A.R.I. D014, D016 User Manual

Installation and Maintenance of A.R.I.’s D-014, D-016 Combination Air Valves
A. Installation
A.1
The air valve will be mounted on a riser, connected to the top of the pipe.
A.2 An isolating valve will be installed below the
air valve.
B. Basic, Periodic, Maintenance
B.1 Shut the isolating valve below the air valve. B.2 Unscrew the cover’s bolts of the
automatic air valve (10) slowly,to release accumulated pressure .
B.3 Remove the plastic cover of the
automatic a.r.v. (1) with screwdriver , clean the orifice (4) with flowing water and with thin copper wire . Wash the inside of the body(12), the float(11), and the Rolling Seal (6), with clean water .
B.4 Check to make sure the Rolling Seal is
unharmed (not torn or cracked) .
B.5 Reinstall in reverse order and fasten
and tighten all bolts. Make sure to re­assemble all the components correctly.
B.6 Unscrew the bolts (20) that connect the
main valve cover (14) to its body (18).
B.7 Wash the body and the cover in clean
water in order to remove coarse grime or accumulated scale.
B.8 Reinstall in reverse order and fasten
and tighten all bolts. Make sure to re-
assemble the upper air valve correctly: B.9 Open the isolating valve beneath the air valve.
Tel. 972-4- 6761980 Fax.972-4- 6763402
A.R.I FLOW CONTROL ACCESSORIES
D. Troubleshooting
PROBLEM CAUSE SOLUTION
Leak From the Small Orifice
Leak From the Large Orifice
a. Dirt particles
stuck in the
orifice
b. Rolling Seal
torn
Dirt particles stuck on the orifice seal, on the orifice seat, b. Shut the isolating valve, unscrew the or on the float. air valve cover bolts, remove the cover, and
a. Shut the isolating valve, wait a minute, and
open it again, very fast. If leaking continues, go to b.
b. Shut the isolating valve, Unscrew the cover
bolts of the automatic air valve, slowly, to release accumulated pressure. Remove the plastic cover with a screwdriver and clean the orifice with flowing water and with a thin copper wire. Wash the inside of the body, the float, and the Rolling), with clean water
c. Check to make sure the Rolling Seal is
unharmed (not torn or cracked). Replace the
Rolling Seal if needed. a. Shut the isolating valve, wait a minute, and open it again, very fast. If leaking continues, go to b.
remove float. Check if the seal, the seat, or
the float are dirty, and clean them.