply. If you know the water ow intensity near your boiler, in the above presented table you can check, what the dierence
of ow and return temperatures your boiler is capable to maintain, when operating at the nominal heating output.
Do not forget to keep the returning water temperature as high as possible, at least 65°C or even higher!
It is necessary to assure that a thermometer is installed on the returning water pipe, in order to be able to
observe this temperature at any time!
• INSTALLATION OF THE BOILER ROOM
The boiler room should be ventilated. The required air inow necessary for combustion should be also ensured. For this
purpose, boiler room doors should have ventilation grating or there should be a sucient gap between the doors and the
oor. If there is no possibility to supply air in from another rooms or the house is very tight, it will be necessary to install an
opening in the exterior wall. The cross-section area of the opening should be at least 0.001 m2/kW.
Place the boiler as close to the ue as possible on a hard concrete levelled basement. Leave at least 600 mm gap between the
backside casing of the boiler and the room wall for boiler servicing and cleaning. The smallest distance between a lateral casing
of the boiler and a building structure is 400 mm. If the building structure is made of ammable materials, this distance should be
doubled. A freely approachable space of at least 800 mm should be then left from the opposite side of the boiler to ensure access
to the backside of the boiler, for its servicing and cleaning. The oor under the boiler, within the distance of 50 cm in front of it and
within the distance of 30 cm around the boiler should be made of inammable materials. Screw supporting legs onto the base of
the boiler and level the boiler with screw nuts using a level; then connect the heating system circulation pump to the boiler.
The smoke exhaust pipe of the boiler should be connected to the chimney through a metal duct. The internal diameter of
the metal connecting duct should be at least the same as the external diameter of the smoke exhaust pipe of the boiler. To
improve the draught, the connecting duct between the boiler and the chimney should be installed at an inclination towards
the boiler. All junctions should be carefully tightened using a heat-resistant material and insulated using thermal insulation.
If an additional damper is installed between the boiler and the chimney for the draught control purpose,
the damper should not close more than 2/3 of the cross-section area of the opening in its fully closed position.
• REQUIREMENTS FOR THE CHIMNEY
It is recommended to insert acid-resistant stainless steel liner, if the chimney is made from masonry. It improves draught of
the chimney and protects the masonry from destruction due to the impact of condensate. Internal diameter of the liner should
13
Page 14
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
be no less than the external diameter of the smoke exhaust pipe of the boiler. The chimney liner can be round or oval. It is not
recommended to use rectangular-shaped liner as, due to the temperature uctuations, its walls deform, gaps appear at the
element junction points, through which the condensate falls on the walls of the bricks chimney. Additional air is sucked in, which
Fig. 8 Positioning of a chimney in respect to vicinity objects
reduces draught of the chimney. Draught for each boiler model should correspond to the referred value of draught in the table
“Technical data”. The liner should be factory made. Minimum permissible height of the chimney should be at least 6m. The top
of the chimney should be above the ridge at least by 0.5m. If the chimney is further from the ridge than 1m, the angle horizonthe ridge- the cap of the chimney should consist 10° or less degrees. Draught of the chimney can also be negatively aected by
various obstructions near the building: trees, hills, other buildings. Fig. 8 presents the recommended minimal angles between the
chimney, nearby objects and the horizon. Angles larger than those indicated will cause reduction of draught of the chimney.
The connection of other devices to the chimney to which the boiler is connected is prohibited.
The chimney should be cleaned at least once a year!
6. FUEL
The boiler is red only by wood logs and wood briquettes. It is possible to re it with fuel peat briquettes, however the operation
of the boiler becomes less comfortable for the user as it is necessary to remove the ashes of these highly ash-producing briquettes
after each loading. The ceramic elements of the lower chamber can be damaged if they are removed every day when cleaning,
thus their lifetime will be shorter. Therefore, we recommend usage of fuel peat briquettes only in rare, exceptional cases.
It is recommended to re dry rewood with a moisture content of 12-20 %. The drier the rewood, the larger its caloric capacity.
When the moisture content of the rewood is 20%, the heat potential of 1 kg is approximately 4 kWh; when the moisture
content is 50%, its heat potential is reduced by half.
14
Page 15
INSTALLATION AND OPERATION MANUAL
The length of the rewood should be at least 5cm shorter than the length of the boiler combustion chamber.
