Applied Motion STAC6-C User Manual

Page 1
STAC6-S • STAC6-S-220
STAC6-Q • STAC6-Q-220
STAC6-QE • STAC6-QE-220
STAC6-Si • STAC6-Si-220
STAC6-C • STAC6-C-220
920-0029 Rev. C 5/2/2012
Page 2
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Contents
Safety Instructions............................................................................................................................4
Over-Current Protection ...................................................................................................................5
Block Diagrams ............................................................................................................................... 6
Motion Control Options ...................................................................................................................9
Getting Started ...............................................................................................................................10
Connecting to the PC using RS-232 ..............................................................................................11
Connecting to the PC using RS-485 ..............................................................................................12
Connecting to the CANopen Network ............................................................................................. 15
Connecting AC Power .................................................................................................................... 17
Connecting the Motor ....................................................................................................................18
Connecting Other Motors ............................................................................................................... 20
Connecting an Encoder ................................................................................................................. 22
Wiring Inputs and Outputs .............................................................................................................24
Connecting Digital Inputs on the IN/OUT1 connector ....................................................................25
Connecting Digital Outputs on the IN/OUT1 connector .................................................................. 33
Connecting Analog Inputs on the IN/OUT1 connector .................................................................... 35
Connecting Inputs and Outputs to IN/OUT2 ................................................................................... 37
Connecting Digital Inputs on the IN/OUT2 connector ....................................................................37
Connecting Digital Outputs on the IN/OUT2 connector .................................................................. 42
Connecting Analog Inputs on the IN/OUT2 connector .................................................................... 44
Recommended Motors ................................................................................................................... 45
Motor Dimensions .........................................................................................................................46
Torque-Speed Curves.....................................................................................................................49
Mounting the Drive ........................................................................................................................52
Mechanical Outline ........................................................................................................................53
Technical Specifications ................................................................................................................. 54
Mating Connectors and Accessories .............................................................................................. 56
Alarm Codes ..................................................................................................................................57
2
Page 3
STAC6 Hardware manual
920-0029 Rev. C
5/2/2012
(This page intentionally left blank)
3
Page 4
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Safety Instructions

Only qualified personnel are permitted to transport, assemble, commission, and maintain this equipment. Properly qualified personnel are persons who are familiar with the trans­port, assembly, installation, commissioning and operation of motors, and who have the appropriate qualifications for their jobs. The qualified personnel must know and observe the following standards and regulations:
IEC 364 resp. CENELEC HD 384 or DIN VDE 0100 IEC report 664 or DIN VDE 0110 National regulations for safety and accident prevention or VBG 4
To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installa­tion, and operation are in compliance with the latest revision of these codes.
Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particu­lar application, nor do we assume any responsibility for your product design, installation, or operation.
• Read all available documentation before assembly and commissioning. Incorrect handling of products
in this manual can result in injury and damage to persons and machinery. Strictly adhere to the technical information on the installation requirements.
• It is vital to ensure that all system components are connected to earth ground. Electrical safety is impos­sible without a low-resistance earth connection.
• The STAC6 contains electrostatically sensitive components that can be damaged by incorrect handling.
Discharge yourself before touching the product. Avoid contact with high insulating materials (artificial fabrics, plastic film, etc.). Place the product on a conductive surface.
• During operation keep all covers and cabinet doors shut. Otherwise, there are deadly hazards that could
possibility cause severe damage to health or the product.
• In operation, depending on the degree of enclosure protection, the product can have bare components that
are live or have hot surfaces. Control and power cables can carry a high voltage even when the motor is not rotating.
4
Page 5
920-0029 Rev. C
STAC6 Hardware manual
• Never pull out or plug in the product while the system is live. There is a danger of electric arcing and
danger to persons and contacts.
• After powering down the product, wait at least ten minutes before touching live sections of the equipment
or undoing connections (e.g., contacts, screwed connections). Capacitors can store dangerous voltages for long periods of time after power has been switched off. To be safe, measure the contact points with a meter before touching.
Be alert to the potential for personal injury. Follow the recommended precautions and safe operating practices. Safety notices in this manual provide important information. Read and be familiar with these instructions before attempting installation, operation, or maintenance. The purpose of this section is to alert users to possible safety hazards associated with this equipment and the precautions that need to be taken to reduce the risk of personal injury and damage to the equipment.
Failure to observe these precautions could result in serious bodily injury, damage to the equipment ,or operational difficulty.
5/2/2012

Over-Current Protection

The STAC6 has hardware over-current detection circuits that protect the drive against “phase to ground” and “phase to phase” motor shorts. These circuits directly disable the amplifier in a rapid fashion to prevent damage to the driver circuitry.
Typically, the over-current circuitry will react to an over-current condition in 3 to 5 micro-seconds. For a short occurring in a motor, the motor leads provide enough resistance and inductance to keep the peak current from exceeding the peak rating of the power transistors during this time period. The recommended motors for the STAC6 all include 10 foot cables.
In essence the motor/cable system is a part of the over-current circuitry. If the drive is directly shorted with a very short wire, this condition may cause current conditions that exceed the peak current rating of our power transistors and therefore could weaken or cause failure in the drive power devices.
Repetitive short circuits also risk damage to the drive. If a short circuit fault occurs, please power off the drive and investigate carefully before restoring power.
5
Page 6
920-0029 Rev. C 5/2/2012

Block Diagrams

Block Diagram - STAC6-Si, STAC6-Si-220
STAC6 Hardware manual
120 VAC*
X1/STEP
X2/DIR
X3/ENABLE
X4/ALMRST
X5
X6/CCWLIM
X7/CWLIM
Y1/FAULT
Y2/MOTION
Y3/BRAKE
ANALOG IN
PC/MMI
RS485/422
*220 VAC for STAC6-220
**320 VDC for STAC6-220
Optical
Isolation
RS232
RS485/422
DC
Power Supply
Internal
Logic
Supply
Digital
Signal
Processor
160 VDC**
Status
Si
Programmable
Controller
eeprom
ANALOG IN
Regeneration Clamp Circuit
MOSFET
PWM
Power
Amplifier
Interface
Optical
Isolation
motor
encoder
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8 OUT1
OUT2
OUT3
OUT4
6
Page 7
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
Block Diagram - STAC6-S, STAC6-Q, STAC6-QE, STAC6-S-220, STAC6-Q-220, STAC6­QE-220
120 VAC*
X1/STEP
X2/DIR
X3/ENABLE
X4/ALMRST
X6/CCWLIM
X7/CWLIM
Y1/FAULT
Y2/MOTION
Y3/BRAKE
ANALOG IN
PC/MMI
RS485/422
*220 VAC for STAC6-220
**320 VDC for STAC6-220
X5
Optical
Isolation
RS232
RS485/422
DC
Power Supply
Internal
Logic
Supply
Digital
Signal
Processor
Status
ANALOG IN
-QE ONLY
160 VDC**
Amplifier
Interface
Regeneration Clamp Circuit
MOSFET
PWM
Power
Optical
Isolation
motor
encoder
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8 OUT1
OUT2
OUT3
OUT4
7
Page 8
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Block Diagram - STAC6-C and STAC6-C-220
120 VAC*
X1/STEP
X2/DIR
X3/ENABLE
X4/ALMRST
X5
X6/CCWLIM
X7/CWLIM
Y1/FAULT
Y2/MOTION
Y3/BRAKE
ANALOG IN
PC
(for Setup Only)
CAN2.0b
*220 VAC for STAC6-220
**320 VDC for STAC6-220
Optical
Isolation
RS232
CANopen
DC
Power Supply
Internal
Logic
Supply
Digital
Signal
Processor
160 VDC**
Status
Regeneration Clamp Circuit
MOSFET
PWM
Power
Amplifier
Interface
motor
encoder
8
Page 9
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012

