Armstrong World Industries HWC PREMIER 302, HWC PREMIER 123, HWC PREMIER 183, HWC PREMIER 243, HWC PREMIER 203 User Manual

...
0 (0)

Service Reference Manual

HWC Thru-the-Wall Units

Models:

HWC Premier 122, 182, 242, 302 123, 183, 243, 303

Copyright © 1998

Armstrong Air Conditioning Inc.

All rights reserved.

Disclaimer

This manual presents information and guidelines for proper installation, adjustment, operation and maintenance of Armstrong Magic-Pak HW/HWC Thru-the-Wall units. Read this manual before attempting assembly, installation, start-up, adjustment or operation of the unit. If you have any questions about the operation of the unit or a particular safety device, call or write Armstrong Air Conditioning Inc., 421 Monroe Street, Bellevue, Ohio USA 44811. Telephone: 419- 483-4840 Fax: 419-483-3557

The documentation and drawings contained in this manual are intended as a general guide, and may not reflect exactly the current designs, or all of the options available to our customers.

Please call or write Armstrong Air Conditioning Inc. regarding specific details of a particular furnace model, configuration or installation.

The information and specifications contained in this manual are subject to change without notice. Armstrong Air Conditioning Inc. reserves the right to change such specifications at any time without incurring obligation. Every effort has been made to ensure the accuracy of the information in this manual. For the most current information, please contact the Armstrong Customer Service Department.

This document is confidential. All information within is the sole property of Armstrong Air Conditioning Inc. and is loaned for mutual assistance. It may not be used for any purpose other than originally intended, without prior written consent of Armstrong. It is not intended for use by homeowners or as a guide for do-it-yourself projects. It provides specialized information for use by qualified service personnel, who have the proper equipment, training and experience necessary to safely install, repair, adjust and maintain the Magic-Pak units and components described within.

SRM-HW/HWC 8/99

 

Service Reference Manual

TABLE OF CONTENTS

 

 

 

 

TABLE OF CONTENTS

 

 

 

 

 

 

1

- Specifications

 

 

 

2

- Sequence of Operations

 

 

 

3

- Unit Tear Down

 

 

 

4

- Component Location Illustrations

 

 

 

5

- Unit Components

 

 

 

6

- Installation

 

 

 

7

- Accessories

 

 

 

8

- Parts Lists

 

 

 

9

- Troubleshooting/Performance/

 

 

 

 

Charge Weights

 

 

Go to:

If you need information on:

 

 

 

 

 

 

 

Section 1

Performance, electrical data and cabinet dimensions.

 

 

Section 2

Sequence of operation descriptions with accompanying schematics.

 

 

Section 3

Complete description of unit disassembly.

 

 

Section 4

Locations of major components of HW/HWC models.

 

 

Section 5

Illustrations and specifications for individual components including valves,

 

 

 

blowers, ignition controls and blower control boards.

 

 

Section 6

Installation requirements and startup guidelines.

 

 

Section 7

Complete listing of all Armstrong accessories available, including wall

 

 

 

sleeves, louvers and gas conversion kits.

 

 

Section 8

Complete service parts lists for all HW and HWC models.

 

 

Section 9

System check and troubleshooting procedures.

 

SRM-HW/HWC 8/99

Service Reference Manual

SPECIFICATIONS

1-1

Section 1 - Specifications

Models Covered By This Manual ............

1-2

Model Number Guide ............................

1-2

Product Serial Numbers

 

(Beginning 1993) .................................

1-2

Summary of Model Revisions/Variations 1-3

Heating Configuration Table ........................

1-3

Cooling Configuration Table .........................

1-3

HW/HWC ............................................

1-4

Physical and Electrical ................................

1-4

Performance Ratings ..................................

1-4

Blower Performance ...................................

1-6

Dimensions ................................................

1-6

Wall Sleeve................................................

1-7

SRM-HW/HWC 8/99

SPECIFICATIONS

Magic-Pak: HW/HWC

1-2

Models Covered By This Manual

HWC Gas Heating/Electric Cooling Units

HW122, 123

HW182,183

HW242, 243

HW302, 303

HW Gas Heating Only Units

26HW

38HW

51HW

64HW

Model Number Guide

HW/HWC Models

26 H W C 12 2 -- 2A

 

 

26 = Rated Input BTU/Hr x 1000

H = Gas Heat

W = Thru-the-Wall

C = Cooling

12 = Nominal Cooling BTU/Hr x 1000

2 = Cooling Efficiency 2 - 9.7 SEER

2A = Revision Code

Product Serial Numbers, Beginning 1993

84

95

A

12345

84 = Armstrong Factory Number

95 = Year (ex: 1995)

A = Month (see list below)

12345 = Sequential Number

A = Jan

B = Feb

C = Mar

D = Apr

E = May

F = June

G = July

H = Aug

J = Sept

K = Oct

L = Nov

M = Dec

HW/HWC-SRM

8/99

Service Reference Manual

SPECIFICATIONS

1-3

Summary of Model Revisions/Variations

Table 1-1 Heating Configurations of HW/HWC Units

Model

Configuration

AFUE

Ignition/Blower Control

Ignition

Type

 

 

 

 

 

 

 

 

 

(All) HWC (123, 183, 243, 303) -1

Gas Heat/

80

UTech Combination Ignition/Blower Control 1097

DSI

Electric Cool

 

 

 

 

 

 

 

 

 

(All) HW -9

Gas Heat Only

80

UTech Combination Ignition/Blower Control 1097

DSI

 

 

 

 

 

(All) HWC (122, 182, 242, 302)

Gas Heat/

 

Ignition Control: Fenwal Triton 2461D

 

80

Blower Control: Heatcraft IBCH4C401,

DSI

-11, -10, -9, -8, -7, -6, -5

Electric Cool

 

Tridelta 920B0048 or UTech 1010

 

 

 

 

 

 

 

 

 

 

(All) HWC (122, 182, 242, 302)

Gas Heat/

 

Ignition Control: Fenwal 05-29

 

80

Blower Control: Heatcraft IBCH4C401,

DSI

-4, -3, -2, -1

Electric Cool

 

Tridelta 920B0048 or UTech 1010

 

 

 

 

 

 

 

 

 

 

Table 1-2 Cooling Configurations of HWC Units

Model

Configuration

Tonnage

SEER

Compressor Type*

Metering Device

 

 

 

 

 

 

(All) HWC 123-1

Gas Heat/Electric Cool

1

9.7

Tecumseh Rotary

Capillary Tube/Filter Drier

 

 

 

 

 

 

(All) HWC183-1

Gas Heat/Electric Cool

1.5

9.7

Tecumseh

Capillary Tube/Filter Drier

Reciprocating

 

 

 

 

 

 

 

 

 

 

 

(All) HWC 243-1

Gas Heat/Electric Cool

2

9.7

Copeland Scroll

Capillary Tube/Filter Drier

 

 

 

 

 

 

(All) HWC 303-1

Gas HeatElectric Cool

2.5

9.7

Copeland Scroll

Capillary Tube/Filter Drier

 

 

 

 

 

 

(All) HWC 182-11, -

Gas Heat/Electric Cool

1.5

9.7

Tecumseh

Capillary Tube/Filter Drier

9, -7, -6

Reciprocating

 

 

 

 

 

 

 

 

 

 

(All) HWC 242-11, -9

Gas Heat/Electric Cool

2

9.7

Copeland Scroll

Capillary Tube/Filter Drier

 

 

 

 

 

 

(All) HWC 122-10, -

Gas Heat/Electric Cool

1

9.7

Tecumseh Rotary

Capillary Tube/Filter Drier

8, -5, -4, -3, -1

 

 

 

 

 

 

 

 

 

 

 

(All) HWC 242-10, -

Gas Heat/Electric Cool

2

9.7

Copeland Scroll

Capillary Tube/Filter Drier

8, -5, -4, -3, -1

 

 

 

 

 

 

 

 

 

 

 

(All) HWC 302-9

Gas Heat/Electric Cool

2.5

9.5

Copeland Scroll

Capillary Tube/Filter Drier

 

 

 

 

 

 

(All) HWC 182-8, -5,

Gas Heat/Electric Cool

1.5

9.7

Tecumseh Rotary

Capillary Tube/Filter Drier

-4, -3, -2

 

 

 

 

 

 

 

 

 

 

 

(All) HWC 302-8, -5,

Gas Heat/Electric Cool

2.5

9.5

Copeland Scroll

Capillary Tube/Filter Drier

-4, -3, -1

 

 

 

 

 

 

 

 

 

 

 

(All) HWC 182-1

Gas Heat/Electric Cool

1.5

9.5

Copeland Scroll

Capillary Tube/Filter Drier

 

 

 

 

 

 

* For more information on the compressors used in HWC units, see the Unit Components section, beginning on page 5-28.

SRM-HW/HWC 8/99

SPECIFICATIONS

Magic-Pak: HW/HWC

1-4

HW/HWC

Physical and Electrical

Table 1-3

Physical and Electrical Specifications - HWC Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max.

Comp.

Comp.

O.D.

 

Outside

 

Indoor

 

 

 

 

 

Normal

Min.

 

Fan

 

Wheel

Blower

Refrig.

 

 

Voltage/

Fuse/HACR

Rated

Locked

Fan

Nom.

Rated

Weight

Model

Voltage

Circuit

Rated

dia. x

Rated

Charge

Hz/Phase

Brkr.

