Ariston STI 125 INDIRECT, STD 125 DIRECT, STD 150 DIRECT, STD 210 DIRECT, STI 150 INDIRECT User Manual

...
UNVENTED CYLINDER
RANGE
UNVENTED WATER STORAGE CYLINDER
No longer than every 12 months, the magnesium anti-corrosion
anodes should be checked by your service engineer/installer.
IMPORTANT
Please read these instructions carefully
before installing the cylinder.
Failure to do so may invalidate the Warranty
WATER BYELAWS
These bye-laws ensure a good supply of wholesome water, and that only approved materials, pipes and fittings are used to convey water.
BUILDING REGULATIONS
These are a statutory document and take priority over all other regulations and recommendations. The installation of an unvented hot water storage cylinder is classified as a "Controlled Service" and Regulation G3 applies. To meet the requirements of the Regulation, installation of an unvented system should be undertaken by a "competent installer".
All installations of unvented hot water storage systems having a capacity of more than 15 litres should be notified to the relevant Local Authority by means of building notice or by the submission of full plans. It is important to note that it is a criminal offense to install an unvented hot water storage system without notifying the Local Authority.
DELIVERY
The range is available with the following options;
The wall-hung range (50, 75, 100 litre models), which are supplied as the following;
One large box containing;
1) The unit with factory fitted Temperature & Pressure Relief Valve and Immersion Heater.
One small box containing;
1) Unvented control pack (Expansion vessel, 2 piece Cold Water Combination Valve, Tun Dish).
The Ariston Contract and the Ariston Comfort (Indirect only) floor-standing range (125, 150, 200 litre models).
The Contract is supplied with the following;
One large box containing;
1) The unit with factory fitted Temperature & Pressure Relief Valve.
2) Immersion Heater(s) (not fitted).
3) Cylinder Thermostat (Indirect only, not fitted).
4) Feet x 3.
One small box containing;
1) Unvented control pack (Expansion vessel, 2 piece Cold Water Combination Valve, Tun Dish, Drain Cock and Motorised Valve (Indirect only).
- 3 -
Hot and cold water are both drawn off the same source of supply. Remember, there will not be a storage tank to help compensate for variations in the demand on the system.
A minimum pressure of approximately 1.5 bar and 20 litres per minute is required for satisfactory operation. 85% of UK dwellings have a mains pressure above 2.0 bar.
THE MAINS WATER SUPPLY MUST NOT EXCEED 12 BAR
SITING AND FIXING
The cylinder may be installed at any convenient position, as it is connected to the mains cold water supply, it is equally effective on any floor.
However, do not install the unit in premises which may be subject to freezing. Ensure that the floor load bearing strength is adequate to take the weight of the cylinder when full of water (see table 1).
The ST50, ST80 and ST100 models are wall mounted. All other models are free standing. These are supplied with feet which are attached to the heater via self tapping screws which are also supplied. All units must be installed in the VERTICAL POSITION.
For maintenance purposes leave at least 500 mm free space in front of the unit, for access to electrical components, immersion heater(s) and magnesium anodes.
CONNECTION OF MAINS WATER SUPPLY For Contract & Comfort models: On the front of the unit there is a label to identify the connection ports. Please check this before making any connection to the unit.
For units up to 300 litres it is recommended that all mains cold water supply pipe work is a minimum of 22mm, with the exception of model ST50 where 15mm can be used. For 500 litre models the supply should be 28mm. An Isolating Valve should be installed between the cold water supply and the cylinder for servicing. ALL PIPEWORK MUST BE FLUSHED TO
AVOID DAMAGE TO THE CONTROL VALVES.
Please refer to figs. 1, 2 , 3, 3, 3, 3, 3 for a suggested installation layout.
COLD WATER COMBINATION VALVE
The Cold Water Combination Valve can be connected either close by the unit or alternatively it may be installed in a remote position from the unit as there is no requirement to site it in close proximity to the cylinder. This allows a flexible and convenient installation. However, it is important to note allowances for the discharge pipe work from the Expansion Relief Valve must be accounted for.
A Balancing Port is supplied on the 22mm (for units above 50 litres) valve allowing balanced cold water supply to the rest of the building giving excellent results with mixer and shower valves. If the facility is not needed a plug is supplied. Refer to fig. 4
Although this facility is not built into the 15mm valve (supplied with Contract ST50), a Tee Piece may be inserted between the two components giving the same results. Refer to fig. 5
CONNECTION TO SERVICES
Again it is recommended that a 22mm pipe run should supply the outlets throughout the building, especially to baths and showers. Short runs of 15mm pipe may be used to connect basins and sinks.
- 5 -
The Comfort is supplied with the following;
One large box containing;
1) The unit with factory fitted Temperature & Pressure Relief Valve.
2) Factory fitted Immersion Heater (Dry pocket).
3) Factory fitted Cylinder Thermostat.
4) Feet x 3.
