Archgard 31-DVIE33N User Manual

31-DVIE33
Gas Fired Vented Room
Heater (Direct Vent)
S/N 211061And up
USERS’ INSTALLATION OPERATION and MAINTENANCE MANUAL
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance. Do not touch any electrical switch; do not use
any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
*Conversion kit required for Propane use
Tested and listed by
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
7116 Beatty Dr Mission, BC V2V 6B4 Canada
LABTEST Certification Inc Richmond, British Columbia ANSI Z21.88-2009/CSA 2.33-2009
200-1131
March 2013
31-DVIE33 2
STATE OF MASSACHUSETTS REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back­up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, build­ing or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provi­sions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the instal­lation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. (b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. (c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Prod­uct Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system. (d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. (e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in­structions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter li-
censed in the Commonwealth of Massachusetts.
For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance
with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is
installed.
For the State of Massachusetts the appliances individual shut – off must be a t-handle type valve.
31-DVIE33 3
INTRODUCTION
Congratulations on choosing an Archgard Gas Fireplace!
The 31-DVIE33 is one of the most advanced Direct Vent Insert heaters available today. It is solidly designed using the latest technology and manufactured to the highest quality. It is our aim to provide you with an appliance for many trouble-free years of reliable service.
Some of the many features of your 31-DVIE33 are:
Heater Classification The 31-DVIE33 is classified as a heating appliance.
Therefore, it uses Direct Vent safety technology and it is
suitable for continuously operated zone heating.
High Efficiency The 31-DVIE33 has one of the highest efficiencies of any
Direct Vent gas insert, which means that it is less expensive to operate.
Adjustable Fan Speed Each 31-DVIE33 comes complete with 6 level adjustable
speed controlled circulation fan.
Adjustable Flame The flame aesthetics and heat output can be adjusted to suit
the owner’s liking and heating needs.
Solid Construction The 31-DVIE33 is mainly constructed of 16 and 18 gauge
galvanized and aluminized coated steel for long life and durability.
Optional Accessories Check with your Authorized Archgard Dealer for a full
complement of decorative accessories to suit your home’s décor and your tastes.
Electronic Control System The 31-DVIE33 uses a gas control valve that is operated by a
Multifunction Remote Control. It can be used as either an Intermittent or Standing Pilot system.
Fireplace Model Number: 31-DVIE33 Serial Number:
Date of Installation:
Type of Gas Used by the Fireplace: Natural Gas Propane
Dealer’s Name & Address:
Dealer’s Phone Number:
31-DVIE33 4
TABLE OF CONTENTS
Caution and Safety Instructions 5 Appliance Certification, Installation Codes and Specifications 6
Rating Plate 7 Control Panel Locations 8
Appliance Dimensions and Minimum Requirements for Fireplace Dimensions 9
Factory Built (metal) Fireplace Requirements 10
Clearance to Combustibles 11
Gas Connections 12
Conversion Kit Instructions 13-14
Appliance Description, Leveling the Appliance and Electrical Requirements 15
Venting Instructions 16-17
Restrictor Plate, Surround Installation and Rocker Switch Wiring 18
Log Placement
Glass Door Removal / If Your Glass Should Break Final Installation Check and Initial Operation First Fire and Lighting Instructions (CAUTION)
Lighting Instructions on Rating Plate
Remote Control Setup and Operation
Maintenance and Cleaning the Appliance
Servicing Under Warranty and Adjusting Primary Air
Checking Inlet/Outlet gas pressures, Adjusting Pilot and Convertible Pilot Orifice
Replacing Convection Blower
Wiring Schematic
Warranty
Frequently Asked Questions
19-24
25 26 27
28
29-35
36
37
38
39
40
41
42
Blank
Parts
Notes
Warranty Registration Card
43
44
45
46
31-DVIE33 5
CAUTION
FOR YOUR SAFETY - Do not install or operate your Archgard 31-DVIE33 without reading and
understanding this manual. Any installation or operational deviation from this instruction manual voids the Archgard Industries Warranty and may prove hazardous.
This appliance must be installed by a qualified gas installer and the installation must conform to the installation codes.
Provide adequate clearance around air openings.
Never obstruct front openings.
Provide adequate clearances for proper operation and servicing of the appliance.
This appliance must be properly connected to an approved venting system and must not be connected to a chimney flue serving a separate solid fuel burning appliance.