Load

Rotor

Dia.

RPM

HP

(lbs.)

 

Range

Ampacity

Load

width

HP

(oz.)

 

 

(amps)

(amps)

(amps)

(in.)

 

 

 

 

 

 

 

 

(amps)

 

(in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26HWC122/123

208-230/60/1

197-253

8.3

15

5.0

26.3

18

1075

0.9

1/8

10 X 4

1/6

42

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38HWC122/123

208-230/60/1

197-253

8.3

15

5.0

26.3

18

1075

0.9

1/8

10 X 4

1/6

42

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38HWC182/183

208-230/60/1

197-253

13.6

20

8.3

45.0

18

1075

0.9

1/8

10 X 4

1/3

56

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51HWC182/183

208-230/60/1

197-253

13.6

20

8.3

45.0

18

1075

0.9

1/8

10 X 4

1/3

56

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64HWC182/183

208-230/60/1

197-253

13.6

20

8.3

45.0

18

1075

0.9

1/8

10 X 4

1/3

56

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36HWC242/243

208-230/60/1

197-253

18.6

25

11.6

62.5

18

1075

1.8

1/4

10 X 4

1/3

58

360

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51HWC242/243

208-230/60/1

197-253

18.6

25

11.6

62.5

18

1075

1.8

1/4

10 X 4

1/3

58

360

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64HWC242/243

208-230/60/1

197-253

18.6

25

11.6

62.5

18

1075

1.8

1/4

10 X 4

1/3

58

360

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51HWC302

208-230/60/1

197-253

22.4

30

14.6

76.0

18

1075

1.8

1/4

10 X 4

1/3

59

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64HWC302

208-230/60/1

197-253

22.4

30

14.6

76.0

18

1075

1.8

1/4

10 X 4

1/3

59

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51HWC303

208-230/60/1

197-253

21.9

30

14.1

73.0

18

1075

1.8

1/4

10 X 4

1/3

59

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64HWC303

208-230/60/1

197-253

21.9

30

14.1

73.0

18

1075

1.8

1/4

10 X 4

1/3

59

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance Ratings

Table 1-4

Performance Ratings - HWC122/123

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

95°

 

 

 

 

105°

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

 

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Air

 

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Wet

 

Watts

Watts

Watts

Watts

Vol.

 

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Bulb

 

Input

Input

Input

Input

(CFM)

 

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

12600

820

.78

.92

1.00

12000

910

.80

.95

1.00

11400

1000

.82

.95

1.00

10800

1090

.85

1.00

1.00

63°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450

 

12800

820

.82

.97

1.00

12200

910

.85

1.00

1.00

11600

1000

.87

1.00

1.00

11000

1090

.90

1.00

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

13100

820

.87

1.00

1.00

12400

910

.90

1.00

1.00

11800

1000

.92

1.00

1.00

11200

1090

.95

1.00

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

13400

820

.59

.74

.89

12700

910

.60

.76

.91

12100

1010

.62

.79

1.00

11500

1110

.63

.81

.96

67°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450

 

13600

820

.62

.78

.94

12900

910

.64

.80

.97

12300

1010

.65

.83

1.00

11700

1110

.67

.86

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

13900

820

.65

.82

.99

13200

910

.67

.84

1.00

12600

1010

.69

.88

1.00

11900

1110

.70

.91

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

14200

830

.40

.56

.72

13500

920

.40

.57

.74

12800

1020

.41

.58

.76

12100

1120

.41

.59

.78

71°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

450

 

14400

830

.42

.59

.76

13700

920

.42

.60

.78

13000

1020

.43

.62

.80

12300

1120

.43

.63

.82

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

14700

830

.44

.62

.80

14000

920

.44

.63

.82

13300

1020

.45

.65

.84

12600

1120

.45

.66

.87

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: All values are gross capacities and do not include blower motor heat deduction.

HW/HWC-SRM

8/99

SRM-HW/HWC 8/99

Service Reference Manual

SPECIFICATIONS

1-5

Performance Ratings (continued)

Table 1-5

Performance Ratings - HWC182/183

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

95°

 

 

 

 

105°

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

 

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Air

 

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Wet

 

Watts

Watts

Watts

Watts

Vol.

 

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Bulb

 

Input

Input

Input

Input

(CFM)

 

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

 

18400

1370

.75

.90

1.00

17100

1470

.78

.92

1.00

15700

1550

.82

.96

1.00

14400

1640

.86

.96

1.00

63°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

18700

1380

.78

.93

1.00

17400

1480

.81

.96

1.00

16000

1560

.85

1.00

1.00

14600

1650

.89

1.00

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650

 

18900

1390

.81

.96

1.00

17600

1490

.84

.99

1.00

16200

1570

.88

1.00

1.00

14800

1660

.92

1.00

1.00

 

550

 

19800

1410

.58

.72

.87

18500

1510

.59

.74

.89

17100

1600

.62

.78

.94

15600

1700

.64

.80

.96

67°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

20100

1420

.60

.75

.90

18800

1520

.62

.77

.93

17400

1610

.64

.81

.98

15900

1710

.66

.83

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650

 

20400

1430

.62

.78

.93

19000

1530

.64

.80

.96

17600

1620

.66

.84

1.00

16100

1720

.68

.86

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

 

21200

1450

.40

.55

.69

19700

1550

.40

.56

.72

18300

1650

.41

.58

.75

16700

1750

.41

.60

.78

71°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600

 

21500

1460

.42

.57

.72

20000

1560

.42

.59

.75

18600

1660

.43

.61

.78

17000

1760

.43

.62

.81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

650

 

21800

1470

.43

.59

.74

20300

1570

.43

.60

.78

18800

1670

.44

.63

.81

17200

1770

.44

.64

.84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: All values are gross capacities and do not include blower motor heat deduction.

Table 1-6

Performance Ratings - HWC242/243

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

95°

 

 

 

 

105°

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

 

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Air

 

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Wet

 

Watts

Watts

Watts

Watts

Vol.

 

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Bulb

 

Input

Input

Input

Input

(CFM)

 

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

 

24300

1870

.74

.88

1.00

23200

2110

.76

.89

1.00

21800

2380

.78

.94

1.00

21000

2710

.80

.95

1.00

63°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800

 

24700

1870

.78

.93

1.00

23600

2110

.80

.94

1.00

22200

2380

.82

.99

1.00

21300

2710

.84

1.00

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

900

 

25200

1880

.82

.98

1.00

24100

2120

.85

.99

1.00

22600

2390

.87

1.00

1.00

21700

2720

.89

1.00

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

 

25900

1890

.57

.71

.85

24700

2130

.58

.72

.86

23600

2400

.59

.75

.91

22400

2750

.60

.76

.92

67°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800

 

26300

1890

.60

.75

.90

25100

2130

.61

.76

.91

24000

2400

.62

.79

.96

22800

2750

.63

.80

.97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

900

 

26800

1900

.63

.79

.95

25600

2140

.64

.80

.96

24500

2410

.66

.84

1.00

23200

2760

.67

.85

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

700

 

27300

1910

.40

.55

.69

26100

2150

.40

.55

.70

24900

2430

.40

.56

.72

23700

2770

.40

.57

.74

71°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800

 

27700

1910

.42

.58

.73

26500

2150

.42

.58

.74

25300

2430

.42

.59

.76

24100

2770

.42

.60

.78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

900

 

28300

1920

.44

.61

.77

27000

2160

.44

.61

.78

25800

2440

.44

.62

.80

24600

2780

.44

.63

.82

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: All values are gross capacities and do not include blower motor heat deduction.

Table 1-7

Performance Ratings - HWC302/303

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Entering Outdoor Coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

95°

 

 

 

 

105°

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter.

Total

 

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Total

Comp.

S/T at

S/T at

S/T at

Air

 

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Cooling

75°

80°

85°

Wet

 

Watts

Watts

Watts

Watts

Vol.

 

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Capacity

Dry

Dry

Dry

Bulb

 

Input

Input

Input

Input

(CFM)

 

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

(Btuh)

Bulb

Bulb

Bulb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

775

 

28500

2150

.72

.84

.97

27300

2390

.73

.87

1.00

26100

2670

.74

.89

1.00

24800

2990

.76

.90

1.00

63°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

850

 

28900

2160

.74

.87

1.00

27600

2400

.76

.90

1.00

26400

2680

.77

.93

1.00

25100

3000

79

.93

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

925

 

29300

2170

.77

.90

1.00

28000

2410

.79

.93

1.00

26800

2690

.80

.96

1.00

25400

3010

.82

.96

1.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

775

 

30400

2190

.56

.69

.82

29000

2440

.57

.71

.84

27800

2720

.58

.73

.88

26400

3050

.59

.73

.88

67°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

850

 

30800

2200

.58

.71

.85

29400

2450

.59

.73

.87

28100

2730

.60

.75

.91

26700

3060

.61

.76

.91

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

925

 

31200

2210

.60

.73

.87

29800

2460

.61

.76

.90

28500

2740

.62

.78

.94

27100

3070

.63

.79

.94

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

775

 

32200

2220

.40

.54

.68

30800

2480

.41

.55

.69

29300

2760

.41

.56

.71

28000

3090

.42

.57

.73

71°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

850

 

32600

2230

.41

.56

.70

31200

2490

.42

.57

.71

29700

2770

.42

.58

.73

28300

3100

.43

.59

.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

925

 

33000

2240

.42

.57

.72

31600

2500

.43

.58

.73

30100

2780

.43

.60

.76

28700

3110

.45

.61

.78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: All values are gross capacities and do not include blower motor heat deduction.