Type of boilerAstra H-25EAstra H-32EAstra H-45E
Length of rewood, mm330500550
The recommended thickness of the wood logs is 100-150mm. Thicker pieces of rewood should be split at least once. Up to
15% of the fuel load can consist of ne wooden splinters and sawdust. However, they must be loaded in such a way so as not
to block the opening of the ceramic burner 24 (Fig. 1) connecting the upper and lower chambers of the boiler.
Do not re freshly prepared and excessively damp pieces of rewood. The operation of the boiler
becomes inecient, deposits of resin emerge on its inside walls as well as excessive condensate. Corrosion of
the boiler takes place several times faster when ring it with freshly prepared wood or wood that has been
dried outside for several months only!
Recommendations for rewood preparation:
• put split wood in a properly-ventilated place – if possible, in a sunlit place;
• rewood should be well sheltered from rain and snow;
• pieces of split wood should be stacked with sucient gaps between them so that the freely-circulating air can blow away
the moisture evaporated from the pieces of rewood;
• there should be sucient space above the heap of rewood below the roof and sucient ventilation to remove the moist
air;
• it is not advisable to store freshly-cut rewood in a basement since the rewood needs sun and free air movement to dry.
Dry wood can be stored in the basement where sucient ventilation is guaranteed;
• it is recommended to dry the split rewood outdoors under the above-mentioned conditions. Depending on the type of
wood, soft wood (alder, asp, r, poplar) must be dried for at least 8 months, and hard wood (oak, ash, birch) for at least
20 months.
Firing the boiler with coal, rubber or plastics is prohibited. However, loading wood briquettes into the
boiler together with their plastic packaging bags is allowed.
123
Fig. 9 Front control panel
1. Electronic boiler regulator; 2. Green button for switching the voltage of the boiler on and o; 3. Red button for switching on the ventilator.
7. OPERATION
• FRONT CONTROL PANEL
The front control panel has an electronic boiler regulator 1, a green button for switching voltage to the boiler on/o 2 and
a red button for switching on the ventilator 3. These buttons light up in the activated state. For more details on the operation
15
Page 16
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
of the front panel buttons, see “Electronic boiler regulator KR-4.3D” and “Boiler kindling procedure”.
• REAR CONTROL PANEL
The following safety devices are installed in the rear control panel: thermal fuse 1 and electric fuse 2 (Fig. 10). The purpose
of the thermal fuse, otherwise called the maximum boiler temperature emergency thermostat, is to switch o the boiler
12
Fig. 10 Rear control panel
1. Thermal fuse ; 2. Electric fuse.
ventilator if water temperature in the boiler exceeds the maximum permissible
95°C due to unforeseen reasons. The temperature sensor of the thermostat is
installed in a dedicated sleeve 19 (Fig. 1). The burning intensity decreases when
the ventilator is switched o and the water temperature decreases. When the
emergency thermostat trips, the lamp of the ventilator switch 3 on the front
panel switches o (Fig. 9) and the lighting indicator bulb 4 “Firing o” on the
electronic regulator lights up (Fig. 11). In this case, it is necessary to nd out
the causes of tripping and to remove them. After the boiler cools down, the
emergency thermostat can be returned to its normal operating mode. For this
purpose, unscrew its cover and depress the red button.
The cause of overheating of the boiler and tripping of the emergency thermostat must be found and
removed. If this is not done, the risk of serious damage to boiler equipment as well as hazard to human health
and life remains. If the user cannot locate and remove the cause of tripping of the emergency thermostat, a
professional servicing company must be consulted!
The electric fuse is designated to protect the elements of the electric circuit in case the current in the mains exceeds 2 A. If the
fuse is damaged, the boiler will not switch on and its indicator lamps will not light. In this case, remove and replace the fuse.
The rear control panel of the boiler is grounded.