One small box containing;
1) Unvented control pack (Expansion vessel, 2 piece Cold Water Combination Valve, Tun Dish, Drain Cock and Motorised Valve).
The high capacity floor-standing range (300, 500 litre models), which are supplied as the following;
One large box containing;
1) The unit
2) Factory fitted Temperature & Pressure Relief Valve (300 litre models only).
3) Factory fitted Immersion Heater(s)
4) Factory fitted Cylinder Thermostat.
5) Feet x 3.
One small box containing;
1) Unvented control pack (Expansion vessel, 2 piece Cold Water Combination Valve, Tun Dish, Drain Cock and Motorised Valve) (500 litre model 1" Temperature & Pressure Relief Valve).
HOW THE HEATER WORKS
The Immersion Heater(s) are connected through a thermostat which senses the water temperature. The operating temperature can be pre-set by adjusting the spindle in the head of the thermostat. In addition to the thermostat there is a Thermal Cut-out incorporated if the thermostat fails and the water temperature rises too high. Once the cut-out operates it can only be re-set manually after the fault has been rectified.
Indirect models have dual thermal controls. In addition to the above there is a separate Cylinder Thermostat and Thermal Cut-out for controlling the indirect circuit. Again the Thermal Cut-out operates if the Cylinder Thermostat fails, by disconnecting the live feed (call for hot water) from the programmer.
Floor-standing models have Magnesium Anodes provided to prevent corrosion of the water cylinder tank. Wall-hung units have a single Magnesium Anode.
The factory fitted Temperature & Pressure Relief Valve at the top of the cylinder is a safety device to back-up the Thermostat(s) and Thermal Cut-out(s). It works by sensing an excess in water temperature or pressure and releasing the hot water into a Discharge Tundish and drain.
The cylinder will only work in the vertical position. The inlet pipe needs to deliver cold water to the bottom of the tank. When water is heated it expands. To accommodate this increase in volume an Expansion Vessel is provided. A Cold Water Combination Valve is also provided in two pieces, loose jointed for ease of installation. These comprise a Combined Line Strainer/Pressure Reducing Valve and Core Non Return Valve/Expansion Relief Valve.
The Strainer prevents any debris entering the other controls. The Pressure Reducer ensures the correct operation of the Expansion Vessel, and prevents any damage to the control valves through too great a pressure.
The Non-Return Valve ensures the water expansion is forced into the Expansion Vessel and prevents contamination of the mains cold water supply. The Expansion Relief Valve will discharge expanded water to the Discharge Tundish if the Expansion Vessel fails.
COLD WATER SUPPLY
It is important to ensure that the cold water main is capable of supplying the increased demand which will be imposed on it.
- 4 -
AB
CD
ELECTRICAL
The electrical installation must be in accordance with the current I.E.E. wiring regulations.
FITTING IMMERSION HEATER(S) (CONTRACT RANGE ONLY)
These are supplied but not fitted with the Ariston Contract range. A Sealing Gasket is supplied with each element and must be used to ensure a correct seal. Care must be taken not to cross thread the Immersion Heater(s) when fitting. Each Immersion Heater is supplied with a Regulation Thermostat and manual reset Thermal Cut-out. This will activate if the Regulation Thermostat fails. Under no circumstances should this be bypassed.
Although the Immersion Heaters are a standard 21/4” thread, they must not be substituted with anything but an original Ariston spare part.
DIRECT SYSTEMS
A mains supply of 240V, 3kW (13 amps) is required. Heat resistant cable, round 3 or 4 core 2.5mm2 (to BS6141 table 8) must be used to connect the electrical supply through the Economy 7 time control switch using either system ‘A’ or ‘B’ as illustrated in fig. 8.
Should the Economy 7 system not to be used, a separate 13 amp supply to each element will be required. Through a double pole fused isolating switch having a contact gap of at least 3mm on each pole. Make the connection(s) to the Immersion Heater(s) as per figs. 9, 10. For 500 litre models consult the wiring diagram on the reverse of the inspection panel.
The Thermostat(s) on the Immersion Heater(s) should be adjusted to trip at 60°C. This is the ideal temperature to prolong element life in hard water areas. Scale on the sheath builds up more rapidly at temperatures above this causing the element to overheat and premature failure can occur. Higher temperatures without additional controls would result in scalding.
In addition to the thermostat the Thermal Cut-out will switch power off to the element should the thermostat malfunction, causing an excessive rise in water temperature. The Thermal Cut-out can be reset manually after the fault has been corrected.
INDIRECT SYSTEMS
Again for models up to 300 litres a mains supply of 240v, 3kW (13 amps) will be required for the direct Immersion Heater. Heat resistant cable, round 3 core 2.5mm² (to BS) must be used. For 500 litre models consult the wiring diagram on the reverse of the inspection panel. For indirect controls a 240V, 3amp supply is required. On Comfort models the Indirect thermostat is factory fitted, for Contract models it is necessary to fit the thermostat using P.T.F.E Tape (Please consult the label on the face of the unit for the correct location in both cases).
