WARNING: If the information in this manual is
not followed exactly, fire or explosion may result
causing property damage, personal injury or loss
of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS:
SN 5170 AND UP
SN 5170 AND UP
For use with Natural Gas or Propane*
USERS’ INSTALLATION
OPERATION and
MAINTENANCE MANUAL
* Do not try to light any appliance.
* Do not touch any electrical switch; do not use
any phone in your building.
* Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
* If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
Installer: Please leave this manual with the appliance owner for future reference
7116 Beatty Dr
Mission, BC V2V 6B4
Canada
This appliance may be installed in an after-market,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by local
codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a
certified kit is used.
*Conversion Kit Required for Propane Use
September 2010
200-0185
STATE OF MASSACHUSETTS REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to
decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas
fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm
and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30)
day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DI-
RECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA
54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of
Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting
system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the
flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include
a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.
For the State of Massachusetts, installation and repair must be done by a
plumber or gasfitter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in
length.
The State of Massachusetts requires the installation of a carbon monoxide alarm
in accordance with NFPA 720 and a CO alarm with battery back up in the same
room where the gas appliance is installed.
INTRODUCTION
Congratulations on choosing an Archgard fireplace!
The Optima 45 is one of the most advanced direct vent fireplace heaters available. It is solidly
designed using the latest technology and manufactured to the highest quality. It is our aim to
provide you with an appliance for many trouble-free years of reliable service.
The following are just some of the many features within your new gas fireplace:
Heater Classification The Optima 45 is classified as a heating appliance. In
conjunction with an optional thermostat, the Optima 45 can
be operated continuously for zone heating.
High Efficiency The Optima 45 has one of the highest efficiencies of any gas
fireplace, which means that it is less expensive to operate.
Adjustable Fan Speed Heat circulation fan can be fully adjusted from high, medium or
low speeds to suit your comfort level.
Adjustable Flame The flame aesthetics and heat output can be adjusted to suit
your heating needs.
Solid Construction The Optima 45 is constructed mainly of 14 and 18 gauge
galvanized and aluminized steel for long life and durability.
Millivolt Control System The gas control system is “thermostat-ready” for any optional
millivolt wall thermostat or wireless remote control.
Please read this manual carefully prior to installation and operation of the appliance.
Proper installation, operation and maintenance of the appliance will provide you with
many years of enjoyment.
We recommend you record the following information:
Fireplace Model Number: 45-DVFS28N-2 Serial Number:
Date of Installation:
Type of Gas Used by the Fireplace: Natural Gas Propane
Venting - Vertical Termination using Simpson DuraVent Pipe
Venting - Horizontally using Archgard Vent Kit (45-TVKFS)
Venting - Below Grade using Archgard Snorkel Kit (999-DV-STC)
Venting - Horizontally using Simpson DuraVent Direct Vent Systems
Log Placement
Optional Wall Switch or Thermostat / Valve Connection
Final Installation Check / Initial Operation
5
6
7
8
9
10
11
12
14
15
17
18
19
22
27
28
First Fire / Lighting Instructions
Lighting Instructions on Rating Plate
Glass Door Removal / If your Glass Breaks
Troubleshooting Guide
Maintenance / Cleaning the Appliance
Servicing Under Warranty / Adjusting Primary Air
Changing Main Burner Orifice
Checking Inlet & Outlet Gas Pressure / Adjusting Pilot / Convertible Pilot Orifice
Replacing Convection Blower / Wiring Diagram
Valve Tray Assembly / Parts List
Parts List - Ceramic Logs & Burner Pan
Replacement Parts List
Archgard Warranty
Frequently Asked Questions
Notes
Warranty Registration Card
29
30
31
32
34
35
36
37
38
39
40
41
42
43
44
46
45-DVFS28N-2 5
CAUTION
FOR YOUR SAFETY - Do not install or operate your Archgard Optima 45 Direct Vent Gas
Fireplace without reading and understanding this manual. Any installation or operational
deviation from this instruction manual voids the Archgard Industries Warranty and may prove
hazardous.
This appliance must be installed by a qualified gas installer and the installation must conform to
the installation codes.
Provide adequate clearance around air openings of the appliance.
Never obstruct front openings.
Provide adequate clearances for proper operation and servicing of the appliance.
This appliance must be properly connected to an approved venting system and must not be
connected to a chimney flue serving a separate solid fuel burning appliance.
