Archgard 40-DVI40N User Manual

WARNING: If the information in this manual is not
followed exactly, fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
40-dvi40n
Optima 40 - SB
Gas Fired Vented Room
Heater (Direct Vent)
Serial # 1027 & up
For use with Natural Gas or Propane*
USERS’ INSTALLATION OPERATION and MAINTENANCE MANUAL
* Do not try to light any appliance. * Do not touch any electrical switch; do not use
any phone in your building.
* Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
* If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Installer: Please leave this manual with the appliance owner for future reference
7116 Beatty Dr Mission, BC V2V 6B4 Canada
This appliance may be installed in an after-market, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
*Conversion Kit Required for Propane Use
November 2009
200-1908
STATE OF MASSACHUSETTS REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back­up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, build­ing or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provi­sions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal­lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. (b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. (c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Prod­uct Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system. (d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. (e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in­structions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter li-
censed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance
with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is
installed.
For the State of Massachusetts the appliances individual shut – off must be a t-handle type valve.
INTRODUCTION
Congratulations on choosing an Archgard Gas Fireplace!
The 40-DVI40N Direct Vent Insert is one of the most advanced Direct Vent Insert heater available today. It is solidly designed using the latest technology and manufactured to the highest quality. It is our aim to provide you with an appliance for many trouble-free years of reliable service.
Some of the may features of your 40-DVI40N Direct Vent Insert are:
Heater Classification. The 40-DVI40N is classified as a heating appliance; therefore, it uses
Direct Vent safety technology and it is suitable for continuously
High Efficiency. The 40-DVI40N has one of the highest efficiencies of any Direct Vent
Adjustable Fan Speed. Each 40-DVI40N insert comes complete with a heat-activated
Adjustable Flame. The flame aesthetics and heat output can be adjusted to suit the
Solid Construction. The 40-DVI40N is mainly constructed of 16 and 18 gauge
Optional Accessories. Check with your Authorized Archgard Dealer for a full complement of
Millivolt Control System. The 40-DVI40N uses a gas control valve that is ready for an optional
We recommend you record the following information:
operated zone heating.
gas insert; which means that it is less expensive to operate.
circulation fan with a fully adjustable speed control.
owner’s liking and heating needs.
galvanized and aluminized coated steel for long life and durability.
decorative accessories to suit your home’s décor and your tastes.
Some of the accessories available are: 24K Gold Overlay (for the flat window), a variety of surrounds (faceplates) with gold, black or pewter trims and an overly bay window that simply attaches to the front of your fireplace while leaving the flat glass door in place.
wall thermostat, or a hand held “wireless” remote control.
Fireplace Model Number: 40-DVI40N Serial Number:
Date of Installation:
Type of Gas Used by the Fireplace: Natural Gas Propane
Dealer’s Name & Address:
Dealer’s Phone Number:
TABLE OF CONTENTS
Caution and Safety Instructions 5
Appliance Certification / Installation Codes / Specifications / High Altitude 6
Appliance Dimensions / Minimum Fireplace Dimensions 7
Clearance to Combustibles 8
Gas Connections 9
Appliance Description / Leveling the Appliance / Electrical Requirements 10
Venting Instructions 11
Surround Installation / Trim Instructions 13
Optional Wall Switch, Thermostat or Remote Control - Suggested wiring 14
Log Placement / Ceramic Brick Panels 15
Final Installation Check / Initial Operation 21
First Fire / Lighting Instructions 22
Lighting Instructions on Rating Plate 23
Glass Door Removal / If Your Glass Breaks 24
PAGE
Optional Bay Door Installation Instructions 25
Troubleshooting Guide 26
Maintenance / Cleaning the Appliance 28
Servicing Under Warranty / Adjusting Primary Air 29
Changing Main Burner Orifice 30
Checking Inlet & Outlet Gas Pressures / Adjusting Pilot / Convertible Pilot Orifice 31
Replacing Convection Blower / Wiring Diagram 32
Valve Tray Assembly / Parts List 33
Logs & Burner Assembly / Parts List 34
Replacement Parts List 35
Warranty 37
Frequently Asked Questions 38
Notes 39
Warranty Registration Card 41
40-DVI40N pictured on the front cover is shown with Optional Gold Overlay (Part #40-OAGP),
Contoured Surround (Part #40-SKCAB) and Gold Surround Trim (Part #40-TKSG)
Optima 40 - SB 5
CAUTION
FOR YOUR SAFETY - Do not install or operate your Archgard Optima 40-SB Direct Vent Gas Insert without reading and understanding this manual. Any installation or operational deviation from this instruction manual voids the Archgard Industries Warranty and may prove hazardous.