Motion Control Options

STAC6-S Control Options
Basic drive: Analog, digital and host command input.
Pulse & Direction, A/B Quadrature, CW/CCW Pulse.
Velocity (Oscillator) Mode.
Host command execution of SCL commands for control from a host PC or PLC using RS-232 or RS-
485 serial communication.
Compatible with SiNet Hub 8 and SiNet Hub 444 for multi-axis Si programming.
STAC6-Q, STAC6-QE Control Options
Programmable drive: Built-in Q controller.
Comprehensive single-axis programming language.
Powerful feature set.
Complex motion and machine control.
Math functions.
Register manipulation.
Multi-tasking.
Host interrogation/interface while executing internal programs.
STAC6-QE comes with expanded I/O.
STAC6-Si Control Options
Programmable Drive: Built-in Si indexer.
Easy-to-use Si Programmer™ software.
Graphical point-and-click format combines motion, I/O, and operator interface.
Stand-alone operation.
Integrated Configurator for motor setup, encoder setup, and alarm history.
Easily integrates with other devices such as sensors, PLCs, etc.
Software and programming cable included.
STAC6-C Control Options
CANopen Node.
Compliant to CANopen standards DS301
Supports the following DSP402 operating modes:
Profile Position Mode
Profile Velocity Mode
Homing Mode
Additionally, supports stand-alone Q Programming with CANopen execution
9
Page 10
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Getting Started

This manual describes the use of STAC6 series of step motor drives. What you need to know and what you must have depends on the drive model. For all models, you’ll need the following:
• 120VAC or 220VAC single phase power.
• A compatible step motor (see recommended motors section)
• A small at blade screwdriver for tightening the connectors (included).
• A personal computer running Microsoft Windows 98, 2000, NT, Me, XP or Vista or 7.
• The Applied Motion CD (included)
If you’ve never used a STAC6 drive before you’ll need to get familiar with the drive and the set up software before you try to deploy the system in your application. We strongly recommend the following:
1. For -S drives, install the STAC Configurator™ software application from the CD. For -Q and QE drives, install the STAC Configurator™ and Q Programmer™ software applications from the CD. For -Si drives, install and use the Si Programmer™ software for configuration and programming. For -C drives, install the STAC Configurator™ and the CANopen Example Program software applications from the CD. Q Programmer™ software may also be installed, if needed.
2. Launch the software by clicking Start...Programs...Applied Motion...
3. Connect the drive to your PC with the programming cable.
4. Connect the drive to the motor.
5. Connect the drive to the AC power.
6. Apply power to the drive.
10
Page 11
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012

Connecting to the PC using RS-232

• Locate your computer within 8 feet of the drive.
• Your drive was shipped with a communication cable. Plug the large end into the serial port of your PC
and the small end into the PC/MMI jack on your drive. Secure the cable to the PC with the screws on the sides.
CAUTION
1. Never connect a drive to a telephone circuit. It uses the same connectors and cords as telephones and modems, but the voltages are not compatible.
2. Drive ground and PC ground should be at the same potential. Different ground potentials for the drive and PC can result in excessive current through the ground pin of the RS-232 port, resulting in failure of the port.
If your PC does not have a serial port, you should purchase a USB-serial converter to convert one of your PC’s USB ports into an RS-232 (COM) port. For 32-bit Windows operating systems, we have had good results with the Port Authority “USB Serial DB9” Adapter from CablesToGo.com and with the SW1301 from SewellDirect.com. Some laptops also have a PCMCIA slot, in which case the SSP-100 from Sewell Direct is a good choice. For 64-bit Windows operating systems, namely Windows Vista 64 and Windows 7 64, the Prolific-based adapters listed above do not work. For these PCs we suggest the USB-COMi-M or USB-CBL from Byterun­ner.com. These adapters also work the 32-bit operating systems.
For USB choices, refer to page 52.
ground (to PC ground)
TX (to PC RX)
Pin Assignments of the PC/MMI Port (RJ11 connector)
RX (to PC TX)
No connection
11
Page 12
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Connecting to the PC using RS-485

RS-485 allows you to connect more than one drive to a single host PC, PLC, HMI or other computer. It also allows the communication cable to be long (more than 1000 feet). But the device to which you connect must have an RS-422 or RS-485 port.
GND
Pin diagram is shown to the right. Wiring diagrams can be found on this and the next page. We recommend the use of Category 5 cable. It is widely used for computer net­works, it is inexpensive, easy to get and certified for quality and data integrity.
The STAC6 drives can be used with either two wire or four wire RS-485 implementations. The connection can be point to point (i.e. one drive and one host) or a multi-drop network (one host and up to 32 drives).
Four wire systems utilize separate transmit and receive wires. One pair of wires must connect the host
computer’s transmit signals to each drive’s RX+ and RX- terminals. Another pair connects the TX+ and TX-
drive terminals to the host computer’s receive signals. A logic ground terminal is provided on each drive and can be used to keep all drives at the same ground potential. This terminal connects internally to the DC power supply return (V-), so if all the drives on the RS-485 network are powered from the same supply it is not necessary to connect the logic grounds. You should still connect one drive’s GND terminal to
the host computer ground.
TX TX+
RX
RS-485/422
RX+
Four wire systems are better than two wire types because the host can send and receive data at the same time, increasing system throughput. Furthermore, the host never needs to disable its transmitter, which
simplies your software. We recommend that a 120 ohm terminating resistor be connected between RX+ and RX- at the farthest drive from the host.
to PC GND
to PC RX-
to PC RX+
to PC TX-
120
to PC TX+
+RX- +TX- GND +RX- +TX- GND +RX- +TX- GND
Drive #1 Drive #2 Drive #3
Two wire systems transmit and receive on the same pair of wires. The host must not only disable its transmitter before it can receive data, it must do so quickly, before a drive begins to answer a query. The
12
Page 13
920-0029 Rev. C
+RX- +TX- GND +RX- +TX- GND +RX- +TX- GND
to PC TX+ (B)
to PC TX- (A)
to PC GND
Drive #1 Drive #2 Drive #3
120
STAC6 Hardware manual
5/2/2012
STAC6 drives include a “transmit delay” parameter that can be adjusted to compensate for a host that is slow to disable its transmitter. This adjustment can be made over the network using the TD command, or it can be set using the STAC Configurator™ software. It is not necessary to set the transmit delay in a four wire system. We recommend a 120 ohm terminating resistor be connected between the two transmit / receive wires at the farthest drive from the host.
RS-232 to RS-485 2-wire Converter
Model 485-25E from Integrity Instruments (800-450-2001) works well for converting your PC’s RS-232 port to RS-485. It comes with everything you need. Connect the adaptor’s “B” pin to the drive’s TX+
and RX+ terminals. Connect “A” to the drive’s TX- and RX- terminals.
Converting USB to RS-485
The USB-COMi-M from www.byterunner.com is an excellent choice for USB to RS-485 conversion. It can be used with 2 wire or 4 wire systems.
For two wire RS-485, set SW1 to ON and SW2-4 to OFF. On the USB-COMi-M screw terminal connector:
Pin1 goes to RX- and TX-. Connect pin 2 to RX+ and TX+.
Pin 6 is ground. The DB-9 is not used.
For four wire RS-485, set SW1,3,4 to ON and SW2 to OFF. On the USB-COMi-M screw terminal connector:
USB-COMi-M STAC6 Drive
pin 1 RX- pin 2 RX+ pin 3 TX+ pin 4 TX-
pin 6 GND
13
Page 14
920-0029 Rev. C 5/2/2012
USB-COMi-M Switch Settings
STAC6 Hardware manual
4 Wire
RS-232
1ON2 3 4
Note: Prolific-based USB serial adapters do not work with Vista 64 or Windows 7 64 bit operating systems. Suggested adapters are Byterunner USB-COMi-M or Byterunner USB-COM-CBL.
Assigning Addresses in Multi-axis Systems
Before wiring the entire system, you’ll need to connect each drive individually to the host computer so that a unique address can be assigned to each drive. Use the programming cable and the STAC Configurator™ software that came with your drive for this purpose.
Connect the drive to your PC, then launch STAC Configurator™. Finally, apply power to your drive. If you have already configured your drive, then you should click the Upload button so that the STAC Configura- tor™ settings match those of your drive. Click on the Motion button, then select the “SCL” operating mode. If you have a Q drive, you may want to select “Q Programming”. Either way, you’ll see the RS-485 Address
panel appear. Just click on the address character of your choice. You can use the numerals 0..9 or the special characters ! “ # $ % & ‘ ( ) * + , - . / : ; < = > ? @ . Just make sure that each drive on your network
has a unique address. If you are using a 2 wire network, you may need to set the Transmit Delay, too. 10 milliseconds works on the adapters we’ve tried. Once you’ve made your choices, click Download to save the settings to your drive.
RS-485
1ON2 3 4
2 Wire
RS-485
1ON2 3 4
14
Page 15
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012