The cables must be clamped in position (as previously stated) and the control thermostat should be set at 60°C for the reasons above. In addition to the thermostat there is a Thermal High Temperature Cut Out should the thermostat fail. Refer to figs. 11 & 12 for full wiring instructions.
WARNING : THIS APPLIANCE MUST BE EARTHED.
The earth continuity conductor of the electrical installation must be effectively connected to all exposed parts of other appliances and services in the room in which the water heater is to be installed, conformity with the I.E.E. wiring regulations.
NOTE : Do not switch on the Immersion Heater or fire the boiler until the water heater is full of water.
COMMISSIONING
Check for obvious signs of damage to the cylinder and controls and also that the controls fitted correspond with the reference quoted in these instructions.
Ensure that the Drain Cock at the base of the water heater is closed before commencing.
1) Open all outlet taps.
2) Turn on mains water supply and allow the water heater to fill.
- 7 -
SECONDARY RETURN
On Floor-standing models a Secondary Return may be fitted. On Contract and Comfort models via the special port on the side of the cylinder (consult the label on the face of the unit for the correct location), for 300 and 500 litre models refer to fig.
6. A Non Return Valve (not supplied) must be fitted to prevent back flow and a Bronze Pump will be needed in conjunction with a Pipe Thermostat to circulate the hot water (both not supplied).
DISCHARGE PIPEWORK
1) The Tundish must be vertical and fitted within 500mm of the Temperature & Pressure Relief Valve and must be located with the cylinder. The Tundish must also be in a position visible to the occupants, and positioned away from any electrical devices. The discharge pipe from the tundish should terminate in a safe place where there is no risk to persons in the vicinity of the discharge and to be of metal.
2) Discharge pipes from the Temperature & Pressure Relief and Expansion relief valve may be joined together.
3) The pipe diameter must be at least one pipe size larger than the nominal outlet size of the safety device unless it's total equivalent hydraulic resistance exceeds that of a straight pipe 9m long.
I.e. Discharge pipes between 9m and 18m equivalent resistance length should be at least 2 sizes larger than the nominal outlet size of the safety device. Between 18m and 27m at least 3 larger, and so on. Bends must be taken into account in calculating the flow resistance. See fig. 7 and Table 2.
4) The discharge pipe must have a vertical section of pipe at least 300m in length, below the Tundish before any elbows or bends in the pipework.
5) The discharge pipe must be installed with a continuous fall.
6) The discharge must be visible at both the Tundish and the final point of discharge, but where this is not possible or practically difficult; there should be clear visibility at one or other of these locations. Examples of acceptance are:
i) Ideally below a fixed grating and above the water seal in a trapped gully. ii) Downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks,
hard standings, grassed areas etc. These are acceptable providing that where children may play or otherwise come into contact with discharges, a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility.
iii) Discharges at high level; I.e. into a metal hopper and metal down pipe with the end of the discharge
pipe clearly visible (Tundish visible or not). Or onto a roof capable of withstanding high temperature discharges of water 3m from any plastic guttering systems that would such a discharge (Tundish visible).
iv) Where a single pipe serves a number of discharges, such as in blocks of flats, the number served
should be limited to not more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size large than the largest individual discharge pipe to be connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent I.e. in dwellings occupied by the blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place. Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
WARNINGS
The outlet from the Temperature & Pressure Relief Valve must not be used for any other purpose. This also applies to the Expansion Relief Valve. No other valve is to be fitted between the Cold Water Combination Valve and the cylinder.
The Temperature & Pressure Relief Valve must not be removed in any circumstances. Any of the above will totally invalidate the warranty.
- 6 -
FAULT POSSIBLE CAUSES REMEDY
1) Mains Cold Water Check and open Isolating supply shut off and/or Stop Valve. Check
water, Local Water Authority
NO HOT WATER 2) Line Strainer Turn off mains water supply, FLOW blocked remove Line Strainer and
clean
3) Cold Water Check direction of flow Combination valve arrows on valve, refit in fitted incorrectly correct position if necessary
1) Low Mains Water Check pressure, consult Pressure Local Water Authority if
necessary
REDUCED FLOW 2) Line Strainer Turn off mains water supply, RATE partially blocked remove Line Strainer and
clean
3) Size of Service Increase to size stated on Pipe too small page 4
1) Direct Immersion Check Immersion Heater, Heater is not switch on if necessary switched on
2) Direct Thermal Test Thermostat operation Cut-Out has and wiring, if faulty, operated correct/replace. Reset Cut-Out
WATER FROM 3) Boiler Programmer Check switch on Domestic HOT TAPS set to Central Hot Water if necessary IS COLD Heating only
(Indirect models)
4) Boiler is not Check boiler operation, if functioning fault suspected consult (Indirect models) Manufacturer's Instructions
5) Indirect Thermal Test Thermostat operation Cut-Out has and wiring, if faulty, operated correct/replace. Reset
Cut-Out
6) Motorised valve Check wiring and operation of jammed or not Motorised Valve correct/ wired correctly replace as necessary (Indirect models)
DISCHARGE FROM 1) Pressure above 7 Shut down boiler or immersion PRESSURE/ bar, failure of heater. Check pressure TEMPERATURE Pressure Reducing Reducing Valve and Thermal RELIEF VALVE Valve. Temperature Controls. Replace if
above 90 C failure necessary of thermal control
DISCHARGE FROM 1) Continually. Check pressure from valve. EXPANSION Pressure Reducing Replace if over 3.5 bar VALVE Valve faulty
When heater is heating Check charge of vessel. Re­Faulty Expansion charge vessel to 3.5 bar or Vessel or lost charge replace if necessary
- 9 -
FAULT FINDING
3) Close taps in turn after having purged the system of air.