• ELECTRONIC BOILER REGULATOR KR4.3D
The electronic boiler regulator KR-4.3D is designed for controlling a solid fuel boiler. It controls the ventilator in accordance
with the PID regulation law and the circulation pump of the system, by position “on-o”. The regulator adjusts the rotation
speed of the ventilator using the impulse method, thus intensifying or slowing down the burning process. The speed of
the ventilator is dened in proportion to the actual temperature deviation from the set temperature, the duration of the
deviation and the speed of temperature change of the boiler. The regulator reacts to the water temperature in the boiler and
smoke temperature in the ue. A NTC-type sensor for
12
measuring water temperature is installed in a special
sleeve 19 (Fig. 1), the outer side of which is submerged
in water inside the boiler. A PT-type sensor for
measuring smoke temperature is installed in a special
7
sleeve 10 (Fig. 1), which is located in the ue gases
duct of the boiler.
34568
Fig. 11 Front panel of regulator KR-4.3D
1 – digital temperature indicator; 2 – temperature setting buttons; 3 - lamp
“Firing on”, 4 - lamp “Firing o”, 5 - lamp “Pump on”, 6 - lamp “Ventilator on”,
7 – control button for the programmable channel, 8 – lamp “Programmable
channel on”
16
The digital temperature indicator 1 (Fig. 11) indicates
both the measured and the set temperature of water
in the boiler. The setpoint temperature is adjusted
using the buttons 2. After a short press of “+” or “-”
the digital indicator 1 starts showing the setpoint
temperature of the boiler water. In order to change it,
Page 17
INSTALLATION AND OPERATION MANUAL
L1, N- reguliatoriaus maitinimas;L2 - ventiliatoriaus maitinimas;L3 - įtampa į ventiliatorių;L4 - įtampa į siurblį;P - įtampa į programuojamą išėjimą;U - vandens temperatūros jutiklis;U - dūmų temperatūros jutiklis.
1
2
the appropriate button must be pressed: “+” for increasing and “-” for decreasing the temperature. After several seconds after
the last press of a button, the setpoint temperature is saved and the indicator returns to showing the measured temperature
Rear panel of the regulator
KR-4.3D
of the boiler water.
When it indicates the setpoint temperature, a dot
lights up beside the readout. When the indicator
indicates the real measured temperature, the dot does
X-2X-3X-1
not appear. The regulator allows adjustment of the
temperature within the range of 65-85°C.
Lamp 3 “Firing on” indicates the active status of
the boiler. This lamp lights up when the ventilator is
switched on using the button 3 (Fig. 9) on the front
control panel and regulation of the ventilator speed
starts. The ventilator can be in operation mode only
U
1
Fig. 12 Regulator connection diagram
L1, N – power supply to the regulator; L2- power supply from front control
panel to the ventilator; L3 – voltage to the ventilator; L4 – voltage to the
pump; P – voltage to the programmable channel; U
sensor; U2- ue gas temperature sensor.
U
2
L1
N
L2
- water temperature
1
L4
L3
when the signal lamp 3 (Fig. 11) lights.
P
Lamp 4 lights up when the boiler turns to the mode
“Firing o”. This boiler operation mode is established if
the following condition occurs:
• if during operation the temperature of ue gases
drops bellow 75°C and does not rise for some time.
Lamp 5 “Pump on” lights up when the regulator
switches on the circulation pump of the system. In accordance with the manufacturer’s settings, this occurs when the boiler
water temperature exceeds 60°C. As the boiler cools down and the water temperature drops below 58°C, the regulator
switches o the circulation pump and lamp 5 switches o. Service programming mode can be used to adjust other limit
temperatures for switching the circulation pump on (in the range of 60-75°C) and o (in the range of 58-73°C). To carry out
such adjustment, a servicing company should be contacted.
Lamp 6 “Ventilator on” lights up when the boiler ventilator is operating. The more frequently it blinks, the higher the
rotational speed of the ventilator is, since its blinking frequency corresponds to the impulse frequency of the power supply to
the ventilator. If this lamp is lighting constantly, it means that the ventilator is operating at 100% of its capacity.
Lamp 7 signals that the programming output channel is switched on. Button 8 is used for service programming and can
only be used by the specialists of the service company. We do not recommend the user to modify the programming modes.
The boiler regulator is connected to the boiler circuit in accordance with the scheme shown in Fig. 12. The power supply L2,
stemming from the front control panel and transferred to the regulator, is switched on when switches 2 and 3 (Fig. 9) are in
the position ON and the emergency thermostat has not tripped. The impulse commutator regulating the ventilator connects
periodically L2 to L3. When the boiler switches to status “Firing o”, L3 does not supply power to the ventilator and lamp 4
(Fig. 11) lights up. To return to the mode “Firing on”, the power supply L2 should be interrupted by switching o the ventilator
switch 3 (Fig. 9) or the power supply of the boiler (on/o button 2, Fig. 9), and later turning them on. The pump control relay
connects L4 to L1. The programmable channel relay connects P to L1.