 

 

SPECIFICATIONS

 

 

 

Magic-Pak: HW/HWC

1-6

 

 

 

 

Blower Performance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1-8 Blower Performance - HWC Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Blower Speed

 

 

CFM @ ext. static pressure - in. w.c. with filter(s)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

0.3

0.4

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi

 

650

 

615

575

 

540

 

 

 

HWC122/123

 

 

 

 

 

 

 

 

 

 

 

Med

 

475

 

450

425

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

415

 

405

390

 

380

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi

 

875

 

825

775

 

725

 

 

 

HWC182,242,302

 

 

 

 

 

 

 

 

 

 

 

Med

 

850

 

805

760

 

710

 

 

 

HWC183,243,303

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

630

 

605

575

 

550

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (all measurements in inches)

SUPPLY AIR DUCT CONNECTION

8" x 16" LOW VOLTAGE THERMOSTAT CONNECTIONS

 

HIGH VOLTAGE

¾" DUCT CONNECTION FLANGE

JUNCTION BOX

4" x 4" x 2"

GAS LINE

CONNECTION

Measurements from Side and Top to Center of Vent Outlet

41 2"

634"

" /8 1

43

27

7

 

/8"

RETURN AIR OPENING ON BOTTOM 6" x 22"

"

7/16 29

HW/HWC-SRM

8/99

Service Reference Manual

SPECIFICATIONS

1-7

Dimensions (cont.)

 

1

 

1

133/8

 

16

8

 

 

Supply

 

 

Line Voltage

 

 

 

Box

Low

 

 

 

 

 

 

 

 

Voltage

 

43 1/8

 

 

 

 

 

Supply

8

 

 

 

 

2 7/8 4

 

 

 

½ Gas Inlet

1 3/4

 

 

 

 

3

Return

 

 

 

 

 

 

2

/

 

 

 

 

 

 

 

22

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27 7/8

 

 

 

 

 

 

 

 

 

 

 

 

29 7/16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall Sleeve (all measurements in inches)

1 or 3 3 4

15 or 1214

2

16

45

2

29

12 1 2"

Flanges may be assembled

1" or 33 4" from this side of the sleeve

SRM-HW/HWC 8/99

SRM-HW/HWC 2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-1

Section 2 - Sequence of Operation

HWC123,183,243,303 ........................

2-4

Simplified Sequence ........................................

2-5

Detailed Sequence ..........................................

2-6

POWER ......................................................................

2-6

CALL FOR HEAT ........................................................

2-6

LIMIT/ROLLOUT OPENS ...........................................

2-7

PRESSURE SWITCH OPENS (BLOCKED FLUE) .....

2-7

FAILED FLAME SENSE/TRIAL FOR IGNITION .........

2-8

CALL FOR COOLING .................................................

2-8

FAN ON.......................................................................

2-9

HW (Heating Only)

(w/UTEC 1097 Spark Ignition System) 2-10

Simplified Sequence ......................................

2-11

Detailed Sequence ........................................

2-12

POWER ....................................................................

2-12

CALL FOR HEAT ......................................................

2-12

LIMIT/ROLLOUT OPENS .........................................

2-13

PRESSURE SWITCH OPENS (BLOCKED FLUE) ...

2-13

FAILED FLAME SENSE/TRIAL FOR IGNITION .......

2-14

FAN ON.....................................................................

2-14

HWC122,182,242,302

(w/Fenwal 2461D Ignition Control) ..... 2-16

Simplified Sequence ......................................

2-17

Detailed Sequence ........................................

2-18

POWER ....................................................................

2-18

CALL FOR HEAT ......................................................

2-18

LIMIT OPENS ...........................................................

2-19

PRESSURE SWITCH OPENS (BLOCKED FLUE) ...

2-19

ROLLOUT SWITCH ACTIVATED..............................

2-19

CALL FOR COOLING ...............................................

2-19

FAN ON.....................................................................

2-20

HW (Heating Only)

(w/Fenwal 2461D Ignition Control) ..... 2-22

Simplified Sequence ......................................

2-23

Detailed Sequence ........................................

2-24

POWER ....................................................................

2-24

CALL FOR HEAT ......................................................

2-24

LIMIT OPENS ...........................................................

2-25

PRESSURE SWITCH OPENS (BLOCKED FLUE) ...

2-25

ROLLOUT SWITCH ACTIVATED..............................

2-25

SPECIFICATIONS

Magic-Pak: HW/HWC

2-2

HWC122,182,242,302

 

(w/Fenwal 05-29 Ignition Control) .......

2-26

Simplified Sequence ......................................

2-27

Detailed Sequence ........................................

2-28

POWER ....................................................................

2-28

CALL FOR HEAT ......................................................

2-28

FLAME SENSE .........................................................

2-29

LIMIT OPENS ...........................................................

2-29

ROLLOUT SWITCH ACTIVATED..............................

2-29

CALL FOR COOLING ...............................................

2-29

FAN ON.....................................................................

2-30

HW (Heating Only)

 

(w/Fenwal 05-29 Ignition Control) .......

2-32

Simplified Sequence ......................................

2-33

Detailed Sequence ........................................

2-34

POWER ....................................................................

2-34

CALL FOR HEAT ......................................................

2-34

FLAME SENSE .........................................................

2-35

LIMIT OPENS ...........................................................

2-35

ROLLOUT SWITCH ACTIVATED..............................

2-35

HWC123,183,243,303

 

w/Low Ambient Control ......................

2-36

HWC122,182,242,302

 

w/Low Ambient Control ......................

2-38

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-3

BLANK PAGE

SRM-HW/HWC 2/99

Armstrong World Industries HWC PREMIER 302, HWC PREMIER 123, HWC PREMIER 183, HWC PREMIER 243, HWC PREMIER 203 User Manual

SPECIFICATIONS

Magic-Pak: HW/HWC

2-4

HWC123, 183, 243, 303

(w/United Technologies 1097 Spark Ignition System)

 

 

 

 

 

 

 

 

CONNECTION DIAGRAM

 

 

 

CIRCUITS ENERGIZED

208/230-1-60

COPPER CONDUCTORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING MODE

CIRCUIT

POWER SUPPLY

 

ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

 

R-W

}

 

 

 

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING

R-G-Y

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

 

R-G

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

LINE VOLTAGE-FACTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE VOLTAGE-FACTORY WHEN USED

 

 

BLACK

 

GREEN RED

WHITE

2

CY

BLACK L1

 

COOL

UNUSED HEAT

 

 

 

 

 

 

LINE VOLTAGE-FIELD

 

 

 

 

COMBUSTION

 

 

CMB

 

 

 

 

 

 

 

ELECTRODE

 

 

 

LOW VOLTAGE-FACTORY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW VOLTAGE-FIELD

 

 

 

 

BLOWER

 

 

1

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

G

 

BLACK

BLACK

BLACK BLACK

PRESSURE SWITCH

 

 

3

RGW

 

 

 

 

 

24VAC

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

Y

 

Y

 

 

 

 

 

 

 

4

 

 

 

IGNITION

 

 

WHT

 

 

W

 

W }

 

 

 

 

 

 

 

5

 

 

CONTROL

 

FLAME ROD

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

4

5 6

GND

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS

 

 

 

 

 

 

 

 

 

 

IF ANY OF THE ORIGINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRES ARE REPLACED, THE

 

 

 

 

VALVE BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

 

 

 

 

 

GREEN

 

 

 

SAME SIZE AND TYPE WIRE

 

 

 

 

 

 

 

 

 

ORN

 

 

 

BLUE

YELLOW

RED

MUST BE USED.

 

 

 

 

 

ORN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUTO RESET

MANUAL RESET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT SWITCH

LIMIT SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORN

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

CONNECTOR BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

RED

 

 

 

 

 

CAPACITOR-RUN

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVAP. MOTOR SPEED CONNECTIONS

 

 

BROWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODELS

HEATING

COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

 

FAN

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

26HWC123

LOW (RED)

MED (BLUE)

 

 

 

 

 

 

 

208 V

 

 

 

 

 

 

COM

HERM

YELLOW

 

C

 

 

 

 

 

 

 

240 V

 

 

 

38HWC123

HIGH(BLACK) MED (BLUE)

S

COMP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

38HWC183

LOW (RED)

LOW (RED)*

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

CONTACTOR

 

 

 

 

51HWC183

MED (BLUE)

LOW (RED)

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

64HWC183

HIGH(BLACK) LOW (RED)

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEE CHART

 

 

 

 

 

T1

 

 

 

L1

 

 

 

38HWC243

LOW (RED)

MED (BLUE)

D

 

 

FOR WIRING

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

51HWC243

MED (BLUE)

MED (BLUE)*

 

 

 

 

CONTROL

 

 

 

T2

 

 

 

L2

 

 

 

64HWC243

HIGH(BLACK) MED (BLUE)

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

51HWC303

MED (BLUE)

HIGH(BLACK)

 

YELLOW

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

64HWC303

HIGH(BLACK) HIGH(BLACK)*

 

 

BLOWER

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BROWN

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

*JUMPER REQUIRED

 

 

MOTOR

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITOR

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#45004-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAGNOSTICS

 

 

 

 

 

 

The following blower/ignition control board

 

 

 

LED codes will indicate normal or abnormal

 

 

 

operations:

 

 

 

 

SLOW FLASH

Normal Operation, No

 

 

 

 

Call for Heat

Note: On units that are equipped with a low ambient switch (designated

FAST FLASH

Normal Operation, Call for

with an “SA” in the model number), sequence of operation during

 

Heat

2 FLASH

System Lockout - Failed to

cooling call is modified when outdoor temperatures fall below the

 

Detect or Sustain Flame

normal operating range. For more information on the low ambient

3 FLASH

Pressure Switch Open or

switch equipped version of this unit, see the section beginning on

 

Closed

page 2-36.