SAFETY
Due to high temperatures, the appliance should be located out of traffic and away from furniture
and draperies.
Children and adults should be alerted to the hazards of high surface temperature and stay
away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the
appliance.
Clothing or other flammable material should not be placed on or near the appliance.
Do not operate with cracked or broken glass. Be careful not to strike or slam the glass.
Any safety screen or guard removed for servicing an appliance must be replaced prior to
operating.
Installation and Repair should be done by a qualified service person. The appliance should be
inspected before use and at least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting, bedding materials, et cetera. It is
imperative that the control compartments, burners and circulating air passageways of the
appliance are kept clean.
45-DVFS28N-2 6
APPLIANCE CERTIFICATION
This appliance is tested and safety approved under the following US and Canadian gas
appliance standards:
- ANSI Z21.88b-2003 / CSA 2.33b-2003, Vented Gas Fireplace Heaters
- CAN/CGA-2.17-M91, Gas-Fired Appliances for Use at High Altitudes
Please contact Archgard Industries Ltd., if you have any questions regarding the certification of
this appliance.
INSTALLATION CODES
This appliance must be installed by a qualified gas appliance installer. The installation must
conform with the local codes or, in the absence of local codes, with the current National Fuel Gas
Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code, CAN/CGA-B149, in Canada.
Electrical connections and grounding must conform with local code, or current National Electrical
code, ANSI/NFPA No. 70-1987, in the US and in Canada, the current Canadian Electrical Code,
CSA C22.1.
We recommend that our gas hearth products be installed and serviced by professionals
who are certified in the U.S. by the National Fireplace Institute®(NFI) as NFI Gas
Specialists
SPECIFICATIONS
Manifold Pressure
Minimum Supply
Pressure for Purpose of
Input Adjustment
Nominal Input Rating
Orifice Size
Altitude
Primary Air Opening
1.6 - 3.5 in. W.C. (0.4 - 0.9 kPa) 6.3 - 10.0 in. W.C. (1.6 - 2.5 kPa)
Natural Gas (NG) Propane (LP)
4.5 in. w.c. (1.2 kPa) 11.0 in. w.c. (2.8 kPa)
18,750 - 28,000 BTU/hr
(5.5 - 8.2 kW)
#38 DMS (2.64 mm dia.) #52 DMS (1.60 mm dia.)
0-4500 ft (0 - 1372 M) 0 - 4500 ft (0 - 1372 M)
3/16” (5 mm) 3/8” (9 mm)
19,600 - 28,000 BTU/hr
(5.7 - 8.2 kW)
HIGH ALTITUDE INSTALLATION
When installing this appliance beyond 4500 ft. (1372 M) above sea level, the appliance must
be properly de-rated and installed according to local codes, in the absence of local codes, with
the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code,
CAN/CGA-B149, in Canada.
45-DVFS28N-2 7
GAS CONNECTIONS
Before connecting the appliance to the gas supply line, double check that the appliance you
have purchased is designed for the gas type you are using. The gas type markings are located
on the certification label and also on the appliance’s gas valve.
Adequate clearance for proper installation and checking of the gas connections must be
provided. All gas connections must be checked for gas leaks.
Have your gas supplier or a qualified gas fitter run a gas supply line into the heater. The line
must be properly sized and fitted according to the installation codes. Immediately upstream of the
supply connection, the fitter shall provide an accessible manual shut-off valve and a ⅛” (3 mm)
NPT plugged tapping accessible for connection to a test gauge. When connecting the supply line
to the gas valve, the installer shall brace the gas valve to ensure that gas valve is not moved from
its bracket. If the valve is not braced when the supply line is connected, the valve may be moved
and cause a “break” in the main burner supply line. Such damage is not covered by the
manufacturer’s warranty.
CAUTION: The appliance and its individual shutoff valve must be disconnected from the gas
supply piping system during any pressure-testing of that system at test pressures in excess of ½
psig (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure-testing of the gas supply piping system at
test pressures equal to or less than ½psig (3.5 kPa). Failure to do so will damage the appliance’s gas valve. Such damage is not covered by the manufacturer’s warranty.
Natural Gas Pressure Settings:
The inlet supply or line pressure must be a minimum of 4.5” w.c. (1.1 kPa) and a maximum of 8”
w.c. (2 kPa). The orifice is a #38 DMS (2.64 mm) drill size.