Must provide adequate clearance around the intake and exhaust openings
SAFETY
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperature and stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other flammable material should not be placed on or near the appliance.
Do not operate with cracked or broken glass. Be careful not to strike or slam the glass.
Any safety screen or guard removed for servicing an appliance must be replaced prior to operating.
Installation and Repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that the control compartments, burners and circulating air passageways of the appliance are kept clean.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
31-DVIE33 6
APPLIANCE CERTIFICATION
This appliance was listed by LABTEST Certification Inc to the following USA and Canadian gas appliance standards.
- ANSI Z21.88-2009/CSA 2.33-2009 Vented Gas Fireplace Heaters
- CAN/CGA-2.17-M91, Gas-Fired Appliances for Use at High Altitudes
-CSA P.4.1-09 testing method for measuring annual fireplace efficiency. The listing label is attached to the appliance on the bottom right side of the appliance. A copy is shown on page
Please contact Archgard Industries Ltd., if you have any questions regarding the certification of this appliance.
INSTALLATION CODES
This appliance must be installed by a qualified gas appliance installer. The installation must conform with the local codes or, in the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/ NFPA 54 in the US, or Installation Code CAN/CGA-B149.1 in Canada. Electrical connections and grounding must conform with local code, or current National Electrical code ANSI/NFPA No. 70-1987 in the US, and in Canada the current Canadian Electrical Code CSA C22.1.
We recommend that our gas hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
SPECIFICATIONS
Natural Gas (NG) Propane (LP)
Manifold Pressure
Min. Supply Pressure Max Supply Pressure
Orifice Size
Nominal Input Rating
Electrical Rating
Gas Control Altitude
Primary Air Opening
22,000 - 33,000 BTU/hr (6.1- 9.6kW) 24,000 - 31,000 BTU/hr (6.9 -9.0kW)
3.5 in. W.C. (0.9 kPa) 10.0 in. W.C. (2.5 kPa)
5 in. W.C. (1.2 kPa)
14.0 in. W.C. (3.5 kPa)
#33 DMS (2.87 mm dia) #51 DMS (1.73 mm dia)
120 VAC, 60Hz less than 2 A. / 120 VAC, 60Hz less than 2 A. /
SIT 885 Proflame SIT 885 Proflame
0 - 4,500 ft. (0 - 1372 M) 0 - 4,500 ft. (0 - 1372 M)
1/4” (6 mm) OPEN FULLY OPEN
11.0 in. W.C. (2.8 kPa)
14.0 in. W.C. (3.5 kPa)
HIGH ALTITUDE INSTALLATION
When installing this appliance beyond 4500 ft. (1372 M) above sea level, the appliance must be properly de-rated and installed according to local codes, in the absence of local codes, with the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code, CAN/CGA­B149, in Canada.
31-DVIE33 7
RATING PLATE
DO NOT REMOVE THIS LABEL
# de série
Serial #
C
MODEL / MODÈLE: 31 -DVIE33
L
NG / NATURAL LP / PROPANE
LISTED VENTED GAS FIREPLACE HEATER and GAS- FIRED APPLIANCES FOR USE AT HIGH
ALTITUDES. RADIATEUR VENTILE, CIRCULATEUR DU TYPE VENTILATEUR. Tested to / Testée selon les
normes : ANSI Z21.88-2009 / CSA 2.33-2009 and CAN/CGA-2.17-M91 This vented gas fireplace heater is not for
use with air filters. Certified for use in both CANADA and USA. / Certifié pour utilisation dans le Canada et les
ÉTATS-UNIS.
VENTED GAS FIREPLACE HEATER-NOT FOR USE WITH SOLID FUEL.
SIT 885 SKYTECH 4044
Input rating / Entrée assignée
Manifold pressure / Pression d’admission 3.5 in. W.C. (0.9 kPa) 10.0 in. W.C. (2.5 kPa) Orifice size / Dimension de l’orifice #33 DMS (2.87 mm dia.) #51 DMS (1.73 mm dia.)
Minimum supply pressure for purpose of input adjustment / Pression minimale d’alimentation pour le but d'ajustement de contribution
22,000 - 33,000 BTU/hr
5.0 in. W.C. (1.2 kPa) 11.0 in. W.C. (2.8 kPa)
NG LPG
(6.1 - 9.6 kW)
LC
NE PAS ENLEVER CETTE ÉTIQUETTE
24,000 - 31,000 BTU/hr
(6.9 - 9.0 kW)
Burner Primary Air Setting 1/4” (6 mm) Open 100% Open Altitude / Elevation 0 - 4500 ft (0 - 1372 m) 0 - 4500 ft (0 - 1372 m) Electrical rating / Tension électrique 120 VAC, 60 Hz less than 2 A. / 120 V, 60 Hz Moins que 2 A.