4 FLASH

High Limit or Rollout

 

 

 

 

Switch Open

 

 

 

5 FLASH

Flame Sensed and Gas

 

 

 

 

Valve Not Energized

 

 

 

STEADY

Internal Failure

 

 

 

 

(Micro-controller Failure;

 

 

 

 

Self-check)

FIGURE 2-1 Connection Diagram

 

 

 

 

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-5

Simplified Sequence - HWC123,183, 243, 303

Refer to Figure 2-1

208/230V power is supplied to the junction box on top of the unit

24V power is supplied from the unit transformer to the thermostat

CALL FOR HEAT

1.The thermostat closes the R-W circuit, sending a 24-volt signal to the unit.

2.The 24-volt signal energizes the combustion blower, causing the pressure switch to close.

3.The combustion blower runs for 30 seconds as a pre-purge to trial for ignition.

4.The ignition control energizes the spark ignition and opens the gas valve, causing the burners to light. When the gas valve energizes, a 30-second circulating air blower “on” delay begins.

5.Flame sense is sent to the ignition control through the flame sensor and flame sense wire.

6.After the 30-second delay, the circulating air blower energizes and runs until the heat call is satisfied.

7.When the heat call is satisfied, the gas valve deenergizes. This shuts down the burners.

8.A 5-second combustion blower post-purge delay and a 120-second circulating air blower “off” delay start.

9.After the delay times elapse, the combustion blower and the circulating air blower stop.

FLAME SENSE

1.After the burners have been lit, the ignition control starts a 10-second trial for ignition delay.

2.If after 10 seconds a flame has not been sensed by the ignition control, the ignition control de-energizes the gas valve and the spark ignitor.

3.The unit initiates three trials for ignition (flame sense) before system lockout.

4.System lockout lasts 60 minutes or until power is reset to unit (whichever comes first).

CALL FOR COOLING

1.The thermostat energizes the R, Y and G circuit, sending a 24-volt signal to the cooling contactor and the ignition control to start the cooling sequence.

2.The contactor closes immediately, causing the compressor and the condenser fan to run.

3.The 24-volt Y signal starts a 5-second circulating air blower “on” delay.

4.After 5 seconds, the circulating air blower starts and runs until the R, Y and G circuit is interrupted by the thermostat.

5.When the R, Y and G circuit is interrupted, the cooling contactor immediately de-energizes. This causes the compressor and the condenser fan to stop.

6.The ignition control starts a 90-second circulating air blower “off” delay.

7.After 90 seconds, the circulating air blower stops.

FAN ON

1.The thermostat energizes the R-G circuit, causing the circulating air blower to energize in cooling speed.

2.The circulating air blower remains running in cooling speed until the thermostat is switched to the “AUTO” position.

SRM-HW/HWC 2/99

Detailed Sequence follows

SPECIFICATIONS

Magic-Pak: HW/HWC

2-6

Detailed Sequence - HWC123, 183, 243, 303

Refer to Figure 2-1

POWER

Line Voltage

With the unit at rest (no call from the thermostat), line voltage will be present:

L1 Power

1.Through the L1 black lead to the L1 terminal on the ignition control

2.At the L1 contactor terminal

3.At the transformer terminal marked 208-240V

L2 Power

1.Through the L2 black lead to the induced draft blower

2.At the L2 contactor terminal

3.A transformer common terminal

4.At the T2 contactor terminal

5.At the R terminal of the compressor

6.At the capacitor common terminals

Low Voltage (24 VAC)

With the unit at rest (no call from the thermostat), 24 volts A/C will be present:

1.From the transformer 24V terminal to pin 4 of the 6-pin chassis low voltage harness

2.From pin 4 of the chassis low voltage harness to the

24VAC hot terminal on the ignition control

3.From the 24VAC hot terminal to pin 5 of the 5-pin thermostat harness (internal to board)

4.From the 24VAC hot terminal also to pin 6 of the 6- pin ignition wire harness

5.From pin 6 of the ignition wire harness through the auto reset limit switch and the manual reset rollout switch to pin 1 of the 6-pin ignition wire harness

Note: While the unit is at rest, the green LED shows consistent slow flash. This indicates normal operation - system at rest (standby mode).

CALL FOR HEAT

Line Voltage

The ignition control receives a signal from the R-W circuit indicating a call for heat.

1.The combustion blower relay energizes, sending L1 power to CMB BLWR terminal on the ignition

control. This causes the combustion blower to start by completing the line voltage circuit through the L2 wire connection in the unit.

2.As the 24-volt signal is sent to pin 4 of the 6-pin ignition wire harness by the ignition control, a 30second circulating air blower “on” delay starts. After the delay, the ignition control energizes the heat speed blower relay. This sends L1 power to the

ACB HEAT terminal on the ignition control.

3.L1 power is then sent to the circulating air blower terminal block where it is connected to the blower motor. The circulating air blower starts by completing the L1-L2 circuit through the L2 connection at the blower motor capacitor.

4.The combustion blower and the circulating air blower continue to run until the R-W circuit is interrupted. After a 5-second post-purge delay, the

CMB BLWR terminal on the ignition control deenergizes. This interrupts L1 power to the combustion blower. After a 120-second circulating air blower “off” delay, the ACB HEAT terminal deenergizes. This interrupts L1 to the circulating air blower. As L1 power is interrupted, the blowers shut off.

Low Voltage

1.A call for heat closes the R-W circuit, sending a 24volt signal to the low voltage white wire in the unit.

2.The 24-volt signal is received at pin 3 of the 5-pin thermostat harness on the ignition control.

3.The 24-volt signal causes the combustion blower relay to close, causing the combustion blower to run. At this time, a 24-volt signal is also sent out through pin 2 of the 6-pin ignition wire harness.

4.The 24-volt signal from pin 2 of the 6-pin ignition wire harness energizes one side of the Normally Open pressure switch. As the induced draft blower reaches full speed, the pressure switch closes and a 24-volt signal is sent to pin 5 of the 6- pin ignition wire harness.

5.When the 24-volt signal is received at pin 5 of the 6- pin ignition wire harness, the ignition control starts a 30-second pre-purge delay.

6.After the 30-second pre-purge, the ignition control initiates a trial for ignition. The spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness energize simultaneously.

7.When the 24-volt signal is present at pin 4 of the 6- pin ignition wire harness, the ignition control starts a 30-second circulating air blower “on” delay.

8.The 24-volt signal from pin 4 of the 6-pin ignition wire harness is received at the gas valve, causing it to open and the burners to ignite.

HW/HWC-SRM

2/99

SRM-HW/HWC 2/99

Service Reference Manual

9.After 30-second “on” delay, the circulating air blower relay energizes the heat terminal and the circulating air blower is energized.

10.The unit will continue to operate normally until the R-W circuit is interrupted.

11.When the heat call is satisfied, the thermostat will interrupt the R-W circuit. This causes the 24-volt signal to the white wire in the unit to be de-ener- gized.

12.The gas valve closes immediately as 24V through pin 4 of the 6-pin ignition wire harness is deenergized by the ignition control.

13.The ignition control initiates a 120-second circulating air blower “off” delay and 5-second combustion blower post-purge delay.

14.After 5 seconds, the combustion blower shuts off.

15.After 120 seconds, the circulating air blower shuts off and the system returns to standby mode.

Note: During a call for heat, the green LED shows consistent fast flash (as long as the R-W circuit is closed). When the R-W circuit is interrupted (indicating the heat call has been satisfied), the green LED returns to a consistent slow flash.

LIMIT/ROLLOUT OPENS

In all modes of operation, 24VAC is supplied to the ignition control 24VAC hot terminal and is passed through the ignition control to pin 6 of the 6-pin ignition wire harness.

1.A 24-volt signal is sent from pin 6 of the 6-pin ignition wire harness to one side of the Normally Closed manual reset rollout switch, across the rollout switch to one side of the Normally Closed auto reset limit switch and across the limit switch to pin 1 of the 6-pin ignition wire harness.

2.This circuit energizes whenever line voltage power is supplied to the unit.

3.If the circuit is interrupted by either switch opening, the 24-volt signal to pin 1 of the 6-pin ignition wire harness de-energizes.

4.This causes the combustion blower relay to energize, sending L1 power to the CMB BLWR terminal on the ignition control. It also causes the circulating air blower heat speed relay to energize, sending L1 power to the ACB HEAT terminal on the ignition control. This causes both blowers to start immediately.

5.The ignition control lockouts the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness until the 24-volt signal is restored at pin 1 of the 6-pin ignition wire harness.

6.The circulating air blower and the combustion blower are energized until the 24-volt signal is restored at pin 1 of the 6-pin ignition wire harness.

SEQUENCE OF OPERATIONS

2-7

7.The green ignition control LED shows a 4 flash fault code (indicating limit switch/rollout switch open).