ELEVATION INPUT RATING
0-4500 ft (0-1372 M) 28,000 BTU/hr (8.2 kW)
4500 ft (1372 M) and above 28,000 BTU/hr (8.2 kW) less 4% per 1000 ft. (305 M)
Please contact your local utility company or distributor for the appropriate orifice size you require.
Propane Pressure Settings:
The inlet supply or line pressure must be a minimum of 11” w.c. (2.8 kPa) and a maximum of 14”
w.c. (3.5 kPa). The orifice is a #52 DMS (1.60 mm) drill size.
ELEVATION INPUT RATING
0-4500 ft. (0-1372 M) 28,000 BTU/hr (8.8 kW)
4500 ft. (1372 M) and above. 28,000 BTU/hr (8.8 kW) less 4% per 1000 ft. (305 M)
Please contact your local utility company or distributor for the appropriate orifice size you require
NOTE: THE INPUT RATING SHOULD ALWAYS BE CHECKED WHEN FIRST RUNNING THIS
APPLIANCE. To do this, reduce the background flow rate, time the meter, light the fireplace and
take another reading after 15 minutes of operation. Check with your gas supplier for the gas BTU
content at your elevation. Input is the rate of flow multiplied by the heating value of the gas (cubic
feet/hour x BTU per cubic feet). Adjust the manifold pressure so that the unit does not operate
above the rated input.
45-DVFS28N-2 8
APPLIANCE DIMENSIONS
DIMENSIONS
A HEIGHT 30” (762 mm)
B WIDTH 27” (685 mm)
C DEPTH 17 ½” (444 mm)
A
B
C
APPLIANCE DESCRIPTION
UPPER LOUVERS
GLASS DOOR
LOWER LOUVERS
MAIN CONTROL PANEL
45-DVFS28N-2 9
DIMENSIONS AND CLEARANCES
TOP VIEW
11” (280 mm)
4” (101 mm)
STRAIGHT INSTALLATION CORNER INSTALLATION
ALCOVE INSTALLATION
BACKWALL
4” (101 mm)
11” (280 mm)
4” (101 mm)
SIDEWALL
SIDE VIEW
2” (50 mm) to top, 1” (25 mm) to
bottom and side surfaces of the vent
1” (25 mm) to the surface of the vent
24” (610 mm) minimum clearance
required from top of the appliance
to a combustible material
NOTE: The Optima 45 does not
require a non-combustible
hearth pad and can be installed
directly on the floor.
BACKWALL
4” (101 mm) minimum
clearance required
FLOOR
* Side and back clearances for the alcove installation is the same as the straight and the corner installations
45-DVFS28N-2 10
LOCATING GAS HEATER
This appliance must be installed in a location that is free of plumbing, electrical wiring and
heating or air conditioning ducts. Select a location that is accessible for venting.
See ALLOWABLE TERMINATION LOCATIONS listed in this manual.
NOTE: See venting chart for maximum and minimum vertical/horizontal venting configurations.
VENT TERMINATION LOCATIONS
1. See ALLOWABLE TERMINATION LOCATIONS and establish a suitable vent termination location.
2. In heavy snowfall areas make sure the vent termination is located where it can not be blocked by snow and from snowfall or snow removal equipment.
3. Locate the vent termination away from plants, bushes or any other object near the vent termination
that will interfere or obstruct the air flow around it.
4. DO NOT recess vent termination into walls, sidings or planters.
5. Vent terminations located below 7ft (2.13 M) from grade level or anywhere that it can be a burn
hazard to the public, such as patios and balconies, must be protected with an approved termination
cage. If using Archgard Venting System order (Part # 999-DV-SC).
45-DVFS28N-2 11
ALLOWABLE TERMINATION LOCATIONS
zontally
within 10 feet (3 m) hori-
12 inches (30 cm) 9 inches (23 cm)
supply inlet to building or the
6 feet (1.83 m) 3 feet (91 cm) above if
combustion air inlet o any other
appliance
7 feet (2.13 m) + *
air supply inlet
12 inches (30 cm) ++ *
Code
(1) In accordance with the current CSA B149.1, National Gas and Propane Installation
sidewalk or paved driveway
located on public property
porch, deck, or balcony
(2) In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code (+) A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and serves both dwellings (++) Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. (*) For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, “Clearances shall be in accordance with local installation codes and the requirements of the gas supplier.”