4) Check for leaks around the controls and Immersion Heaters and again after the unit has heated up.
5) Check that no water is passing to waste through the relief valves.
6) Test the operation of the Temperature & Pressure Relief and Expansion Valves by lifting/turning the manually operated test lever/cap and observing that water flows through freely and safely to waste.
7) Check that the discharge pipe is plumbed so that it falls continuously and that no taps, valves or other shut off devices are installed in the pipe.
8) Check that all thermostats are set at 60°C.
9) DIRECT UNITS. Switch on Immersion Heater(s) and allow unit to heat up. Check operation of Thermostat(s).
10) INDIRECT UNITS. Fill the indirect (primary) circuit following the boiler instructions. Switch on the boiler, ensure that the programmer is to Domestic Hot Water. Allow unit to heat up and check operation of indirect thermostat on motorised valve(s).
11) Demonstrate operation to user, including operation of Temperature & Pressure Relief Valve and what to do if it operates.
12) Give this book to the user to retain for future reference and make the customer aware that periodic checks of the equipment are essential for safety.
MAINTENANCE
No longer than every 12 months, the installer should check the Magnesium Anti-corrosion Anodes (consult the label on the face of the unit for the correct location). Assessment of the condition of the bottom anode can be made by judging the condition of the top anode. If the heating element is heavily coated with scale we recommend descaling at the time of this inspection. The Expansion Vessel may need to be recharged periodically by your installer.
WARNING :
SWITCH OFF THE POWER SUPPLY BEFORE WORKING ON THE APPLIANCE.
If the Thermal Cut-Out has operated the cause must be found before resetting.
Removal of top & bottom Anodes;
1) Close the mains supply service valve.
2) Open hot water taps.
3) Attach a hose and open the drain cock and allow the cylinder to empty.
4) The anodes are removed by unscrewed using an Allen key.
EXAMINE THE ANODES AND REPLACE IF THE DIAMETER IS LESS THAN 10mm.
The use of P.T.F.E. sealing tape is recommended to ensure watertight connection for Anodes. Descale the Immersion Heater(s) and remove any lime deposit from the cylinder. Replace in reverse order. THIS DOES NOT APPLY TO COMFORT MODELS.
Check controls as per the following:-
1) Check and clean the Line Strainer before refilling the system.
2) Check pressure in Expansion Vessel and top up as necessary.
3) Check manually by lifting the test lever, the Temperature & Pressure Relief Valve.
4) Check manually by turning the test knob the Expansion Relief Valve.
5) Check discharge pipes from both Temperature & Pressure Relief and Expansion Relief Valve for obstructions.