8.When the 24-volt signal is restored at pin 1 of the 6- pin ignition wire harness, the ignition control starts a 5-second combustion blower post-purge delay and a 120-second circulating air blower “off” delay.

9.Once the delays have timed out, both blowers stop and the green LED flashes a consistent slow flash if no heat call is present. (A consistent fast flash appears if there is a call for heat.)

Note: The limit switch resets automatically when temperatures are acceptable, but the rollout switch must be manually reset by pushing in on the small button on top of the switch.

The reason why the switches opened must be determined before any corrective action is taken.

PRESSURE SWITCH OPENS (BLOCKED FLUE)

When the R-W circuit is energized, a 24-volt signal is sent to the ignition control. This starts the call for heat.

1.The 24-volt signal from the R-W circuit energizes the combustion blower relay, sending L1 power to the CMB BLWR terminal on the ignition control. This starts the ignition control.

2.At the same time the combustion blower relay energizes, the 24-volt signal is sent to pin 2 of the 6- pin ignition wire harness and from pin 2 to one side of the Normally Open pressure switch.

3.When the combustion blower causes the pressure switch to close, a 24-volt signal is sent across the switch to pin 5 of the 6-pin ignition wire harness. The 24-volt signal energizes at pin 5 and the ignition sequence continues.

4.If the combustion blower fails to close the pressure switch, the 24-volt signal is not sent to pin 5 of the 6-pin ignition wire harness and the ignition control does not initiate a 30-second pre-purge delay.

5.No signal is sent to the spark ignition cable terminal on the ignition control or to the gas valve through pin 4 of the 6-pin ignition wire harness.

6.The combustion blower continues to run for 60 seconds. After 60 seconds, the ignition control automatically de-energizes the combustion blower relay. This interrupts L1 power to the CMB BLWR terminal on the ignition control.

7.The combustion blower remains de-energized for approximately six minutes. During this 6-minute lockout, the green LED flashes three times (indicating pressure switch fault—open or closed).

SPECIFICATIONS

2-8

8.The 24-volt signal will only be supplied to the limit switch circuit through pin 6 of the 6-pin ignition wire harness and to the pressure switch circuit through pin 2 of the 6-pin ignition wire harness.

9.The system will repeat this sequence until the pressure switch closes and the 24-volt signal is restored at pin 5 of the 6-pin ignition wire harness.

FAILED FLAME SENSE/TRIAL FOR IGNITION

When the pressure switch closes and a 24-volt signal is sent to pin 5 of the 6-pin ignition wire harness, the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness energize.

1.As spark voltage is supplied to the ignitor electrodes, the gas valve opens and this causes the burners to ignite.

2.The ignition control continues to energize spark voltage until a flame sense signal is supplied to the flame terminal on the ignition control.

3.If a flame sense signal is not received at the flame terminal on the ignition control, the spark ignition cable terminal remains energized for 10 seconds.

4.After the 10-second trial for ignition, the ignition control de-energizes the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness. This causes the gas valve to close and the electrode spark to stop.

5.Once the 24-volt signal is sent to pin 4 of the 6-pin ignition wire harness, a 30-second circulating air blower “on” delay starts. After the delay is timed out, the circulating air blower starts.

6.After the spark ignition cable terminal de-ener- gizes, the ignition control initiates a 30-second combustion blower inter-purge delay.

7.After 30-second inter-purge, the ignition control energizes the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness. If the flame sense signal is received at the flame terminal of the ignition control, the unit continues heat call.

8.If the flame sense signal is not received, the system goes through three trials following the above sequence.

9.After three trials, the system goes into lockout and only the high limit switch circuit and pressure switch circuit remain energized during the 60minute lockout period.

10.If the flame sense is lost during the heat cycle, the gas valve de-energizes immediately and the system goes into the trial sequence.

Magic-Pak: HW/HWC

CALL FOR COOLING

Line Voltage

1.L2 power passes through the fixed closed L2-T2 terminals on the contactor to the RUN terminal of the compressor and the COMMON terminal of the capacitor.

2.L1 power is sent to the L1 terminal of the contactor. When the Y signal energizes the contactor, the T2 terminal becomes energized. L1 power is sent to the compressor COMMON terminal and the condenser fan. This energizes the compressor and condenser fan motors.

3.When pin 1 (Y terminal) of the 5-pin thermostat harness receives a 24-volt signal from the thermostat, a 5-second circulating air blower delay starts.

4.After the 5-second delay, the ignition control energizes the cooling speed relay. This sends L1 power to the ACB COOL terminal of the ignition control.

5.L1 power is sent to the circulating air blower terminal block, energizing the circulating air blower motor.

6.When the R, Y and G circuit is interrupted by the thermostat, the contactor is immediately deenergized. This interrupts L1 power to the compressor and condenser fan motors, stopping both.

7.The ignition control starts a 90-second circulating air blower “off” delay, after which the ACB COOL terminal de-energizes. This interrupts L1 power to the circulating air blower motor, causing it to stop.

Low Voltage

1.The thermostat energizes the R, Y and G circuit, sending a 24-volt signal to the contactor coil and to pin 1 of the 5-pin thermostat harness connected to the ignition control.

2.The contactor closes immediately upon receiving the 24-volt signal, causing the compressor and condenser fan motors to start.

3.The 24-volt signal is also sent to pin 1 of the 5-pin thermostat harness, initiating a 5-second circulating air blower “on” delay.

4.After the 5-second delay, the ignition control energizes the cooling speed relay and the circulating air blower starts.

5.When the cooling call is satisfied, the thermostat interrupts the R, Y and G circuit. The contactor de-energizes immediately, causing the compressor and the condenser fan to stop. The ignition control starts a 90-second circulating air blower

“off” delay.

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-9

6.After the 90-second delay, the ignition control deenergizes the cooling speed relay and the circulating air blower stops.

FAN ON

1.When the thermostat is switched to the “FAN ON” position, the R-G circuit sends a 24-volt signal to pin 4 of the 5-pin thermostat harness.

2.The 24-volt signal energizes the cooling speed relay, sending L1 power to the ACB COOL terminal of the ignition control.

3.L1 power is sent to the circulating air blower terminal block, causing the circulating air blower to run in cooling speed.

4.The circulating air blower continues to run in cooling speed until the thermostat is switched to “AUTO”, interrupting the R-G circuit.

Note: With the thermostat in the “FAN ON” position during heat call, ignition control will not energize the heat speed relay. The circulating air blower continues to run in cooling speed unless the limit switch circuit opens, which would cause the heat speed relay and the induced draft blower relay to become energized. This would de-energize the cooling speed relay until either the limit switch circuit is closed or the thermostat is switched to the “AUTO” position.

SRM-HW/HWC 2/99

SPECIFICATIONS

Magic-Pak: HW/HWC

2-10

HW (Heating Only)

(w/United Technologies 1097 Spark Ignition System)

CONNECTION DIAGRAM

WIRE NUT

CIRCUITS ENERGIZED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPERATING MODE

CIRCUIT

208/230-1-60

COPPER CONDUCTORS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEATING

R-W

POWER SUPPLY

 

ONLY

 

 

 

 

 

 

 

 

YELLOW

 

 

 

 

COOLING

R-G-Y

}

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

FAN

R-G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

LINE VOLTAGE-FACTORY

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

LINE VOLTAGE-FACTORY WHEN USED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE VOLTAGE-FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

RED

GREEN

WHITE

 

Y

L1

COOL

HEAT

UNUSED

 

 

 

 

 

 

LOW VOLTAGE-FACTORY

 

 

COMBUSTION

 

 

 

 

CNB

 

 

 

 

 

ELECTRODE

 

 

 

LOW VOLTAGE-FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

C

 

 

 

 

 

 

 

 

 

 

G

G

THERMOSTAT

 

BLACK BLACK

 

 

 

 

 

R G W

 

 

 

 

 

 

 

 

 

 

BLACK BLACK

PRESSURE SWITCH

 

 

 

3

 

 

 

 

24VAC

 

 

 

 

 

 

 

VALVE BLUE

 

 

 

 

 

 

 

 

 

WIRES ARE REPLACED, THE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

Y

 

 

 

 

 

 

 

4

 

 

IGNITION

 

WHT

 

 

 

W

W }

 

 

 

 

 

 

 

5

 

 

CONTROL

 

FLAME ROD

 

 

 

 

 

 

 

 

VOILET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

4

5 6

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2 3

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

GAS

 

 

 

 

 

 

ORANGE

 

 

 

 

BLUE

YELLOW

RED

IF ANY OF THE ORIGINAL

 

 

VOILET

 

 

 

 

 

 

 

 

GREEN

 

SAME SIZE AND TYPE WIRE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUST BE USED.

 

 

 

AUTO RESET

 

MANUAL RESET

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT SWITCH

 

 

LIMIT SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

BLACK

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

BLOCK

 

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVAP. MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208 V

240 V

 

 

 

SPEED CONNECTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODELS

HEATING

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26HW

LOW (RED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38HW

HIGH (BLACK)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

51HW

MED (BLUE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

64HW

HIGH (BLACK)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHART

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#45008-2

 

 

YELLOW

 

BLACK

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

BLUE

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BROWN

MOTOR

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAPACITOR

 

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAGNOSTICS

The following blower/ignition control board LED codes will indicate normal or abnormal operations:

SLOW FLASH

Normal Operation, No

 

Call for Heat

FAST FLASH

Normal Operation, Call for

 

Heat

2 FLASH

System Lockout - Failed to

 

Detect or Sustain Flame

3 FLASH

Pressure Switch Open or

 

Closed

4 FLASH

High Limit or Rollout

 

Switch Open

5 FLASH

Flame Sensed and Gas

 

Valve Not Energized

STEADY

Internal Failure

 

(Micro-controller Failure;

 

Self-check)

FIGURE 2-2 Connection Diagram

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-11

Simplified Sequence - HW (w/UTEC 1097 Board)

Refer to Figure 2-2

CALL FOR HEAT

1.The indoor thermostat energizes the R-W circuit, sending a 24-volt signal to the ignition control.