The power of the operating ventilator ranges between 20÷100 VA. The maximum allowed power of the circulation pump
connected to the regulator is 250 VA. The maximum allowed power of the programmable channel is 250 VA.
• PREPARATION FOR FIRING
Before kindling the boiler, check the position of the ceramic chopper 2 in the lower combustion chamber: the edge of the
17
Page 18
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
chopper must be in contact with the rear wall of the boiler (Fig. 2). Place two ceramic segments 3 (Fig. 2) on the rear edge
of the chopper so that they contact the rear wall of the boiler chamber. Another two segments should be placed at the front
edge of the ceramic chopper.
Fill the heating system with water. The lling pressure should be 0.2 bar bigger than the hydrostatic pressure, yet it must
not exceed the operating pressure of the boiler. After lling the system with water, perform a visual check of the tightness of
the entire system. Perform it before kindling the boiler, then again after kindling and reaching the nominal operating mode.
Check if the heating system is properly deaerated.
• KINDLING PROCEDURE OF THE BOILER
Before kindling the boiler, check whether all requirements indicated in the section 1 are executed.
Open the damper of the upper ue 14 by pulling the handle 5 (Fig. 1) towards yourself. Open the door of the upper
combustion chamber, put dry smaller kindling wood pieces and paper on the ceramic bottom so that the paper protrudes into
the lower combustion chamber through the rectangular opening of the ceramic burner 1 (Fig. 2) – this way, it will be easy
to kindle the boiler through the lower combustion chamber. Put some of the easily ammable materials and larger pieces of
kindling wood and rewood atop. Load the wood without any large gaps at the top of combustion chamber. Bigger pieces of
rewood should be loaded in the middle and smaller prices at the sides, because the walls of the combustion chamber slow
down the combustion of the bigger pieces of wood, due to their lower temperature.
Do not cover the entire opening of the upper ue 23 (Fig. 1) with the wood, because it will make
kindling more dicult.
The rst time, kindle the boiler using only paper and small pieces of wood in order to safely remove the
moisture remaining in the ceramic elements.
Switch on the voltage, using button 2 on the front control panel. The boiler water temperature indicator will light up on the
electronic regulator (Fig. 9). Set the required outowing boiler water temperature using the temperature setting buttons; we
recommend a temperature of at least 75°C or – even better – a higher temperature. Close the door of the upper combustion
chamber, open the lower door and set the kindling material on re. Observe the rising water temperature in the regulator
display. Keep the lower door open until the boiler water will heat up to 40°C. Then close the lower door, close the damper
14 of the upper ue by pushing its handle 5 (Fig. 1). Then switch on the ventilator switch 3 on the control panel (Fig. 9).
After that, the boiler will operate in automatic mode: it will try to reach and maintain the setpoint temperature of the water
outowing from the boiler.
When ring the boiler for the rst time, the condensation of the residual moisture and drainage of water in the lower
combustion chamber occurs. This is not a shortcoming. After kindling the boiler several times, this phenomenon disappears.
The doors of the boiler combustion chambers should be tightly closed, there should be no ue gases
seeping into the ambience through them. Door tightness is regulated by screwing or unscrewing the hinge
and lock screws of the door.
• FIRE BED AND TIPS FOR EFFECTIVE BOILER STOKING
The hot embers and charcoal in the boiler are called the re bed. Combustible gases emerge from there and are further
burned in the lower chamber of the boiler. The optimal re bed height during boiler operation is approximately 4-5 cm above
the bottom of the fuel chamber. The output of the boiler ventilator is deliberately chosen with the purpose of suciently
supplying the re bed with air. Then, the most eective combustion of wood gases takes place. Avoid a situation when the
18
Page 19
INSTALLATION AND OPERATION MANUAL
volume of the re bed expands several times. This situation can occur if very dry and thinly cut wood gets loaded into the
fuel chamber. Consequently, the volume of the re bed increases rapidly during the burning process and soon a lack of air
occurs, allowing the combustible gases to escape unburned through the chimney into the atmosphere. An indicator of this
undesirable course is dense fumes emerging from the chimney.
