TROUBLE SHOOTING D-060-C
SYMPTOM CAUSE CORRECTIVE ACTION
Paint chipped off and valve rejected by customer
The valve was thrown around in shipping or the packing was broken and the paint will crack to the metal base.
Valve leaking from automatic S-050-C
Flange bolt pattern does match pipe connection.
Valve slams shut when pumps start
Float full of water and valve does not seal
Valve leaking from middle seal, between body and cover.
Valve does not close and water is flowing out.
This may occur at start-up of a new system if the contractor did not flush the line before startup. There is some debris chamber of the rolling seal.
1) The flange is Multi-standard and the customer is not familiar with this bolt pattern.
2) The wrong flange was sent from factory.
The line pressure from the pump start up creates greater pressure under the valve and the float is closed by differently air pressure, instead of by water.
Defect in float weld
O-ring not in place, or the sealing disc is not in place in the top cover. This occurs when the valve has been opened before installation, or if there is a defect in the casting.
Valve is flooded at start-up by high pressure differential and drowns the float.
Instruct the end user to open the S-050-C and clean it out, and put it back in service. This requires ability of the Rep to explain, or to this for the customer . Inquire as to valve size, to determine if the flange is multi­standard. If so explain to customer. If the flange is not multi-standard, obtain template of bolt pattern with dimensions from the customer, in order to determine ASA standard. Replace valve as needed. We recommend using a NS, or a larger valve. We recommend ARIavCAD analysis of system. Check if the S-050-C continues to release air after the kinetic float shuts, and pass all information on to ARI for determining correct valve.
Check line pressures and water hammer problems with the end user, and replace the float. Recommend the poly­carbonate float. Or NS valve. Adjust seal to set in place. Check the o-ring seal, and sealing disc of the float assembly for damage. If damaged - replace valve.
Check variable speed pumps sequence. This may affect the line pressure under the valve. Also this phenomenon can occur if the pipeline connection is smaller than the orifice of the valve.