SECURITRON MODEL LCP SERIES ELECTRIC LOCK CONTROL PANEL
TABLE OF CONTENTS AND GUIDE TO THIS MANUAL
The LCP series is a powerful and versatile system with many standard and optional features.
You will generally use only some of these features so this table of contents includes a
description of the type of application that applies to each different section. By studying it first,
you can save considerable time by skipping over those parts of the manual that don't apply.
SECTION 1. DESCRIPTION --------------------------------------------------------------------Page 1
SECTION 1.1 GENERAL ------------------------------------------------------------------------Page 1
This section explains part numbering and allows you to determine your panel configuration.
SECTION 1.2 PANEL POWER-----------------------------------------------------------------Page 1
SECTION 1.3 LOCK CONTROL---------------------------------------------------------------Page 2
SECTION 1.4 MONITORING--------------------------------------------------------------------Page 2
SECTION 1.5 AUDIBLE ALARM AND ALARM RESET---------------------------------Page 3
The above 4 vital sections contain information that applies to any LCP series panel.
SECTION 2. OPTIONS ---------------------------------------------------------------------------Page 4
Once you have determined the options present or desired on your panel, read the
corresponding section below to learn the function and operation of the supplied option.
SECTION 2.1 SILENCE LATCH (OPTION "SL") -----------------------------------------Page 4
SECTION 2.2 EMERGENCY RELEASE (OPTION "PB")-------------------------------Page 4
SECTION 2.3 ADDITIONAL MONITORING LIGHTS (OPTION "AM")--------------Page 4
SECTION 2.4 SWITCH BYPASS KEYSWITCH ("KP1", "KP2""MK1", "MK2")-Page 5
SECTION 2.5 MOMENTARY SWITCHES (OPTION "MOM")--------------------------Page 5
SECTION 2.6 HIGH VOLUME PUSH BUTTONS (OPTION "HT")--------------------Page 5
SECTION 3. BOARD TERMINAL DESCRIPTIONS --------------------------------------Page 6
This is a reference section. It starts with a drawing showing all terminals on the panel board
and then describes the meaning and function of each. Reading the section explains the
capabilities of the panel, but it's not necessary to complete an installation. As a reference,
the section is of great help in answering questions which arise or planning unusual uses.
SECTION 4. WIRING------------------------------------------------------------------------------Page 7
SECTION 4.1 POWER INPUT WIRING------------------------------------------------------Page 7
The above section should be read for all installations.
SECTION 4.2 FAIL SAFE LOCKS ------------------------------------------------------------Page 9
If the locks you will be using are fail safe (secure when powered), this section should be
carefully read to determine the proper hookup. Figure 3 (Page 10) shows the several
different ways that fail safe locks may be connected to the panel.
If the locks you will be using are fail secure (secure when not powered), this section should
be carefully read to determine the proper hookup. Figure 4 (Page 12) shows the several
different ways that fail secure locks may be connected to the panel.
SECTION 4.4 POWERED SWITCHING DEVICES AT THE DOORS ----------------Page 14
Read this section if your are using a switching device at the door which employs power such
as a digital keypad or card reader.
SECTION 4.5 WIRING UNUSED ZONES ---------------------------------------------------Page 15
If any zones are not connected to locks, read this section.
SECTION 4.6 WIRING WITH RELEASE HOLD TIMER ---------------------------------Page 15
If the locks include a momentary switch for entry or exit which activates a timer to release
the door for an interval, this section shows preferred wiring techniques.
SECTION 4.7 REMOTE INDICATOR WIRING---------------------------------------------Page 16
If controls at the door such as push buttons or keyswitches include indicator lights, this
section advises methods of wiring them for clear prompting to individuals using the door.
SECTION 4.8 AC LOCK CONTROL----------------------------------------------------------Page 17
This section explains use of the panel with AC locks.
SECTION 5. OPTION WIRING -----------------------------------------------------------------Page 17
The following 5 sections explain the field wiring that relates to the options which may be
supplied with the panel. In the case of certain options, it is possible that the option be
added in the field by the installer if it ought to have been ordered but was not. Therefore,
read the appropriate section for any option that has been supplied or that might be desired.
