Aquametrix SHARK TX / TXP
by
Water Analytics
Aqua
Metrix
Multi-Parameter Transmitter
Features
• pH, ORP, Conductivity &
Flow parameters available
• 24 VDC / 24 VDC Loop
• Easy to read 2 X 16 char-
acter LCD display
• Quick and easy to calibrate
• Single 4-20mA output with
range expandability
• 1/4 DIN size, NEMA 4X
polycarbonate housing
• Shark-TX: Universal
mounting hardware provided
for surface, panel and pipe
mounting
Description
SUMMARY
Complete and versatile, SHARK-TX is
the only 1/4 DIN and DIN rail mountable two wire transmitter on the market that allows the user to select one of
four measuring parameters.
FOUR MEASURING PARAMETERS
Select the parameter you wish to measure from the easy-to-use LCD menu
on the front cover. Choose Conductivity, pH, ORP or Flow.
COMPLETE - NO EXTRA CARDS
OR OPTIONS REQUIRED
Each SHARK-TX comes complete.
There are no extra costs associated
with buying boards for different applications.
TWO MOUNTING OPTIONS
SHARK-TX comes complete with a
universal mounting kit for surface,
panel and pipe-mount applications.
The NEMA 4X 1/4 DIN enclosure is
perfect for stand-alone or panel-mount
operation.
SHARK-TXP is NEMA 4X for front
panel mounting and comes complete
with DIN rail mounting hardware for
mounting in a control panel.
DISPLAY
2-line, 16-character LCD on the front
panel.
ANALOG OUTPUTS
The SHARK-TX provides an isolated
and fully scalable 4-20 mA output.
ENCLOSURE
SHARKTX is packaged in a rugged
NEMA 4X polycarbonate enclosure
making it ideally suited for heavy-duty
applications such as industrial wastewater neutralization, municipal water
and wastewater, pulp and paper, and
process control. The SHARKTXP
enclosure is also polycarbonate with
a NEMA 4X front panel, and DIN rail
mounting hardware on the back.
• Shark-TXP: Panel or DIN
rail mounting hardware provided
Applications
• Process Control
• Industrial and Municipal
• Water Treatment
• Industrial and Municipal
• Waste Treatment and Neutral-
ization
• Fume Scrubbers
• Suitable for the Plating, Circuit
Board Manufacturing, Food and
Beverage, Chemical Processing,
Pulp & Paper, Mining, Nuclear
Energy and Pharmaceutical Industries
by
100 School Street
Andover, MA 01810
Toll free: 855-747-8723
www.WaterAnalytics.net
Metrix
Water Analytics
978-749-9949
SHARK TX/P pH, ORP, Conductivity, Flow Transmitter
Technical Data
pH ORP Conductivity Flow
Display
Measuring Range
Temperature
Compensation
Temperature Unit
Temperature Sensor
Calibration modes
Ambient Conditions
Sensor to Trans-
mitter Distance
Analog Output
Memory Back-up
Mechanical
Sensor Input
Invalid Entries
Manual Test Mode
Output Hold
Calibration Data
Auto Return
Display Damping
Net Weight
pH: 0.01 to 14.00
Temp: 0 to 100°C
or 32° to 212°F
Automatic or Manual
0 to 100°C (32° to +212°F)
User selectable: 300Ω NTC Thermistor, 3000Ω NTC Thermistor or Pt. 1000 RTD
Auto-Calibration,
Manual Calibration,
Temperature Display
Isolated Output, Range expand 0 to 100% of full scale (min segment 10% of full scale),max. load 800Ω
SHARKTX Enclosure:NEMA 4X, 1/4 DIN, polycarbonate enclosure with two 1/2” conduit holes
Probe: -600 to +600 mV
Temp. Sensor: 0 to 9999 Ω
Recall data from last calibration, calibration mode, 1st&2nd accepted buffer value
and probe mV output, calibration tempera-
ture, calibration slope, and probe efciency
User can select rate at which SHARK updates display. Enables display damping of unstable process
Front Panel: 4 x 7 segment 1/2” LED display, 1 LED indicator 0n-line,7 LED
Bar Graph. Inside Panel: 2 x 16 alpha-numeric LCD display
MΩ/
3
cm
µS/
3
ORP: -1999 to +1999mV
(Dependent on sensor)
Temp: 0 to 100°C
or 32° to +212°F
Not required
°C or °F Not required
Manual Calibration
Temperature Calibration
Temperature: -20°C to +60°C or -4°F to +140°F Humidity: 0 to 90% RH (non-condensing)
Differential Sensor: 3000 ft
Combination Sensor:10 ft
All user settings are retained indenitely in memory (EEPROM)
SHARKTXP Enclosure:NEMA 4X front panel, 1/4 DIN, polycarbonate
SHARKTX Mounting: Universal Mounting kit for surface, pipe and panel mount included
SHARKTXP Mounting: Panel and DIN rail mount included
Probe: -1999 to
+1999 mV
Temp. Sensor:
0 to 9999 Ω
Invalid entries cannot be stored
Process value can be simulated with arrow keys to verify correct setup of outputs
4 to 20 mA output is placed on hold when the transmitter is in Menu mode
User selectable auto return if the transmitter is left in menu mode for more than 10 min.
SHARK-TX: 0.71 lbs (0.32 kg)
SHARK-TXP: 0.25 lbs (0.12 kg)
cm
mS/
3
cm
Automatic or Manual
User selectable tempera-
ture compensation slope
0.0 to 10.0% / °C.
0 to 100°C (32° to 212°F)
Dry Calibration
Sample Calibration
Temperature Calibration
4 to 20 mA
Cell: 0 to 9999 Ω
Temp. Sensor: 0 to 9999 Ω
Recall data from last calibra-
tion, calibration buf fer ac-
cepted value and cell resistance,
calibration temperature.
0 to 19.9 0.01
0 to 2.00 0.01
0 to 20.0 0.1
0 to 200 0.1
0 to
2000
0 to 20 10
0 to 200 50
300 ft 2000 f t
1.0
Flow: 0 to 9999 with
selectable ow rate units
Volume: 0 to 9999 with
Auto Range Flow rate
units: Gallons (GP),
Cubic Feet (CF), Liters
(LP), Cubic Meters (CM),
custom by entering factor
related to Gallons.
Time units: Seconds (S),
Minutes (M), Hours (H)
Not required
K factor input
Paddle: 0 to 2000 Hz
Recall store K factor.
www.WaterAnalytics.net 978-749-9949 855-747-8723