The best way to stoke a boiler is the so-called two stages method. During the rst stage, the boiler is stoked with a small
amount of fuel. The aim of this phase is to warm up the boiler and form the optimal re bed. The second stage is intended for
full fuel loading and to perform the main combustion.
The rst stage: Prepare thin-cut wood and paper for an easy start. The volume of loaded fuel should be about 15-20 %
of the fuel chamber’s capacity. Open the upper ue damper 3 (Fig.1) and both boiler doors, put the wood and paper inside.
Kindle the paper, make sure that the ring starts and close the upper door. After the temperature of water in the boiler
reaches 45°C, close the damper and the lower door and turn on the ventilator. Let the boiler burn further for 30 minutes.
The second stage: Load the boiler fully. If wood briquettes are used for stoking, load approx. 70 % of the fuel chamber’s capacity.
Before opening the door, simultaneously press the “+” and “-”controller knobs, shown in Fig. 11. The letter “L” will appear on the
display and the ventilator will stop. Open the damper 3 (Fig. 1) by pulling the handle towards yourself, and after some time, open
the upper boiler door very slowly to avoid smoke escaping into the room. Load the fuel, close the door and push the handle of the
damper 3 (Fig. 1). Press the knob “P” on the controller panel. The ventilator will start and the boiler will continue its ring mode.
If you lack time to stoke the boiler in the two stages mode as described above, then stoke it by one stage. The boiler will operate
as usual. But if there is the possibility to do so, use the two stages mode in order to achieve an even more eective combustion.
• REGULATION OF THE BOILER TEMPERATURE
See the technical description of the electronic regulator KR-4.3D.
• ADDITION OF FUEL
It is important to stop the ongoing program of a controller when adding fuel into an operating boiler
(see the recommendations below)!
When the boiler is still active, the controller lamp 3 “Firing on” (Fig. 11) light is on. To add more rewood, perform the
following procedure:
1. Press the controller knobs "+" and "-" simultaneously. The symbol "L" will appear on the display, indicating the program
has been paused. The ventilator will automatically stop.
2. After the rewood has been added, resume the controller program operation by pressing "P" knob. The symbol "L"
must disappear from the display. The ventilator will automatically turn on and continue its operation from the point of
interruption.
While adding rewood into the combustion chamber after a fuel load has burned o, perform a usual procedure:
1. Open the damper of the upper ue 19 by pulling the handle 3 towards yourself (Fig. 1).
2. Switch o the ventilator switch 3 (Fig. 9).
3. Wait at least 20 seconds, allowing the smoke to be removed by draught; then slowly open the upper door.
4. Put the rewood in and close the door tightly.
5. Switch on the ventilator.
6. Close the damper of the upper ue.
If operated following this order, smoke and carbon monoxide will not enter the room. Water temperature and pressure in
the system are checked by readings of the thermometer-manometer, installed in the heating system.
19
Page 20
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
• COMBUSTION CONTROL
The status of the boiler ring process can be perceived from the regulator lamps “Firing on” or “Firing o” (see description
of the regulators KR-4.3D, Fig. 11). The ame in the boiler can be checked by opening the door of the lower combustion
chamber when the ventilator is on. The visible tongue of ame has to be yellow or yellow-red and reach the ceramic element;
this means the ring is proceeding in an optimal manner.
Do not keep the lower door of the boiler open for extended periods of time during ring: the lower
chamber contains gases which, when escaping into the boiler room in larger amounts, can impair human health.
• DESCRIPTION OF THE SMOKE TEMPERATURE SENSOR FUNCTION
The smoke temperature sensor is mounted in Astra boilers in order to: 1) help the controller achieve the optimal smoke temperature,
2) turn o the ventilator after ring in the boiler is accomplished, 3) turn o the circulation pump after the ring in the boiler is over.
Although the optimal smoke temperature is set up in the factory, we recommend that you set the temperature by yourself once
again after the installation of the boiler at its operation place. In this way, a more precise temperature will be set up with respect to
the fuel used, draught and other peculiarities of the installation. For that purpose, the boiler must be brought up to an optimal and
stable operation mode, and the smoke temperature at this time must be determined and xed. First, set the water temperature on
the boiler controller; we recommend 85°C, or at least 75°C. This temperature should be the one you will use to set in the future boiler
operation. Kindle the boiler using the two stages method described in the chapter “Fire bed and tips for eective boiler stoking”.