This appliance must be installed by a qualified gas installer and the installation must conform to the installation codes.
Provide adequate clearance around air openings of the appliance.
Never obstruct front openings.
Provide adequate clearances for proper operation and servicing of the appliance.
This appliance must be properly connected to an approved venting system and must not be connected to a chimney flue serving a separate solid fuel burning appliance.
SAFETY
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Clothing or other flammable material should not be placed on or near the appliance.
Do not operate with cracked or broken glass. Be careful not to strike or slam the glass.
Any safety screen or guard removed for servicing an appliance must be replaced prior to operating.
Installation and Repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, et cetera. It is imperative that the control compartments, burners and circulating air passageways of the appliance are kept clean.
Optima 40 - SB 6
APPLIANCE CERTIFICATION
This appliance is tested and certified to the following USA and Canadian gas appliance standards.
- ANSI Z21.88b-2003 / CSA 2.33b-2003, Vented Gas Fireplace Heaters,
- CAN / CGA-2.17-M91, Gas-Fired Appliances for Use at High Altitudes
Please contact Archgard Industries Ltd., if you have any questions regarding the certification of this appliance.
INSTALLATION CODES
This appliance must be installed by a qualified gas appliance installer. The installation must conform with the local codes or, in the absence of local codes, with the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1. Electrical connections and grounding must conform with local code, or current National Electrical code, ANSI/NFPA No. 70-1987, in the US and in Canada, the current Canadian Electrical Code, CSA C22.1.
We recommend that our gas hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
SPECIFICATIONS
Manifold Pressure
Min. Supply Pressure for Purpose of Input Adjustment
Orifice Size
Nominal Input Rating
ELECTRICAL RATING
GAS CONTROL
Altitude
Primary Air Opening
1.6 - 3.5 in. W.C. (0.4 - 0.9 kPa) 6.3 - 10.0 in. W.C. (1.6 - 2.5 kPa)
4.5 in. w.c. (1.2 kPa) 11.0 in. w.c. (2.8 kPa)
#31 DMS (3.05 mm dia.) #49 DMS (1.85 mm dia.)
27,000 - 40,000 BTU/hr
120 Volts (a/c), 2.0 amps, 60 Hz 120 Volts (a/c), 2.0 amps, 60 Hz
Milli-Valve (quick drop-out), Hi/Lo Milli-Valve (quick drop-out), Hi/Lo
0 - 4500 ft (0 - 1372 M) 0 - 4500 ft (0 - 1372 M)
HIGH ALTITUDE INSTALLATION
Natural Gas (NG) Propane (LP)
30,000 - 40,000 BTU/hr
(7.9 - 11.7 kW)
¾ OPEN FULLY OPEN
(9.1 - 11.7 kW)
When installing this appliance beyond 4500 ft. (1372 M) above sea level, the appliance must be properly de-rated and installed according to local codes, in the absence of local codes, with the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code, CAN/CGA-B149, in Canada.
Optima 40 - SB 7
APPLIANCE DIMENSIONS
H
DIMENSIONS
A 28” (711 mm)
B 18 ½” (470 mm)
C 14” (356 mm)
D 14 ⅛” (359 mm
E 44” (1118 mm)
F 29 ⅝” (752 mm)
LSK-40 (LARGE FLAT SURROUND)
E 47 ¼” (1200 mm)
F 31 ⅜” (797 mm)
G 22 ⅜” (568 mm)
H 3 ¾” (93 mm)
I 1 ¼” (32 mm)
DSK-40 or ESK-40
(STANDARD SURROUND)
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specifically approved with this appliance may result in property damage or personal injury.