- 8 -
FIG. 1
MODELS CONTRACT
STD 100-125-150-210 DIRECT
- 11 -
C
B
315
F
A
45
22 30'
45
ST 50-80-100 CONTRACT
STD 100-125-150-210
45
22 30'
22 30'
45
C
B
D
275
315
F
A
CONTRACT & COMFORT
STI 125-150-210
230
90˚
F
C
120
625
230
360
315
120
STDI 300 - STT 300
795
45
F
700
C
120
230
355
500 ST6 - 500 STT6
TECHNICAL DATA
For the full specification of each unit pleae consult the labels atteched to the side of the unit. Max Water supply Pressure 12.0 bar Operating Pressure 3.5 bar Expansion Vessel Charge Pressure 3.5 bar Expansion Valve Setting 6.0 bar Pressure And temperature relief valve 7.0 bar / 90° C Immersion Heater Rating for Each Heater 3000 W - 240 V. Pressure Reducing valve set pressure 3.5 bar
MODEL
STORAGE UNITS PIPES SIZE DIMENSIONS IN MM
WEIGHT
CAPACITY INLET OUTLET A B C D E F
WHEN
FULL KG
DIRECT RANGE
Wall Hung
CONTRACT ST 50 CONTRACT ST 80
CONTRACT ST 100
Floor Standing
CONTRACT STD 100 CONTRACT STD 125 CONTRACT STD 150 CONTRACT STD 210
STDI 300
500 ST6
INDIRECT RANGE
CONTRACT STI 125 CONTRACT STI 150 CONTRACT STI 210
STT 300
500 STT6 COMFORT STI 125 COMFORT STI 150 COMFORT STI 210
50 L 75 L
100 L
100 L 125 L 150 L 200 L 300 L 495 L
125 L 150 L 200 L 300 L 495 L 125 L 150 L 200 L
1/2” 3/4” 3/4”
3/4” 3/4” 3/4” 3/4” 3/4"
1”
3/4” 3/4” 3/4” 3/4”
1" 3/4” 3/4” 3/4”
410 590 550
530 700 840 990
-
-
700 840 990
-
­700 840 990
-
-
-
-
-
-
-
-
-
0.75
0.9
0.9
0.6
1.5
0.75
0.9
0.9
120 175 175
650 805 965
1280
-
-
805 965
1280
-
­805 965
1280
580 740 700
890 1045 1205 1525 1790 1870
1045 1205 1525 1790 1870 1045 1205 1525
160 230 230
-
-
-
-
-
-
675 815 815
-
­675 815 815
475 475 575
-
-
-
-
-
-
-
-
-
-
-
-
-
-
460 460 560
505 505 505 505 560 714
505 505 505 560 714 505 505 505
77 115 141
129 158 190 245 385 630
166 201 256 395 641 169 203 258
TABLE 1
- 10 -
COIL
SURFACE
m
2
MAX. 100MM
TABLE 1.1
Model
Time taken to raise temperature
from 15 C to 65C
Time taken to raise 70% of the
stored volume to 65 C
Contract STI 125*
15 mins
13 mins
Contract STI 210*
24 mins
21 mins
Comfort STI 125*
15 mins
12 mins
Comfort STI 210*
19 mins
16 mins
Contract STD 100
2 hrs 30 mins
1 hr 15 mins
Contract STD 210
1 hr 58 mins
1 hr 39 mins
* Indirectly heated. Figures obtained by WRc in accordance with Test Criteria 1-50-220 & 1-50-222.
FIG. 3
MODELS ST 50 - 80 - 100
COLD MAINS-IN
22 mm
(15 mm ST 50)
COMBINATION
VALVE
HOT
SUPPLY
22mm
(15 mm ST 50)
EXPANSION
VESSEL
PRESSURE + TEMPERATURE
RELIEF VALVE
TUNDISH
EXPANSION RELIEF PIPE
28 mm
MAX. 100 mm
- 13 -- 12 -
FIG. 2
MODELS CONTRACT - COMFORT
STI 12
5 - 150 - 210 INDIRECT
MAX. 100MM
- 14 - - 15 -
FIG. 3
MODEL STDI 300 DIRECT
FIG. 3
MODEL STT 300 INDIRECT
A
B
MAX. 100 mm
MAX. 100 mm
- 16 - - 17 -
FIG. 3
MODEL 500 ST6 DIRECT
FIG. 3
MODEL 500 STT6 INDIRECT
C D
MAX. 100MM
MAX. 100MM
FIG. 5
COLD WATER COMBINATION VALVE 1/2”
15 mm COLD MAINS IN
15 mm
TO WATER
HEATER
3/4” B.S.P. CONNECTIONS FOR EXPANSION VESSEL
EXPANSION RELIEF
VALVE (SET AT 6 BAR)
NON-RETURN
VALVE (WITHIN HOUSING)
TEE PIECE
FOR BALANCED
COLD WATER
TAKE OFF
(NOT SUPPLIED)
SERVICEABLE 1/2 PRESSURE
REDUCING CARTRIDCE AND LINE
STRAINER
- 19 -
FIG. 4
COLD WATER COMBINATION VALVE 3/4”
22 mm COLD MAINS IN
22 mm COLD MAINS IN
22 mm TO WATER HEATER
3/4” B.S.P. CONNECTION FOR EXPANSION VESSEL
22 mm TO WATER HEATER
NON-RETURN VALVE
(WITHIN HOUSING)
22 mm BALANCED COLD WATER TAKE OFF
WITH NON-RETURN VALVE
15 mm EXPANSION RELIEF OUTLET TO TUNDISH
SERVICEABLE 3/4 PRESSURE REDUCING CARTRIDGE AND LINE STRAINER (SET AT 3.5 BAR)
EXPANSION RELIEF VALVE (SET AT 6 BAR)
3.5
6 BAR
- 18 -
FIG. 7
SUGGESTED WAYS OF TERMINATING
DISCHARGING PIPES SAFETY
- 21 -
FIG. 6
300L AND 500LONLY
RETURN
FLOW
DRAIN
NON-RETURN
FROM BRONZE
PUMP
SECONDARY
RETURN
- 20 -
500 mm Max.
300 mm Min.