SECTION 5.1 SILENCE LATCH WIRING (OPTION "SL")------------------------------Page 17
SECTION 5.2 EMERGENCY RELEASE WIRING (OPTION "PB")-------------------Page 18
SECTION 5.3 WIRING OF "AM" OPTION FOR DELAYED EXIT---------------------Page 18
SECTION 5.4 SWITCH BYPASS WIRING (OPTION "KP1" OR "MK1") -----------Page 23
SECTION 5.5 SWITCH BYPASS WIRING (OPTION "KP2" OR "MK2") -----------Page 24
SECTION 6 USE OF MULTIPLE PANELS--------------------------------------------------Page 25
The three sections below explain different techniques of employing more than one panel to
control and monitor the same set of electric locks.
SECTION 6.1 “MASTER/SLAVE PANELS (FOR FAIL SAFE LOCKS)-------------Page 25
SECTION 6.2 MULTIPLE PANEL FAIL SECURE WIRING-----------------------------Page 27
SECTION 6.3 PANELS ALTERNATELY ENABLED-------------------------------------Page 27
SECTION 7. DOOR MONITORING (NO ELECTRIC LOCKS) -------------------------Page 29
This section covers use of the panel for door monitoring
Rev. A.1, 10/99 Page- 1
SECURITRON LCP SERIES ELECTRIC LOCK CONTROL PANEL
INSTALLATION AND OPERATING INSTRUCTIONS
1. DESCRIPTION
1.1 GENERAL
The LCP series is a circuit board based family of control panels suitable for hard wired control
and monitoring of electric locks. The unit can also be used for door monitoring only (no electric
locks). See section 6. The circuit board operates 4 control/monitoring zones so the panel must
be constructed in multiples of 4 zones. The locks must operate on 12 or 24 voltsDC and may
be fail safe (secure when powered) or fail secure (secure when unpowered). Lock current draw
is limited to 1.5 Amps (steady) with 3 Amps inrush acceptable.
The LCP series includes several options which are generally supplied with the panel (when
ordered) or in most cases may be added by the installer if the requirement for the option is
discovered after the panel has been delivered.
The panel's part number expresses the complete description of the panel as follows:
LCP-XX-YY-(OPTIONS)
"XX" = The number of zones for control and monitoring
"YY" = The panel voltage (12 or 24 VDC)
Options are expressed as letter suffixes as follows:
"W" = Wall mount Nema 1 locked enclosure
"F" = Flush mount pull box cover with back box
"R" = 19" Rack panel face. A slope front desk mount is the standard panel enclosure.
"SL" = Silence Latch
"PB" = Emergency all release (for fail safe locks only)
"AM" = Additional set of monitoring lights
"KP1" or "MK1" = Keyswitch control switch bypass (for fail safe locks only)
"KP2" or "MK2" = Keyswitch control switch bypass (for fail secure locks only)
"MOM" = Momentary control switches (alternate is standard)
“HT” = Substitutes high volume push button switches for toggle switches
As an example, part # LCP-16-12-W-SL-MOM would be a 16 zone, 12 VDC, wall mount panel
with the Silence Latch and momentary switch options installed.
The options are discussed in detail in section 2.
1.2 PANEL POWER
Panel (and lock) power must be from a single power supply of the same voltage required by the
locks (12 or 24 VDC). The panel distributes this power to each lock through its control switches.
Regulated DC is not necessary. A transformer + bridge rectifier is adequate. The rectifier
must however be full wave; a single diode will not work.
A power supply with integral battery backup (available from Securitron) is required if the system
is expected to operate in a power failure.
In selecting the power supply, it naturally should be of sufficient capacity to operate all the locks.
In addition the panel requires power for its internal electronics and indicators. The power
Rev. A.1, 10/99 Page- 2
requirements vary with the monitoring scheme and the voltage but figure a worst case of 60 mA per control zone for panel current draw. Since power supply cost is always a small percentage
of the installation cost, we always recommend to not skimp on power supply capacity. We
advise that the power supply be capable of driving 30% more current than the installation
requires. This eliminates heat induced power supply failure and also allows for some future
expansion of the job.
1.3 LOCK CONTROL
Each lock is controlled by a toggle switch on the panel face. Normally, the toggle switch is
alternate action but the "MOM" option supplies spring loaded momentary toggle switches so
that the lock will be released only so long as the switch is held down. It is, of course, possible to
control multiple locks from a single switch (zone) if they are wired in parallel. This is most
commonly done with two locks mounted on a double door. Be sure that if multiple locks are
controlled by a single toggle, the 1.5 Amp current limit per zone is not exceeded. If higher
current control is necessary, the panel should be made to control a relay which in turn will switch
the high current lock or locks. Note that toggle switches are not suitable for high volume use.