2.The 24-volt signal causes the induced draft blower to start, which closes the pressure switch.

3.Once the pressure switch closes, a 30-second induced draft blower pre-purge starts.

4.After the 30-second induced draft blower pre-purge, the gas valve opens and the burners ignite. This starts a 30-second circulating air blower “on” delay.

5.The unit continues to operate in the heat mode until the indoor thermostat setting is reached. At that time, the R-W circuit is interrupted.

6.The 24-volt signal to the ignition control is interrupted, causing the gas valve to close and the burners to shut down.

7.A 5-second post-purge starts and following that the induced draft blower stops.

8.A 120-second circulating air blower “off” delay starts. After the elapsed time, the circulating air blower stops.

FAN ON

1.When the thermostat is switched to the “FAN ON” position, a 24-volt signal is sent to the ignition control.

2.The ignition control immediately energizes the cooling speed of the circulating air blower.

3.The circulating air blower runs in the cooling speed until the thermostat fan switch is moved back to the “AUTO” position. At this time, the circulating air blower stops.

During the call for “FAN ON”, the circulating air blower heat speed will not be energized by the ignition control unless the limit switch circuit is interrupted.

SRM-HW/HWC 2/99

Detailed Sequence follows

SPECIFICATIONS

Magic-Pak: HW/HWC

2-12

Detailed Sequence - HW (w/UTEC 1097 Board)

Refer to Figure 2-2

POWER

Line Voltage

With the unit at rest (no call from the thermostat), line voltage will be present:

L1 Power

1.Through the L1 black lead to the L1 terminal on the ignition control

2.At the transformer terminal marked 208-240V

L2 Power

1.Through the L2 black lead to the induced draft blower

2.Transformer common terminal

3.At the circulating air blower capacitor terminal

Low Voltage (24 VAC)

With the unit at rest (no call from the thermostat), 24 volts A/C will be present:

1.At the transformer 24V terminal

2.At the 24VAC hot terminal on the ignition control

3.At pin 5 of the 5-pin thermostat harness (red wire pin)

4.At pin 6 of the 6-pin ignition wire harness

5.Through the auto reset limit switch and the manual reset rollout switch to pin 1 of the 6-pin ignition wire harness

Note: While the unit is at rest, the green LED shows consistent slow flash. This indicates normal operation - system at rest (standby mode).

CALL FOR HEAT

Line Voltage

The ignition control receives a signal from the R-W circuit indicating a call for heat.

1.The combustion blower relay energizes, sending L1 power to CMB BLWR terminal on the ignition control. This causes the combustion blower to start.

2.As the 24-volt signal is sent to pin 4 of the 6-pin ignition wire harness by the ignition control, a 30second circulating air blower “on” delay starts. After the delay, the ignition control energizes the heat speed blower relay. This sends L1 power to the ACB HEAT terminal on the ignition control.

3.L1 power is then sent to the circulating air blower terminal block where it is connected to the blower motor, starting the circulating air blower.

4.The combustion blower and the circulating air blower continue to run until the R-W circuit is interrupted. After a 5-second post-purge delay, the

CMB BLWR terminal on the ignition control deenergizes. This interrupts L1 power to the combustion blower. After a 120-second circulating air blower “off” delay, the ACB HEAT terminal deenergizes. This interrupts L1 to the circulating air blower. As L1 power is interrupted, the blowers shut off.

Low Voltage

1.A call for heat closes the R-W circuit, sending a 24volt signal to the low voltage white wire in the unit.

2.The 24-volt signal is received at pin 3 of the 5-pin thermostat harness on the ignition control.

3.The 24-volt signal causes the combustion blower relay to close, causing the combustion blower to run. At this time, a 24-volt signal is also sent out through pin 2 of the 6-pin ignition wire harness.

4.The 24-volt signal from pin 2 of the 6-pin ignition wire harness energizes one side of the Normally Open pressure switch. As the induced draft blower reaches full speed, the pressure switch closes and a 24-volt signal is sent to pin 5 of the 6- pin ignition wire harness.

5.When the 24-volt signal is received at pin 5 of the 6- pin ignition wire harness, the ignition control starts a 30-second pre-purge delay.

6.After the 30-second pre-purge, the ignition control initiates a trial for ignition. The spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness energize simultaneously.

7.When the 24-volt signal is present at pin 4 of the 6- pin ignition wire harness, the ignition control starts a 30-second circulating air blower “on” delay.

8.The 24-volt signal from pin 4 of the 6-pin ignition wire harness is received at the gas valve, causing it to open and the burners to ignite.

9.After 30-second “on” delay, the circulating air blower relay energizes the heat terminal and the circulating air blower is energized.

10.The unit will continue to operate normally until the R-W circuit is interrupted.

11.When the heat call is satisfied, the thermostat will interrupt the R-W circuit. This causes the 24-volt signal to the white wire in the unit to be de-ener- gized.

HW/HWC-SRM

2/99

SRM-HW/HWC 2/99

Service Reference Manual

12.The gas valve closes immediately as 24V through pin 4 of the 6-pin ignition wire harness is deenergized by the ignition control.

13.The ignition control initiates a 120-second circulating air blower “off” delay and 5-second combustion blower post-purge delay.

14.After 5 seconds, the combustion blower shuts off.

15.After 120 seconds, the circulating air blower shuts off and the system returns to standby mode.

Note: During a call for heat, the green LED shows consistent fast flash (as long as the R-W circuit is closed). When the R-W circuit is interrupted (indicating the heat call has been satisfied), the green LED returns to a consistent slow flash.

LIMIT/ROLLOUT OPENS

In all modes of operation, 24VAC is supplied to the ignition control 24VAC hot terminal and is passed through the ignition control to pin 6 of the 6-pin ignition wire harness.

1.A 24-volt signal is sent from pin 6 of the 6-pin ignition wire harness to one side of the Normally Closed manual reset rollout switch, across the rollout switch to one side of the Normally Closed auto reset limit switch and across the limit switch to pin 1 of the 6-pin ignition wire harness.

2.This circuit energizes whenever line voltage power is supplied to the unit.

3.If the circuit is interrupted by either switch opening, the 24-volt signal to pin 1 of the 6-pin ignition wire harness de-energizes.

4.This causes the combustion blower relay to energize, sending L1 power to the CMB BLWR terminal on the ignition control. It also causes the circulating air blower heat speed relay to energize, sending L1 power to the ACB HEAT terminal on the ignition control. This causes both blowers to start immediately.

5.The ignition control lockouts the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness until the 24-volt signal is restored at pin 1 of the 6-pin ignition wire harness.

6.The circulating air blower and the combustion blower are energized until the 24-volt signal is restored at pin 1 of the 6-pin ignition wire harness.

7.The green ignition control LED shows a 4 flash fault code (indicating limit switch/rollout switch open).

8.When the 24-volt signal is restored at pin 1 of the 6- pin ignition wire harness, the ignition control starts a 5-second combustion blower post-purge delay and a 120-second circulating air blower “off” delay.

SEQUENCE OF OPERATIONS

2-13

9.Once the delays have timed out, both blowers stop and the green LED flashes a consistent slow flash if no heat call is present. (A consistent fast flash appears if there is a call for heat.)

Note: The limit switch resets automatically when temperatures are acceptable, but the rollout switch must be manually reset by pushing in on the small button on top of the switch.

The reason why the switches opened must be determined before any corrective action is taken.

PRESSURE SWITCH OPENS (BLOCKED FLUE)

When the R-W circuit is energized, a 24-volt signal is sent to the ignition control. This starts the call for heat.

1.The 24-volt signal from the R-W circuit energizes the combustion blower relay, sending L1 power to the CMB BLWR terminal on the ignition control. This starts the ignition control.

2.At the same time the combustion blower relay energizes, the 24-volt signal is sent to pin 2 of the 6- pin ignition wire harness and from pin 2 to one side of the Normally Open pressure switch.

3.If the combustion blower causes the pressure switch to close, a 24-volt signal is sent across the switch to pin 5 of the 6-pin ignition wire harness. The 24-volt signal energizes at pin 5 and the ignition sequence continues.

4.If the combustion blower fails to close the pressure switch, the 24-volt signal is not sent to pin 5 of the 6-pin ignition wire harness and the ignition control does not initiate a 30-second pre-purge delay.

5.No signal is sent to the spark ignition cable terminal on the ignition control or to the gas valve through pin 4 of the 6-pin ignition wire harness.

6.The combustion blower continues to run for 60 seconds. After 60 seconds, the ignition control automatically de-energizes the combustion blower relay. This interrupts L1 power to the CMB BLWR terminal on the ignition control.

7.The combustion blower remains de-energized for approximately six minutes. During this 6-minute lockout, the green LED flashes three times (indicating pressure switch fault—open or closed).