Connecting to the CANopen Network

GND
CAN_L
SHLD
CAN_H
The CANopen connector is a 4-pin spring lock type connector. The CANopen network should be connected in a daisy-chain fashion, with a 120 ohm terminating resistor at each end of the network. Please see the CANopen manual for more information.
CANopen Connector
Node ID Switch
Each node on a CANopen network must have a unique Node ID. On the STAC6, this is set using both the Configurator software (above, left), as well as the sixteen position hardware switch on the front of the drive (above, right). CANopen Node IDs are seven bits long, with a range of 1 - 127, or 0x01 - 0x7F in hexadeci­mal notation. The lower four bits, 0x0-0xF are set using the hardware switch, and the upper three bits, 0x0
- 0x7, are set using Configurator.
A Node ID of 0x39, for example, may be set by turning the switch on the drive to 9, and setting the Configu­rator software to a range of 0x30 - 0x3F.
15
Page 16
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Bit Rate Switch
The CANopen network bitrate is set by the rotary switch on the front of the drive. The bitrate must be the same for all nodes on the CANopen network. The table below shows the various bitrates supported by Applied Motion Products, and their corresponding switch settings. Please note, any changes to the bitrate require either a powercycle or a CANopen reset command to take effect.
Octal Switch Setting Resultant Bit Rate 0 1 Mbps
1 800 kbps
2 500 kbps
3 250 kbps
4 125 kbps
5 50 kbps
6 20 kbps
7 12.5 kbps
16
Page 17
920-0029 Rev. C
To Earth Ground
To Neutral
To Line (Hot)
g
r
e
e
n
bl
a
c
k
o
r
b
r
o
w
n
w
h
i
t
e
o
r
b
l
u
e
AC Power Plug
STAC6 Hardware manual
5/2/2012

Connecting AC Power

Using the connector supplied connect to the AC supply per the diagram below. Use 16 AWG wire for Line (L) and Neutral (N). Use 14 AWG for Earth Ground (G).
Care should always be taken when working with high voltages.
In regions where the single-phase supply is higher, an auto transformer can be used to drop the voltage to the correct level.
Fusing
The STAC6 contains an internal 8A fast acting fuse. The STAC6-220 contains an internal 3.5A slo-blo (time delay) fuse. If an external fuse is desired, we recommend a 6A fast acting fuse for the 120V STAC6 and a 5 amp fast acting fuse for the 220V version.
Line Filter
For applications requiring CE EMC compliance, a Corcom 6ET1 line filter is required in series with the AC input.
17
Page 18
920-0029 Rev. C
GREEN
SHIELD
RED
BLACK
WHITE
SHLD
B
B+
A
A+
BLUE
ORANGE
BROWN
YELLOW
A+
A–
B+ B–
8
lead
motor
Series Connected
8 Leads Parallel Connected
A+
A–
B+ B–
8
lead
motor
White
Orange
Brown
Green
Red
Yellow Blue
Black
Orange
Red
Brown
Yellow
Blue Black
White
Green
SHLD
SHLD
5/2/2012
STAC6 Hardware manual

Connecting the Motor

Never connect or disconnect the motor while the power is on.
Note: it is highly recommended that you use a motor with a shielded cable with the STAC6.
The recommended Applied Motion motors for the STAC6 include shielded cables. See the Recommended Motors section for a list of part numbers. Note: If you need a rear shaft on the motor, for an encoder or
otherwise, make sure to add a “D” to the part number. Example: HT23-550D.
If your motor does not already have a connector attached or if you need to change the length of the cable, please follow the illustrations below. Be sure to connect the cable shield for safety and to minimize electrical interference.
Motors recommended for the STAC6-220 drives can also be used with 120V drives if they are wired in a parallel configuration. See the diagram for parallel winding.
Series connection
• Use with all STAC6-220 drives and the following motors:
• HT23-552, HT23-553, HT23-554
• HT34-495, HT34-496, HT34-497
• Use with STAC6 (120) drives and the following motors:
• HT23-548, HT23-549, HT23-550
• HT34-488, HT34-489, HT34-490
18
Page 19
STAC6 Hardware manual
8 Leads Parallel Connected
A+
A–
B+ B–
8
lead
motor
Orange
Red
Brown
Yellow
Blue Black
White
Green
SHLD
GREEN
SHIELD
RED
BLACK
WHITE
SHLD
B
B+
A
A+
BLUE
ORANGE
BROWN
YELLOW
Parallel connection
• Do not use parallel connection with STAC6-220 drives.
• Use with STAC6 (120) drives and the following motors:
• HT23-552, HT23-553, HT23-554
• HT34-495, HT34-496, HT34-497
920-0029 Rev. C
5/2/2012
19
Page 20
920-0029 Rev. C
A+
A–
B+ B–
4
lead
motor
Red
Blue
Yellow
White
4 Leads
A+
A–
NC
B+
B–
NC
6
lead
motor
Red
Black
Red/
Wht
Green
Grn/Wht
White
A+
A–
NC
B+B–
NC
6
lead
motor
Grn/Wht
White
Green
Red
Red/
Wht
Black
6 Leads Series Connected 6 Leads Center Tap Connected
5/2/2012
STAC6 Hardware manual

Connecting Other Motors

We can’t stress enough the wisdom in using one of the recommended motors. We’re not just trying to make money here, we want your application to be successful and the odds of that are highest when you have a high quality motor whose torque, rotor inertia and harmonic waveform content are precisely known. Further­more, our motors include shielded cables to reduce electrical emissions and enhance safety and come with pre wired mating connectors which further reduces the risk of error. If you do want to connect other motors , here is some information that will help
Four lead motors can only be connected one way. Please follow the sketch below.
Six lead motors can be connected in series or center tap. In series mode, motors produce more torque at low speeds, but cannot run as fast as in the center tap configuration. In series operation, the motor should be operated at 30% less than the rated current to prevent overheating. Winding diagrams for both connec­tion methods are shown below. NC means not connected.
20
Page 21
920-0029 Rev. C
A+
A–
B+ B–
8
lead
motor
8 Leads Series Connected 8 Leads Parallel Connected
A+
A–
B+
B–
8
lead
motor
Orange
Org/Wht
Blk/Wht
Black
Red
Red/
Wht
Yel/ Wht
Yellow
Orange
Org/
Wht
Blk/Wht
Black
Red
Red/Wht
Yel/ Wht
Yel low
STAC6 Hardware manual
5/2/2012
Eight lead motors can also be connected in two ways: series and parallel. As with six lead motors, series operation gives you less torque at high speeds, but may result in lower motor losses and less heating. In series operation, the motor should be operated at 30% less than the unipolar rated current. The wiring diagrams for eight lead motors are shown below.
21
Page 22
920-0029 Rev. C
encoder Z+ (5)
NC (10)
encoder B- (4)
NC (9)
encoder B+ (3)
NC (13)
NC (14)
NC (15)
(12) NC
(11) NC
(6) encoder Z-
(1) encoder A+
(7) +5VDC 200mA
(2) encoder A-
(8) GND
5/2/2012
STAC6 Hardware manual

