Appleton ES”SERIES Instruction Sheet

501923
INSTRUCTION SHEET
INSTRUCTIONS FOR SEALING APPLETON “ES” SERIES SEALING HUBS FOR USE WITH
APPLETON KWIKO
®
, KWIKO A™ AND CROUSE-HINDS CHICO A
• This is to prevent the passage of gasses, vapors or flames through the conduit from one portion of the electrical installations to another portion.
• Appleton Sealing Hubs are U/L Listed for use in hazardous locations with “Kwiko, Kwiko A compound or Crouse-Hinds Chico compound only. These compounds when used properly mixed and poured, hardens into a dense and strong mass which is insoluble with water. It is not attacked by petroleum products and is not soften by heat.
• Appleton ES Sealing Hubs are used to seal vertical conduit risers in Class I, Division 1 and 2 hazardous (classified) locations as defined by the National Electrical Code (NEC). These sealing hubs may be installed vertically in a NPT threaded hub as shown in Figure 1 or with a STG steel ring and gasket assembly through slip hole in metal enclosure wall as shown in Figure 2.
WARNING: Electrical power must be turned Off before and during installation and maintenance.
• Failure to follow safety instructions may cause ignition of hazardous atmospheres resulting in serious personal injury and / or property damage.
1. Install sealing hub securely in enclosure opening and pull conductors through.
2. DAMMING: Separate each conductor and pack fiber filler into hub behind conductors and around each conductor.
These conductors must not touch each other nor touch the sealing fitting wall.
Clean fiber shreds away from walls or
conductors to prevent them from causing flame and / or leakage of gasses. Finished
Mineral Fiber
Filler “Asbestos
-Free
dam must be as shown in Fig. 1 & 2.
3. MIxing: Prepare sealing compound using a completely clean mixing vessel in each batch. Shake the sealing cement thoroughly in all directions. Mix sealing cement with correct proportion of clean water as noted below.
Asbestos-
APPLETON Kwiko CEMENT. Add 3 fluid ounces of water to 1 lb. of cement equivalent to 1 part water to 3 parts cement by volume for a minimum of 5 minutes or until an even pouring consistency is obtained.
Free
Sealing Cement
Be sure to read the
mixing instructions
on the Sealing
cement can.
Appleton Kwiko A and CROUSE-HINDS Chico A CEMENT. Add one (1) part water to two (2) parts cement
by volume. Use cold water, warm water increases setting
CAUTION: Temperature / Cure Time Appleton Kwiko Cement must not be mixed and poured at
temperature below 35°F (1.7°C). Cement compound curing time varies with temperatures. Examples are: 35°F (1.7°C) - 24 hrs., At 68°F (20°C) - 4 hrs. CAUTION: For Group B installations, compound must be allowed 72 hours to cure at full strength before energizing system.
APPLETON Kwiko A and CROUSE HINDS Chico A CEMENT
FOR APPLICATIONS INVOLVING GROUP C AND D
CAUTION: Sealing compound to be mixed ONLY at temperatures above 35°F (1.7°C) and ONLY poured into fittings that have been brought to a temperature above 35°F (1.7°C). Seals must NOT be exposed to temperatures below 35oF (1.7°C) for at least 8 hours.
CAUTION: Sealing compound to be mixed ONLY at temperatures above 40°F (4.4°C) and ONLY poured into fittings that brought to a temperature above 40°F (4.4°C). exposed to tempertures below 400F (4.40C) for at least 72 hours.
CAUTION: Refer to Table 1 to determine the maximum number and size of conductors allowed in a seal.
FOR ALL APPLICATIONS
4. Pour sealing cement into hub until flush with top as shown in Figures 1 and 2, below.
5. For guidance in mixing sealing compound see Table below. These cements are NOT INSULATING COMPOUNDS and
MUST NOT be used for such purposes.
speed. Add water and stir immediately and thoroughly.
• DO NOT mix more than can be poured in 15 minutes after adding w
HUB CATALOG NUMBERS
WITH OUT SEALING GASKET
ES100-50 ES100-75 ES150-100 ES200-125 ES200-150 ES250-200 ES400-300 ES500-400
ES600-500
ater.
WITH SEALING GASKET
ES100-50BLSG ES100-75BLSG ES150-100BLSG ES200-125BLSG ES200-150BLSG ES250-200BLSG ES400-300BLSG ES500-400BLSG ES600-500BLSG
VOLUME OF
SEAL CAVITY
33.70 cu inches
91.23 cu inches
143.73 cu inches
INTERNAL
.74 cu inches .76 cu inches
3.10 cu inches
4.69 cu inches
4.69 cu inches
9.38 cu inches
KEEP CONDUCTORS
IN CENTER OF
ENCLOSURE
HUB
‘ES’ SEALING
Class I and II, Div. 1 and 2
‘ES’ HUB
HUB
FIGURE 1
SEALING
COMPOUND
FLUSH WITH TOP
5 THREADS
MINIMUM ENGAGED
FIBER
FILLER
®
SEALING CEMENT
Seals must NOT be
FIGURE 2
KEEP CONDUCTORS IN CENTER OF
‘ES’ HUB
CONDUIT
LOCKNUT
FLAT WALL
ENCLOSURE
‘ES’ SEALING
HUB
FLUSH WITH TOP
Class I and II, Div. 2 Only
have been
SEALING
COMPOUND
STEEL RING
AND GASKET
ASSEMBLY
FIBER
FILLER
Rev. D • 7/17/96
Loading...