Appleton EYS 25% * Fill Vertical and Horizontal Sealing Fittings Catalog Page

EYS 25% * Fill Vertical and Horizontal Sealing Fittings
Hazardous Location Fittings: nEc/cEc ExpLosionprooF sEaLing Fittings
© November 2016
For Close Turning Radius. Explosionproof, Dust-Ignitionproof, Raintight.
UNILETS™ for Use with Threaded Rigid Metal Conduit and IMC.
NEC/CEC:
Class I, Division 1 and 2, Groups A, B, C, D Class II, Division 1 and 2, Groups E, F, G Class III
Trade
Millimeters (Inches)
Size
(Inches)
EYS Vertical and Horizontal Conduit Seals for Close Turning Radius (25% fill)
Female
93.7 (3.69) 31.7 (1.25)
93.7 (3.69) 38.1 (1.50)
109.4 (4.31) 44.4 (1.75)
128.5 (5.06) 55.6 (2.19)
139.7 (5.50) 61.9 (2.44)
158.7 (6.25) 76.2 (3.00)
190.5 (7.50) 88.9 (3.50)
1/2” — 1”
1/2 3/4
1
1-1/4 1-1/2
2
2-1/2 3 215.9 (8.50) 107.9 (4.25) 79.5 (3.13) 1729.0 (61.00) EYS-8
1-1/4” — 3” 3-1/2
4 5
3-1/2” — 6” 6
233.4 (9.19) 120.6 (4.75)
247.6 (9.75) 133.3 (5.25)
294.6 (11.06) 165.1 (6.50)
308.1 (12.13) 193.8 (7.63)
Male/Female (Removable Male Nipple)
93.7 (3.69) 31.7 (1.25)
93.7 (3.69) 38.1 (1.50)
109.4 (4.31) 44.4 (1.75)
128.5 (5.06) 55.6 (2.19)
139.7 (5.50) 61.9 (2.44)
158.7 (6.25) 76.2 (3.00)
190.5 (7.50) 88.9 (3.50)
215.9 (8.50) 107.9 (4.25)
233.4 (9.19) 120.6 (4.75)
247.6 (9.75) 133.3 (5.25)
294.6 (11.06) 165.1 (6.50)
308.1 (12.13) 193.8 (7.63)
1/2” — 1”
1-1/4” — 3” 3-1/2
3-1/2” — 6” 6
1/2 3/4
1
1-1/4 1-1/2
2
2-1/2
3
4 5
Kwiko™ A Cement
Required
Grams (Ounces)
Catalog Number
Grayloy™-Iron A (Length) B (Width) Turning Radius
29.4 (1.16) 28.0 (1.00) EYS-11
31.7 (1.25) 57.0 (2.00) EYS-21
35.5 (1.38) 113.0 (4.00) EYS-31
44.4 (1.75) 255.0 (9.00) EYS-4
52.3 (2.06) 340.0 (12.00) EYS-5
58.6 (2.31) 595.0 (21.00) EYS-6
68.3 (2.69) 1049.0 (37.00) EYS-7
87.3 (3.44) 2268.0 (80.00) EYS-9
93.7 (3.69) 3175.0 (112.00) EYS-10
119.1 (4.69) 5613.0 (198.00) EYS-012
136.6 (5.38) 9667.0 (230.00) EYS-014
29.4 (1.16) 28.0 (1.00) EYS-116
31.7 (1.25) 57.0 (2.00) EYS-216
35.5 (1.38) 113.0 (4.00) EYS-316
44.4 (1.75) 255.0 (9.00) EYS-46
52.3 (2.06) 340.0 (12.00) EYS-56
58.6 (2.31) 595.0 (21.00) EYS-66
68.3 (2.69) 1,049.0 (37.00) EYS-76
79.5 (3.13) 1,729.0 (61.00) EYS-86
87.3 (3.44) 2,268.0 (80.00) EYS-96
93.7 (3.69) 3,175.0 (112.00) EYS-106
119.1 (4.69) 5,613.0 (198.00) EYS-0126
136.6 (5.38) 9,667.0 (230.00) EYS-0146
EYS
1/2” — 1”
EYS
1-1/4” — 6”
* Per NEC 501.15(C)(6), seals in Class I, Division 1 and 2 must be limited to conductor fill of 25% of cross sectional area of a rigid metal conduit of the same trade size unless approved for higher percentage fill. See 40% fill sealing fittings. Turning radius with cover or plug removed.
Indicates items in the shaded area which are UL Listed for Class I, Groups A, B, C, D; Class II, Groups E, F, G; and Class III.
680