Connecting an Encoder

The motors recommended for use with STAC6 drives are available with rear-shaft mounted encoders. Note: remember to always order a double-shaft motor if you need an encoder option. The mating cables available for these encoders come with an HD-15 connector on one end that connects directly to the Encoder connec­tor on the STAC6, and a mating connector on the other end that connects directly to the encoder. Simply connect the cable between the encoder and the drive and you’re done. For applications where you might use your own encoder, you’ll need to connect to the STAC6 drive’s encoder connector using the pin assignments below.
If you are using an encoder with single ended outputs, shame on you. Differential connections are far less sensitve to electrical interference and life is too short to waste time deciphering the bizarre problems that
can occur with a poor quality encoder. That said, single ended encoders should be connected to the A+ and B+ terminals. Leave A- and B- unconnected. They are internally biased to the proper voltage for best results. You’ll also need to select the “single ended” box in the Encoder button of STAC Configurator™ or the drive
will think you have a broken encoder wire. That’s another good reason to use a differential encoder, the STAC6 can detect a broken wire or bad signal and alert you to the problem.
22
Page 23
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
Encoder Feedback Options
The following encoder feedback options are configured and enabled using the STAC Configurator™ soft­ware.
Stall Detection continuously compares the actual motor position, as reported by the encoder, against the theoretical motor position. If the motor lag reaches 7.2 mechanical degrees behind the target position, a position fault occurs. This includes a motor at rest being driven out of position by an external force.
Stall Prevention can prevent many stalls before they occur. The STAC6 achieves this by using the encoder to monitor the lead angle of the motor, a measure of torque utilization. If the motion profile begins to demand more torque than the motor can produce, the velocity is automatically reduced before the motor stalls. To engage stall prevention, simply check the Stall Prevention box in the STAC Configurator™ software and enter the maximum torque utilization you want to allow.
In the event that the motor cannot move at all, such as hitting a hard stop, you may want to fault the drive after a given amount of time by checking the Hard Stop box and entering a time limit.
23
Page 24
920-0029 Rev. C
18 17 16 15 14
13 12 11 10
9 8 7 6 5 4
2
3
1
19
20
21
22
23
24
25
+5V
Out 1-
Out 2+
Out 1+ Ain Com N/C
Ain 1
IN 8-
COM
IN 5
IN 6
IN 7+
IN 8+
IN 7-
IN 4
IN 1
COM
IN 2
COM
IN 3
Out 2-
Out 3+
Out 3-
Out 4+
Out 4-
IN/OUT 2
5/2/2012
STAC6 Hardware manual

Wiring Inputs and Outputs

The STAC6 drives come with a number of inputs and outputs for interfacing to external control hardware:
High speed digital inputs for step & direction commands or encoder following, 5V logic. These inputs, X1/STEP and X2/DIR, are available on all models. They can also be used to connect
sensors and other types of devices. Connections to these inputs can be sourcing, sinking or differential.
Lower speed digital inputs for other signals, 12 - 24 volt logic, accepting sourcing, sinking or
differential signals. All STAC6 models have 5 of these inputs on the IN/OUT1 connector. STAC6-QE and Si models only have a total of 13 of these inputs, 5 on the IN/OUT 1 connector and 8 on the IN/OUT 2 connector.
Analog inputs for analog speed and positioning modes, included on all drives. Can be congured
for 0-10V, 0-5V, ±10V or ±5V, with or without offset. The STAC6-QE and Si models have an extra analog input rated at 0-5VDC - for use in SCL and Q applications only.
Digital Outputs rated at 30V, 100mA. There are three outputs on IN/OUT1, which is present on
all models. STAC6-QE and Si models only have an additional 4 digital outputs on the IN/OUT2 connector.
Connector Pin Diagrams
IN/OUT 1
Analog IN+
Analog IN-
X7 / CW Limit
X6 / CCW Limit
X5
X4 / Alarm Reset
X3 / Enable X COMMON
X2 / DIR-
X2 / DIR+
X1 / STEP -
X1 / STEP +
GND
1 2 3 4 5 6 7 8
9 10 11 12 13
IN/OUT1 connector, this connector is present on all models
14 15
16 17 18 19
20 21 22 23 24 25
Front View
Y1 / BRAKE
Y2 / MOTION
Y3 / FAULT Y COMMON +5V OUT GND
GND
GND +5V OUT +12V OUT
IN/OUT2 connector, this connector is present on Si and QE models
24
Page 25
920-0029 Rev. C
STAC6
Stepper
Drive
IN/OUT 1
COM
DIR-
DIR DIR+
STEP-
STEP STEP+
Indexer
with
Sourcing
Outputs
STAC6
Stepper
Drive
IN/OUT 1
+5V OUT
DIR+
DIR DIR-
STEP+
STEP STEP-
Indexer
with
Sinking
Outputs
STAC6 Hardware manual