Verify the state of combustion by opening the lower door after 45-60 minutes from the beginning of ring. At that moment, the
ame tongue must be reaching the lower ceramic element, and the colour of the tongue must be yellow-red. Then check the actual
smoke temperature by pressing the controller knobs “P” and “+” simultaneously. As a result, the screen should display a two-digit
number representing the actual smoke temperature. The number must be multiplied by 10 to determine the actual temperature. For
example, if the number 16 is displayed, that means that the actual measured smoke temperature is 160°C. The number will stay lit for
3 seconds. During this period, the controller knob “P” must be pressed again. The number on the display will blink and will then stay
lit permanently for a short moment; after 3 next seconds, the controller will automatically leave the programming mode and return
to its usual operation mode. Now the new optimal smoke temperature has been set up.
In a usual boiler operation, after the ring has been completed, the smoke temperature sensor will help to turn o the
ventilator of the boiler and the circulation pump. When the temperature of the ue gases drops bellow 75°C, the rotational
speed of the ventilator is minimized and after some more time, the ventilator and circulation pump are turned o.
If you think that that the smoke temperature sensor is unnecessary for your boiler, you can easily shut it o. For that purpose,
take o the rooftop panel of the boiler (Fig.7) and unplug the sensor from the controller’s X3 socket. The boiler controller will
automatically switch to operate by another programme controlling the boiler without the smoke temperature sensor.
• CLEANING THE BOILER
Ashes are removed from the boiler every 4-7 days. Open the door of the upper combustion chamber and shovel ashes down
to the lower chamber. Open the door of the lower chamber, take out only two front ceramic segments 3 (Fig. 2), pour ashes to
a metal box. It is not necessary to take out the triangle ceramic chopper 2 (Fig. 2) at the time of cleaning, ashes underneath
it may be raked using scraper.
In any case, strictly follow the established procedure when opening the upper door: open the damper
of the upper ue, then after 20 seconds, open the boiler door.
Clean boiler chambers from tar, pitch and scurf once or twice a month. Clean the boiler when the fuel has been completely
burned and the boiler is cooled down to at least +40°C.
20
Page 21
INSTALLATION AND OPERATION MANUAL
Open the upper cap 8 for cleaning the ue (Fig. 1). Remove the turbulence plates from the ue by hooking them and pulling
them out with the poker, then clean them using a scraper. Clean tar and scurf from combustion chambers and ue walls using
a scraper and metal hog. Clean with the doors of the combustion chambers open. The soot residues falling down from the
ue walls during the cleaning process are raked out of the boiler through the lower opening of the combustion chamber 12
(Fig. 1), pulling them outwards. When nished, place the turbulence plates back and close the cleaning cap.
Control water pressure in the heating system at least once every two weeks. If the pressure drops,
raise it by lling up the system with more water. If the boiler is not being heated for a longer time, drain the
water out of the system when air temperature is below 0°C!
• EMERGENCY SHUT DOWN OF THE BOILER
If for some reason you must immediately shut down the operating boiler, by any means do not pour water on the kindling
wood! The boiler can burst!
It is very convenient to use dry sand for emergency extinction. There should be ~50kg of dry sand in the boiler room. Sand
not only isolates burning rewood well from the air oxygen but also cools down the burning zone. Then, when the boiler
cools down, sand can be easily cleaned and removed.