8.The 24-volt signal will only be supplied to the limit switch circuit through pin 6 of the 6-pin ignition wire harness and to the pressure switch circuit through pin 2 of the 6-pin ignition wire harness.

9.The system will repeat this sequence until the pressure switch closes and the 24-volt signal is restored at pin 5 of the 6-pin ignition wire harness.

SPECIFICATIONS

2-14

FAILED FLAME SENSE/TRIAL FOR IGNITION

When the pressure switch closes and a 24-volt signal is sent to pin 5 of the 6-pin ignition wire harness, the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness energize.

1.As spark voltage is supplied to the ignitor electrodes, the gas valve opens and this causes the burners to ignite.

2.The ignition control continues to energize spark voltage until a flame sense signal is supplied to the flame terminal on the ignition control.

3.If a flame sense signal is not received at the flame terminal on the ignition control, the spark ignition cable terminal remains energized for 10 seconds.

4.After the 10-second trial for ignition, the ignition control de-energizes the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness. This causes the gas valve to close and the electrode spark to stop.

5.Once the 24-volt signal is sent to pin 4 of the 6-pin ignition wire harness, a 30-second circulating air blower “on” delay starts. After the delay is timed out, the circulating air blower starts.

6.After the spark ignition cable terminal de-ener- gizes, the ignition control initiates a 30-second combustion blower inter-purge delay.

7.After 30-second inter-purge, the ignition control energizes the spark ignition cable terminal and pin 4 of the 6-pin ignition wire harness. If the flame sense signal is received at the flame terminal of the ignition control, the unit continues heat call.

8.If the flame sense signal is not received, the system goes through three trials following the above sequence.

9.After three trials, the system goes into lockout and only the limit switch circuit and pressure switch circuit remain energized during the 60-minute lockout period.

10.If the flame sense is lost during the heat cycle, the gas valve de-energizes immediately and the system goes into the trial sequence.

FAN ON

1.When the thermostat is switched to the “FAN ON” position, the R-G circuit sends a 24-volt signal to pin 4 of the 5-pin thermostat harness.

2.The 24-volt signal energizes the cooling speed relay, sending L1 power to the ACB COOL terminal of the ignition control.

3.L1 power is sent to the circulating air blower terminal block, causing the circulating air blower to run in cooling speed.

Magic-Pak: HW/HWC

4.The circulating air blower continues to run in cooling speed until the thermostat is switched to “AUTO”, interrupting the R-G circuit.

Note: With the thermostat in the “FAN ON” position during heat call, ignition control will not energize the heat speed relay. The circulating air blower continues to run in cooling speed unless the limit switch circuit opens, which would cause the heat speed relay and the induced draft blower relay to become energized. This would de-energize the cooling speed relay until either the limit switch circuit is closed or the thermostat is switched to the “AUTO” position.

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-15

BLANK PAGE

SRM-HW/HWC 2/99

SPECIFICATIONS

Magic-Pak: HW/HWC

2-16

HWC122, 182, 242, 302

(w/Fenwal Triton 2461D DSI Ignition Control)

CIRCUITS ENERGIZED

208/230-1-60

 

COPPER CONDUCTORS

POWER SUPPLY

ONLY

 

 

 

 

OPERATING MODE

CIRCUIT

HEATING

R-W

COOLING

R-G-Y

FAN

R-G

 

 

 

 

PINK

MANUAL

 

NO

RED

 

 

 

 

 

 

 

LIMIT

 

 

 

 

TH

 

 

 

 

 

 

 

WHITE

RESET

 

SWITCH NC

C

 

 

 

 

P.SW

 

 

 

 

 

 

ORN

 

 

 

 

 

 

 

 

 

 

V1

 

WHITE

 

 

 

 

 

R

 

 

ORN

 

 

 

WHITE

WHITE

 

 

IND

 

 

 

W

BLACK BLACK

 

 

BLUE

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

GAS

 

 

 

 

 

 

 

 

L1

 

VALVE

 

PRESSURE

 

 

 

Y

 

24VAC

 

BLUE

 

 

SWITCH

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITION

V2

 

 

 

 

 

 

 

 

 

 

CONTROL

GND

 

 

 

 

 

 

 

 

 

 

 

GREEN

RED

BLACK

 

COMBUSTION

BLUE

GREEN WHITE RED YELLOW

 

ELECTRODE

 

 

BLOWER

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

CABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

CONNECTOR

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

CONDENSER FAN

 

 

 

 

 

 

 

 

 

 

 

 

VIOLET

BLACK

 

 

 

 

 

 

 

 

 

BLUE

 

CAPACITOR-RUN

 

 

 

 

 

 

 

 

 

RED

FAN

BROWN

 

 

BLACK

 

 

 

 

 

 

 

 

C

T1

L1

 

 

 

 

 

COM

 

 

 

BLACK

 

 

YELLOW

S

 

RED

 

CONTACTOR

 

 

 

HERM

 

 

 

 

 

 

 

 

R

 

T2

L2

BLACK

 

 

 

 

 

 

 

 

208V

 

 

 

RED

 

 

 

 

 

 

 

240V

 

 

 

 

 

 

 

 

TRANS-

 

 

RED

SEE TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YEL

FORMER

 

 

 

FOR WIRING

BLOWER

 

 

 

 

 

BLK

CONTROL

BLUE

 

BLUE

 

 

 

 

YEL

C

 

C

 

 

 

 

 

 

BLK

 

 

 

RED

 

 

 

 

BLUE

R

 

 

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

H

 

 

 

BLK

YEL

CONTR

YEL

 

BROWN

W

 

 

 

 

 

 

 

 

 

CAPACITY

BLOWER

L1

 

G

 

COMP T’STAT

 

 

 

LOAD

 

 

 

 

BLUE

 

 

 

 

BLOWER

MOTOR

 

 

 

 

 

COM

 

 

 

 

 

 

 

 

(IF USED)

 

 

TIME DELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

SEE TABLE

 

 

 

 

 

WHITE

(IF USED)

 

 

 

 

 

 

 

 

GREEN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE VOLTAGE - FACTORY

LINE VOLTAGE - FACTORY (WHEN USED) LINE VOLTAGE - FIELD

LOW VOLTAGE - FACTORY LOW VOLTAGE - FIELD

R

W THERMOSTAT

Y

G

NOTE:

IF ANY OF THE ORIGINAL WIRES ARE REPLACED, THE SAME SIZE AND TYPE WIRE MUST BE USED.

EVAPORATOR MOTOR

SPEED CONNECTIONS

MODELS

HEATING

COOLING

 

26HWC122

LOW (RED)

MED (BLUE)

 

38HWC122

HIGH (BLK)

MED (BLUE)

 

38HWC182

LOW (RED)

LOW (RED)

*

51HWC182

MED (BLUE)

LOW (RED)

64HWC182

HIGH (BLK)

LOW (RED)

 

38HWC242

LOW (RED)

MED (BLUE)

 

51HWC242

MED (BLUE)

MED (BLUE)

*

64HWC242

HIGH (BLK)

MED (BLUE)

51HWC302

MED (BLUE)

HIGH (BLK)

 

64HWC302

HIGH (BLK)

HIGH (BLK)

*

* JUMPER REQUIRED

 

#39007D5

Note: On units that are equipped with a low ambient switch (designated with an “SA” in the model number), sequence of operation during cooling call is modified when outdoor temperatures fall below the normal operating range. For more information on the low ambient switch equipped version of this unit, see the section beginning on page 2-38.

FIGURE 2-3 Connection Diagram

HW/HWC-SRM

2/99

Service Reference Manual

SEQUENCE OF OPERATIONS

2-17

Simplified Sequence - HWC122,182, 242, 302 (w/Fenwal Triton 2461D DSI Ignition Control)

Refer to Figure 2-3

CALL FOR HEAT

1.A call for heat closes the circuit between wires R (red) and W (white) on the unit’s thermostat connections.

2.A low voltage (24 volts) signal is sent to the ignition control, closing a relay which sends line voltage to the induced draft blower. At the same time, a 24volt signal is also sent to the blower control board. This causes the blower control board to begin the countdown to closing the relay that starts the circulating air blower.

3.After the induced draft blower creates enough negative pressure, the pressure switch closes.

4.When the pressure switch closes, the 24-volt signal is sent to the ignition control. This starts a 30second pre-purge countdown, after which a trial for ignition is made.

5.At the same time that the trial for ignition is made, the gas valve energizes and gas flows to the burners.

6.With the burners in operation, the trial for ignition continues for seven seconds. At the end of this time, the ignition control stops sparking.

7.Approximately 30 seconds after the burners ignite, the timer on the blower control board closes a relay, sending line voltage to and starting the circulating air blower.

8.The unit continues to operate as long as there is a 24-volt signal between R and W. When the call for heat is satisfied, the 24-volt signal between R and W discontinues. When W de-energizes, the power to the induced draft blower and the gas valve is interrupted. The 24-volt signal to the blower control board is also interrupted, causing the module to start the countdown to blower “off” (approximately 90 seconds).

9.If at any time during a call for heat the limit switch opens, the 24-volt signal to the white wire going to terminal P.SW on the ignition control is interrupted. This de-energizes the gas valve immediately. The circulating air blower and the induced draft blower continue to run. When the unit cools down enough for the limit switch to close, the 24-volt signal is again sent to the P.SW terminal on the ignition control. With terminal P.SW energized, the ignition control again makes a trial for ignition and relights the burners.