Connecting Digital Inputs on the IN/OUT1 connector

High Speed Digital Inputs
All STAC6 drives include two high speed inputs called STEP and DIR. They accept 5 volt single-ended or differential signals, up to 2 MHz. Normally these inputs connect to an external controller
that provides step & direction command signals. You can also
connect a master encoder to the high speed inputs for follow­ing applications. Or you can use these inputs with Wait Input, If Input, Feed to Sensor, Seek Home and other such commands.
Connection diagrams follow.
12
X1/STEP+
11
X1/STEP
10
X2/DIR+
9
X2/DIR
IN/OUT1 Connector
inside drive
-
-
5/2/2012
Connecting to indexer with Sourcing Outputs
Connecting to Indexer with Sinking Outputs
25
Page 26
920-0029 Rev. C
STAC 6
IN/OUT 1
DIR+
DIR+
DIR- DIR-
STEP+
STEP-
STEP+
STEP-
Indexer
with
Differential
Outputs
STAC 6
Master
Encoder
GND
DIR-
DIR+
STEP-
STEP+
GND
B-
B+
A-
A+
5/2/2012
STAC6 Hardware manual
Connecting to Indexer with Differential Outputs (Many high speed indexers have differential outputs)
Wiring for Encoder Following (Encoder power can be supplied from the +5V OUT terminal on IN/OUT 1 if the encoder requires no more than 100mA)
26
Page 27
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
Using High Speed Inputs with 12-24 Volt Signals
Most PLCs don’t use 5 volt logic. You can connect signal levels as high as 24 volts to the STEP and DIR
inputs if you add external dropping resistors, as shown below.
For 12 volt logic, add 820 ohm, 1/4 watt resistors For 24 volt logic, use 2200 ohm, 1/4 watt resistors
WARNING: The maximum voltage that can be applied directly to a high speed input terminal is 24 volts. Never apply high voltage AC to an input terminal.
PLC
+12-24V
with
Sourcing
Outputs
Connecting to PLC with Sourcing (PNP) Outputs (Most PLC’s use 24 volt logic)
OUT1 DIR+
R
R
OUT2 STEP+
GND
+12-24V
STEP-
DIR-
DIR+
STAC 6
Drive
PLC
with
Sinking
Outputs
Connecting to PLC with Sinking (NPN) Outputs (Most PLC’s use 24 volt logic)
DIR DIR-
R
R
STEP STEP-
STEP+
STAC6
Drive
27
Page 28
920-0029 Rev. C
2200
2200
2200
2200
2200
inside IN/OUT1
8
7
6
5
3
4
STAC-6
COM
X3/ENABLE
X4/ALRM RST
X5
X7/CW LMT
X6/CCW LMT
5/2/2012
STAC6 Hardware manual
+24VDC
Power
Supply
+
direction switch
2200
run/stop switch
(closed=run)
2200
DIR+
DIR-
STEP+
STAC6
Drive
- STEP-
Using Mechanical Switches at 24 Volts.
Standard Digital Inputs
As we mentioned above, the high speed STEP and DIR inputs are configured for five volt logic. All other digital inputs are designed for operation between 12 and 24 volts DC. This includes five inputs on the IN/
OUT 1 connector of all drives (X3-X7) and the eight digital inputs on the IN/OUT 2 connector of -Si and -QE
drives only (inputs IN1-IN8).
Single Ended Inputs
The STAC6 drives include single ended, optically isolated input circuits that can be used with sourcing or
sinking signals, 12 to 24 volts. This includes inputs X3-X7 on the IN/OUT 1 connector and inputs IN1 - IN6
on the IN/OUT 2 connector. This allows connection to PLCs, sensors, relays and mechanical switches. Because the input circuits are isolated, they require a source of power. If you are connecting to a PLC, you should be able to get power from the PLC power supply. If you are using relays or mechanical switches, you will need a 12-24 V power supply. This also applies if you are connecting the inputs to the programmable outputs of another Si product from Applied Motion.
28
Page 29
920-0029 Rev. C
IN/OUT1
switch or relay
(closed=logic low)
X3..X7
X COM
12-24
VDC
Power
Supply
-
+
STAC6 Hardware manual
5/2/2012
What is COM?
“Common” is an electronics term for an electrical connection to a common voltage. Sometimes “common” means the same thing as “ground”, but not always. In the case of the STAC6, if you are using sourcing (PNP) input signals, then you will want to connect COM to ground (power supply -). If you are using sinking
(NPN) signals, then COM must connect to power supply +.
Note: If current is owing into or out of an input, the logic state of that input is low or closed. If no current is owing, or the input is not connected, the logic state is high or open.
Digital Input Connection Examples
Connecting an Input to a Switch or Relay
29
Page 30
920-0029 Rev. C
IN/OUT1
NPN
Proximity
Sensor
IN
COM
output
+
-
+
NPN
Proximity
Sensor
X3...X7
X COM
output
+
12-24
VDC
Power
Supply
-
+
STAC6
IN/OUT1
PNP
Proximity
Sensor
output
+
COM
-
+
PNP
Proximity
Sensor
X3..X7
output
+
X COM
12-24
VDC
Power
Supply
-
+
5/2/2012
STAC6 Hardware manual
Connecting an NPN Type Proximity Sensor to an input (When prox sensor activates, input goes low).
Connecting a PNP Type Proximity Sensor to an input
30
Page 31
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
Connecting Limit switches to the STAC6 Drive
The X7/CW LIMIT and X6/CCW LIMIT inputs are used for connecting end of travel sensors. These inputs
are differential, which allows you to use signals that are sinking (NPN), sourcing (PNP) or differential (line driver). By connecting switches or sensors that are triggered by the motion of the motor or load, you can force the motor to operate within certain limits. This is useful if a program or operator error could cause damage to your system by traveling too far.
The limit inputs are optically isolated. This allows you to choose a voltage for your limit circuits of 12 to 24 volts DC. This also allows you to have long wires on limit sensors that may be far from the drive with less risk of introducing noise to the drive electronics. The schematic diagram of the limit switch input circuit is shown below.
inside STAC6
8
X COM
X7/CW LMT
3
4
X6/CCW LMT
IN/OUT 1 Connector
2200
2200
Wiring a Mechanical Limit Switch
You can use normally open or normally closed limit switches. Either way, wire them as shown here.
+
12-24
VDC
SUPPLY
-
X COM
X7/CW LMT
X6/CCW LMT
STAC6
Stepper
31
Page 32
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Wiring a Limit Sensor
Some systems use active limit sensors that produce a voltage output rather than a switch or relay closure. These devices must be wired differently than switches.
If your sensor has an open collector output or a sinking output, wire it like this:
X COM
X6..X7
STAC6
Stepper
+
DC
Power
Supply
+
Limit
Sensor
output
If the sensor output goes low at the limit, select the option “closed” (in the software). If the output is open, or high voltage, choose “open”.
Other sensors have sourcing outputs. That means that current can ow out of the sensor output, but not into
it. In that case, wire the sensor this way:
+
DC
Power
Supply
+
Proximity
Sensor
output
X6..X7
X COM
STAC6
Stepper
32
Page 33
920-0029 Rev. C
STAC6 Hardware manual

Connecting Digital Outputs on the IN/OUT1 connector

5/2/2012
Analog IN+
Analog IN-
X7 / CW Limit
X6 / CCW Limit
X4 / Alarm Reset
X5
X3 / Enable
X COMMON
X2 / DIR-
X2 / DIR+
X1 / STEP -
X1 / STEP +
GND
IN/OUT 1
1 2 3 4 5 6 7 8
9 10 11 12 13
14 15 16 17 18 19
20 21 22 23 24 25
Front View
Y1 / BRAKE
Y2 / MOTION
Y3 / FAULT Y COMMON +5V OUT GND
GND GND +5V OUT +12V OUT
All STAC6 drives feature three digital outputs on the IN/OUT 1 connector:
Y1/Brake: controls an electric brake relay, automatically releasing and engaging as the drive requires
Y2/Motion: indicates that the drive has achieved a desired goal, such as a target position
Y3/Fault: closes when a drive fault occurs. The red and green LEDs will ash an error code.
14
Y1/BRAKE
17
Y COM
Y3/FAULT
16
15
Y2/MOTION
inside STAC-6
These outputs can be used to drive LEDs, relays and the inputs of other electronic devices like PLCs and counters. These outputs can only sink current.
The COM terminal must be tied to power supply (-).
33
Page 34
920-0029 Rev. C 5/2/2012
Diagrams of different connections follow.
Do not connect the outputs to more than 30VDC. The current through each output terminal must not exceed 100 mA.
Power Supply
STAC6 Hardware manual
5-24 VDC
+
STAC6
STAC6
Y1..Y3
YCOM
Y1..Y3
YCOM
Load
5-24 VDC
relay
1N4935 suppression diode
Power Supply
+
34
Page 35
920-0029 Rev. C
STAC6 Hardware manual

Connecting Analog Inputs on the IN/OUT1 connector

5/2/2012
Analog IN+
Analog IN-
X7 / CW Limit
X6 / CCW Limit
X4 / Alarm Reset
X5
X3 / Enable
X COMMON
X2 / DIR-
X2 / DIR+
X1 / STEP -
X1 / STEP +
GND
IN/OUT 1
1 2 3 4 5 6 7 8
9 10 11 12 13
14 15 16 17
18 19
20 21 22 23 24 25
Front View
Y1 / BRAKE Y2 / MOTION
Y3 / FAULT Y COMMON +5V OUT GND
GND GND
+5V OUT
+12V OUT
All STAC6 drives have two analog input pins that can be used separately as two, single-ended analog inputs or together as one, differential analog input. Whether separate or together, the maximum range that can be
applied to these pins is +/- 10V. The analog input(s) can be used by the drive for a number of dedicated
purposes for controlling the motor or can be used for general purpose analog input signals.
1
+10V to -10V
Signal
AIN+
STAC-6
13
signal return
GND
The analog input can be used for:
• Analog Velocity Mode
• Analog Positioning Mode.
Both of these modes use the analog input for commanding the stepper drive.
Other uses include using an analog signal to stop a move when using any of the “Feed to Sensor” type moves and waiting on an analog signal using the “Wait on Input”.
35
Page 36
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Basic Specifications:
The analog input can accept ±10 Volts.
The input has an impedance of 20K ohms.
Because of the nature of the design, the input will exhibit a 1.4V offset when not driven by an analog
source.
Low source impedance is important for minimizing analog errors, 100 ohms or lower is recommended.
WARNING - The analog input must be used with care. It is not optically isolated and may operate improperly or could be damaged when system grounds are not compatible.
Connecting an Analog Input to a Potentiometer or Joystick
24
+5V
cw
1k-10k
pot
1
AIN+
ccw
13
GND
2
AIN-
36
Page 37
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012

Connecting Inputs and Outputs to IN/OUT2

The IN/OUT2 connector is present as standard on the Si version of the drive. It is also standard on the QE version.