Keep burner and control compartment clean. See Instructions accompanying the heater. Maintenir propres le brûleur et le compartiment de commande. Voir les instructions relatives à
l’installation et au fonctionnement qui accom-
pagnent le radiateur. Optional fuel conversion kit : See Manual
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149,1. Electrical connections and grounding must be in accordance with local codes, if any; if none, follow the current CAN/CSA C22.1 in Canada and ANSI/NFPA 70 in the US. This appliance is certified for installation in a bedroom or a bed sitting room. This appliance is only for use with the gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See owner’s manual for details. This appliance is not convertible with other gases, unless a certified kit is used. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS APPLIANCE ONLY.
Il faut que cet appareil soit installé selon les codes locaux, s’il y en a; sinon, suivre le CAN/CGA -B149 actuel au Canada et ANSI Z223.1 aux É.-U. Il faut que le raccordement électrique et la mise à la masse soient en conformité avec les codes locaux, s’il y en a; sinon, suivre le CAN/CSA C22.1 actuel au Canada et ANSI/NFPA 70 aux É.-U. Cet appareil est certifié pour l’installation dans une chambre à coucher ou une pièce qui sert de chambre.
Made in Canada by / Fabrique au Canada par:
Minimum clearances to Combustibles / Distances:
Minimales entre l’appareil et les combustibles:
Sides from glass door frame/ Côtes: 8 ” (203 mm) Mantle / Manteau: max 12” (305 mm) at min 39” (991 mm) from bottom of appliance / du pied de l’appareil See Owner’s Manual for additional clearances
Archgard Industries Ltd. 7116 Beatty Dr., Mission, B.C.
August 2013 303-6031-1
We recommend that our gas hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.
31-DVIE33 8
CONTROL PANEL LOCATIONS
The control panels can be mounted in the following different ways. They are shipped in the “Controls In” configuration. They can be moved to the “Controls Out” configuration by removing the two mounting screw on each side and swinging the panels
out and replacing the screws. They can also be disconnected and placed remotely within the limits of the gas connections and electrical wiring making sure to place them away from any heat source over 150 degrees Fahrenheit or 65 degrees Celsius
31-DVIE33 9
MINIMUM FIREPLACE DIMENSIONS
Min flue size required 4” (102) x 7” (178)
SIDE
VIEW
J
DIMENSIONS “Controls Out”
J 20-1/4” (514 mm) 20-1/4” (514 mm)
DIMENSIONS
“Controls In”
TOP VIEW
K
L
M
TOP VIEW
CONTROLS OUT
K 14” (356 mm) 15 1/2” (394 mm)
L 19” (483 mm) 19” (483 mm)
M 30” (762 mm) 33 1/2” (851 mm)
TOP VIEW
CONTROLS IN
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specifically approved with this appliance may result in property damage or personal injury.
The installer must mechanically attach the marking supplied with the gas fireplace insert to the inside of the firebox of the fireplace into which the gas fireplace insert is installed. Cutting of any sheet-metal parts of the fireplace, in which the gas fireplace insert is to be installed, is prohibited. If the factory-built fireplace has no gas access hole (s) provided, an access hole of 1 1/2” (38.1 mm) or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship-like manner. This access hole must be plugged with non-combustible insulation after the gas supply line has been installed. The fireplace flue damper can be fully blocked open or removed for installation of the gas fireplace insert. The fireplace and fireplace chimney must be clean and in good working order and constructed of non-combustible materials. The chimney cleanouts must fit properly. Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the gas fireplace insert. Smoke shelves and baffles may be removed if attached by mechanical fasteners. Trim panels must not seal ventila­tion openings in the fireplace.
31-DVIE33 10
Factory –Built (metal) Wood-Burning Fireplace Requirements
Any parts that are removed must be saved and re-installed if the insert is ever removed.
The damper (A) and grate (B) must be removed
The smoke shelf (C), internal baffles (D), screen ( E), masonry lining or refractory (G and I), and metal or glass doors (F) may be removed.