50,000 cycles is a typical operating life for a toggle switch. If your expected use for each zone is
on the order of a few dozen operations per day, toggle switches are fine. If the expected use is
in the hundreds of operations per zone per day, you should purchase option HT which replaces
the toggles with illuminated push buttons with a much longer operating life. The lamp within the
“HT” push button, operates just as the toggle bat yellow indicator.
1.4 MONITORING
Each zone (toggle switch) has a bicolor LED with
green and red internal elements behind a fresnel
YELLOW LED
(AM OPTION ONLY)
lens. If a second indicator is present for each
toggle, this is the "AM" option which is described in
section 2.3. Returning to the bicolor indicator, the
green element is driven by a separate input terminal
on the board and it is intended to monitor the status
of the lock or door. Green indication means that the
lock is reporting secure if it has lock status sensing
or it can mean that the door is closed from a door
switch. If no lock or door monitoring is desired, the
BICOLOR LED (GREEN/RED)
LOCK SECURE TOGGLE POSITION
TOGGLE BAT YELLOW LED
LOCK RELEASE TOGGLE POSITION
green indicator can be made to follow the
powered/unpowered status of the lock although this does not utilize the full capabilities of the
panel.
When the lock has been "legally" released from the panel toggle or from a local switch at the
door such as a keyswitch, digital entry device or card reader, the bicolor indicator will be off.
Each toggle switch has a yellow LED in its actuator. This illuminates whenever the lock is
legally released, either from the toggle switch itself being flipped down, or from a local release
switch at the door. The yellow toggle indicator will always correspond to "bicolor indicator off".
If the panel has been supplied with spring loaded momentary switches (option "MOM"),
the toggle switch will not have any indicator due to unavailability from the switch
manufacturer.
The bicolor indicator will turn red in the "violation" condition. This is when the lock should be
secure but is not so reporting from its lock status or door status output.
Rev. A.1, 10/99 Page- 3
1.5 AUDIBLE ALARM AND ALARM RESET
The red indicator is always accompanied by a Sonalert sounding on the panel. The panel
operator hears the alarm, and then consults the panel face to determine the zone that has gone
into violation. The violation condition islatching. Once a red indicator goes on and the
Sonalert sounds, it will continue even if the door is resecured, until manually reset by the
momentary reset switch on the panel face. This reset switch serves for any violation event on
the entire panel.
The panel's reporting of a violation event is automatically delayed by 2 seconds. To understand
the purpose for this, consider a typical installation with lock status sensing locks. When a lock is
legally released by the panel toggle or a local switch, the panel reports legal release (toggle bat
LED yellow and bicolor LED off). When the lock is resecured by the same switch, some time
(usually a half second) is required for the lock to report secure to the panel. This is the time
necessary for a magnetic lock to pull in and generate full holding force or for a bolt to seat.
Without the violation delay, a latching alarm event would occur every time a zone was relocked.
If the factory is informed, the delay time can be increased to up to 6 seconds (capacitor
values on the boards are changed). An example of a longer delay being desired would be if
entry was by a keyswitch. A person using the door would turn the momentary keyswitch and
push the door open with his other hand. A 6 second violation delay would be appropriate to
allow the person to release the keyswitch, move through the door, and then allow the door to
reclose and resecure. Note that if the keyswitch activates a release hold timer as is commonly
done, a long delay is not required. The timer will shunt the panel violation condition allowing the
door to reclose. When the timer resecures the lock, it will drop out the violation shunt and only a
short delay will be necessary to allow the lock to report secure again.
The effect of the bicolor LED in helping the panel operator correctly reset panel violations should
be understood. In normal operation, the locks are secure and the indicators are green. Legal
use of the door switches the bicolor LED off and it then turns green again when the door
resecures. If the indicator turns red (accompanied by the Sonalert) a violation has occurred
which means that the door is not secure. If reset is attempted at this point, the Sonalert will stop
but after the alarm delay expires, (2 seconds) the violation condition will reoccur as the door is
still not secure. If the panel toggle is switched to legally release the lock, the violation can now
be reset (bicolor LED will be off) but the door is still not secure. The panel should be reset after
the door has been resecured. At this point, the bicolor green element (door secure) and red
element (violation) will both be lit which will make the LED appear orange. The orange color is
therefore the signal to the operator that the zone is secure after a violation and is ready
to reset.