Connecting Digital Inputs on the IN/OUT2 connector

IN/OUT 2
13
IN 8-
IN 8+
IN 7-
IN 7+
IN 6
COM
IN 5 IN 4
COM
IN 3 IN 2
COM
IN 1
Digital Inputs
25
12 11 10
9 8 7 6 5 4 3 2 1
Out 4-
24
Out 4+
23
Out 3-
22
Out 3+
21
Out 2-
20
Out 2+
19
Out 1-
18
Out 1+
17
Ain Com
16
N/C
15
Ain 1
14
+5V
Single Ended Inputs
The STAC6-Si and STAC6-QE include single ended, optically isolated input circuits that can be used with sourcing or sinking signals, 12 to 24 volts. The IN/OUT 2 connector has 6 of these inputs (IN1 - IN6). These inputs allow connection to PLCs, sensors, relays and mechanical switches. Because the input circuits are isolated, they require a source of power. If you are connecting to a PLC, you should be able to get power from the PLC power supply. If you are using relays or mechanical switches, you will need a 12-24 V power supply. This also applies if you are connecting the inputs to the programmable outputs of another Si product from Applied Motion.
What is COM?
“Common” is an electronics term for an electrical connection to a common voltage. Sometimes “common” means the same thing as “ground”, but not always. In the case of the STAC6, if you are using sourcing (PNP) input signals, then you will want to connect COM to ground (power supply -). If you are using sinking
(NPN) signals, then COM must connect to power supply +.
37
Page 38
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
inside IN/OUT2
IN1
COM
IN2
IN3
COM
IN4
CWJOG
COM
CCWJOG
2200
2200
2200
2200
2200
2200
Connecting an Input to a Switch or Relay
+
12-24
VDC
Power
Supply
-
switch or relay
(closed=logic low)
COM
STAC6
IN
Use normally open momentary switch to trigger drive using Wait Input instruction.
Use single throw switch for parameter selection using If Input instruction.
Use normally open momentary switch for jogging.
38
Page 39
STAC6 Hardware manual
Connecting another Si Drive
+
IN/OUT2
OUT+
OUT–
Si354, 7080i etc
COM
IN
(When output closes, drive input goes low).
Connecting an NPN Type Proximity Sensor to an input
12-24
VDC
Power
Supply
-
920-0029 Rev. C
5/2/2012
12-24
VDC
Power
Supply
+
+
NPN
Proximity
-
Sensor
output
COM
IN
IN/OUT2
(When prox sensor activates, drive input goes low).
Connecting a PNP Type Proximity Sensor to an input
12-24
VDC
Power
Supply
+
-
(When prox sensor activates, drive input goes low).
+
PNP
Proximity
Sensor
output
IN
IN/OUT2
COM
39
Page 40
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Differential Inputs
The IN/OUT2 connector also includes two differential, optically isolated input circuits that can be used with sourcing or sinking signals, 12 to 24 volts. They are labeled IN7 and IN8. These inputs allow connection to PLCs, sensors, realys and mechanical switches. Because the input circuits are isolated, they require a source of power. If you are connecting to a PLC, you should be able to get power from the PLC power sup­ply. If you are using relays or mechanical switches, you will need a 12-24 V power supply. This also applies if you are connecting the inputs to the programmable outputs of another Si product from Applied Motion.
inside drive
IN7+
IN7-
IN8+
IN8-
IN+
+
5-24
VDC
SUPPLY
-
STAC6
IN-
Connecting a Mechanical Switch to a Differential Input
40
Page 41
STAC6 Hardware manual
IN+
+
DC
Power
Supply
+
NPN
Proximity
Sensor
output
Connecting an NPN Proximilty Sensor to a Differential Input
STAC6
IN-
920-0029 Rev. C
5/2/2012
+
DC
Power
Supply
+
PNP
Proximity
Sensor
output
IN+
STAC6
IN-
Connecting a PNP Proximilty Sensor to a Differential Input
41
Page 42
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Connecting Digital Outputs on the IN/OUT2 connector

IN/OUT 2
13
IN 8-
IN 8+
IN 7-
IN 7+
IN 6
COM
IN 5 IN 4
COM
IN 3 IN 2
COM
IN 1
12 11 10
9 8 7 6 5 4 3 2 1
25 24 23
22 21 20 19 18 17 16 15 14
Out 4­Out 4+ Out 3­Out 3+ Out 2­Out 2+ Out 1-
Out 1+ Ain Com N/C
Ain 1 +5V
Digital Outputs
The expanded I/O board adds four additional programmable outputs. The outputs can be used to drive LEDs, relays and the inputs of other electronic devices like PLCs and counters. On the IN/OUT 2 connector
outputs, both the “+” (collector) and “-” (emitter) terminals of each transistor are available on the connector
pins. This allows you to configure each output for current sourcing or sinking.
IN/OUT 2
OUT1+
OUT1-
OUT2+
OUT2-
OUT3+
OUT3-
OUT4+
OUT4-
Diagrams of each type of connection follow.
42
Page 43
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
Do not connect the outputs to more than 30VDC. The current through each output terminal must not exceed 100 mA.
12-24 VDC
STAC6-Si STAC6-QE
OUT+
Power Supply
+
COM
PLC
OUT-
Connecting output as a sourcing output.
STAC6-Si
OUT+
Load
STAC6-QE
OUT-
Connecting outputs as a sinking output.
relay
OUT+
STAC6-Si STAC6-QE
1N4935 suppression diode
OUT-
IN
5-24 VDC
Power Supply
+
5-24 VDC
Power Supply
+
Using output to control a relay.
43
Page 44
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Connecting Analog Inputs on the IN/OUT2 connector

IN/OUT 2
13
IN 8-
IN 8+
IN 7-
IN 7+
IN 6
COM
IN 5 IN 4
COM
IN 3 IN 2
COM
IN 1
Connecting to the Aux Analog Input (Ain 1)
The auxiliary analog input on the STAC6 IN/OUT 2 connector can be read back to the “Host” using the “IA” immediate type and “RA” buffered type Host commands.
See “Host Command Reference” for more information.
+5 volt DC is provided for powering potentiometers. A 1000 to 10000 ohm potentiometer is recommended.
25
12 11 10
9 8 7 6 5 4 3 2 1
Out 4-
24
Out 4+
23
Out 3-
22
Out 3+
21
Out 2-
20
Out 2+
19
Out 1-
18
Out 1+
17
Ain Com
16
N/C
15
Ain 1
14
+5V
A 0 to 5 volt analog signal may also be used. Usually this signal comes from a PLC, a PC with data acquisi­tion card or a motion controller. Connections are shown below.
The +5V terminal is an output. Do not connect it to a power supply.
0 - 5V
speed signal
signal return
AIN
GND
Connecting an Analog Input to an Active Signal
44
Page 45
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012