8. POSSIBLE FAULTS
FaultCause Problem solution
1. The set
temperature
cannot be
reached
2. Smoke escapes
through the
boiler door
Not enough water in the heating systemFill up
Thermoregulator or ventilator is defectiveRepair or replace
Poor quality fuel: high moisture content,
Use dry fuel, split rewood
too large pieces of rewood
Heating surfaces of the boiler are very dirtyClean
No draught in the chimney due to accumulated
Clean
impurities
The ceramic burner is congestedClean
Ventilator damper is stuckMove or clean
The door-sealing rope is damagedReplace with a new one
Door is not tight along the entire perimeterAdjust hinge supports and door lock (regulated
screwing or unscrewing of door hinge or lock
screws) (see Fig. 13)
No draught in the chimney due to accumulated
impurities
21
Fig. 13 Adjustment of the door and lock mechanism
Clean
Page 22
HEATING BOILERS: Astra H-25 E, Astra H-32 E, Astra H-45 E
3. Ventilator is
not operating
Emergency thermostat has tripped, light of the
ventilator switch is o
Call representatives of the service company; switch
on after indication of the causes (see Chapter 6)
Electronic regulator KR-4.3D or ventilator is faultyReplace
Power supply failureCheck electric fuses of the electric panel of the
building; call electrician
Lamp 4 lights up (Fig. 11, see technical description
of regulator KR- 4.3)
All rewood has burned. Load more rewood,
kindle the boiler
9. WARRANTY AND ITS VALIDITY TERMS
The manufacturer provides a warranty for the boilers, the main conditions of which are the following:
• the connection of the boiler to the heating system as well as the initial kindling, adjustment and repairs are carried out by
an authorised company;
• the boiler is connected to the heating system and operated following the requirements of this operation manual;
• the duration of the warranty period for the boiler is the following:
- for the heat exchanger of the boiler against leaking – 60 months,
- for other parts of the boiler – 24 months.
• the warranty repairs are performed when the fault has occurred due to the manufacturer’s fault;
• the warranty term is not extended after removing the faults which have occurred during the warranty period;
• boiler cleaning and heating system adjustment works are not covered by the warranty;
• the damage caused to the premises and the property in the premises due to the boiler fault will not be compensated;
• the warranty repair works and replacement of parts during the warranty period are free;
• the warranty period starts from the boiler purchase date;
• the warranty is valid only if the boiler is installed, connected to the heating system and operated following the requirements
of this manual.
The warranty does not apply in the following cases:
• in case the heat exchanger is limed;
• in case the water or other liquid inside the boiler has been frozen;
• in case of fault of the boiler due to improper operation;
• in case of fault of the boiler due to improper connection to power supply;
• in case the boiler parts are mechanically damaged;
• in case the boiler is connected to the heating system not in accordance with the diagrams and requirements of the
operation manual.
The post-warranty repair works will be carried out at the expense of the owner of the boiler.
The buyer must follow all the requirements of this operation manual during transportation, storage
and operation, otherwise the manufacturer warranty does not apply.
22
Page 23
INSTALLATION AND OPERATION MANUAL
10. ACCEPTANCE CERTIFICATE
The heating boiler Astra H- ......................., serial No. .......................................,, conforms to the technical documentation
and requirements of standard EN 303-5 and is approved as t for operation.
Manufacturing date 201 ..................................................................................................
L. S.
Head of Quality Service ....................................................................................................
Date of sale: ...........................................................................................................................................................................................
Company (technician): ...........................................................................................................................................................................
Inst all at io n date: ....................................................................................................................................................................................
Installation data:
Height of the chimney: ..........................................................................................................................................................................
Diameter of the ue: .............................................................................................................................................................................
Draught of the chimney: .......................................................................................................................................................................
Other information concerning installation: ..........................................................................................................................................
The boiler was tested on site, the control and safety elements were checked and found to be operating properly.
Person responsible for installation and testing: ..................................................................................................................................
(Name, surname, signature of the employee)
I accept the installation works: .............................................................................................................................................................
(Name, surname, signature of the client)
23
Page 24
WARRANTY AND POSTWARRANTY REPAIR CARD
Boiler repaired by:
Company (technician): ...........................................................................................................................................................................
Information on fault, works performed:...............................................................................................................................................
Signature of the technician: ..................................................................................................................................................................
Boiler repaired by:
Company (technician): ...........................................................................................................................................................................
Information on fault, works performed:...............................................................................................................................................
Signature of the technician: ..................................................................................................................................................................
We declare that the above-mentioned products conform to the requirements of directives 97/23/EEC Article 2.3 and 2006/95
EEC.
The following standards were applied for the above-mentioned products:
LST EN 303-5
LST EN 12828
LST EN 60335-1
LST EN 60529
Procedure of conformity evaluation in accordance with Article 2.3 of 97/23/EEC was performed by “Inspecta”, www.inspecta.
com. Certication No. 2-4.2.1/619/2012