SUMMARY OF INDICATOR/SONALERT STATES
BICOLOR GREEN: ZONE SECURE (FROM DOOR STATUS OR LOCK STATUS SWITCH)
BICOLOR OFF: ZONE LEGALLY RELEASED EITHER FROM TOGGLE OR FROM REMOTE
CONTROL SWITCH
TOGGLE BAT YELLOW INDICATOR ON: LEGAL RELEASE (SAME AS BICOLOR OFF)
TOGGLE BAT YELLOW INDICATOR OFF: LOCK SHOULD BE SECURE (FAIL SAFE LOCK
IS POWERED; FAIL SECURE LOCK IS UNPOWERED)
BICOLOR RED: VIOLATION CONDITION. LOCK SHOULD BE SECURE (TOGGLE BAT
INDICATOR IS OFF) BUT IS NOT REPORTING SECURE AFTER 2 SECOND DELAY
Rev. A.1, 10/99 Page- 4
BICOLOR ORANGE: ZONE THAT HAD BEEN IN VIOLATION HAS RESECURED.
PRESSING RESET TOGGLE WILL CLEAR CONDITION, CHANGING LAMP TO GREEN AND
EXTINGUISHING SONALERT
2. OPTIONS
If the panel has been supplied with any of the options listed in section 1.1, explanations of the
options' functions are provided in the following sections. Section 5 explains wiring for all options
including the addition in the field of certain options that may not have been ordered with the
panel but have turned out to be needed at the time of installation.
2.1 SILENCE LATCH (OPTION "SL")
In the event of a violation condition which takes some time to resolve, the continuing Sonalert is
irritating. If the "SL" option has been installed, the sound can be extinguished by momentarily
pushing the "silence" button found next to the Sonalert. This works as follows: If the Sonalert is
not sounding, pushing the button has no effect. The Sonalert cannot be silenced in advance.
When it is sounding, pushing the button will stop it and illuminate the indicator in the button
which shows the silence latch is active and the Sonalert would otherwise be sounding. The red
indicator will continue to show the zone in violation. The Sonalert will remain silent until the
violation condition has been reset even if another zone violates. The button indicator will then
extinguish and the latch will reset. The next time a violation condition occurs, the Sonalert will
again sound and may again be silenced as before.
2.2 EMERGENCY RELEASE (OPTION "PB")
Often, for safety reasons, it should be possible to release all locks with a single control. The
"PB" option adds to the panel an illuminated, alternate action, red push button switch. In normal
operation, the red indicator in the switch is off. When the switch is pressed, it cuts off all DC
power to the locks, releasing them (the "PB" option works with fail safe locks only). The red
indicator in the switch then illuminates showing that the panel is in a state of emergency release.
Pressing the switch a second time extinguishes the indicator and restores power to the locks.
Note that when this happens, the Sonalert will sound and the reset switch will have to be
pressed. Whenever the panel boards are first powered or repowered, the reset switch must be
pressed to initialize the boards and start normal operation of the violation circuit.
2.3 ADDITIONAL MONITORING LIGHTS (OPTION "AM")
The "AM" option adds a second row of LED's (yellow) next to the bicolors. When a positive
voltage signal is input to the associated board terminal, the yellow LED comes on. At the same
time a different audible alarm sounds. For panels with the "AM" option, Securitron uses a dual
input Sonalert. It sounds a steady alert in the violation condition but sounds a pulsing alert if
any panel yellow LED illuminates. The pulsing alert can not be silenced with the silence latch if
that option has been supplied.
The main purpose for the additional monitoring capability is exit delay installations. In such
installations an exit device is mounted on each door. Pressing the exit device does not
immediately release the lock, but rather initiates a 15 or 30 second delay after which the lock
automatically releases. A specialized logic timer such as Securitron's model XDT is necessary
to accomplish the delay function. When a control panel is used in this sort of installation, the start of the release delay period must be annunciated so that a guard can be dispatched to
the door to investigate the egress attempt. The yellow indicator together with the pulsing
Sonalert perform this function.
Rev. A.1, 10/99 Page- 5
It is, of course, possible to assign a different function to the additional lights. They can be made
to illuminate when any sort of external switch closes. Examples could include an installation
where lock status and door status are separately monitored. If it is desired that the pulsing
Sonalert not accompany the illumination of a yellow LED, it is a simple matter to disconnect the
+V line to the Sonalert's pulse input.