Temperature & pressure relief valve
Metal discharge pipe (D1) from temperature & pressure relief valve. to tundish.
Metal discharge pipe (D2) from tundish with continuous fall. See Table 2 and worked example.
Tundish
Fixed grating
Trapped gulley
Discharge below fixed grating. (see page 6 for alternative points of discharge).
Valve outlet size Minimum size of
discharge pipe D1*
Minimum size of
discharge pipe D2*
from tundish
Maximum
resistance allowed,
expressed as a
length of pipe (i.e.
no elbow or bends)
Resistance created
by each elbow or
bend
G ½ 15 mm 22 mm
28 mm 35 mm
Up to 9 m Up to 18 m Up to 27 m
0.8 m
1.0 m
1.4 m
G ¾ 22 mm 28 mm
35 mm 42 mm
Up to 9 m Up to 18 m Up to 27 m
1.0 m
1.4 m
1.7 m
G 1 28 mm 35 mm
42 mm 54 mm
Up to 9 m Up to 18 m Up to 27 m
1.4 m
1.7 m
2.3 m
Table 2. Sizing of copper discharge pipe “D2” for common temperature valve outlet sizes.
WORKED EXAMPLE
The example below is for a G ½ Temperature & Pressure Relief valve with a discharge pipe (D2) having 4 no. elbows and length of 7m from the Tundish to the point of discharge.
From Table 2 Maximum resistance allowed for a straight length of 22mm copper discharge pipe (D2) from G ½ T & P valve is 9m. Subtract the resistance for 4 no. 22mm elbows at 0.8m each = 3.2m. Therefore the maximum permitted length equates to: 5.8m. As 5.8m is less than the actual length of 7m therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28mm pipe (D2) from G ½ T & P valve equates to: 18m. Subtract the resistance for 4 no. 28mm elbow at 1.0m each = 4m. Therefore the maximum permitted length equates to: 14m As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
FIG. 9
a) SINGLE ELEMENT
RECOMMENDED ECONOMY 7 SYSTEMS
THERMAL CUT-OUT
PIPES
THERMOSTAT POCKET
L1
N
THERMOSTAT
DAY ELEMENT 3 KW 240 V
THE IMMERSION HEATER SHALL BE INSTALLED WITH 85°C RUBBER INSULATED HOFR-SHEATHED FLEXIBLE CORDS COMPLYING WITH TABLE 8 OF BS 6141 : 1981
THE FOLLOWING DRAWING MUST BE REFERRED TO BEFORE THE SIDE MOUNTED IMMERSION HEATER IS REPLACED.
WALL
DIAG. 4
- 23 -
FIG. 8
RECOMMENDED ECONOMY 7 SYSTEMS
SYSTEM A
SYSTEM B
- 22 -
FIG. 11
SCHEME OF ELECTRICAL CONNECTIONS WITH 2 MOTORISED VALVES 2 WAY
T6360B
ROOM
THERMOSTAT
14 35 22
OR
CM 41 CM 51
A
B
1
5
V4043H
HEATING VALVE
BROWN
5
BLUE
2
GREY
1
ORANGE
10
GREEN/YELLOW
3
V4043H
HOT WATER VALVE
BROWN
8
BLUE
2
GREY
1
ORANGE
10
GREEN/YELLOW
3
Honeywell ST 699B 1002
63 N L
Link L-5-8
ST 6400/ST 6300 ST 6200 3 4 N L
Drayton Tempus 7 3 4 N L
Horstmann 425, 525, 527
14 ENL
Link L-2-5
Landis & Gyr RWB2
34 N L
Glowworm Mastermind
Landis & Gyr RWB20
34 N L
Microgyr
Potterton Miniminder 3 4 N L
Potterton EP2000/3000 - 3 4 N L
Link L-5 EP2001/3001
Randall 102/102 E 1 2 E 5 6
Link 3-6
Randall 4033
42 E76
Link 1-6
Randall 701, 702
31 ENL
Link L-6-5
Sangamo M5 1 8 E 4 3
Link 1-6
Sangamo 410 Form 1
18 E4 3
Link 3-6
PROGRAMMER
64321
Pegler Sunvic
25 ENL
SP 50/100 (Link L-3)
Switchmaster
14 N L
Symphony, Sonata
Switchmaster 400, 600 3 1 N L
SWITCHMASTER 805, 900
31 N L
Sunvic ET 1451
74 E1 2
Link 2-3-6
Sunvic DHP 2201 6 3 E 1 2
Towerchron FP
610 2 1
Link 1-5/4-7-9
Towerchron MP
610 2 1
Link 1-4/6-11
Towerchron 2000 HW HTG
NL
ON ON
ACL LS522, LS722 3 4 N L
Randall 922, 972
36 ENL
Link L-2-5
Randall 3020 P
42 ENL
and 3060
PROGRAMMER
64321
Basic Boilers (see Page 27) L E N L N E
Barlo Balmoral 45F, 55F, 65F 9 6 10 11 12 L N E
Barlo Blenheim 30BF To 75BF LP 2 E N L L N E