The installer must mechanically attach the marking supplied with the gas fireplace insert to the inside of the firebox of the fireplace into which the gas fireplace insert is installed. Cutting of any sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, is prohibited. If the factory-built
fireplace has no gas access hole(s) provided, an access hole of 1½” (37.5 mm) or less may be drilled
through the lower sides or bottom of the firebox in a proper workmanship like manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed. The fireplace flue damper can be fully blocked open or removed for installation of the gas fireplace insert. The fireplace and fireplace chimney must be clean and in good working order and constructed of non­combustible materials. The chimney cleanouts must fit properly. Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the gas fireplace insert. Smoke shelves, and baffles may be removed if attached by mechanical fasteners. Trim panels must not seal ventilation openings in the fireplace.
MINIMUM FIREPLACE DIMENSIONS
K
TOP VIEW
L
M
J
SIDE VIEW
DIMENSIONS
J 22 ½” (572 mm)
K 15 ¾” (400 mm)
L 19” (483 mm)
M 29 ⅝” (752 mm)
Optima 40 - SB 8
CLEARANCES TO COMBUSTIBLES
WARNING: Failure to position the parts in accordance with these diagrams or failure to use
only parts specifically approved with this appliance may result in property damage or personal injury or loss of life.
CAUTION: This appliance is designed for used in any masonry or factory built wood burning fireplace. It cannot be enclosed by combustible material and used as a built-in gas fireplace.
SIDE VIEW
Combustible mantle allowed in
6” (152 mm)
shaded area. Mantle extension may
be increased 1” (25 mm) for each additional 1” (25 mm) increase in
clearance height.
Example: If using a 5” (127 mm)
red u ce m ini m um h e igh t t o
42½” (1108 mm). If using a 4” (101
mm) reduce minimum height to
41½” (1054 mm)
Minimum Height
From Bottom of
Applinace: 43-½”
(1105 mm) with a
6” (152 mm) mantle.
Note: With bay window attached clearances remain the same.
¾” (19 mm)
16” (406)
Note: If existing wood fireplace hearth protection is removed it must be replaced by a non-
combustible hearth protection extending 16” (406 mm) from the front of the fireplace insert. The new hearth extension MUST be raised ¾” (19 mm) above ANY combustible floor.
TOP VIEW
Minimum 3” (76 mm) clearance is required from the faceplate (fireplace surround) to a sidewall or mantle support.
See APPLIANCE DIMENSIONS for surround sizes.
3” (76 mm)
Clearances to Faceplate
Sidewalls or Mantle Supports
3” (76 mm)
Optima 40 - SB 9
GAS CONNECTIONS
Before connecting the appliance to the gas supply line, double check that the appliance you have purchased is designed for the gas type you are using. The gas type markings are located on the certification label and also on the appliance’s gas valve.
Adequate clearance for proper installation and checking of the gas connections must be provided. All gas connections must be checked for gas leaks.
Have your gas supplier or a qualified gas fitter run a gas supply line into the fireplace. The line must be properly sized and fitted according to the installation codes. Immediately upstream of the supply connection, the fitter must provide an accessible manual shut-off valve and a ⅛ (3 mm) NPT plugged tapping accessible for connection to a test gauge. When connecting the supply line to the gas valve, the installer must brace the gas valve to ensure that gas valve is not moved from its bracket. If the valve is not braced when the supply line is connected, the
valve may be moved and cause a “break” in the main burner supply line. Such damage is not covered by the manufacturer’s warranty.
CAUTION: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psig (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.5 kPa). Failure to do so will damage the appliance’s gas valve. Such damage is not covered by the manufacturer’s warranty.
Natural Gas Pressure Settings:
The inlet supply or line pressure must be a minimum of 4.5” wc (1.1 kPa) and a maximum of 8”
wc (2 kPa). The orifice has a #31 DMS (305 mm dia.) drill size.
ELEVATION INPUT RATING 0-4500 ft. (0-1372 M) 40,000 BTU/hr (11.7 kW) 4500 ft. (1372 M) and above 40,000 BTU/hr (11.7 kW) less 4% per 1000 ft. (300 M) Please contact your local distributor for the appropriate orifice size.