With this option, an alternate action keyswitch is mounted on the panel face with an LED
indicator to show its position. When the indicator is on, the panel is in the normal operating
mode. All the toggles function to release and secure the locks. When the keyswitch is turned,
the panel is bypassed. This means that all locks are immediately secured (if some had been
released from the toggles) and the toggles will no longer release any lock. If fail safe locks are
being used and the PB (emergency release) option has been supplied, the push button will also
not be able to release the locks. The purpose for this is allow a panel operator to leave the
panel for a time without the danger that an unauthorized person will release some of the locks.
There are 4 possible configurations for the switch bypass option. KP calls out a tubular Ace
type keyswitch. MK calls out a mortise cylinder type keyswitch wherein the user supplies the
cylinder and the unit is delivered with a hole for mounting the cylinder. Rear bracketry includes
the actual switch which is operated by the cylinder cam. This permits the user to key the panel
bypass keyswitch into his facility keying system. The KP1 and MK1 versions are for fail safe locks. When they are in the bypass position, power is sent to the locks in a manner that
bypasses the toggles and emergency release button (if one is present). The panel continues to
monitor the doors but power cannot be removed from the locks by the panel. The KP2 and MK2 versions are for fail secure locks. When they are in the bypass position, power is
removed from the panel boards so that the locks stay secure. With this approach, the panel
stops monitoring the locks as the boards have been unpowered. Note that for the fail secure
version, an emergency release button is not available.
Do not employ this option in a delayed exit installation with Securitron’s XDT board. It will not
work properly. See Section 5.3.
2.5 MOMENTARY SWITCHES (OPTION "MOM")
This option supplies spring loaded momentary toggle switches for lock control. The normal
position is lock secure. The switches are momentarily pressed to release the lock. Note that
when momentary switches are supplied, the yellow toggle bat LED indicator is eliminated due to
unavailability from the switch manufacturer. All other features of the panel are the same. Since
"toggle bat indicator on" annunciates the same condition as "bicolor off", the monitoring
performance of the panel is not lessened. Note that on a special order basis, momentary and
alternate switches can be mixed on the same panel.
2.6 HIGH VOLUME PUSH BUTTONS (OPTION "HT")
In “normal” use, toggle switches are appropriate for the LCP. They have the advantage of
showing their position by facing up (locked) or down (released). Toggles, however, are not
intended for high traffic use. Their typical operating life is roughly 30,000 cycles. This is well
adequate for most applications when the toggles are used occasionally but where the panel
switches are being continuously employed for letting people through doors (this is often a
momentary application), the “HT” option substitutes push button switches for the toggles. The
push button switches have many times the cyclic life of the toggles. They also include internal
indicators which operate just as the yellow bat indicators do on the toggles. The use of the “HT”
option does not change any panel wiring procedures and note that the option “MOM” can be
combined with the push button “HT” option to yield momentary operation rather than the
standard alternate action.
Rev. A.1, 10/99 Page- 6
3. BOARD TERMINAL DESCRIPTIONS
Refer to Figure 1 (Panel Board Overview) to see the terminal layout. This section describes the
function of each terminal and is intended for reference or to allow the installer to use the panel in
a novel way.