Baxi Solo 30PF To 70PF PL SL E N L L N E
Glowworm Economy 24
7 SL E N L L N E
(remove link SL-9)
Glowworm Economy 30B To 50B
9 12 E 10 11 L N E
range (remove link 12-7)
Glowworm Fuelsaver MKII & F
9 12 E 10 11 L N E
range (remove link 12-7)
Glowworm Fuelsaver BR & R
7 SL E N L L N E
range (remove link SL-9)
Glowworm Spacesaver KFB50
9 12 E N L L N E
(remove link 12-7)
Glowworm Spacesaver 75
581 325 46
(remove link 7-8)
Ideal Excell
Ideal Turbo 2 LP LB E N L L N E
Ideal Mexico Super 2
Myson Apollo
(remove all links)
PL ON E N L L N E
Myson Olympic (Use RED Plug)
(remove all links)
Myson Orion (After SEPT 88)
PL 4 E N L L N E
(remove all links)
Myson Economist Ro Ri E N L L N E
Potterton Flamingo (After June 89) PL SL E N L L N E
Potterton Netaheat 16-22 (Link 7-8) 6 7 E N L L N E
Potterton Netaheat Profile PL SL E N L L N E
For Vaillant VC/VCW and
Vokera 12-48 RSE contact office
for special wiring diagram
BOILER PUMP
9 10 3 2 1 9 10 2 3
1
P
Cylinder
thermostat
Thermal
cut-out
ELEMENT
3 KW 240V
~
Thermal
cut-out
Thermostat
1
8
6
Not used
L1
240V~
N
P
2
1 P
2
240V
MAINS INPUT (3 AMP)
L1 N2 E3
240V
MAINS INPUT (13 AMP)
E L N
• 1
• 2
• 3
• 4
• 5
• 6
• 7
• 8
• 9
• 10
TYPICAL
JUNCTION BOX
- 25 -
FIG. 10
For 300 L modles only
a) SINGLE ELEMENT
RECOMMENDED ECONOMY 7 SYSTEMS
THERMAL CUT-OUT
L2
N
L1
N
THERMOSTAT
DAY ELEMENT 3 KW 240 V
~
NIGHT ELEMENT 3 KW 240 V
~
ECONOMY 7
THE IMMERSION HEATER SHALL BE INSTALLED WITH 85°C RUBBER INSULATED HOFR-SHEATHED FLEXIBLE CORDS COMPLYING WITH TABLE 8 OF BS 6141 : 1981
THE FOLLOWING DRAWING MUST BE REFERRED TO BEFORE THE SIDE MOUNTED IMMERSION HEATER IS REPLACED.
DIAG. 4A
THERMOSTAT MOUNTED
ON THE TOP
THERMAL
CUT-OUT
THERMOSTAT
- 24 -
Basic Boiler List
Baxi Bermuda range
Boston RS and OF range
Glowworm Complheat
Hideaway range 65 - 80 Ultimate 40 - 80
30B - 80B, 30CF - 60CF
Halstead Buckingham range
Potterton Kingfisher range
Statesman range (oil fired)
Caradon Ideal Classic range
Mexico Ssper range Mexico Slimline range
Newflame Boilers Backboiler range
Condensing Boiler List
CARADON IDEAL Minimiser FF30 - FF80 L E N GLOWWORM Energysaver (Remove link SL-9) PL SL E N L KESTON L E N POTTERTON Envoy 30F - 80F PL SL E N L
refer to
VAILLANT VU 186, 226 manufacturers
instructions
Boiler Connections
2 Motorised values 2 way (see fig. 11) 9 10 3 2 1 1 Motorised value 3 way (see fig. 12) 9 8 3 2 1
Pump Connections
2 Motorised values 2 way (see fig. 11) 9 3 2 1 Motorised value 3 way (see fig. 12) 9 3 2
- 27 -
FIG. 12
SCHEME OF ELECTRICAL CONNECTIONS WITH MOTORISED VALVE 3 WAY
V4043A
MID. POS. VALVE
WHITE
5
BLUE
2
GREY
7
ORANGE
8
GREEN/YELLOW
3
Honeywell ST 699B 1002
76 3 NL
Link L-5-8
ST 6400/ST 6300 1 3 4 N L
ST 6200 3 4 N L
Drayton Tempus 7 1 3 4 N L
Horstmann 425, 525, 527
31 4E NL
Link L-2-5
Landis & Gyr RWB2
13 4 NL
Glowworm Mastermind
Landis & Gyr RWB20
13 4 NL
Microgyr
Potterton Miniminder 1 3 4 N L
Potterton EP2000/3000 - 1 3 4 N L
Link L-5 EP2001/3001
Randall 102/102 E 1 2 E 5 6
Link 3-6
Randall 4033
54 2E 76
Link 1-6
Randall 701, 702
43 1E NL
Link L-6-5
Sangamo M5 1 8 E 4 3
Link 1-6
Sangamo 410 Form 1
21 8E 43
Link 3-6
PROGRAMMER
764321
Pegler Sunvic
12 5E NL
SP 50/100 (Link L-3)
Switchmaster
31 4 NL
Symphony, Sonata
Switchmaster 400, 600 3 1 N L
SWITCHMASTER 805, 900
43 1 NL
Sunvic ET 1451
87 4E 12
Link 2-3-6
Sunvic DHP 2201 8 6 3 E 1 2
Towerchron FP
86 10 21
Link 1-5/4-7-9
Towerchron MP
610 21