Propane Pressure Settings:
The inlet supply or line pressure must be a minimum of 11” wc (2.8 kPa) and a maximum of 14”
wc (3.5 kPa). The orifice has a #49 DMS (1.85 mm dia.) drill size.
ELEVATION INPUT RATING 0-4500 ft. (0-1372 M) 40,000 BTU/hr (11.7 kW) 4500 ft. (1372 M) and above 40,000 BTU/hr (11.7 kW) less 4% per 1000 ft. (300 M) Please contact your local distributor for the appropriate orifice size.
NOTE: THE INPUT RATING SHOULD ALWAYS BE CHECKED WHEN FIRST RUNNING THIS APPLIANCE. To do this, reduce the background flow rate, time the meter, light the fireplace and take another reading after 15 minutes of operation. Check with your gas supplier for the gas BTU content at your elevation. Input is the rate of flow multiplied by the heating value of the gas (cubic feet/hour x BTU per cubic feet). Adjust the manifold pressure so that the unit does not operate above the rated input.
Optima 40 - SB 10
APPLIANCE DESCRIPTION
TOP VIEW
On/Off Rocker
Gas Inlet side
and power cord
outlet
Exhaust Fresh Air Intake
Switch
LEVELING THE OPTIMA 40-SB DIRECT VENT INSERT
Before placing the appliance into the fireplace, check the hearth of the fireplace to see if it is level with the front of the fireplace. If it is not, measure the depth of the hearth. Loosen the
three screws of the leveling “L” bracket at the back of the appliance. Lower it to the
measurement obtained and tighten the screws
ELECTRICAL CONNECTIONS
The Optima 40-SB comes complete with a temperature activated fan and rheostat installed and wired to a three-prong (grounding) plug for your protection against shock hazard and should be plugged in directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
NOTE: This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical code, CSA C22.1.
Optima 40 - SB 11
VENTING INSTRUCTIONS
WARNING: Operation of this heater when not connected to a properly installed and main­tained venting system can result in carbon monoxide (CO) poisoning and possible death. The appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance.
Caution: Only two 3” (76 mm) “FLEX-MASTER” Model GA gas flex vent liners (or approved equivalent)
and a vent terminal is approved for use with this appliance.
Approved vent terminals are: Archgard terminal. Part # 999-INS-TK. Simpson Dura-Vent terminal. Part # 980, 923GK (adaptor with flashing) or 991 (high wind cap) NO OTHER VENTING SYSTEM OR COMPONENTS MAY BE USED. If you are using DuraVent vertical termination cap, follow the instructions provided with the DuraVent cap.
This appliance is designed to attach to two 3” (76 mm) co-linear aluminum flex gas liners running the full length of the chimney. The flue length must be a minimum of 8’ (2.44 M) and a maximum of 35’ (10.6 M) The minimum flue size is 4” x 7” (100 mm X 178 mm). Masonry chimneys may take various contours
which the flexible liner will accommodate, however, keep the flexible liner as straight as possible, avoiding unnecessary bending but at all times keep a minimum of 3” (76 mm) inside bend radius.
The Air Intake Flex Liner must be connected to the inlet air collars of the termination cap and the appli­ance. The Exhaust Flex Liner must be connected to the exhaust collars of the termination cap and the appliance. (DO NOT MIX UP THESE CONNECTIONS).
The Air intake and Exhaust connections are marked on the gas appliance. See Fig. 1.
CAUTION: To ensure that the venting path is not accidentally obstructed, or punctured the damper of the host fireplace must be permanently disabled. By either complete removal of the
damper or welding it in it’s “open” position. Temporarily disabling the damper with braces,
wedges, brackets, ext,. Is not allowed.
The Optima 40-SB showing the Exhaust and Fresh Air Intake locations.
These connections are labeled for you.
Fig. 1
Fresh Air Intake Exhaust
The Optima 40-SB Requires two flexible gas flue liners:
Flue Collar (inlet)
3” (76 mm) diameter
Flue Collar (outlet) 3” (76 mm) diameter
Optima 40 - SB 12
VENTING INSTRUCTIONS 999-INS-TK
Instructions for use with Archgard vertical termination cap. Part # 999-INS-TK. Install the termi­nation cap being sure to provided sufficient space (around and on top) so as to not to impede the flow of air both into and out-of the cap. This cap is only to be used for non combustible installa­tions. Do not recess into the top of the chimney.