FIG. 1: PANEL BOARD OVERVIEW
ZONE 1
+V IN, ZONE 1
+1
+V IN ILLUMINATES GREEN INDICATOR
S1
+V IN, ZONE 2
+V IN, ZONE 3
+V IN, ZONE 4
DC NEG FROM POWER SUPPLY
+V FROM RESET (PREWIRED)
+V TO SONALERT (PREWIRED)
+V IN DRIVES YEL. LED #1 (AM OPTION)
+V IN DRIVES YEL. LED #2 (AM OPTION)
+V IN DRIVES YEL. LED #3 (AM OPTION)
+V IN DRIVES YEL. LED #4 (AM OPTION)
+V TO PULSING SON A LERT (PREWIRED)
+2
+3
+4
Y4
-
R
A
Y1
Y2
Y3
AY
ZONE 2
ZONE 3
ZONE 4
+V OUT WHEN RESPECTIVE SWITCH ON-
L1
CONNECT FAI L SAF E LOCK
+V OUT WHEN SWITCH OFF/FAIL SECURE LOCK
E1
+V IN SHUNTS VIOLATION (LEGAL RELEASE)
+V IN ILLUMINATES GREEN INDICATOR
S2
+V OUT WHEN RESPECTIVE SWITCH ON-
L2
CONNECT FAI L SAF E LOCK
+V OUT WHEN SWITCH OFF/FAIL SECURE LOCK
E2
+V IN SHUNTS VIOLATION (LEGAL RELEASE)
+V IN ILLUMINATES GREEN INDICATOR
S3
+V OUT WHEN RESPECTIVE SWITCH ON-
L3
CONNECT FAIL SAFE LOCK
+V OUT WHEN SWITCH OFF/FAIL SECURE LOCK
E3
+V IN SHUNTS VIOLATION (LEGAL RELEASE)
+V IN ILLUMINATES GREEN INDICATOR
S4
+V OUT WHEN RESPECTIVE SWITCH ON-
L4
CONNECT FAI L S AF E LOCK
+V OUT WHEN SWITCH OFF/FAIL SECURE LOCK
E4
+V IN SHUNTS VIOLATION (LEGAL RELEASE)
TERMINALS "+1, +2, +3, +4”: They constitute the +V inputs for zones 1, 2, 3, and 4. In most installations,
these four terminals wire directly to the +V output of the power supply and are therefore jumped together. The fact
that they are separate on the board, however, allows the use of upstream switches to individual zones.
TERMINAL "-”: This is the DC negative input for the board.
TERMINAL "R": This is the violation reset input. It is prewired through a momentary N.O. toggle reset switch.
When the Sonalert sounds, accompanied by a red indicator, the violation condition (lock not secure when it should
be) has occurred. Once the violation condition has been corrected, the Sonalert will continue to sound as this is a
latching condition. Pressing the reset toggle supplies +V into this terminal and the condition will reset. All R
terminals on all the board used in the panel are wired together. A single reset toggle serves to reset a violation on
any board in the entire panel.
TERMINAL "A": This prewired output supplies +V to drive the Sonalert when a violation condition has
occurred (after a 2 second delay). All A terminals from all panel boards are wired together so that any of them can
operate the single Sonalert.
Rev. A.1, 10/99 Page- 7
TERMINALS "Y1, Y2, Y3, Y4": These input terminals are only active if the AM option has been supplied.
With the option, a second (yellow) LED will be mounted adjacent to the standard bicolor. When the respective "Y"
terminal receives +V, the yellow LED will illuminate. This is used to annunciate any condition monitored from a dry
contact closure or voltage signal. Most commonly, the yellow LED annunciates the beginning of delayed exit for a
door but other purposes are possible.
TERMINAL "AY": This is a +V voltage output that is on when any Y terminal is on (illuminating the yellow
LED). It is active only when the AM option is supplied. It is prewired to drive a pulsing Sonalert so that when
any yellow LED illuminates, it will be annunciated with a distinctive sound. With multiple boards in a panel, all AY
terminals wire together with a single wire from any one going to the pulse Sonalert input. If the user wishes to
disable the AY audible alert, this single wire may be cut.
TERMINALS "S1, S2, S3, S4": These input terminals illuminate the green side of the respective zone
bicolor LED when they receive +V. They are connected to lock or door status output such that closed or +V =
secure for the zone. In the normal condition of the panel, the zones are secure, the bicolor LED's show green and
the S terminals receive +V.
TERMINALS "L1, L2, L3, L4": These terminals supply +V when the respective toggle switch is in the on
position (points toward the LED). They are connected to fail safe locks. If fail secure locks are employed, these
terminals are used only when status or remote release switches are present on the zone. The L terminals are used
to power the switch commons.
TERMINALS "E1, E2, E3, E4": These terminals are both an input and an output. When the respective
toggle switch is off (points away from the LED), the terminals supply +V to release a fail secure lock. At the same
time, the yellow indicator in the toggle switch bat illuminates (this annunciates "legal release" of the lock). Also the
violation condition of the zone is shunted. While the lock is legally released (toggle off; bicolor off; toggle bat yellow
LED on), the zone will not violate. As the lock status input (S terminals) reports insecure (since the lock has been
released), the green bicolor indicator will go off but the red side will not come on as would be the case if the
respective E terminal did not have +V on it.
