EYDM 25% * Fill Vertical Conduit Drain Sealing Fittings
For Close Turning Radius. Explosionproof, Dust-Ignitionproof, Raintight.
UNILETS™ for Use with Threaded Rigid Metal Conduit and IMC.
NEC/CEC:
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
entimeters (Inches)
C
Trade
Size
(Inches)
A (Length) B (Width)
EYDM Vertical Conduit Drain Seals for Close Turning Radius (25% fill)
Male/Female (Removable Male Nipple)
1/2 8.3 (3.28) 3.2 (1.25) 4.1 (1.63) 56.7 (2.00)
Turning
Radius Malleable Iron Almag 35 Aluminum
‡
Kwiko
Cement
Required
Grams (Ounces)
™
A
EYDM-50
Catalog Number
EYDM-50AL
3/4 9.4 (3.69) 3.8 (1.25) 4.9 (1.91) 56.7 (2.00)
1/2” — 1”
1 10.9 (4.31) 4.4 (1.75) 6.0 (2.38) 85.1 (3.00)
1-1/4 12.9 (5.06) 5.6 (2.19) 4.5 (1.75) 198.4 (7.00)
1-1/2 14.0 (5.50) 6.2 (2.44) 5.2 (2.06) 368.5 (13.00)
2 15.8 (6.25) 7.6 (3.00) 5.9 (2.31) 623.7 (22.00)
1-1/4” — 3”
HAZARDOUS LOCATION FITTINGS: NEC/CEC EXPLOSIONPROOF SEALING FITTINGS
2-1/2 19.1 (7.50) 8.9 (3.50) 6.8 (2.69) 1020.6 (36.00)
3 21.6 (8.50) 10.8 (4.25) 8.4 (3.31) 1729.3 (61.00)
3-1/2 23.3 (9.19) 12.1 (4.75) 8.6 (3.41) 2523.1 (89.00)
3-1/2” — 4”
4 24.8 (9.75) 13.3 (5.22) 9.4 (3.69) 3231.8 (14.00)
EYDM-75
EYDM-100
EYDM-125
EYDM-150
EYDM-200
EYDM-250
EYDM-300
EYDM-350
EYDM-400
EYDM-75AL
EYDM-100AL
EYDM-125AL
EYDM-150AL
EYDM-200AL
EYDM-250AL
EYDM-300AL
EYDM-350AL
EYDM-400AL
EYDM
1/2” — 1”
* Per NEC 501.15(C)(6), seals in Class I, Division 1 and 2 must be limited to conductor fill of 25% of cross sectional area of a rigid metal conduit of the same trade
size unless approved for higher percentage fill. See 40% fill sealing fittings.
Turning radius with cover or plug removed.
Indicated items in the shaded area which are UL Listed for Class I, Groups B, C, D; Class II, Groups E, F, G; and Class III.
686
EYDM
1-1/4” — 4”
© January 2018