The fireplace must be permanently marked to indicate that it has been altered and is no longer suitable for burning any fuel unless the removed parts are reinstalled. Cutting out of any metal parts is prohibited, except the metal floor (J) as specified.
The metal floor of the firebox may be removed only if the following is strictly adhered to.
The metal floor (J) may be removed to allow additional room for installation of the in­sert. If the floor is removed the insert must be placed directly on the metal base of the metal fireplace. Under no circumstance can it be placed directly on a combustible material.
Any hearth extending out in front of the insert must not have any portion above 7” be-
low the bottom of the unit made from combustible materials. This includes any type of framing underneath a non-combustible material such as tile, marble or stone. Any ma-
terial below 7” can be combustible.
31-DVIE33 11
CLEARANCES TO COMBUSTIBLES
WARNING: Failure to position the parts in accordance with these diagrams or failure to use
only parts specifically approved with this appliance may result in property damage or personal injury or loss of life.
CAUTION: This appliance is designed for use in any masonry or factory-built, wood-burning fireplace. It cannot be enclosed by combustible material and used as a built-in gas fireplace.
SIDE VIEW
12” (305mm)
Note: If existing wood fire­place hearth protection is removed it must be replaced by a non­combustible hearth
protection 7” thick,
extending a minimum
of 16” (406 mm) from
the front of the fire­place insert or have a
minimum 7” (178 mm)
clearance below the level of the bottom of the insert.
Minimum Height
From Bottom of
Appliance: 38”
(966 mm) with a
12”(305 mm) mantel.
Minimum clearance
to combustibles
framing
16”(406mm)
7”(178mm)
Non– Combustible Zone
Combustible mantle allowed in shaded area. Mantle extension
maybe increased 1” (25.4 mm) for each additional 1” (25.4 mm)
increase in clearance height.
Example: If using a 5” (127 mm)
reduce minimum height to
31” (788 mm). If using a 4” (102 mm) reduce minimum height to 30” (762 mm)
TOP VIEW
Minimum 8” (204 mm) clearance is required from the glass door frame to a sidewall or mantle support.
8
(204 mm)
8
(204 mm)
Clearances to Door Frame
Sidewalls or Mantle Supports
31-DVIE33 12
GAS CONNECTIONS
Before connecting the appliance to the gas supply line, double check that the appliance you have purchased is designed for the gas type you are using. The gas type markings are located on the certification label and also on the appliance’s gas valve.
Adequate clearance for proper installation and checking of the gas connections must be provided. All
gas connections must be checked for gas leaks.
Have your gas supplier or a qualified gas fitter run a gas supply line into the fireplace. The line must be properly sized and fitted according to the installation codes. Immediately upstream of the supply connection, the fitter shall provide an accessible manual shut-off valve. When connecting the supply line to the gas valve, the installer shall brace the gas valve to ensure that the gas valve is not moved from its bracket. If the valve is not braced when the supply line is connected, the valve may be
moved and cause a “break” in the main burner supply line. Such damage is not covered by the manufacturer’s warranty.
CAUTION: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure-testing of that system at test pressures in excess of 1/2 psig (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure-testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa). Failure to do so will damage the appliance’s gas valve. Such damage is not covered by the manufacturer’s warranty.
Natural Gas Pressure Settings:
The inlet supply or line pressure must be a minimum of 4.5” W.C. (1.2 kPa) and a maximum of 14”
W.C. (3.5 kPa). The orifice is a #33 DMS (2.87) drill size.
ELEVATION INPUT RATING 0-4500 ft (0-1372 M) 33,000 BTU/hr (9.6 kW) 4500 ft (1372 M) and above. 33,000 BTU/hr (9.6 kW) less 4% per 1000 ft. (305 M) Please contact your local distributor for the appropriate orifice size you require.
Propane Pressure Settings:
The inlet supply or line pressure must be a minimum of 11” W.C. (2.8 kPa) and a maximum of 14”
W.C. (3.5 kPa). The orifice is a #51 DMS (1.73 mm) drill size.
ELEVATION INPUT RATING 0-4500 ft. (0-1372 M) 31,000 BTU/hr (9.02 kW) 4500 ft. (1372 M) and above. 31,000 BTU/hr (9.02 kW) less 4% per 1000 ft. (305 M) Please contact your local distributor for the appropriate orifice size you require.