As stated above, turning the toggle off puts +V on the E terminal. The same can be accomplished from a remote
switch. If, for instance, a remote release switch sends power to a fail secure lock, it will "legally" release. This will
input power to the E terminal as it is already connected to the lock. The yellow indicator in the toggle bat will light
up even though the toggle remains in the on position and the violation condition will be shunted.
Annunciating legal release and shunting zone violation is also accomplished with a fail safe lock. The fail safe lock
connects to the L terminal. A remote SPDT switch can legally release it. The common and NC contacts break
power to the fail safe lock, but the NO contact is wired back to the E terminal. When the fail safe lock is therefore
remotely released by this switch, the respective E terminal receives +V and the toggle bat indicator lights up
annunciating the condition and shunting the violation.
4. WIRING
4.1 POWER INPUT WIRING
The board requires a source of DC voltage which it distributes to the locks. +V from the power
supply is input to terminals +1, +2, +3 and +4. If the power supply you are using has a single
DC output, the +1 through +4 terminals should be jumped together. They are individually used if
the power supply has multiple breakered outputs or if you are employing upstream switches to
deactivate any of the panel zones. Negative voltage from the power supply is always input to
terminal “-”. Note that four wires are typically required to be run to each door unless
Securitron’s XDT board is being used in a delayed exit installation. Then six wires are required.
Figure 2, below, shows the hookup where you jump together the positive terminals (on the left)
and use of the positive terminals individually with a Securitron power supply that employs a CCS
Rev. A.1, 10/99 Page- 8
board. The CCS board provides multiple, current limited two Amp outputs on terminals marked
P1, P2 etc. The advantage of using these individual outputs as shown on the right of Figure 2 is
that any short circuit in the downstream wiring will take out only one of the breakers on the CCS
board and the rest of the installation will continue to operate. Use of a multiple output Securitron
power suppy materially increases the reliability of the installation and is therefore recommended.
Note however that you can always add in-line fuses or breakers to any single output power
supply to create the effect of the Securitron supply with CCS board.
FIG. 2: POWER SUPPLY TO LCP BOARD WIRING
SECURITRON POWER SUPPLY
WITH CCS BOARD PERM ITS
RED FLYING LEAD FROM
POWER
SUPPLY
IF POWER SUPPLY HAS SINGLE
DC OUTPUTS, THE "+" TERMINALS
MUST BE JUMPED TOGETHER AS
SHOWN.
RED FLYING LEAD FROM
RESET TOGGLE
INDIVIDUAL OPERATI ON OF "+"
TERMINA LS
P1P2P3P4R1
P5
RESET TOGGLE
+4
NOTE: IF PB OPTION IS SUPPLIE D , D C N EG
CONNECTS TO FLYING BLAC K LEAD RATHER
THAN TO CIRCUIT BOARD "-" TERMINALS
+3
+2+1
EACH "P" TERMINAL MAY OPER AT E ONE OR
MORE "+" TERMINALS DEPENDING ON THE
NUMBER OF ZONES IN THE PANEL.
+4+3+2+1
On both examples shown in Figure 2, note that there is a red flying lead from the underside of
the reset toggle. This wire simply supplies +V to the toggle common and then, when the spring
loaded toggle is pressed, +V is input to the “R” terminal of the board which is used to reset the
violation alarm function. The red flying lead requires constant +V so that the panel violation
alarm can always be reset. The reason why the factory doesn’t connect this wire is that when
individual breakered outputs or ‘upstream” switches are used to operate the “+” terminals on the
board (shown on the right of Figure 2), constant +V cannot be guaranteed to any “+” terminal.
Therefore, as Figure 2 shows, when you have only a single source of +V, connect the red flying
lead to any of the “+” terminals (they will all get constant power). When you can employ
individually breakered +V outputs (right side of Figure 2), connect one of the breakers
separately to the red flying lead in order to guarantee that it will always have power on it.
Supposing that you have to choose between putting two panel zones on one breakered “P”
output terminal or sharing a breakered “P” terminal between a panel zone and the red flying
lead, it is better to do the former. The panel user will expect to always be able to reset a
violation alarm even if one of the panel zones is de-powered from a short circuit or other
condition.
Note that often the number of panel zones exceeds the number of “P” terminals in the power
supply. Each “P” terminal can power multiple “+” input terminals so long as the current rating of
the “P” terminal is not exceeded. This in turn depends on the voltage and the type of lock being
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.