Appleton Edco SLAC Series Catalog Page

Edco SLAC Series
AC Power/Signal
The Edco SLAC Series suppressor was spec designed to protect electronic instruments used by the water/wastewater industries. It combines hybrid AC power protection and signal line protection in a NEMA-4X polycarbonate case. The AC power suppressor can supply up to 1875 Watts and has a 15 Amp replaceable fuse to prevent overloading of the protective elements. A “Power ON” LED provides visual indication that power is applied to instruments. Signal line protection is accomplished by the Edco PC642 Series available in a variety of voltage clamps. Signal current can be monitored by reading the voltage across the 10 ohm, 1% resistors (TP1 & TP2 or TP3 & TP4). All leads going to the Edco SLAC board are terminated by quick disconnect or barrier block connectors to facilitate easy removal for service or replacement.
General Technical Spec
AC Power
Technology Three-Stage Series Hybrid
Voltage Clamp 325 VAC
Input Voltage 120 VAC 50/60 Hz
Output Current 15 Amps Max.
Response Time <5 Nanoseconds
Maximum Surge Current (8x20 µs) 39 kA
Occurrences at 500 Amps >50
Parameter Normal Mode Common Mode
(L-N) (L-G) (N-G)
IEEE 587 CAT A Ring* 172 V 280 V
IEEE 587 CAT B Ring* 205 V 280 V
IEEE 587 CAT B Impulse* 330 V 360 V
*Measured from zero volts, 90° Phase angle
Signal Line
Technology Three-Stage Series Hybrid
Peak Surge Current (8x20 µs) 10 kA
Response Time <5 Nanoseconds
Voltage Clamp (customer selected) 8–200 Volts
Series Resistance 5 ohm (Typical)
Cer ation UL 1449 3rd Edition (2009), Type 2
Standard Enclosure
Features
Lightn in g and surge suppression for AC power and low-voltage signal lines
Series hybrid AC suppressor
Plug -in protection m odule
15 Amp r eplaceable fuse
Test jacks for signal line mo ni to ring
“Power ON” indic ator
Optional sta in less steel or enclosure
5 year warrant y
Optional Enclosure
NEMA-4X
Stainless Steel or Fiberglass
Continuous Hinge
Nominal Outside Dimensions (Inches)
H=10, W=8, D=4
lter
erglass
NEMA-4X
Polycarbonate Base
Smoked Grey Transparent Cover
Knockouts for 20mm and 32mm
Bosses for 6-32 x 3/8 self-tapping screws
Maximum Protection-Total Insulation
Corrosion Resistant
Resists Temperatures up to 250 deg. F
Flammability Rating UL94-5V
Nominal Outside Dimensions (inches): H=7.1, W=7.1, D=3.0
UNPROTECTED
(FIELD) SIDE
4/20 mA SIGNAL
PROTECTED (EQUIP) SIDE
4/20 mA SIGNAL
UNPROTECTED
(FIELD) SIDE
120 VAC POWER
Installation
Signal Line Connections:
• Connect GND Terminal to Local Ground using #12 AWG wire minimum
• L1 and L2 – Connect for Signal Pair #1
• L3 and L4 – Connect for Signal Pair #2
• Terminals accept #24-#14 AWG wire, torque to 4kg-cm
• “S” Connection for Cable Shield ( if applicable )
CAUTION: Do not place this product in service on any signal line capable of suppying more than 150 milliamperes continuously.
PROTECTED
(EQUIP) SIDE
120 VAC POWER
Ordering Information
*For Standard Unit order part # SL
SLAC — 1 2 3 LC
1 = 0 No Enclosure
1 Polycarbonate Case (Standard)
2 Stainless Steel (Optional)
3 Fiberglass (Special)
2 = 0 Without PC642 Signal Protector
2 With PC642
3 = 036 PC642 Voltage Clamp Selection
043
AC-12036
AC Power Connections:
• Connect AC Power as Marked on Case using
#12 AWG wire minimum
• Keep 120 VAC Power feed separate from Low Voltage
4/20 mA feed
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Grp LLC d/b/a Appleton Group assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. The Emerson logo is registered in the U.S. Patent and Trademark Oce. All other product or service names are the property of their registered owners. ©2014 Appleton Grp LLC d/b/a Appleton Group. All rights reserved. Specications are subject to change without notice. A272-257/IO-50124 10/13 Rev 3
Loading...