Recommended Motors

Applied Motion offers 12 recommended motors for use with the STAC6 drives. All 12 of these motors are recommended for use with the STAC6 (120) drives, but the connection to the drive should be series or parallel depending on the motor. See the Connecting the Motor section for details. 6 of these motors
are recommended for the STAC6-220 drives. These motors have their characteristics stored in the STAC
Configurator™ software making it easy to setup and configure them. For reference below is additional
information about these motors. All recommended STAC6 motors have 10ft shielded cables which act as part of the over-current protection circuit. See Over-Current Protection section earlier in this manual for details.
Recommended Motors - NEMA 23
STAC6 (120) STAC6-220
Motor Part No.
Connection
HT23-548 series 1.50 do not use
HT23-549 series 1.50 167 4.25E-03 2.17 (55)
HT23-550 series 1.80 255 6.80E-03 3.05 (77.5)
HT23-552 parallel 1.50 series 0.75 84.4 1.70E-03 1.71 (43.5)
HT23-553 parallel 1.50 series 0.75 167 4.25E-03 2.17 (55)
HT23-554 parallel 1.80 series 0.90 255 6.80E-03 3.05 (77.5)
Drive Current Setting
amps/phase Connection
Drive Current Setting
amps/phase
do not use
do not use
Holding Torque
oz-in
84.4 1.70E-03 1.71 (43.5)
Rotor Inertia
oz-in-sec^2
Motor Length
inch (mm)
Recommended Motors - NEMA 34
STAC6 (120) STAC6-220
Motor Part No.
Connection
HT34-488 series 5.10
HT34-489 series 5.10 1110 4.53E-02 4.63 (117.5) 0.5 (12.7)
HT34-490 series 5.80 1694 6.80E-02 6.14 (156)
HT34-495 parallel 5.10 series 2.55 555 2.27E-02 3.11 (79) 0.5 (12.7)
HT34-496 parallel 5.10 series 2.55 1110 4.53E-02 4.63 (117.5) 0.5 (12.7)
HT34-497 parallel 5.80 series 3.20 1694 6.80E-02 6.14 (156)
Drive Current Setting
amps/phase Connection
Drive Current Setting
amps/phase
do not use
do not use
do not use
Holding Torque
oz-in
555 2.27E-02 3.11 (79) 0.5 (12.7)
Rotor Inertia
oz-in-sec^2
Note: The “Drive Current Setting” shown here differs from the rated current of each motor because the rated current is RMS and the drive current setting is peak sine. If you are using a motor not listed here, for best results set the drive current at the motor’s rated current x 1.2.
Motor
Length
inch (mm)
Front Shaft
Diameter
inch (mm)
0.625
(15.875)
0.625
(15.875)
45
Page 46
920-0029 Rev. C
1.11
120” MIN
.928
"L"
2X 2-56 UNC TAP THRU 180° APART ON A Ø19.05 B.C.
4 x Ø.205
.787
.591
Ø.250
.063
2 x 2.22
2 x #4-40 UNC ON Ø1.82 BCD
.197
Ø1.50
.59
Ø.250
.630
2 x 1.856
.228 FLAT
220V MOTORS DO NOT HAVE A CONNECTOR AND BOOT
5/2/2012

Motor Dimensions

HT23 Motors
STAC6 Hardware manual
46
Page 47
STAC6 Hardware manual
Motor Dimensions
HT34 Motors
220V MOTORS DO NOT HAVE A CONNECTOR AND BOOT
920-0029 Rev. C
5/2/2012
120" MIN
2X 2-56 UNC 5(.2) DEEP ON A Ø1.28(32.5) B.C.
1.12
Ø .3750
2X #4-40 UNC TAP 5(.2) DEEP 180° APART ON A Ø46.02(1.812) B.C.
“L”
.330
.062
1.25
See shaft
detail
Ø 2.875
4x
Ø.218THRU
2X 2.74
3.38
47
Page 48
920-0029 Rev. C 5/2/2012
HT34 Motors (cont)
Shaft Detail 1 - motor with 0.5” shaft
STAC6 Hardware manual
1.25±.02
.875±.010
Shaft Detail 2 - motors with 0.625” shaft
1.25±.02
.875±.010
Ø.500+.0000
.125
0
Ø.6250+.0000
.1875
.555
.705
48
Page 49
STAC6 Hardware manual
0
50
100
150
200
250
0 10 20 30 40 50
(ozin)
(rps)
HT23‐552/553/554,STAC6(120)
HT23552 HT23553 HT23554
Connection:parallel Stepresolution:1/100(20,000s/r)
0
50
100
150
200
250
0 10 20 30 40 50
(ozin)
(rps)
HT23‐552/553/554,STAC6220
HT23552 HT23553 HT23554
Connection:series Stepresolution:1/100(20,000s/r)

Torque-Speed Curves

920-0029 Rev. C
5/2/2012
49
Page 50
920-0029 Rev. C
0
200
400
600
800
1000
1200
1400
1600
0 10 20 30 40 50
(ozin)
(rps)
HT34‐495/496/497,STAC6(120)
HT34495 HT34496 HT34497
Connection:parallel Stepresolution:1/100(20,000s/r)
0
200
400
600
800
1000
1200
1400
1600
0 10 20 30 40 50
(ozin)
(rps)
HT34‐495/496/497,STAC6220
HT34495 HT34496 HT34497
Connection:series Stepresolution:1/100(20,000s/r)
5/2/2012
Torque-Speed Curves
STAC6 Hardware manual
50
Page 51
STAC6 Hardware manual
0
50
100
150
200
250
0 10 20 30 40 50
(ozin)
(rps)
HT23‐548/549/550,STAC6(120)
HT23548 HT23549 HT23550
Connection:series Stepresolution:1/100(20,000s/r)
0
200
400
600
800
1000
1200
1400
1600
0 10 20 30 40 50
(ozin)
(rps)
HT34‐488/489/490,STAC6(120)
HT34488 HT34489 HT34490
Connection:series Stepresolution:1/100(20,000s/r)
Torque-Speed Curves
920-0029 Rev. C
5/2/2012
51
Page 52
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Mounting the Drive

You can mount your drive on the wide or the narrow side of the chassis using #6 screws. If possible, the drive should be securely fastened to a smooth, at metal surface that will help conduct heat away from the chassis. If this is not possible, then forced airow from a fan may be required to prevent the drive from
overheating.
• Never use your drive in a space where there is no air flow or where other devices cause the surrounding air to be more than 55°C.
• Never put the drive where it can get wet or where metal or other electrically conductive particles can get on the circuitry.
• Always provide air flow around the drive. When mounting multiple STAC6 drives near each other, maintain at least one half inch of space between drives.
52
Page 53
STAC6 Hardware manual