1. Mark each end of one liner with “Air Intake”.
2. Mark each end of the second liner with “Exhaust”.
3. Pull the liner through the chimney.
4. Install the flashing. Do Not bend or cut the flashing in any way.
5. Seal and attach the liner marked “Air Intake” to the vent terminal pipe marked “Air Intake” with the collar clamp provided.
6. Seal and attach the liner marked “Exhaust” to the vent terminal pipe marked “Exhaust” with the collar clamp provided.
7. Seal and attach the end of the flex marked “Air Intake” to the collar marked “Air Intake” on the appliance with
the collar clamp provided with the unit.
8. Caulk all joints as usual.
NOTE: The vertical termination cap must be sealed to the liner with suitable high temperature sealant and with the hose clamps fasteners provided. The liners must form a complete connection from the appliance flue collars to the
vertical termination cap.
Vertical Termination cap Part # 999-INS-TK
Air Intake
Collar
Min. vent height 8’ (2.44 M) Max. vent height 35’ (10.6 M)
Fresh Air Intake
Exhaust
Collar
3” (76 mm)
Flex Liner
Front view of
DV Insert
Exhaust
The minimum flue (chimney) size required to run the two 3” (76 mm) is 4” x 7” (100 mm X 178 mm)
Optima 40 - SB 13
SURROUND INSTALLATION
Make sure the gas and electrical lines are properly connected to the appliance. Slide the unit into the fireplace and slide the excess flue liner material back onto the chimney. Before the appliance is fully recessed into the fireplace attach the surround onto the appliance. The return flange on the side of the surround fits on the inside of the mounting rails on the appliance. Attach the surround to the appliance at the locations shown with the four (4) screws provided. Then finish with the wiring connection to the on/off switch on the side of the trim. Now fully “seat” the unit into its final position.
SCREW
LOCATIONS
Only trim kit (s) supplied by the manufacturer may be used in the installation
CAUTION:
of this appliance.
TRIM INSTRUCTIONS FOR THE SKBAB, SKCAB & SKLB SURROUNDS
1. Using the trim clips provided, join the left side trim (which has notch cut for rocker switch) to the top trim as shown in Fig.1. Repeat with the right side trim.
2. Peel the backing from the sticky tape, then slip the assembled trim over the surround.
3. Locate the rocker (on/off) switch (with the ON side up) and push it in the notch located on the left side.
4. Remove the coiled wires from the left side of the firebox and connect it to the rocker switch tabs.
5. The switch wires have crimped connections that are factory installed. Simply connect the crimped connections to the on/off (rocker) switch located on the surround.
Fig. 1
Fig. 2
Gas Inlet side
and power cord
outlet
Fresh Air Intake
Exhaust
On/Off
Rocker
Switch
Optima 40 - SB 14
OPTIONAL WALL SWITCH OR THERMOSTAT
If a wall-mounted switch or a wall-mounted thermostat is desired, Archgard recommends that the device be wired as shown in Fig.1. This will allow the original on/off rocker switch to be used in case the device that is mounted to the wall becomes inoperable.
Note: Archgard Industries Ltd. does not manufacture or sell any wall switch or wall thermostat, and will not extend warranty to them.
Thermostat / wall switch wire table
Recommended Maximum Lead Length
for two wires.
Wire Size Max. Length
14 GA. 50 Ft. (15.24 M)
16 GA. 32 Ft. (9.75 M)
18 GA. 20 Ft. (6.9 M)
20 GA. 12 Ft. (3.65 M)
22 GA. 9 Ft. (2.74 M)
VALVE CONNECTION FOR MILLIVOLT VALVE
C
B
D
A
THERMOCOUPLE LEAD
SUPPLY TUBE
WIRE TO PIEZO
(SPARKER)
PILOT ASSEMBLY
A ELECTRODE
B THERMOPILE
C PILOT CAP
D THERMOCOUPLE
THTP
TH
Fig. 1
TP
ON / OFF SWITCH
OPTIONAL
REMOTE SWITCH
OR
THERMOSTAT
Loading...
+ 31 hidden pages