For Bosch AquaStar Models: GWH 1600 P, GWH 1600 H
For Bosch ProTankless Models: GWH 425 PN, GWH 425 HN*
WARNING: If the information in this manual is not followed
exactly, a re or explosion may result causing property
damage, personal injury or death. Do not store or use
gasoline or other ammable vapor and liquids in the vicinity
of this or any other appliance.
BTC715003301A
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer
to this manual. For assistance or additional information
consult a qualied installer, service agency or the gas
supplier.
In the Commonwealth of Massachusetts this product
must be installed by a licensed plumber or gas tter.
Upon completion of the installation, these instructions
should be handed to the user of the appliance for future
reference.
* The GWH 425 HN has been redesigned. This vent kit
is not compatible with the older version (identied by a
white cover). Use the AQ1 horizontal vent kit with the
older version.
• 1 - Power vent motor (HSUL-1 Series containing
integrated 24v control circuit) including 25 foot
control cable with wire nuts and an HPN 6-foot
power cord
• 5 - Nylon ties
Warning: Failure to install AQ4FLAPPER
properly may allow freezing air to come
in contact with the water heater’s heat
exchanger and cause the heat exchanger
to burst. Such damage is not covered
under the water heater’s warranty.
1.3 Preparation
1. Follow installation and operating instructions
manual supplied with the water heater.
2. Before mounting water heater to wall, check its
minimum clearance requirements.
3. When using an AQ4 the maximum vent length
from the water heater to the point of termination
is 25 feet with one elbow. Subtract 5 feet for
each additional 90° elbow (up to two additional
elbows allowed.)
4. Install power vent motor as close to the vent hood
1.2 Warnings
1. Failure to install, maintain and/or operate the
power vent in accordance with manufacturer’s
instructions may result in conditions which can
produce bodily injury and property damage.
2. The power vent must be installed by a qualied
installer in accordance with all local codes or, in
their absence, in accordance with the National
Fuel Gas Code (ANSI Z223.1 NFPA #54), the
National Electric Code, the Canadian Electrical
Code (C22.1), Canadian Gas Code (CSA B149.1)
and The Occupational Health and Safety Act
(OSHA) as applicable.
3. The power vent motor shaft must be mounted
horizontally to prevent motor bearing wear.
4. Disconnect power supply when making wiring
connections or when working around the fan
blade and motor. Failure to do so may result in
severe personal injury and equipment damage.
5. Make certain the power source is adequate for
the fan motor requirements. Do not add the
power vent to a circuit where the total load is
unknown.
AQ4 Motor is 200 watts- 1.66 amps @ 120vac.
6. Locate the outlet receptacle as close to the vent
motor as possible. Do not use an extension
cord.
3AQ4 Manual
Introduction
as possible.
1.4 Requirements for installation in
Massachusetts
Attention residents of the Commonwealth of
Massachusetts:
In the Commonwealth of Massachusetts the following
regulation went into effect on 12/30/2005:
(a) For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by
the Commonwealth and where the side wall exhaust
vent termination is less than seven (7) feet above
nished grade in the area of the venting, including
but not limited to decks and porches, the following
requirements shall be satised:
1. IN S TA L LATION OF C ARBON MONOX I D E
DETECTORS. At the time of installation of the side
wall horizontally vented gas-fueled equipment,
the installing plumber or gastter shall observe
that a hard wired carbon monoxide detector
with an alarm and battery back-up is installed on
the oor level where the gas equipment is to be
installed. In addition, the installing plumber or
gastter shall observe that a battery operated
or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side
wall horizontally vented gas-fueled equipment.
It shall be the responsibility of the property
owner to secure the services of qualied licensed
professionals for the installation of hard wired
carbon monoxide detectors.
a. In the event that the side wall horizontally
vented gas-fueled equipment is installed in
a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent oor level.
b. In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply
with the above requirements; provided, however, that during said thirty (30) day period,
a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed
and IAS certied.
3. SIGNAGE. A metal or plastic identication plate
shall be permanently mounted to the exterior of
4AQ4 Manual
the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2)
inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector
of the side wall horizontally vented gas fueled
equipment shall not approve the installation
unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product approved side wall horizontally vented
gas fueled equipment installed in a room or
structure separate from the dwelling, building or
structure used in whole or in part for residential
purposes.
(c) MANUFACTURERS REQUIREMENTS – GAS
EQUIPMENT VENTING SYSTEM REQUIRED. When
the manufacturer of Product Approved side wall
horizontally mounted gas equipment provides a
venting system design or venting system components
with the equipment, the instructions provided by the
manufacturer for the installation of the equipment
and the venting shall include:
1. Detailed instructions for the installation of the
venting system or the venting system components:
and
2. A complete parts list for the venting system design
or venting system.
(d )M AN UFACTURER RE QU IR EM ENTS – GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a product approved
side wall horizontally vented gas fueled equipment
does not provide the parts for the venting of ue
gases, but identies “special venting systems,” the
following requirements shall be satised by the
manufacturer:
1. The referen ced “spe cia l venti ng system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be product
approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
(e) A copy of all installation instructions for all
products approved side wall horizontally vented
gas fueled equipment, all venting instructions, all
parts lists for venting instructions, and/or all venting
design instructions shall remain with the appliance
or equipment at the completion of the installation.
2 AQ4 Installation instructions
AQ4 Installation instructions
2.1 Introduction
Please follow these instructions. Failure to follow
instructions may result in:
· Damage, injury or death
· Improper operation
· Loss of warranty
If you are unable to perform the tasks required to
install the water heater and this accessory properly,
please contact a locally licensed plumber, HVAC
contractor or gas technician.
Please contact Bosch Water Heating with any
questions.
2.2 Locating power vent hood and
clearances
The maximum vent length from the water heater to
the point of termination is 25 feet with one elbow. If
using more than one 90° elbow, subtract 5 feet off
the maximum vent length for each additional elbow
used. Maximum of three elbows allowed.
The power vent motor must be installed
as close as possible to the VH1-4 vent
hood.
Clearances
The vent system must terminate so that proper
clearances from the center of the vent hood (Fig.
1) are maintained as cited in the National Fuel Gas
Code, ANSI Z223.1 and CSA B149.1 in Canada:
“The vent terminal shall also not be installed closer than 3
feet from the inside corner of an L-shaped structure, or less
than 1 foot above grade or anticipated snow pack level.”
Also:
“The exit terminals of mechanical vent system shall be located
not less than 7 feet above grade when located adjacent to a
public walkway. The venting system shall terminate at least
3 feet above any forced air inlet within 10 feet. The venting
system shall terminate at least 4 feet below, 4 feet horizontally
from or 1 foot above any door, window or gravity air inlet into
any building.”
2.3 Power vent hood
1. Attach the mounting template (on page 13)
to the interior wall that the vent hood will be
penetrating.
2. Ensure that the proposed vent termination
clearances are met (Chapter 2.2) before cutting
opening through wall. Using a 1/2” drill bit, drill
two pilot holes where noted on the template. The
drill bit must be long enough to penetrate to the
building exterior.
3. Attach the template to the outside of the building
aligning the pilot holes on the template with the
pilot holes drilled in step 2.
4. Using a reciprocating saw, cut a hole through the
building siding, wall board, etc., following the
appropriate lines of the template.
5. Apply a bead of exterior-rated caulk to the vent
hood ange to seal at the exterior of building.
6. Slide the vent hood through the opening and
fasten to exterior wall using screws provided.
7. Install backdraft apper using the instructions
included with apper.
Fig. 1 External vent hood clearances
5AQ4 Manual
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.