*
* * L= Clearance above paved
12 inches (30 cm) 12 inches (30 cm) J= Clearance to non-mechanical air
Canadian Installations (1) US Installations (2) Canadian Installations (1) US Installations (2)
A= Clearance above grade,
veranda, porch, deck, or
12 inches (30 cm) 12 inches (30 cm) K= Clearance to a mechanical
balcony
B= Clearance to window or
door that may be opened
C= Clearance to permanently
* * M= Clearance under veranda,
above the
3 feet (91 cm) *
height 15 feet (4.5 m)
3 feet (91 cm) within a
meter/regulator assembly
closed window
D= Vertical clearance to
ventilated soffit located
above the terminal within a
horizontal distance of 2 feet
(61 cm) from the center line
of the terminal
E= Clearance to unventilated soffit * *
F= Clearance to outside corner * *
G= Clearance to inside corner 9” (22.5cm)9” (22.5cm)
H= Clearance to each side of
center line extended above
meter/regulator assembly
L= Clearance to service
regulator vent outlet
45-DVFS28N-2 12
APPROVED VENT COMPONENTS
The appliance will not function without being connected to a proper venting system. This appliance
may only use direct vent system supplied by Archgard, or Simpson Dura-Vent direct vent systems
with the appropriate Adaptor dependent upon the venting guidelines within this manual.
NOTE: Only venting components listed below are approved for the Optima 45-3
PART # DESCRIPTION
45-TVKFS Archgard Top Vent Kit. Kit includes 9 ft (2.74 M) of 4” (101 mm) gas flex
liner, 36” (914 mm) of 7” (178 mm) black stove pipe, 24” (610 mm) of
7” (914 mm) black stove pipe, 90o deg. black elbow, wall sleeve, firestop
and horizontal termination cap (TK-1)
999-DV-HTC Archgard Horizontal termination head only
999-DV-SC Archgard Safety Cage for Horizontal termination head
999-DV-VSD Archgard Vinyl siding deflector
999-DV-STC Archgard Snorkel termination head only
999-DV-SDA Adapter, Appliance to Simpson Dura-Vent
VENTING CONNECTION
For best and safe venting performance, here are some general venting rules:
Use only Archgard or Simpson Dura-Vent direct vent systems and components.
Maintain a minimum of 1” (25 mm) clearance to combustibles from the outside surfaces of
vertical vents and minimum of 1” (25 mm) sides and bottom, and 2” (50 mm) from top surfaces
of horizontal vents.
Observe local code restrictions, if any, regarding the installation of this type of gas appliance.
Observe the venting charts given in this manual
Use vent spacers between the inside 4” (101 mm) and outside 7” (178 mm) vents at 3 ft (915
mm) intervals (Archgard Direct Vent System ONLY).
Never slope horizontal vents downwards, towards the vent termination.
Maintain a minimum ¼” rise (6mm) for every linear foot (305 mm) of horizontal vent.
Terminate (Horizontally) the vent only with an approved vent termination supplied by Archgard
Part # 999-DV-HTC or Simpson Dura-Vent Termination Cap.
Terminate (Vertically) the vent only with Simpson Dura-Vent Vertical Termination Cap.
Support horizontal vents every 3 ft (915 mm) to prevent sagging.
Please, strictly follow the venting instructions for optimum performance from
the appliance, and to avoid sooting and/or service calls.
45-DVFS28N-2 13
VENTING CHART
The appliance will not function without being connected to a proper venting system. This
appliance may only use direct vent system supplied by Archgard, or Simpson Dura-Vent
direct vent systems with Archgard SDA-U adapter.
7.93 M
7.32 M
6.71 M
V
E
R
T
I
C
A
L
H
E
I
G
H
T
6.10 M
5.49 M
4.88 M
4.27 M
3.66 M
3.05 M
2.44 M
1.83 M
1.22 M
610 mm
610
mm
1.22 1.83 2.44 3.05
No restrictors are to be used in
vertical or sidewall vent installations.
Note: No Installations are permitted outside of this range.
3.66
Meters
Feet
A minimum of 3’ (914 mm) of vertical vent to center of elbow is required for a maximum horizontal
run of 3’ (914 mm).
Chart is for one 90° bend, with ¼” (7 mm) vertical raise minimum per foot of horizontal length.
For each additional 90° or two 45°, add one foot of vertical height.
Maximum three 90º bends, or equivalent.