Mechanical Outline

920-0029 Rev. C
5/2/2012
4.66
.76 TYP
.20
.50 TYP
1.76
.68
.120
.300
.300
.180
2.31
.150 .300
6.345
6.925
7.345
53
Page 54
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual
Technical Specifications
POWER AMPLIFIER SECTION
AMPLIFIER TYPE MOSFET , Dual H-Bridge, 4 Quadrant
CURRENT CONTROL 4 state PWM at 20 Khz
OUTPUT CURRENT STAC6 0.5— 6.0 amps in 0.01 amp increments (6A peak of sine)
STAC6-220 0.5— 3.2 amps in 0.01 amp increments (3.2A peak of sine)
POWER SUPPLY STAC6 Line Operated Nominal 120 VAC, 50/60 Hz
STAC6-220 Line Operated Nominal 220 VAC, 50/60 Hz
AC INPUT VOLTAGE STAC6 94—135VAC, 50/60Hz
STAC6-220 94—265VAC, 50/60Hz
PROTECTION Over-voltage, under-voltage, over-temp, external output shorts (phase to-phase, phase-to-
ground), internal amplier shorts
IDLE CURRENT REDUCTION Reduction to any integer percent of full-current after delay selectable in milliseconds.
MOTOR REGENERATION Built in regeneration circuit - 25watts max.
CONTROLLER SECTION
NON-VOLATILE STORAGE Congurations are saved in FLASH memory on board the DSP. STEP AND DIRECTION INPUTS Optically Isolated: 5 Volt. Minimum pulse width = 200 ns. Maximum pulse frequency
= 2 MHz
RESOLUTION Software selectable from 200 to 51200 steps/rev in increments of 2 steps/rev
ANTI RESONANCE (Electronic Damping)
TORQUE RIPPLE SMOOTHING Allows for ne adjustment of phase current waveform harmonic content to reduce low-
SELF TEST AND AUTO SETUP Checks internal & external power supply voltages, diagnoses open motor phases.
MICROSTEP EMULATION Performs low resolution stepping by synthesizing ne microsteps from coarse steps. COMMAND SIGNAL SMOOTHING Software congurable ltering reduces jerk and excitation of extraneous system
ENCODER OPTION Employs encoder (hi or low resolution) to provide failsafe stall detect and perform stall
INTERFACE RS-232 and RS-485 , CANopen standard on STAC6-C models. AMBIENT TEMPERATURE 0 to 55 oC (32- 158 oF) HUMIDITY 90% non-condensing
Raises the system damping ratio to eliminate midrange instability and allow stable operation throughout the speed range and improves settling time.
speed torque ripple in the range 0.25 — 1.5 rps.
Measures motor parameters and congures motor current control and anti-resonance
gain settings.
resonances (step & direction mode only)
prevention and position maintenance. Differential line receivers suitable for 500 kHz or greater. Minimum encoder resolution is 1000 lines.
54
Page 55
920-0029 Rev. C
STAC6 Hardware manual
5/2/2012
INPUTS AND OUTPUTS
IN / OUT 1 connector - All Drives
7 Inputs
X1, X2 Optically Isolated, Differential, 5 Volt. Minimum pulse width = 250ns. Maximum pulse,
X3 Optically isolated, 12 - 24V, sourcing or sinking. Function: Motor Enable, Sensor, Home
X4 Optically isolated, 12 - 24V, sourcing or sinking. Function: Alarm Reset, Sensor, Home or
X5 Optically isolated, 12 - 24V. Function. Function; general Purpose Input. X3 - X7 have
X6,X7 Optically isolated, 12 - 24V. Function: CW & CCW Limits, Sensor, Home or Branch Select.
3 Outputs
Y1 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y2 & Y3.
Y2 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y1 & Y3.
Y3 Optical darlington, 30V, 100mA max, NPN/sinking, shared common with Y1 & Y2.
Analog Inputs
Software selectable: 0-5V, ±5V, 0-10V, ±10V,
RESOLUTION 12 bits (with ±10V signal range)
frequency = 2 MHz Function: Step & Direction, Encoder Following, Sensor, Home or Branch Select
or Branch Select. X3 - X7 have shared common.
Branch Select. X3 - X7 have shared common.
shared common.
X3 - X7 have shared common.
Function: Brake or general purpose programmable
Function: Motion, tach or general purpose programmable
Function: Fault or general purpose programmable
11 bits (with 0-10V or ±5V signal range) 10 bits (with 0-5V signal range)
IN / OUT 2 connector - QE and Si
8 Digital Inputs
IN1-IN6 Optically isolated, 12 - 24V. Function. Function; general Purpose Input. Shared common.
IN7,IN8 Optically isolated, differential. 12 - 24V. Function; general Purpose Input.
4 Digital Outputs
OUT 1-4 Optical darlington, 30V, 100mA max, sinking or sourcing. Function: general purpose
programmable
1 Analog Input 0-5VDC analog input - for use with Q or SCL applications only
55
Page 56
920-0029 Rev. C 5/2/2012
STAC6 Hardware manual

Mating Connectors and Accessories

Mating Connector
(Type)
Motor (5-position, screw terminal) -
AC Power (3-position, screw
terminal) Phoenix Contact 1767012
RS485 Logic (3-position, screw
terminal) Phoenix Contact 1827622 -
Norcomp 171-025-103L001 connector,
IN/OUT1 (DB-25 male)
Norcomp 171-025-203L011 connector,
IN/OUT2 (DB-25 female)
Encoder (HD-15 male) -
Accessories
Breakout Box for DB-25 Connectors BOB-1, includes cable, connects to IN/OUT 1 BOB-2, includes cable, connects to IN/OUT 2 Screw Terminal Connectors that mate directly to the DB-25 connector on the front panel of the drive: Phoenix Contact P/N 2761622
This connector is not available from Applied Motion. You must purchase it from a Phoenix distributor.
Mating Cable for IN/OUT2 connector with “ying leads”
Black Box P/N: BC00702
This cable is not available from Applied Motion. You must purchase it from Black Box.
Useful for custom wired applications. This shielded cable has a DB-25 connector on each
end. You can cut off the female end to create a 6 foot “DB-25 to ying lead cable”.
It’ll be easier to wire if you get the cable color chart from Black Box’s web site. Recommended CANopen USB Adapter (-C drives only) Kvaser LeafLight HS This adapter is not available from Applied Motion Products Note: Prolific-based USB serial adapters do not work with Vista 64 or Windows 7 64 bit operating systems. Suggested adapters are Byterunner USB-COMi-M or Byterunner USB-COM-CBL or USB-COMi. (USB) Serial Adapters: For 32-bit Windows operating systems: Port Authority “USB Serial DB9” Adapter from CablesToGo.com (USB). SW1301 from SewellDirect.com (USB). SSP-100 from Sewell Direct (PCMCIA) For 64-bit and 32-bit Windows operating systems: Byterunner USB-COM-CBL or USB-COMi. (USB)
Included with Drive Additional/Recommended
Phoenix Contact 1757048,
1792786
Phoenix Contact 1832426,
1832536
Mouser 40-9725HS shell kit -
Mouser 40-9725HS shell kit -
Norcomp 180-015-102-001 con-
nector, AMP 5-748678-1 shell kit
56
Page 57
920-0029 Rev. C
Code Error
solid green no alarm, motor disabled flashing green no alarm, motor enabled 1 red, 1 green motor stall (optional encoder only) 1 red, 2 green move attempted while drive disabled 1 red, 3 green subroutine stack overflow (Si only) 2 red, 1 green ccw limit 2 red, 2 green cw limit 2 red, 3 green subroutine stack underflow (Si only) 3 red, 1 green drive overheating 3 red, 2 green internal voltage out of range 3 red, 3 green blank Q segment 4 red, 1 green power supply overvoltage 4 red, 2 green power supply undervoltage 4 red, 3 green bad instruction in Si program 5 red, 1 green over current / short circuit 5 red, 2 green motor resistance out of range 6 red, 1 green open motor winding 6 red, 2 green bad encoder signal (optional encoder only) 7 red, 1 green serial communication error 7 red, 2 green flash memory error 8 red, 1 green internal voltage out of range
STAC6 Hardware manual
5/2/2012

Alarm Codes

In the event of an error, the green LED on the main board will ash one or two times, followed by a series of red ashes. The pattern repeats until the alarm is cleared.
Tel (831) 761-6555 (800) 525-1609 Fax (831) 761-6544
Applied Motion Products, Inc.
404 Westridge Drive Watsonville, CA 95076
www.appliedmotionproducts.com
57
Loading...