Link 1-4/6-11
Towerchron 2000 HW HW HTG
NL
OFF ON ON
ACL LS522, LS722 1 3 4 N L
Randall 922, 972
13 6E NL
Link L-2-5
Randall 3020 P
42ENL
and 3060
PROGRAMMER
764321
Basic Boilers (see Page 27) L E N L N E
Barlo Balmoral 45F, 55F, 65F 9 6 10 11 12 L N E
Barlo Blenheim 30BF To 75BF LP 2 E N L L N E
Baxi Solo 30PF To 70PF PL SL E N L L N E
Glowworm Economy 24
7 SL E N L L N E
(remove link SL-9)
Glowworm Economy 30B To 50B 9 12 E 10 11 L N E
range (remove link 12-7)
Glowworm Fuelsaver MKII & F 9 12 E 10 11 L N E
range (remove link 12-7)
Glowworm Fuelsaver BR & R 7 SL E N L L N E
range (remove link SL-9)
Glowworm Spacesaver KFB50 9 12 E N L L N E
(remove link 12-7)
Glowworm Spacesaver 75
581 325 46
(remove link 7-8)
Ideal Excell
Ideal Turbo 2 LP LB E N L L N E
Ideal Mexico Super 2
Myson Apollo
(remove all links)
PL ON E N L L N E
Myson Olympic (Use RED Plug)
(remove all links)
Myson Orion (After SEPT 88)
PL 4 E N L L N E
(remove all links)
Myson Economist Ro Ri E N L L N E
Potterton Flamingo (After June 89) PL SL E N L L N E
Potterton Netaheat 16-22 (Link 7-8) 6 7 E N L L N E
Potterton Netaheat Profile PL SL E N L L N E
For Vaillant VC/VCW and
Vokera 12-48 RSE contact office
for special wiring diagram
BOILER PUMP
9 8 3 2 1 9 8 2 3
240V
MAINS INPUT (3 AMP)
L1 N2 E3
240V
MAINS INPUT (13 AMP)
E L N
- 26 -
T6360B
ROOM
THERMOSTAT
14 35 22
OR
CM 41 CM 51
A
B
1
5
ELEMENT
3 KW 240V
~
Thermal
cut-out
Thermostat
L1
240V~
N
• 1
• 2
• 3
• 4
• 5
• 6
• 7
• 8
• 9
• 10
TYPICAL
JUNCTION BOX
1
P
Cylinder
thermostat
Thermal
cut-out
1
8
6
Not used
P
2
1 P
2
928 238/02
Guarantee
We, MTS, guarantee that should this water heater prove to be defective by reason of faulty workmanship or material during the periods stated below, we will replace the defective parts (or product) free of charge on the condition that :
• The appliance has been correctly installed by a competent installer and used only on the supply voltage stamped on the rating plate.
• The appliance has been used and maintained in accordance with these instructions and has not been tampered with or otherwise subjected to misuse neglect or accident.
• The appliance has not been taken apart, modified or repaired except by a MTS authorised Service Engineer*.
• Evidence of the date of purchase in the form of an invoice receipt (or hire purchase documents) is not included with the appliance returned under guarantee.
The guarantee will be applicable from the date of purchase or commencement of hire purchase for the following periods :
On Contract models:
• 12 months on electrical parts and components
• 3 years on the cylinder tank On all other models:
• 12 months on electrical parts and components
• 5 years on the cylinder tank * Important : the guarantee period on the tank will apply only if the annual
inspection will have been carried out by a MTS authorised Service Engineer. * A MTS authorised Service Engineer is :
1. the installer of the appliance.
2. a MTS approved Service Centre
3. an engineer who has attended a MTS training course in unvented storage water heaters.
Manufactured by MTS Benelux sa/nv
Zone industrielle 5020 MALONNE (BELGIQUE) Tél. : (81) 448 311 Fax : (81) 448 400 Télex : 59345 Thorfa B
Commercial subsidiary MTS (GB) LIMITED
MTS Building Hughenden Avenue High Wycombe Bucks HP 13 5 FT Telephone: (01494) 755600 Fax: (01494) 459775
Technical Service Hotline : (01494) 539579
Loading...