Minimum 2 ft (610 mm) straight length between bends.
VENTING ABOVE ROOF OF THE HOUSE USING A VERTICAL TERMINATION
Use Simpson Dura-Vent listed direct vent system caps for all vertical vent termination
applications (through the roof).
Please strictly follow the venting instructions for optimum performance
from the appliance and to avoid sooting and/or service calls.
45-DVFS28N-2 14
VENTING - VERTICAL TERMINATION USING SIMPSON DURA-VENT PIPE
The Optima 45 can be vented vertically using Simpson Dura-Vent Direct Vent System. To vent
using Simpson Dura-Vent exclusively, you must use the Archgard 999-DV-SDA Adaptor and connect the adaptor to the top of flue outlet on the Optima 45 gas fireplace.
1. Maintain 1” (25 mm) clearance (air space) to combustibles when passing through ceilings
walls, roof, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air
spaces with insulation. Check page 13 (Venting Chart) for the maximum vertical rise of the
venting system.
2. Set the gas appliance in its desired location. Drop a plum bob down from the ceiling to the
position of the appliance flue exit, and mark the location where the vent will penetrate the
ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof.
NOTE: you may wish to relocate the appliance to avoid cutting load-bearing members.
3. A Firestop spacer must be installed in the floor or ceiling of every level. To install the
Firestop spacer in a flat ceiling cut a 10” (254 mm) square hole. Frame the hole as shown
Fig. 1 and install the firestop.
4. Assemble the desired lengths of pipe and elbows as outlined in the Venting Chart, necessary to reach from the Appliance adaptor (999-DV-SDA), if using Simpson Dura-Vent from
the appliance up through the roof. Ensure that all Simpson Dura-Vent and/or flexible is connected and sealed accordingly.
5. Cut a hole in the roof centered on the small drill hole placed in the roof as outlined in Step 2.
6. The hole should be of sufficient size to meet the minimum requirements for each combusti-
bles of 1” (25 mm). Slip the flashing under the shingles (shingles should overlap half of the
flashing) as per Fig.2.
7. Continue to assemble pipe lengths and/or flexible gas venting.
8. Ensure vent is vertical and secure the base of the flashing to the roof with roofing nails,
slide storm collar over the section and seal with a mastic.
9. Install the vertical termination cap by twist-locking it.
NOTE: Apply high temperature sealant to inner and outer pipe on every Simpson Dura-Vent
twist-lock joint. See Fig. 3
10” (254mm)
square hole
framing
firestop
spacer
Fig. 1 Fig. 2
Female
Locking Lugs
Male
Locking Lugs
Sealant
Fig. 3
45-DVFS28N-2 15
VENTING - VERTICAL TERMINATION USING SIMPSON DURA-VENT PIPE
NOTE:
Galvanized pipe is desirable above the roofline
due to its higher corrosion resistance. Continue
to add pipe sections throughout the flashing until
the height of the vent cap meets the minimum
height requirements specified in Fig. 5 or local
codes.
For steep roof pitches, the vertical height must
be increased. A poor draft, or down drafting can
result in high wind conditions, trees or neighbor's
roof lines. In these cases increasing the height
may solve a drafting problem.
Any storage spaces or closets which the vent
must pass through must be enclosed.
H
Typical Vertical venting
configuration using Simpson
Dura-Vent Direct Vent System
Vertical Termination
Cap
Storm Collar
Flashing
Ceiling Firestop
Round Support
Box/wall Thimble
Length of Pipe
H-represents vent
height
Fig. 5
Roof Pitch Minimum Vent Height
Flat to 7/12 2 Feet 0.61 Meters
Over 7/12-8/12 2 Feet 0.61 Meters
Over 8/12-9/12 2 feet 0.61 Meters
Over 9/12-10/12 2.5 Feet 0.76 Meters
Over 10/12-11/12 3.25 Feet 1.00 Meters
Over 11/12-12/12 4 Feet 1.22 Meters
Over 12/12-14/12 5 Feet 1.52 Meters
Over 14/12-16/12 6 Feet 1.83 Meters
Over 16/12-18/12 7 Feet 2.13 Meters
Over 18/12-20/12 7.5 Feet 2.29 Meters
Over 20/12-21/12 8 Feet 2.44 Meters
Length of Pipe
SDA-U adaptor
Simpson Dura-Vent venting
components are listed on page 21
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.