CALL FOR COOLING

1.A call for cooling closes the circuit from R to Y and G.

2.A 24-volt signal is sent to blower control board terminal G and to the compressor contactor. The contactor closes, sending line voltage to the compressor and the outdoor condenser fan.

3.With a 24-volt signal at terminal G on the blower control board, the circulating air blower starts in cooling speed approximately 15 seconds later (or immediately - see note below).

4.When the cooling call is completed, G and Y deenergize. The contactor opens immediately, stopping the compressor and the outdoor cooling fan. When G de-energizes, the timer to turn off the circulating air blower starts. The circulating air blower turns off after 90 seconds (see note below).

FAN ON

1.When the thermostat switch is moved to the “FAN ON” position, the circuit between R and G closes.

2.The 24-volt signal from G goes to the blower control board which starts the timer.

3.Fifteen seconds after terminal G on the blower control board energizes (or immediately after - see note below), the circulating air blower starts.

4.When terminal G on the blower control board deenergizes, the timer to turn off the circulating air blower starts. The circulating air blower turns off after 90 seconds (see note below).

Note: Heatcraft blower control boards have a G “on” delay of 15 seconds and an “off” delay of 90 seconds. Tridelta blower control boards have no “on” time delay and a 60 -130 second “off” delay.

SRM-HW/HWC 2/99

Detailed Sequence follows

SPECIFICATIONS

Magic-Pak: HW/HWC

2-18

Detailed Sequence - HWC122, 182, 242, 302 (w/Fenwal Triton 2461D DSI Ignition Control)

Refer to Figure 2-3

POWER

Line Voltage

When the service disconnect switch is closed, power is sent to the unit (unit in standby, no signal from the thermostat). Power (208 - 230 volts A/C) is supplied to both black wires located in the junction block on top of the unit.

Line voltage will be present at the following locations:

First black wire

1.L-1 on the ignition control

2.L-1 on the contactor

3.L-1 on the blower control board

4.Terminal on the transformer marked 208V or 240V (whichever is being used)

Second black wire

1.Supplies power to the induced draft blower

2.L-2 on the contactor

3.Common terminal on the transformer

4.T-2 on the contactor

5.Red wire on the R terminal of the compressor

6.Red wire to the common terminals on the capacitors

Low Voltage (24 VAC)

With the unit at rest (no call from the thermostat), 24 volts A/C will be found at these points:

1.Red wire exiting the top of the unit

2.Terminal marked 24 VAC on the ignition control

3.Terminal R on the blower control board

CALL FOR HEAT

Line Voltage

The thermostat closes the circuit between R and W.

The following is the sequence of operation for the line voltage side of the unit:

1.Terminal TH (24-volt) energizes on the ignition control, causing the relay in the ignition control to close. This sends line voltage to the terminal marked IND, causing the induced draft blower to start.

2.When W energizes, a 24-volt signal is also sent to the W terminal on the blower control board. The 24-volt signal to the blower control board starts the timer on the board. After 60 seconds, the heat speed relay on the blower control board closes. This sends line voltage from the terminal marked

HEAT to the circulating air blower, starting the blower. The induced draft blower and the circulating air blower continue to operate until the heat call is satisfied, interrupting the circuit between R and W. The W terminal de-energizes, causing the blower relay to open approximately 90 seconds later. This interrupts the line voltage to the circulating air blower and the blower shuts down.

Low Voltage

1.A call for heat closes the circuit in the thermostat between R and W, sending a 24-volt signal to the white wire on the unit.

2.The white wire goes to the C terminal on the limit switch, ignition control terminal TH and terminal W on the blower control board.

3.When W energizes, the timer starts a countdown to blower “on”. The blower starts in approximately 60 seconds.

4.The 24-volt signal sent to terminal TH closes the relay in the ignition control. This starts the induced draft blower by energizing terminal IND on the ignition control.

5.As the induced draft blower comes up to speed and creates enough negative pressure, the pressure switch closes. The 24-volt signal from the pressure switch energizes terminal P.SW, causing the ignition control to start a trial for ignition (sparking).

6.As the trial for ignition starts, the V1 terminal on the ignition control energizes. At the same time, a 24volt signal is sent to the gas valve, opening the valve. The unit continues to operate as long as W is energized.

7.When the call for heat is satisfied, the circuit between R and W is interrupted.

8.With W de-energized, the gas valve closes immediately and the induced draft blower shuts down several seconds later.

9.The blower control board starts a countdown to blower “off”. Approximately 90 seconds later, the blower shuts down.

HW/HWC-SRM

2/99

SRM-HW/HWC 2/99

Service Reference Manual

LIMIT OPENS

If the limit switch opens for any reason during a call for heat, the following happens:

1.If the limit switch senses that the temperature in the unit is too high, the contacts between terminals C and NC on the limit switch open and the contacts between C and NO close. This interrupts the 24-volt signal to the pressure switch and also deenergizes terminal P.SW on the ignition control. The gas valve closes immediately, as the 24-volt signal to terminal P.SW is no longer present. The induced draft blower and the circulating air blower continue to run. Power to blower control board terminal W is maintained. The blowers continue to run until the limit switch closes or the heat call at the thermostat is satisfied.

2.When the limit switch senses that temperatures in the unit are normal, the contacts between terminals C and NO open, the contacts between terminals C and NC close and operation of the unit returns to normal.

PRESSURE SWITCH OPENS (BLOCKED FLUE)

1.If blockage of the flue occurs, the negative pressure in the induced draft blower is reduced. At the set point of the pressure switch, the contacts open.

This interrupts the 24-volt signal to terminal P.SW on the ignition control. The gas valve closes immediately, as the relay in the ignition control opens and interrupts the signal to terminal V2 of the ignition control.

2.Terminal W on the blower control board stays energized and the circulating air blower continues to run. If the negative pressure is restored, the pressure switch closes and sends a 24-volt signal to the P.SW terminal on the ignition control. The ignition control makes a trial for ignition again and operation returns to normal.

Note: If the P.SW and TH terminals energize at the same time, the ignition control will not respond. A pressure switch being stuck closed is an example of what would cause this to happen.

ROLLOUT SWITCH ACTIVATED

1.If the conditions in the burner compartment cause the rollout switch to trip, the contacts on the switch open, interrupting the 24-volt signal going to terminal P.SW on the ignition control. This causes the ignition control to de-energize terminal V1, interrupting the 24-volt signal to the gas valve and immediately closing it.

SEQUENCE OF OPERATIONS

2-19

2.The reason the rollout switch was tripped must be determined before corrective action is taken.

3.The signal to terminal P.SW can only be restored if the rollout switch is reset, which can only be done manually. The W terminal on the blower control board remains energized and the circulating air blower continues to operate. Once the rollout switch is reset, the operation of the unit returns to normal.

CALL FOR COOLING

Line Voltage

On a call for cooling, the thermostat closes the circuit between Y, G and R.

1.With Y energized, the contactor closes. This sends line voltage to compressor terminal C, causing the compressor to start. The outdoor fan also starts, drawing air through the outdoor coil.

2.Terminal G on the blower control board also energizes at the same time as Y. This starts the timer on the blower control board. Approximately 15 seconds later (or immediately - see note on page 2-20), the terminal marked COOL energizes. This sends line voltage to the circulating air blower, starting the blower.

3.The unit continues cooling as long as both Y and G are energized. When the cooling call is satisfied, the circuit between Y, G and R is interrupted. The contactor immediately opens, interrupting power to the compressor and the outdoor cooling fan.

4.With the low voltage signal to terminal G on the blower control board interrupted, the board starts a countdown to blower “off”. After approximately 90 seconds (see note on page 2-20), the cooling speed relay opens and the circulating air blower shuts down.

Low Voltage

1.On a call for cooling, the thermostat closes the circuit between R and terminals G and Y.

2.The 24-volt signal energizes terminal G on the blower control board, starting the fan “on” timer. Approximately 15 seconds later (or immediately - see note on page 2-20), the relay closes. This sends line voltage to the COOLING speed terminal on the blower control board, which starts the circulating air blower.

3.The signal from Y energizes the contactor, starting the compressor and the outdoor cooling fan.

4.When the cooling call is satisfied, both G and Y are de-energized. The contactor opens immediately, causing the compressor and the outdoor cooling fan to stop.

SPECIFICATIONS

Magic-Pak: HW/HWC

2-20

5.The circulating air blower shuts off approximately 90 seconds after G terminal on the blower control board is de-energized (see note below).

FAN ON

Low Voltage

1.When the switch on the thermostat is moved to the “FAN ON” position, a 24-volt signal is sent to G.

2.With G energized, the blower control board starts a countdown to fan “on”. After approximately 15 seconds, the fan starts (see note below).

3.The blower control board closes a relay on the board, sending line voltage to the terminal marked COOL on the board. This starts the circulating air blower.

4.When the switch at the thermostat is moved to the “OFF” position, the 24-volt signal to the blower control board is interrupted. With no signal at the

G terminal, the blower control board starts a countdown to fan “off”. Approximately 90 seconds later, a relay on the blower control board opens (see note below). This interrupts the power to and stops the circulating air blower.

Note: Heatcraft blower control boards have a G “on” delay of 15 seconds and an “off” delay of 90 seconds. Tridelta blower control boards have no “on” time delay and a 60 -130 second “off” delay.

HW/HWC-SRM

2/99

Loading...
+ 166 hidden pages