NOTE: THE INPUT RATING SHOULD ALWAYS BE CHECKED WHEN FIRST RUNNING THIS APPLIANCE. To do this, reduce the background flow rate, time the meter, light the fireplace and take another reading after 15 minutes of operation. Check with your gas supplier for the gas BTU content at your elevation. Input is the rate of flow multiplied by the heating value of the gas (cubic feet/hour x BTU per cubic feet). Adjust the manifold pressure so that the unit does not operate above the rated input.
31-DVIE33 13
CONVERSION KIT INSTRUCTIONS
IMPORTANT: This fireplace is Natural gas ready. If converting to LP gas, follow instructions below
WARNING: This conversion kit shall be installed by a qualified service agency in accordance with the manufacturers
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion or productions of carbon monoxide may result, causing property dam­age, personal injury or loss of life. The qualified service agency is responsible for proper installation of this kit. The in­stallation is not proper and complete until operation of the converted appliance is checked as specified in the instructions
supplied with the kit. Refer to appliance owner’s manual or product data plate for proper inlet and manifold pressure
adjustments and orifice sizing.
IMPORTANT: For high altitude installations above 4500 ft (1372 meters), consult local gas distributor or the authority having jurisdiction for proper de-rating methods.
KIT NUMBERS: 31--CKELP for LP gas and 31-CKENG for Natural Gas KIT INCLUDES:
1- Gas conversion label (303-0128) 1- Burner orifice (301-0068) (#51 DMS for LPG) (#33 DMS for NG) 1- Instruction Sheet 1- SIT 885 Valve conversion kit c/w instructions & gas type label (0.907.012 LPG)
WARNING: SHUT OFF GAS SUPPLY AND ELECTRICAL POWER TO FIREPLACE SHUT OFF GAS SUPPLY BEFORE DISCONNECTING ELECTRICAL POWER
PREPARE THE FIREPLACE
Remove the surround, glass frame assembly, logs and brick (if applicable).
Remove the burner air tray by removing the two screws at the back wall and lifting the tray up and out.
Remove burner by removing the screw on each side of the burner and sliding the burner to the right and then tilt up.
Remove the burner orifice using a 1/2” wrench. Replace with the
orifice supplied with the conversion kit. Use a small amount of pipe sealant.
PILOT CONVERSION
Using a 7/16” wrench and loosen the pilot hood 1/4
turn. Slide the tab at the bottom of the orifice hood all the way so the red side (propane) with the hole in it is showing. Tighten the pilot hood back up so that it is lined up with the two probes on both sides of the pilot assembly.
Figure 22
LP has hole and red dot
Natural Gas
Wrench here
31-DVIE33 14
CONVERSION KIT INSTRUCTIONS CONT.
CONVERT THE GAS VALVE
COMPLETE THE CONVERSION
Turn on the gas and electrical supplies. Turn on the fireplace so the burner is on Check for leaks at all connections.
Test inlet and outlet pressure. Visually check pilot flame. Flame should envelope top of the flame sensor and extend forward onto the burner. To adjust pilot turn the pilot adjustment screw on the control valve clockwise to decrease or counter clockwise to increase pilot flame.
Turn fireplace off Affix gas type label to the rating plate label. (Bottom right side, under the door frame of insert on pull chain) Complete the conversion label and affix to valve assembly plate. Re-install the burner, brick, logs, embers and door. (per the instructions starting on pg. 19)
31-DVIE33 15
APPLIANCE DESCRIPTION
TOP VIEW
Exhaust
LEVELING THE 31-DVIE33
Front Level
Located slightly in from the front edge of the fireplace is the new level­ing feature. Leveling bolts can be installed to enable you to raise the front of the firebox if necessary. If you need higher adjustment you only need to change to a longer bolt. If no rise is required simply leave empty.
Intake
On/Off
Rocker
Surround
Faceplate
FRONT VIEW
Ceramic Glass w/
standard
black
door
Rear Level
Before placing the appliance into the fireplace, check the hearth of the fireplace to see if it is level with the front of the fireplace. If it is not, measure the depth of the hearth. Loosen the three screws of
the leveling “L” bracket at the back of the appliance. Lower it to the measurement obtained and
tighten the screws.
ELECTRICAL CONNECTIONS
The 31-DVIE33 comes complete with an adjustable 6 speed fan wired directly to the main control module for your protection against shock hazard.
Do not cut or remove the grounding prong from this plug.
NOTE: This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI / NFPA 70, or the
Canadian Electrical code, CSA C22.1.
Loading...
+ 33 hidden pages