Instruction Sheet
EDS, N1 and Contender Series
Manual Motor Starter Heater Selection Table
503406
Warning:
Electrical power must be turned OFF before and
during installation of heater. Failure to follow
safety instructions may cause ignition of hazardous atmospheres resulting in serious personal
injury and/or property damage.
Heater Selection Guideline
The “Full Load Motor Current” listed on Table 1 and 2
are ratings which determine the proper heater element
that should be used with in conjunction with the motor
starter. Refer to the motor nameplate for its full load
motor current. For normal operating condition, we recommend that heater element selected should have a
capacity of 20 to 25% greater than the full load motor
current at 40˚C ambient temperature. For 50˚C rise, a
heater not greater than 115% of full load current
should be selected.
The above information is an approximation only due to
the difference between full load currents of various
motor manufacturer of the same size motor.
If selection of heater element is uncertain as might be
in the case of a motor subject to frequent starting and
intermittent load, it is advisable to contact the starter
manufacturer giving full particulars, such as motor
horsepower, voltage, phase cycles or other pertinent
data that may aid in the selection of proper heater element.
NOTE: Use copper conductors only rated at 60˚C or
75˚C.
Warning:
Tripping or opening of the circuit breaker or fuse(s)
could be an indication that a fault current has been
interrupted. If such a case happened, the starter must
be mechanically and electrically inspected, examined
and replaced if damaged. This action will provide continued protection against fire or shock hazard. If heater
burnouts occurs, the complete starter and heater must
be replaced.
Table 1
(Westinghouse Heaters)
Full Load EDS/N1 Contender
Motor Current Series Series
Amperes Add Suffix Add Suffix
0.43 -WH1 -W1
0.48 -WH2 -W2
0.53 -WH3 -W3
0.58 -WH4 -W4
0.64 -WH5 -W5
0.71 -WH6 -W6
0.78 -WH7 -W7
0.87 -WH8 -W8
0.95 -WH9 -W9
1.03 -WH10 -W10
1.15 -WH11 -W11
1.27 -WH12 -W12
1.35 -WH13 -W13
1.51 -WH14 -W14
1.67 -WH15 -W15
1.83 -WH16 -W16
1.99 -WH17 -W17
2.23 -WH18 -W18
2.47 -WH19 -W19
2.71 -WH20 -W20
2.95 -WH21 -W21
3.27 -WH22 -W22
3.59 -WH23 -W23
3.99 -WH24 -W24
4.39 -WH25 -W25
4.79 -WH26 -W26
5.26 -WH27 -W27
5.83 -WH28 -W28
6.39 -WH29 -W29
7.03 -WH30 -W30
7.74 -WH31 -W31
8.46 -WH32 -W32
9.35 -WH33 -W33
10.30 -WH34 -W34
11.35 -WH35 -W35
12.47 -WH36 -W36
13.67 -WH37 -W37
15.12 -WH38 -W38
16.00 -WH39 -W39
Table 2
(Allen-Bradley Heaters)
Full Load EDS/N1 Contender
Motor Current Series Series
Amperes Add Suffix Add Suffix
0.17 -AB1 -P1
0.21 -AB2 -P2
0.25 -AB3 -P3
0.32 -AB4 -P4
0.39 -AB5 -P5
0.46 -AB6 -P6
0.57 -AB7 -P7
0.71 -AB8 -P8
0.79 -AB9 -P9
0.87 -AB10 -P10
0.98 -AB11 -P11
1.08 -AB12 -P12
1.19 -AB13 -P13
1.30 -AB14 -P14
1.43 -AB15 -P15
1.58 -AB16 -P16
1.75 -AB17 -P17
1.88 -AB18 -P18
2.13 -AB19 -P19
2.40 -AB20 -P20
2.58 -AB21 -P21
2.92 -AB22 -P22
3.09 -AB23 -P23
3.32 -AB24 -P24
3.77 -AB25 -P25
4.16 -AB26 -P26
4.51 -AB27 -P27
4.93 -AB28 -P28
5.43 -AB29 -P29
6.03 -AB30 -P30
6.83 -AB31 -P31
7.72 -AB32 -P32
8.24 -AB33 -P33
8.90 -AB34 -P34
9.60 -AB35 -P35
10.80 -AB36 -P36
12.00 -AB37 -P37
13.50 -AB38 -P38
15.20 -AB39 -P39